Gas detection sensor / monitor · BACnet points list
Opera Electronics Opera 6000 gas detector BACnet points list
Updated 12 November 2026Unofficial source
The Opera 6000 is a gas detector with one or two sensors, relays and an alarm output. On BACnet MS/TP it serves its own gas readings, ambient temperature, an input and the relay/alarm outputs. With BACnet enable P46 = 2 it also publishes the readings of up to 32 remote detectors (sensors A and B) on its local network.
This page lists 71 BACnet objects for the Opera Electronics Opera 6000 gas detector — 3 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Opera Electronics’s documentation hosted by BACnet International catalog, not by Opera Electronics itself, so treat it as unofficial.
- Manufacturer
- Opera Electronics
- Model
- Opera 6000 gas detector
- Equipment
- Gas detection sensor / monitor
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 71 (3 writable)
- Transport
- BACnet MS/TP
- Firmware
- 2x28 (x = A or B hardware), application BB4
- Also known as
- Opera 6000, Opera6000, LC30001
- Source document
- BACnet Protocol Implementation Conformance Statement, Opera 6000 (PICS V1.6) · LC30001 · rev. 2016-12-06 (rev 1.4) (unofficial copy, hosted by BACnet International catalog)
Reference only, provided as-is: verify against Opera Electronics’s current documentation and the live device before use. Not official Opera Electronics information. Terms of use.
BMS integration notes: Opera Electronics Opera 6000 gas detector
Set P46 to 1 for the local readings or 2 to add remote detectors, then read the gas readings and the relay/alarm objects. The relay and alarm BOs can also be written from the BMS.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 0 | Gas Reading 1 | Gas reading, local sensor A | Read |
| AV 1 | Gas Reading 2 | Gas reading, local sensor B | Read |
| BO 0 | Relay 1 | Relay 1 state | Write |
| BO 1 | Relay 2 | Relay 2 / alarm L2 state | Write |
| BO 2 | Alarm L3 | Alarm 3 indication | Write |
Enable & remote start
Parameter P46 enables BACnet: 1 = local readings, 2 = local plus remote detectors.
Network setup
- MS/TP master at 9600, 19200, 38400 or 76800 baud.
- Device object name is limited to 22 characters.
Watch out for
- The gas reading objects change with P46, so rediscover the device after changing it.
Opera Electronics Opera 6000 gas detector BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 0 | Gas Reading 1 | Local sensor A gas reading (P46 = 1) | Read | ||
| AVmin | 1 | Gas Reading 2 | Local sensor B gas reading (P46 = 1, second sensor) | Read | ||
| AV | 2 | Ambient Temp. | Ambient temperature | °C | Read | |
| BI | 0 | Input 1 | Input state | Read | ||
| BOmin | 0 | Relay 1 | Relay 1 control | Write | ||
| BOmin | 1 | Relay 2 | Relay 2 (A hardware) or Alarm L2 (B hardware) control | Write | ||
| BOmin | 2 | Alarm L3 | Alarm indication 3 control | Write | ||
| AV | 100 | Gas Reading 100 | Remote gas reading 0A (P46 = 2) | Read | ||
| AV | 200 | Gas Reading 200 | Remote gas reading 0B (P46 = 2) | Read | ||
| AV | 101 | Gas Reading 101 | Remote gas reading 1A (P46 = 2) | Read | ||
| AV | 201 | Gas Reading 201 | Remote gas reading 1B (P46 = 2) | Read | ||
| AV | 102 | Gas Reading 102 | Remote gas reading 2A (P46 = 2) | Read | ||
| AV | 202 | Gas Reading 202 | Remote gas reading 2B (P46 = 2) | Read | ||
| AV | 103 | Gas Reading 103 | Remote gas reading 3A (P46 = 2) | Read | ||
| AV | 203 | Gas Reading 203 | Remote gas reading 3B (P46 = 2) | Read | ||
| AV | 104 | Gas Reading 104 | Remote gas reading 4A (P46 = 2) | Read | ||
| AV | 204 | Gas Reading 204 | Remote gas reading 4B (P46 = 2) | Read | ||
| AV | 105 | Gas Reading 105 | Remote gas reading 5A (P46 = 2) | Read | ||
| AV | 205 | Gas Reading 205 | Remote gas reading 5B (P46 = 2) | Read | ||
| AV | 106 | Gas Reading 106 | Remote gas reading 6A (P46 = 2) | Read | ||
