- Home
- BACnet points lists
- Measurlogic
- DTS MCM multi-circuit monitoring system (BACnet IP, DTS E4C)
Energy meter (multi-circuit sub-metering system) · BACnet points list
Measurlogic DTS MCM multi-circuit monitoring system (BACnet IP, DTS E4C) BACnet points list
Updated 12 November 2026
The DTS MCM is a weatherproof multi-circuit sub-metering enclosure: 3 to 8 three-circuit DTS 307 meters, breakers and a DTS E4C Ethernet module that serves all meters as one BACnet IP device. Common voltage and frequency objects come first, then one group of current, power, power factor, demand and energy objects for each meter. This entry lists the common objects and meter 1, as printed; the other meters repeat the meter 1 group.
This page lists 25 BACnet objects for the Measurlogic DTS MCM multi-circuit monitoring system (BACnet IP, DTS E4C) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Measurlogic’s own free documentation, linked below.
- Manufacturer
- Measurlogic
- Model
- DTS MCM multi-circuit monitoring system (BACnet IP, DTS E4C)
- Equipment
- Energy meter (multi-circuit sub-metering system)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 25 (0 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Default device instance
- 473001
- Also known as
- DTS MCM, DTS MCM-x-9C, DTS MCM-x-12C, DTS MCM-x-18C, DTS MCM-x-24C, DTS MCM-EB, DTS E4C, Measurlogic MCM
- Source document
- Measurlogic DTS MCM BACnet/IP Object Map · rev. R26A
Reference only, provided as-is: verify against Measurlogic’s current documentation and the live device before use. Not official Measurlogic information. Terms of use.
BMS integration notes: Measurlogic DTS MCM multi-circuit monitoring system (BACnet IP, DTS E4C)
Give the E4C module an IP address with DTS Discover or its web pages and set a unique Device ID (default 473001). Read voltages and frequency once, then the total power, demand and energy objects of each meter group (1n10, 1n31, 1n44).
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 1110 | PowerP_1_Tot | Meter 1 total active power, kW | Read |
| AI 1144 | EnergyP_1_Tot | Meter 1 net active energy, kWh | Read |
| AI 1131 | DmdP_1_Tot | Meter 1 demand, kW | Read |
| AI 1101 | Curr_1_1 | Meter 1 current, phase A | Read |
| AI 1001 | Volt_LN_1 | Voltage L-N, phase A | Read |
| AI 1009 | Frequency | Line frequency, Hz | Read |
Network setup
- Default Device ID 473001; change it on the E4C's BACnet Settings web page.
- DTS Discover finds the E4C on the network and sets its IP address.
- CT type and rating per meter are set on the Electrical Settings web page.
- Modbus TCP (port 502, Modbus address = meter number) is for configuration with DTS Config only.
Watch out for
- Objects for meter groups beyond the model's meter count do not exist (e.g. no 15xx objects on a 12C).
Measurlogic DTS MCM multi-circuit monitoring system (BACnet IP, DTS E4C) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1001 | Volt_LN_1 | Voltage line-neutral A | V | Read | |
| AI | 1002 | Volt_LN_2 | Voltage line-neutral B | V | Read | |
| AI | 1003 | Volt_LN_3 | Voltage line-neutral C | V | Read | |
| AI | 1005 | Volt_LL_12 | Voltage line-line A-B | V | Read | |
| AI | 1006 | Volt_LL_23 | Voltage line-line B-C | V | Read | |
| AI | 1007 | Volt_LL_31 | Voltage line-line C-A | V | Read | |
| AImin | 1009 | Frequency | Frequency | Hz | Read | |
| AImin | 1101 | Curr_1_1 | Meter 1 current phase A | A | Read | |
| AI | 1102 | Curr_1_2 | Meter 1 current phase B | A | Read | |
| AI | 1103 | Curr_1_3 | Meter 1 current phase C | A | Read | |
| AI | 1107 | PowerP_1_1 | Meter 1 active power phase A | kW | Read | |
| AI | 1108 | PowerP_1_2 | Meter 1 active power phase B | kW | Read | |
| AI | 1109 | PowerP_1_3 | Meter 1 active power phase C | kW | Read | |
| AImin | 1110 | PowerP_1_Tot | Meter 1 total active power | kW | Read | |
| AI | 1119 | PF_1_1 | Meter 1 power factor phase A | Read | ||
| AI | 1120 | PF_1_2 | Meter 1 power factor phase B | Read | ||
| AI | 1121 | PF_1_3 | Meter 1 power factor phase C | Read | ||
| AImin | 1131 | DmdP_1_Tot | Meter 1 instantaneous demand | kW | Read | |
| AI | 1132 | DmdP_1_Tot_Max | Meter 1 maximum demand | kW | Read | |
| AI | 1141 | EnergyP_1_1 | Meter 1 net active energy phase A | kWh | Read | |
| AI | 1142 | EnergyP_1_2 | Meter 1 net active energy phase B | kWh | Read | |
| AI | 1143 | EnergyP_1_3 | Meter 1 net active energy phase C | kWh | Read | |
| AImin | 1144 | EnergyP_1_Tot | Meter 1 net active energy total | kWh | Read | |
| AI | 1153 | EnergyP_1_Tot_Imp | Meter 1 active energy consumed from grid | kWh | Read | |
| AI | 1154 | EnergyP_1_Tot_Exp | Meter 1 active energy returned to grid | kWh | Read |
No points match these filters.
