Easy BACnet
  1. Home
  2. BACnet points lists
  3. MSA FieldServer
  4. QuickServer M-Bus profile - Elvaco CMa20

Room temperature and humidity sensor (M-Bus) via QuickServer gateway · BACnet points list

MSA FieldServer QuickServer M-Bus profile - Elvaco CMa20 BACnet points list

Updated 11 November 2026Unofficial source

Short answer

The QuickServer M-Bus gateway polls the meter as an M-Bus master and serves its data as 9 read-only Analog Inputs (BACnet IP or BACnet MS/TP) plus matching Modbus input registers. The object list is the gateway's fixed Elvaco CMa20 profile from the start-up guide.

This page lists 9 BACnet objects for the MSA FieldServer QuickServer M-Bus profile - Elvaco CMa20 — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of MSA FieldServer’s documentation hosted by Chipkin Automation (MSA FieldServer distributor), not by MSA FieldServer itself, so treat it as unofficial.

Manufacturer
MSA FieldServer
Model
QuickServer M-Bus profile - Elvaco CMa20
Equipment
Room temperature and humidity sensor (M-Bus) via QuickServer gateway
Equipment type
Thermostats, sensors & meters
BACnet objects
9 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
CMa20, Elvaco CMa20 M-Bus, FS-QS-1X50, QuickServer M-Bus
Source document
QuickServer Start-up Guide FS-QS-1011/12X0/12X1/1X50/1X51 (Appendix B, M-Bus Data Profiles) · T18600 · rev. Document Revision 2.J (systems made after July 2020) (unofficial copy, hosted by Chipkin Automation (MSA FieldServer distributor))
Download CSV 9 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against MSA FieldServer’s current documentation and the live device before use. Not official MSA FieldServer information. Terms of use.

BMS integration notes: MSA FieldServer QuickServer M-Bus profile - Elvaco CMa20

Integration in brief

Set the meter's M-Bus primary address and readout as its maker describes, wire it to the QuickServer's M-Bus port (R2), pick this profile, then read the Analog Inputs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 2Temp_InstTemperature, instantaneousRead
AI 6RH_InsRelative humidity, instantaneousRead
AI 1MBUS_Meter_$node_id_AlarmsMeter alarm valueRead

Network setup

Watch out for

MSA FieldServer QuickServer M-Bus profile - Elvaco CMa20 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

9 of 9 shown
Type
Analog
Show
MSA FieldServer QuickServer M-Bus profile - Elvaco CMa20 BACnet Points List
DescriptionStates
AImin1MBUS_Meter_$node_id_AlarmsRead
AImin2Temp_InstRead
AI3Temp_MinRead
AI4Temp_MaxRead
AI5Temp_AvgRead
AImin6RH_InsRead
AI7RH_MinRead
AI8RH_MaxRead
AI9RH_AvgRead
Object ID lookup: MSA FieldServer QuickServer Elvaco CMa20 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the QuickServer M-Bus profile - Elvaco CMa20 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the MSA FieldServer QuickServer M-Bus profile - Elvaco CMa20

How many BACnet points does the MSA FieldServer QuickServer M-Bus profile - Elvaco CMa20 have?

This list has 9 BACnet objects: 9 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which MSA FieldServer QuickServer M-Bus profile - Elvaco CMa20 BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official MSA FieldServer QuickServer M-Bus profile - Elvaco CMa20 BACnet documentation?

MSA FieldServer does not publish it on its own website. This list comes from QuickServer Start-up Guide FS-QS-1011/12X0/12X1/1X50/1X51 (Appendix B, M-Bus Data Profiles) (T18600), revision Document Revision 2.J (systems made after July 2020), a copy hosted by Chipkin Automation (MSA FieldServer distributor) at https://cdn.chipkin.com/assets/uploads/2020/Oct/FS-QS-1XXX%20-%20QuickServer%20Gateway%20-%20Manual_08-20-50-57.pdf. Ask MSA FieldServer or its representative for the current revision.

What are the minimum BACnet points to integrate the MSA FieldServer QuickServer M-Bus profile - Elvaco CMa20?

Start with AI 2 Temp_Inst (Temperature, instantaneous); AI 6 RH_Ins (Relative humidity, instantaneous); AI 1 MBUS_Meter_$node_id_Alarms (Meter alarm value).

How do I check these points on the real QuickServer M-Bus profile - Elvaco CMa20?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More MSA FieldServer BACnet points lists

Source: QuickServer Start-up Guide FS-QS-1011/12X0/12X1/1X50/1X51 (Appendix B, M-Bus Data Profiles) · T18600 · rev. Document Revision 2.J (systems made after July 2020). Object names, instances and units are reproduced as published; descriptions are our own.