Short answer

The NT-BAS ProtoNode reads a Network Thermostat RP32H over Ethernet and presents it as a BACnet MS/TP or BACnet IP device (Modbus, Metasys N2 and LonWorks are also offered). Each thermostat gets its own device instance. The profile exposes mode, fan and setpoint commands, temperatures, stage and override status, clock and vacation settings and the full 7-day, 4-period schedule. The H version adds humidify/dehumidify settings.

This page lists 305 BACnet objects for the Network Thermostat RP32H IP-WiFi Thermostat (NT-BAS ProtoNode) — 273 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Network Thermostat’s own free documentation, linked below.

Manufacturer
Network Thermostat
Model
RP32H IP-WiFi Thermostat (NT-BAS ProtoNode)
Equipment
Thermostat (via BACnet gateway)
Equipment type
Thermostats, sensors & meters
BACnet objects
305 (273 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Also known as
RP32H, RP32H IP-WIFI, NT-BAS, ProtoNode FPC-N34, NetX
Source document
Network Thermostat's ProtoNode Startup Guide (ProtoNode FPC-N34 and FPC-N35, NT-BAS) · rev. Document Revision 2.A, Template Revision 24
Download CSV 305 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Network Thermostat’s current documentation and the live device before use. Not official Network Thermostat information. Terms of use.

BMS integration notes: Network Thermostat RP32H IP-WiFi Thermostat (NT-BAS ProtoNode)

Integration in brief

Write the system mode, fan mode and cooling/heating setpoints, and read the indoor temperature, heat/cool status, stage and override status. The thermostat also carries its own schedule, which the BMS can read or rewrite.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 18ModeThermostat system mode commandWrite
MV 19FanFan mode commandWrite
AV 21Cool_SetpointCooling setpointWrite
AV 22Heat_SetpointHeating setpointWrite
AI 15Indoor_TempSpace temperatureRead
MI 23Heat_Cool_StatusCurrent heating/cooling stateRead
AI 24StageActive heat/cool stageRead
BI 25Override_StatusSetpoint override activeRead
AI 16Outdoor_TempOutdoor temperature (if a sensor is fitted)Read

Network setup

Watch out for

Network Thermostat RP32H IP-WiFi Thermostat (NT-BAS ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