Object ID lookup: Measurlogic DTS MCM multi-circuit monitoring system point IDs by name
AI1001Volt_LN_1AI1002Volt_LN_2AI1003Volt_LN_3AI1005Volt_LL_12AI1006Volt_LL_23AI1007Volt_LL_31AI1009FrequencyAI1101Curr_1_1AI1102Curr_1_2AI1103Curr_1_3AI1107PowerP_1_1AI1108PowerP_1_2AI1109PowerP_1_3AI1110PowerP_1_TotAI1119PF_1_1AI1120PF_1_2AI1121PF_1_3AI1131DmdP_1_TotAI1132DmdP_1_Tot_MaxAI1141EnergyP_1_1AI1142EnergyP_1_2AI1143EnergyP_1_3AI1144EnergyP_1_TotAI1153EnergyP_1_Tot_ImpAI1154EnergyP_1_Tot_Exp
Integration notes
- Meter groups 2 to N follow the printed pattern: instance 1n01-1n54 and names with _n_ (e.g. meter 3 total power = AI 1310, PowerP_3_Tot). N is 3, 4, 6 or 8 for the 9C, 12C, 18C and 24C models.
- Only the common objects and meter 1 are listed here, as printed in the map; the other groups are not generated.
- The map lists no access column; all listed objects are measurements and shown read-only. The device ID is changed on the BACnet Settings web page.
- Power factor objects have no units printed.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the DTS MCM multi-circuit monitoring system (BACnet IP, DTS E4C) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Measurlogic DTS MCM multi-circuit monitoring system (BACnet IP, DTS E4C)
How many BACnet points does the Measurlogic DTS MCM multi-circuit monitoring system (BACnet IP, DTS E4C) have?
This list has 25 BACnet objects: 25 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Measurlogic DTS MCM multi-circuit monitoring system (BACnet IP, DTS E4C) BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Measurlogic DTS MCM multi-circuit monitoring system (BACnet IP, DTS E4C) BACnet documentation?
The source is Measurlogic DTS MCM BACnet/IP Object Map, revision R26A, published free by Measurlogic at https://www.measurlogic.com/wp-content/uploads/2026/06/Measurlogic-DTS_MCM-EB-BACnet_IP-Map-R26A.pdf.
What are the minimum BACnet points to integrate the Measurlogic DTS MCM multi-circuit monitoring system (BACnet IP, DTS E4C)?
Start with AI 1110 PowerP_1_Tot (Meter 1 total active power, kW); AI 1144 EnergyP_1_Tot (Meter 1 net active energy, kWh); AI 1131 DmdP_1_Tot (Meter 1 demand, kW); AI 1101 Curr_1_1 (Meter 1 current, phase A); AI 1001 Volt_LN_1 (Voltage L-N, phase A); AI 1009 Frequency (Line frequency, Hz).
How do I check these points on the real DTS MCM multi-circuit monitoring system (BACnet IP, DTS E4C)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Measurlogic BACnet points lists
Source: Measurlogic DTS MCM BACnet/IP Object Map · rev. R26A. Object names, instances and units are reproduced as published; descriptions are our own.