| AV | 206 | Gas Reading 206 | Remote gas reading 6B (P46 = 2) | Read | ||
| AV | 107 | Gas Reading 107 | Remote gas reading 7A (P46 = 2) | Read | ||
| AV | 207 | Gas Reading 207 | Remote gas reading 7B (P46 = 2) | Read | ||
| AV | 108 | Gas Reading 108 | Remote gas reading 8A (P46 = 2) | Read | ||
| AV | 208 | Gas Reading 208 | Remote gas reading 8B (P46 = 2) | Read | ||
| AV | 109 | Gas Reading 109 | Remote gas reading 9A (P46 = 2) | Read | ||
| AV | 209 | Gas Reading 209 | Remote gas reading 9B (P46 = 2) | Read | ||
| AV | 110 | Gas Reading 110 | Remote gas reading 10A (P46 = 2) | Read | ||
| AV | 210 | Gas Reading 210 | Remote gas reading 10B (P46 = 2) | Read | ||
| AV | 111 | Gas Reading 111 | Remote gas reading 11A (P46 = 2) | Read | ||
| AV | 211 | Gas Reading 211 | Remote gas reading 11B (P46 = 2) | Read | ||
| AV | 112 | Gas Reading 112 | Remote gas reading 12A (P46 = 2) | Read | ||
| AV | 212 | Gas Reading 212 | Remote gas reading 12B (P46 = 2) | Read | ||
| AV | 113 | Gas Reading 113 | Remote gas reading 13A (P46 = 2) | Read | ||
| AV | 213 | Gas Reading 213 | Remote gas reading 13B (P46 = 2) | Read | ||
| AV | 114 | Gas Reading 114 | Remote gas reading 14A (P46 = 2) | Read | ||
| AV | 214 | Gas Reading 214 | Remote gas reading 14B (P46 = 2) | Read | ||
| AV | 115 | Gas Reading 115 | Remote gas reading 15A (P46 = 2) | Read | ||
| AV | 215 | Gas Reading 215 | Remote gas reading 15B (P46 = 2) | Read | ||
| AV | 116 | Gas Reading 116 | Remote gas reading 16A (P46 = 2) | Read | ||
| AV | 216 | Gas Reading 216 | Remote gas reading 16B (P46 = 2) | Read | ||
| AV | 117 | Gas Reading 117 | Remote gas reading 17A (P46 = 2) | Read | ||
| AV | 217 | Gas Reading 217 | Remote gas reading 17B (P46 = 2) | Read | ||
| AV | 118 | Gas Reading 118 | Remote gas reading 18A (P46 = 2) | Read | ||
| AV | 218 | Gas Reading 218 | Remote gas reading 18B (P46 = 2) | Read | ||
| AV | 119 | Gas Reading 119 | Remote gas reading 19A (P46 = 2) | Read | ||
| AV | 219 | Gas Reading 219 | Remote gas reading 19B (P46 = 2) | Read | ||
| AV | 120 | Gas Reading 120 | Remote gas reading 20A (P46 = 2) | Read | ||
| AV | 220 | Gas Reading 220 | Remote gas reading 20B (P46 = 2) | Read | ||
| AV | 121 | Gas Reading 121 | Remote gas reading 21A (P46 = 2) | Read | ||
| AV | 221 | Gas Reading 221 | Remote gas reading 21B (P46 = 2) | Read | ||
| AV | 122 | Gas Reading 122 | Remote gas reading 22A (P46 = 2) | Read | ||
| AV | 222 | Gas Reading 222 | Remote gas reading 22B (P46 = 2) | Read | ||
| AV | 123 | Gas Reading 123 | Remote gas reading 23A (P46 = 2) | Read | ||
| AV | 223 | Gas Reading 223 | Remote gas reading 23B (P46 = 2) | Read | ||
| AV | 124 | Gas Reading 124 | Remote gas reading 24A (P46 = 2) | Read | ||
| AV | 224 | Gas Reading 224 | Remote gas reading 24B (P46 = 2) | Read | ||
| AV | 125 | Gas Reading 125 | Remote gas reading 25A (P46 = 2) | Read | ||
| AV | 225 | Gas Reading 225 | Remote gas reading 25B (P46 = 2) | Read | ||
| AV | 126 | Gas Reading 126 | Remote gas reading 26A (P46 = 2) | Read | ||
| AV | 226 | Gas Reading 226 | Remote gas reading 26B (P46 = 2) | Read | ||
| AV | 127 | Gas Reading 127 | Remote gas reading 27A (P46 = 2) | Read | ||
| AV | 227 | Gas Reading 227 | Remote gas reading 27B (P46 = 2) | Read | ||
| AV | 128 | Gas Reading 128 | Remote gas reading 28A (P46 = 2) | Read | ||
| AV | 228 | Gas Reading 228 | Remote gas reading 28B (P46 = 2) | Read | ||
| AV | 129 | Gas Reading 129 | Remote gas reading 29A (P46 = 2) | Read | ||
| AV | 229 | Gas Reading 229 | Remote gas reading 29B (P46 = 2) | Read | ||
| AV | 130 | Gas Reading 130 | Remote gas reading 30A (P46 = 2) | Read | ||
| AV | 230 | Gas Reading 230 | Remote gas reading 30B (P46 = 2) | Read | ||
| AV | 131 | Gas Reading 131 | Remote gas reading 31A (P46 = 2) | Read | ||
| AV | 231 | Gas Reading 231 | Remote gas reading 31B (P46 = 2) | Read |
No points match these filters.