305 of 305 shown
Type
Access
Show
Network Thermostat RP32H IP-WiFi Thermostat (NT-BAS ProtoNode) BACnet Points List
DescriptionStates
AImin15Indoor_TempRead
AImin16Outdoor_TempRead
AImin24StageRead
AI29Firmware_Version_ARead
AI30Firmware_Version_BRead
AI31DIP_Switch_Position_1Read
AI32DIP_Switch_Position_2Read
AI33DIP_Switch_Position_3Read
AI34DIP_Switch_Position_4Read
AI35DIP_Switch_Position_5Read
AI36DIP_Switch_Position_6Read
AI37DIP_Switch_Position_7Read
AI38DIP_Switch_Position_8Read
AI67Start_Vacation_YearRead
AI68Start_Vacation_MonthRead
AI69Start_Vacation_DayRead
AI70Start_Vacation_HoursRead
AI71Start_Vacation_MinsRead
AI72End_Vacation_YearRead
AI73End_Vacation_MonthRead
AI74End_Vacation_DayRead
AI75End_Vacation_HoursRead
AI76End_Vacation_MinsRead
AV1Fan_Recirc_TimerWrite
AV2Override_Cool_SetpointWrite
AV3Override_Heat_SetpointWrite
AV4Balance_Point_LowWrite
AV5Balance_Point_HighWrite
AV6Cool_High_SetpointWrite
AV7Cool_Low_SetpointWrite
AV8Heat_High_SetpointWrite
AV9Heat_Low_SetpointWrite
AVmin21Cool_SetpointWrite
AVmin22Heat_SetpointWrite
AV26Override_Timer_Rem_HoursWrite
AV27Override_Timer_Rem_MinsWrite
AV41Damper_TimeWrite
AV42Damper_Max_TempWrite
AV43Damper_Min_TempWrite
AV44Damper_Max_HumidityWrite
AV45Damper_Min_HumidityWrite
AV47Dehumidify_Above_SetpointWrite
AV48Dehumidify_VarianceWrite
AV50Humidify_Below_SetpointWrite
AV51Humidify_VarianceWrite
AV52YearWrite
AV53MonthWrite
AV54DayWrite
AV57Passive_Start_Vacation_YearWrite
AV58Passive_Start_Vacation_MonthWrite
AV59Passive_Start_Vacation_DayWrite
AV60Passive_Start_Vacation_HoursWrite
AV61Passive_Start_Vacation_MinsWrite
AV62Passive_End_Vacation_YearWrite
AV63Passive_End_Vacation_MonthWrite
AV64Passive_End_Vacation_DayWrite
AV65Passive_End_Vacation_HoursWrite
AV66Passive_End_Vacation_MinsWrite
AV79Start_Vacation_Cool_SetpointWrite
AV80Start_Vacation_Heat_SetpointWrite
AV85Monday_Schedule_1_HoursWrite
AV86Monday_Schedule_1_MinsWrite
AV87Monday_Schedule_1_Cool_SetpointWrite
AV88Monday_Schedule_1_Heat_SetpointWrite
AV93Monday_Schedule_2_HoursWrite
AV94Monday_Schedule_2_MinsWrite
AV95Monday_Schedule_2_Cool_SetpointWrite
AV96Monday_Schedule_2_Heat_SetpointWrite
AV101Monday_Schedule_3_HoursWrite
AV102Monday_Schedule_3_MinsWrite
AV103Monday_Schedule_3_Cool_SetpointWrite
AV104Monday_Schedule_3_Heat_SetpointWrite
AV109Monday_Schedule_4_HoursWrite
AV110Monday_Schedule_4_MinsWrite
AV111Monday_Schedule_4_Cool_SetpointWrite
AV112Monday_Schedule_4_Heat_SetpointWrite
AV117Tuesday_Schedule_1_HoursWrite
AV118Tuesday_Schedule_1_MinsWrite
AV119Tuesday_Schedule_1_Cool_SetpointWrite
AV120Tuesday_Schedule_1_Heat_SetpointWrite
AV125Tuesday_Schedule_2_HoursWrite
AV126Tuesday_Schedule_2_MinsWrite
AV127Tuesday_Schedule_2_Cool_SetpointWrite
AV128Tuesday_Schedule_2_Heat_SetpointWrite
AV133Tuesday_Schedule_3_HoursWrite
AV134Tuesday_Schedule_3_MinsWrite
AV135Tuesday_Schedule_3_Cool_SetpointWrite
AV136Tuesday_Schedule_3_Heat_SetpointWrite
AV141Tuesday_Schedule_4_HoursWrite
AV142Tuesday_Schedule_4_MinsWrite
AV143Tuesday_Schedule_4_Cool_SetpointWrite
AV144Tuesday_Schedule_4_Heat_SetpointWrite
AV149Wednesday_Schedule_1_HoursWrite
AV150Wednesday_Schedule_1_MinsWrite
AV151Wednesday_Schedule_1_Cool_SetpointWrite
AV152Wednesday_Schedule_1_Heat_SetpointWrite
AV157Wednesday_Schedule_2_HoursWrite
AV158Wednesday_Schedule_2_MinsWrite
AV159Wednesday_Schedule_2_Cool_SetpointWrite
AV160Wednesday_Schedule_2_Heat_SetpointWrite
AV165Wednesday_Schedule_3_HoursWrite
AV166Wednesday_Schedule_3_MinsWrite
AV167Wednesday_Schedule_3_Cool_SetpointWrite
AV168Wednesday_Schedule_3_Heat_SetpointWrite
AV173Wednesday_Schedule_4_HoursWrite
AV174Wednesday_Schedule_4_MinsWrite
AV175Wednesday_Schedule_4_Cool_SetpointWrite
