Humidifier controller gateway (ProtoNode) · BACnet points list

Pure Humidifier Intac controller via ProtoNode FPC-N34 / FPC-N35 BACnet points list

Updated 6 November 2026

Short answer

A ProtoNode FPC-N34 (BACnet MS/TP or BACnet IP) or FPC-N35 gateway reads the Pure Humidifier Intac controller over Modbus RTU and serves 90 analog value objects per humidifier: setpoints, timers, PID and sensor-scaling settings, configuration values, measured humidity and temperatures, heater power, water level and I/O error flags.

This page lists 90 BACnet objects for the Pure Humidifier Intac controller via ProtoNode FPC-N34 / FPC-N35 — 68 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Pure Humidifier’s own free documentation, linked below.

Manufacturer
Pure Humidifier
Model
Intac controller via ProtoNode FPC-N34 / FPC-N35
Equipment
Humidifier controller gateway (ProtoNode)
Equipment type
Humidifiers
BACnet objects
90 (68 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Pure Humidifier Intac, Intac controller BACnet, ProtoNode FPC-N34 Pure Humidifier, FPC-N35 Pure Humidifier, Pure Humidifier BACnet
Source document
ProtoNode FPC-N34 and FPC-N35 Start-up Guide - For Interfacing Pure Humidifier Products: Intac Controller · rev. Document Revision 4.B
Download CSV 90 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Pure Humidifier’s current documentation and the live device before use. Not official Pure Humidifier information. Terms of use.

BMS integration notes: Pure Humidifier Intac controller via ProtoNode FPC-N34 / FPC-N35

Integration in brief

Set each Intac controller to Modbus RTU 38400 8-N-1 with a unique Node-ID, wire it to the ProtoNode, pick the BACnet profile on the S DIP switches and set the MAC and device instance, then read and write the AV objects.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 5Operation ModeUnit operating modeWrite
AV 1RH Set PointRelative humidity setpointWrite
AV 28Control SourceControl signal sourceWrite
AV 69Actual HumidityMeasured relative humidityRead
AV 81Heater PowerHeater outputRead
AV 82Water LevelTank water level statusRead
AV 87Interlock Input OpenSafety interlock openRead

Network setup

Watch out for

Pure Humidifier Intac controller via ProtoNode FPC-N34 / FPC-N35 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