Object ID lookup: Opera Electronics Opera 6000 gas detector point IDs by name
AV0Gas Reading 1AV1Gas Reading 2AV2Ambient Temp.BI0Input 1BO0Relay 1BO1Relay 2BO2Alarm L3AV100Gas Reading 100AV200Gas Reading 200AV101Gas Reading 101AV201Gas Reading 201AV102Gas Reading 102AV202Gas Reading 202AV103Gas Reading 103AV203Gas Reading 203AV104Gas Reading 104AV204Gas Reading 204AV105Gas Reading 105AV205Gas Reading 205AV106Gas Reading 106AV206Gas Reading 206AV107Gas Reading 107AV207Gas Reading 207AV108Gas Reading 108AV208Gas Reading 208AV109Gas Reading 109AV209Gas Reading 209AV110Gas Reading 110AV210Gas Reading 210AV111Gas Reading 111AV211Gas Reading 211AV112Gas Reading 112AV212Gas Reading 212AV113Gas Reading 113AV213Gas Reading 213AV114Gas Reading 114AV214Gas Reading 214AV115Gas Reading 115AV215Gas Reading 215AV116Gas Reading 116AV216Gas Reading 216AV117Gas Reading 117AV217Gas Reading 217AV118Gas Reading 118AV218Gas Reading 218AV119Gas Reading 119AV219Gas Reading 219AV120Gas Reading 120AV220Gas Reading 220AV121Gas Reading 121AV221Gas Reading 221AV122Gas Reading 122AV222Gas Reading 222AV123Gas Reading 123AV223Gas Reading 223AV124Gas Reading 124AV224Gas Reading 224AV125Gas Reading 125AV225Gas Reading 225AV126Gas Reading 126AV226Gas Reading 226AV127Gas Reading 127AV227Gas Reading 227AV128Gas Reading 128AV228Gas Reading 228AV129Gas Reading 129AV229Gas Reading 229AV130Gas Reading 130AV230Gas Reading 230AV131Gas Reading 131AV231Gas Reading 231
Integration notes
- AV 0 and AV 1 exist only with P46 = 1; AV 1 also needs a second sensor fitted.
- AV 100-131 and AV 200-231 exist only with P46 = 2; instance = 100 + remote number (sensor A) or 200 + remote number (sensor B).
- BO 1 is Relay 2 on A hardware and Alarm L2 on B hardware.
- A hardware has 2 relays; B hardware has 1 relay, 2 analog outputs and a binary input.
- Object types used: Analog Value, Binary Input, Binary Output and Device.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Opera 6000 gas detector and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Opera Electronics Opera 6000 gas detector
How many BACnet points does the Opera Electronics Opera 6000 gas detector have?
This list has 71 BACnet objects: 67 analog values, 1 binary input, 3 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Opera Electronics Opera 6000 gas detector BACnet points are writable?
3 of the 71 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Opera Electronics Opera 6000 gas detector BACnet documentation?
Opera Electronics does not publish it on its own website. This list comes from BACnet Protocol Implementation Conformance Statement, Opera 6000 (PICS V1.6) (LC30001), revision 2016-12-06 (rev 1.4), a copy hosted by BACnet International catalog at https://www.bacnetinternational.net/catalog/manu/opera%20electronics%20inc/LC30001.PICS.48751328_Opera6000-PICS-V1.6.pdf. Ask Opera Electronics or its representative for the current revision.
What are the minimum BACnet points to integrate the Opera Electronics Opera 6000 gas detector?
Start with AV 0 Gas Reading 1 (Gas reading, local sensor A); AV 1 Gas Reading 2 (Gas reading, local sensor B); BO 0 Relay 1 (Relay 1 state); BO 1 Relay 2 (Relay 2 / alarm L2 state); BO 2 Alarm L3 (Alarm 3 indication).
How do I enable BMS control of the Opera Electronics Opera 6000 gas detector?
Parameter P46 enables BACnet: 1 = local readings, 2 = local plus remote detectors.
How do I check these points on the real Opera 6000 gas detector?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: BACnet Protocol Implementation Conformance Statement, Opera 6000 (PICS V1.6) · LC30001 · rev. 2016-12-06 (rev 1.4). Object names, instances and units are reproduced as published; descriptions are our own.