AV176Wednesday_Schedule_4_Heat_SetpointWrite
AV181Thursday_Schedule_1_HoursWrite
AV182Thursday_Schedule_1_MinsWrite
AV183Thursday_Schedule_1_Cool_SetpointWrite
AV184Thursday_Schedule_1_Heat_SetpointWrite
AV189Thursday_Schedule_2_HoursWrite
AV190Thursday_Schedule_2_MinsWrite
AV191Thursday_Schedule_2_Cool_SetpointWrite
AV192Thursday_Schedule_2_Heat_SetpointWrite
AV197Thursday_Schedule_3_HoursWrite
AV198Thursday_Schedule_3_MinsWrite
AV199Thursday_Schedule_3_Cool_SetpointWrite
AV200Thursday_Schedule_3_Heat_SetpointWrite
AV205Thursday_Schedule_4_HoursWrite
AV206Thursday_Schedule_4_MinsWrite
AV207Thursday_Schedule_4_Cool_SetpointWrite
AV208Thursday_Schedule_4_Heat_SetpointWrite
AV213Friday_Schedule_1_HoursWrite
AV214Friday_Schedule_1_MinsWrite
AV215Friday_Schedule_1_Cool_SetpointWrite
AV216Friday_Schedule_1_Heat_SetpointWrite
AV221Friday_Schedule_2_HoursWrite
AV222Friday_Schedule_2_MinsWrite
AV223Friday_Schedule_2_Cool_SetpointWrite
AV224Friday_Schedule_2_Heat_SetpointWrite
AV229Friday_Schedule_3_HoursWrite
AV230Friday_Schedule_3_MinsWrite
AV231Friday_Schedule_3_Cool_SetpointWrite
AV232Friday_Schedule_3_Heat_SetpointWrite
AV237Friday_Schedule_4_HoursWrite
AV238Friday_Schedule_4_MinsWrite
AV239Friday_Schedule_4_Cool_SetpointWrite
AV240Friday_Schedule_4_Heat_SetpointWrite
AV245Saturday_Schedule_1_HoursWrite
AV246Saturday_Schedule_1_MinsWrite
AV247Saturday_Schedule_1_Cool_SetpointWrite
AV248Saturday_Schedule_1_Heat_SetpointWrite
AV253Saturday_Schedule_2_HoursWrite
AV254Saturday_Schedule_2_MinsWrite
AV255Saturday_Schedule_2_Cool_SetpointWrite
AV256Saturday_Schedule_2_Heat_SetpointWrite
AV261Saturday_Schedule_3_HoursWrite
AV262Saturday_Schedule_3_MinsWrite
AV263Saturday_Schedule_3_Cool_SetpointWrite
AV264Saturday_Schedule_3_Heat_SetpointWrite
AV269Saturday_Schedule_4_HoursWrite
AV270Saturday_Schedule_4_MinsWrite
AV271Saturday_Schedule_4_Cool_SetpointWrite
AV272Saturday_Schedule_4_Heat_SetpointWrite
AV277Sunday_Schedule_1_HoursWrite
AV278Sunday_Schedule_1_MinsWrite
AV279Sunday_Schedule_1_Cool_SetpointWrite
AV280Sunday_Schedule_1_Heat_SetpointWrite
AV285Sunday_Schedule_2_HoursWrite
AV286Sunday_Schedule_2_MinsWrite
AV287Sunday_Schedule_2_Cool_SetpointWrite
AV288Sunday_Schedule_2_Heat_SetpointWrite
AV293Sunday_Schedule_3_HoursWrite
AV294Sunday_Schedule_3_MinsWrite
AV295Sunday_Schedule_3_Cool_SetpointWrite
AV296Sunday_Schedule_3_Heat_SetpointWrite
AV301Sunday_Schedule_4_HoursWrite
AV302Sunday_Schedule_4_MinsWrite
AV303Sunday_Schedule_4_Cool_SetpointWrite
AV304Sunday_Schedule_4_Heat_SetpointWrite
BI0Fan_Recirc_ActiveRead
BI17Outdoor_Temp_ValidRead
BI20Recovery_StatusRead
BImin25Override_StatusRead
BV11Relay_StateWrite
BV13Daylight_Savings_TimeWrite
BV55Vacation_StatusWrite
BV83Monday_Schedule_1_OccupationWrite
BV84Monday_Schedule_1_ActiveWrite
BV91Monday_Schedule_2_OccupationWrite
BV92Monday_Schedule_2_ActiveWrite
BV99Monday_Schedule_3_OccupationWrite
BV100Monday_Schedule_3_ActiveWrite
BV107Monday_Schedule_4_OccupationWrite
BV108Monday_Schedule_4_ActiveWrite
BV115Tuesday_Schedule_1_OccupationWrite
BV116Tuesday_Schedule_1_ActiveWrite
BV123Tuesday_Schedule_2_OccupationWrite
BV124Tuesday_Schedule_2_ActiveWrite
BV131Tuesday_Schedule_3_OccupationWrite
BV132Tuesday_Schedule_3_ActiveWrite
BV139Tuesday_Schedule_4_OccupationWrite
BV140Tuesday_Schedule_4_ActiveWrite
BV147Wednesday_Schedule_1_OccupationWrite
BV148Wednesday_Schedule_1_ActiveWrite
BV155Wednesday_Schedule_2_OccupationWrite
BV156Wednesday_Schedule_2_ActiveWrite
BV163Wednesday_Schedule_3_OccupationWrite
BV164Wednesday_Schedule_3_ActiveWrite
BV171Wednesday_Schedule_4_OccupationWrite
BV172Wednesday_Schedule_4_ActiveWrite
BV179Thursday_Schedule_1_OccupationWrite