90 of 90 shown
Type
Analog
Access
Show
Pure Humidifier Intac controller via ProtoNode FPC-N34 / FPC-N35 BACnet Points List
DescriptionStates
AVmin1RH Set PointRelative humidity setpoint (Modbus 102)Write
AV2High Limit Set pointDuct high-limit RH setpoint (Modbus 103)Write
AV3RH Low AlarmRH Low Alarm (Modbus 104)Write
AV4RH High AlarmRH High Alarm (Modbus 105)Write
AVmin5Operation ModeUnit operating mode (Modbus 202)Write
AV6Drain Duration TimerDrain Duration Timer (Modbus 203)Write
AV7Drain Interval timerDrain Interval timer (Modbus 204)Write
AV8Cool Down DelayCool Down Delay (Modbus 205)Write
AV9Cool Down TempCool Down Temp (Modbus 206)Write
AV10Fill Delay TimerFill Delay Timer (Modbus 207)Write
AV11Water Temp Set PointWater Temp Set Point (Modbus 208)Write
AV12Water Temp HysteresisWater Temp Hysteresis (Modbus 209)Write
AV13End of Use Drain TimerEnd of Use Drain Timer (Modbus 210)Write
AV14Time to Clean TimerTime to Clean Timer (Modbus 211)Write
AV15Clean ResetReset the clean timer (Modbus 212)Write
AV16Intac AddressIntac Address (Modbus 213)Write
AV17Intac Baud RateIntac Baud Rate (Modbus 214)Write
AV18Room Prop bandRoom Prop band (Modbus 302)Write
AV19Room hysteresisRoom hysteresis (Modbus 303)Write
AV20Room IntegralRoom Integral (Modbus 304)Write
AV21Room DerivativeRoom Derivative (Modbus 305)Write
AV22Cycle TimeCycle Time (Modbus 306)Write
AV23Duct Prop BandDuct Prop Band (Modbus 307)Write
AV24Duct HysteresisDuct Hysteresis (Modbus 308)Write
AV25Duct IntegralDuct Integral (Modbus 309)Write
AV26Duct DerivativeDuct Derivative (Modbus 310)Write
AV27RH Input filterRH Input filter (Modbus 311)Write
AVmin28Control SourceControl signal source (Modbus 503)Write
AV29Water SensorWater Sensor (Modbus 504)Write
AV30RH SensorRH Sensor (Modbus 505)Write
AV31RH Process LowRH Process Low (Modbus 506)Write
AV32RH Process HighRH Process High (Modbus 507)Write
AV33High Limit SensorHigh Limit Sensor (Modbus 509)Write
AV34HighLimit Process LowHighLimit Process Low (Modbus 510)Write
AV35HighLimit Process HighHighLimit Process High (Modbus 511)Write
AV36Outdoor Air SensorOutdoor Air Sensor (Modbus 512)Write
AV37OAT Process LowOAT Process Low (Modbus 513)Write
AV38OAT Process HighOAT Process High (Modbus 514)Write
AV39OAT Range LowOAT Range Low (Modbus 515)Write
AV40OAT Range HighOAT Range High (Modbus 516)Write
AV41OAT OffsetOAT Offset (Modbus 517)Write
AV42Process OutputProcess Output (Modbus 518)Write
AV43Out Process LowOut Process Low (Modbus 519)Write
AV44Out Process HighOut Process High (Modbus 520)Write
AV45Dedicated InputDedicated Input (Modbus 521)Write
AV46Temp unitsTemp units (Modbus 522)Write
AV47Capacity UnitsCapacity Units (Modbus 523)Write
AV48Unit CapacityUnit Capacity (Modbus 524)Write
AV49Menu accessMenu access (Modbus 526)Write
AV50Control TypeControl Type (Modbus 702)Write
AV51Active heatersActive heaters (Modbus 703)Write
AV52Water EnableWater Enable (Modbus 704)Write
AV53Air EnableAir Enable (Modbus 705)Write
AV54Water Level SensorWater Level Sensor (Modbus 706)Write
AV55Drain TypeDrain Type (Modbus 707)Write
AV56High limit enableHigh limit enable (Modbus 708)Write
AV57Clean TimeClean Time (Modbus 709)Write
AV58Gas BurnersGas Burners (Modbus 710)Write
AV59Low Fire Set pointLow Fire Set point (Modbus 711)Write
AV60Low Fire HysteresisLow Fire Hysteresis (Modbus 712)Write
AV61Burner #2 Set pointBurner #2 Set point (Modbus 713)Write
AV62Burner #2 HysteresisBurner #2 Hysteresis (Modbus 714)Write
AV63Burner #3 Set PointBurner #3 Set Point (Modbus 715)Write
AV64Burner #3 HysteresisBurner #3 Hysteresis (Modbus 716)Write
AV65Post purge timerPost purge timer (Modbus 717)Write
AV66VFD IntensityVFD Intensity (Modbus 718)Write
AV67Range CheckingRange Checking (Modbus 719)Write
AV68Low H2O TimerLow H2O Timer (Modbus 720)Write
AVmin69Actual HumidityMeasured relative humidity (Modbus 049)Read
AV70Control RH SensorControl RH Sensor (Modbus 050)Read
AV71High Limit RH ActualHigh Limit RH Actual (Modbus 051)Read
AV72High Limit RH SensorHigh Limit RH Sensor (Modbus 052)Read
AV73Water Temp ActualTank water temperature (Modbus 053)Read
AV74Water Sensor(temp)Water Sensor(temp) (Modbus 054)Read
AV75Outdoor Air Temp ActualOutdoor air temperature (Modbus 055)Read
AV76Outdoor Air SensorOutdoor Air Sensor (Modbus 056)Read
AV77Heater #1 %PowerHeater #1 %Power (Modbus 823)Read
AV78Heater #2 %PowerHeater #2 %Power (Modbus 824)Read
AV79Heater #3 %PowerHeater #3 %Power (Modbus 825)Read
AV80Heater #4 %PowerHeater #4 %Power (Modbus 826)Read
AVmin81Heater PowerTotal heater output (Modbus 853)Read
AVmin82Water LevelTank water level status (Modbus 831)Read
AV83Accumulated Run TimeTotal run time (Modbus 852)Read
AV84Internal Module #1 I/O ErrorInternal Module #1 I/O Error (Modbus 847)Read
AV85Internal Module #2 I/O ErrorInternal Module #2 I/O Error (Modbus 848)Read
AV86Internal Module #3 I/O ErrorInternal Module #3 I/O Error (Modbus 849)Read
AVmin87Interlock Input OpenSafety interlock input open (Modbus 857)Read
AV88Dedicated InputDedicated Input (Modbus 858)Read
AV89Actual Water LevelActual Water Level (Modbus 832)Read
AV90Fill Valve StatusFill valve state (Modbus 840)Read
Object ID lookup: Pure Humidifier Intac controller via ProtoNode FPC-N34 / FPC-N35 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Intac controller via ProtoNode FPC-N34 / FPC-N35 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Pure Humidifier Intac controller via ProtoNode FPC-N34 / FPC-N35

How many BACnet points does the Pure Humidifier Intac controller via ProtoNode FPC-N34 / FPC-N35 have?

This list has 90 BACnet objects: 90 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Pure Humidifier Intac controller via ProtoNode FPC-N34 / FPC-N35 BACnet points are writable?

68 of the 90 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Pure Humidifier Intac controller via ProtoNode FPC-N34 / FPC-N35 BACnet documentation?

The source is ProtoNode FPC-N34 and FPC-N35 Start-up Guide - For Interfacing Pure Humidifier Products: Intac Controller, revision Document Revision 4.B, published free by Pure Humidifier at https://www.purehumidifier.com/downloads/O%26M/ProtoNode_O%26M.pdf.

What are the minimum BACnet points to integrate the Pure Humidifier Intac controller via ProtoNode FPC-N34 / FPC-N35?

Start with AV 5 Operation Mode (Unit operating mode); AV 1 RH Set Point (Relative humidity setpoint); AV 28 Control Source (Control signal source); AV 69 Actual Humidity (Measured relative humidity); AV 81 Heater Power (Heater output); AV 82 Water Level (Tank water level status); AV 87 Interlock Input Open (Safety interlock open).

How do I check these points on the real Intac controller via ProtoNode FPC-N34 / FPC-N35?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: ProtoNode FPC-N34 and FPC-N35 Start-up Guide - For Interfacing Pure Humidifier Products: Intac Controller · rev. Document Revision 4.B. Object names, instances and units are reproduced as published; descriptions are our own.