BV180Thursday_Schedule_1_ActiveWrite
BV187Thursday_Schedule_2_OccupationWrite
BV188Thursday_Schedule_2_ActiveWrite
BV195Thursday_Schedule_3_OccupationWrite
BV196Thursday_Schedule_3_ActiveWrite
BV203Thursday_Schedule_4_OccupationWrite
BV204Thursday_Schedule_4_ActiveWrite
BV211Friday_Schedule_1_OccupationWrite
BV212Friday_Schedule_1_ActiveWrite
BV219Friday_Schedule_2_OccupationWrite
BV220Friday_Schedule_2_ActiveWrite
BV227Friday_Schedule_3_OccupationWrite
BV228Friday_Schedule_3_ActiveWrite
BV235Friday_Schedule_4_OccupationWrite
BV236Friday_Schedule_4_ActiveWrite
BV243Saturday_Schedule_1_OccupationWrite
BV244Saturday_Schedule_1_ActiveWrite
BV251Saturday_Schedule_2_OccupationWrite
BV252Saturday_Schedule_2_ActiveWrite
BV259Saturday_Schedule_3_OccupationWrite
BV260Saturday_Schedule_3_ActiveWrite
BV267Saturday_Schedule_4_OccupationWrite
BV268Saturday_Schedule_4_ActiveWrite
BV275Sunday_Schedule_1_OccupationWrite
BV276Sunday_Schedule_1_ActiveWrite
BV283Sunday_Schedule_2_OccupationWrite
BV284Sunday_Schedule_2_ActiveWrite
BV291Sunday_Schedule_3_OccupationWrite
BV292Sunday_Schedule_3_ActiveWrite
BV299Sunday_Schedule_4_OccupationWrite
BV300Sunday_Schedule_4_ActiveWrite
MI12Day_Of_WeekRead
MImin23Heat_Cool_StatusRead
MI28Thermostat_ModelRead
MI39Balance_Point_Compressor_StateRead
MI40Balance_Point_Aux_Heat_StateRead
MV10Relay_FunctionWrite
MV14Time_ZoneWrite
MVmin18ModeWrite
MVmin19FanWrite
MV46Dehumidify_TypeWrite
MV49Humidify_TypeWrite
MV56Passive_Vacation_TypeWrite
MV77Start_Vacation_ModeWrite
MV78Start_Vacation_FanWrite
MV81Monday_Schedule_1_ModeWrite
MV82Monday_Schedule_1_FanWrite
MV89Monday_Schedule_2_ModeWrite
MV90Monday_Schedule_2_FanWrite
MV97Monday_Schedule_3_ModeWrite
MV98Monday_Schedule_3_FanWrite
MV105Monday_Schedule_4_ModeWrite
MV106Monday_Schedule_4_FanWrite
MV113Tuesday_Schedule_1_ModeWrite
MV114Tuesday_Schedule_1_FanWrite
MV121Tuesday_Schedule_2_ModeWrite
MV122Tuesday_Schedule_2_FanWrite
MV129Tuesday_Schedule_3_ModeWrite
MV130Tuesday_Schedule_3_FanWrite
MV137Tuesday_Schedule_4_ModeWrite
MV138Tuesday_Schedule_4_FanWrite
MV145Wednesday_Schedule_1_ModeWrite
MV146Wednesday_Schedule_1_FanWrite
MV153Wednesday_Schedule_2_ModeWrite
MV154Wednesday_Schedule_2_FanWrite
MV161Wednesday_Schedule_3_ModeWrite
MV162Wednesday_Schedule_3_FanWrite
MV169Wednesday_Schedule_4_ModeWrite
MV170Wednesday_Schedule_4_FanWrite
MV177Thursday_Schedule_1_ModeWrite
MV178Thursday_Schedule_1_FanWrite
MV185Thursday_Schedule_2_ModeWrite
MV186Thursday_Schedule_2_FanWrite
MV193Thursday_Schedule_3_ModeWrite
MV194Thursday_Schedule_3_FanWrite
MV201Thursday_Schedule_4_ModeWrite
MV202Thursday_Schedule_4_FanWrite
MV209Friday_Schedule_1_ModeWrite
MV210Friday_Schedule_1_FanWrite
MV217Friday_Schedule_2_ModeWrite
MV218Friday_Schedule_2_FanWrite
MV225Friday_Schedule_3_ModeWrite
MV226Friday_Schedule_3_FanWrite
MV233Friday_Schedule_4_ModeWrite
MV234Friday_Schedule_4_FanWrite
MV241Saturday_Schedule_1_ModeWrite
MV242Saturday_Schedule_1_FanWrite
MV249Saturday_Schedule_2_ModeWrite
MV250Saturday_Schedule_2_FanWrite
MV257Saturday_Schedule_3_ModeWrite
MV258Saturday_Schedule_3_FanWrite
MV265Saturday_Schedule_4_ModeWrite
MV266Saturday_Schedule_4_FanWrite
MV273Sunday_Schedule_1_ModeWrite
MV274Sunday_Schedule_1_FanWrite
MV281Sunday_Schedule_2_ModeWrite
MV282Sunday_Schedule_2_FanWrite
MV289Sunday_Schedule_3_ModeWrite
MV290Sunday_Schedule_3_FanWrite
MV297Sunday_Schedule_4_ModeWrite
MV298Sunday_Schedule_4_FanWrite
Object ID lookup: Network Thermostat RP32H IP-WiFi Thermostat point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the RP32H IP-WiFi Thermostat (NT-BAS ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Network Thermostat RP32H IP-WiFi Thermostat (NT-BAS ProtoNode)

How many BACnet points does the Network Thermostat RP32H IP-WiFi Thermostat (NT-BAS ProtoNode) have?

This list has 305 BACnet objects: 23 analog inputs, 149 analog values, 4 binary inputs, 59 binary values, 5 multi-state inputs, 65 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Network Thermostat RP32H IP-WiFi Thermostat (NT-BAS ProtoNode) BACnet points are writable?

273 of the 305 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Network Thermostat RP32H IP-WiFi Thermostat (NT-BAS ProtoNode) BACnet documentation?

The source is Network Thermostat's ProtoNode Startup Guide (ProtoNode FPC-N34 and FPC-N35, NT-BAS), revision Document Revision 2.A, Template Revision 24, published free by Network Thermostat at https://www.networkthermostat.com/sites/default/files/2023-01/Protonode%20Startup%20Guide%20for%20NT-BAS.pdf.

What are the minimum BACnet points to integrate the Network Thermostat RP32H IP-WiFi Thermostat (NT-BAS ProtoNode)?

Start with MV 18 Mode (Thermostat system mode command); MV 19 Fan (Fan mode command); AV 21 Cool_Setpoint (Cooling setpoint); AV 22 Heat_Setpoint (Heating setpoint); AI 15 Indoor_Temp (Space temperature); MI 23 Heat_Cool_Status (Current heating/cooling state); AI 24 Stage (Active heat/cool stage); BI 25 Override_Status (Setpoint override active); AI 16 Outdoor_Temp (Outdoor temperature (if a sensor is fitted)).

How do I check these points on the real RP32H IP-WiFi Thermostat (NT-BAS ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.