  3. Marley Engineered Products
  4. Smart Series Plus digital heater controller (BACnet MS/TP)

Thermostat / controller for cabinet unit heaters · BACnet points list

Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP) BACnet points list

Updated 12 November 2026

Short answer

The Smart Series Plus is a wall-mount digital controller for Marley Engineered Products heaters, built on Honeywell's BACnet FF (TB3026B) platform with application 5 loaded. It joins BACnet MS/TP and exposes the platform's setpoint, display, occupancy and schedule objects plus the heater application's settings: output enable, fan mode, standby, heating loop gains, fan start/stop and BMS scheduling options.

This page lists 208 BACnet objects for the Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP) — 179 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Marley Engineered Products’s own free documentation, linked below.

Manufacturer
Marley Engineered Products
Model
Smart Series Plus digital heater controller (BACnet MS/TP)
Equipment
Thermostat / controller for cabinet unit heaters
Equipment type
Thermostats, sensors & meters
BACnet objects
208 (179 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
9999
Also known as
Smart Series Plus, Smart-Series Plus, 5200-11256-004, Marley unit heater BACnet controller
Source document
Smart Series Plus Installation and Operations Guide (English section, Appendix A and B) · 5200-11256-004 · rev. 10/23
Download CSV 208 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Marley Engineered Products’s current documentation and the live device before use. Not official Marley Engineered Products information. Terms of use.

BMS integration notes: Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP)

Integration in brief

Set Output Enable (BV 2) ON, the MS/TP MAC and device instance (ISU 800-804), and decide between the internal schedule and BMS scheduling (BV 56). Then write occupancy (BV 40) and the occupied setpoint AV 90, and read the room temperature, active heating setpoint and occupied status.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2Output EnableOutput enable; must be ON for the heater to runWrite
BV 56Enable BMS SchedulingEnable BMS scheduling (overrides internal schedule)Write
AV 90Setpoint (SP)Occupied space setpointWrite
AV 96Unoccupied Heating SPUnoccupied heating setpointWrite
BV 9Enable Communication FailureGo occupied on MS/TP comm failureWrite
AV 104Sensed Room TemperatureRoom temperature (built-in sensor)Read
AV 100Current Heating SPActive heating setpointRead
BV 67Occupied/Unoccupied StatusOccupied / unoccupied statusRead

Enable & remote start

BV 2 Output Enable must be ON. With BV 56 active the BMS schedules occupancy (BV 40, priority array) instead of the internal schedule.

Heartbeat & communication loss

BV 9 Enable Communication Failure: when active the controller falls back to occupied if MS/TP communication fails.

Network setup

Watch out for

Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

208 of 208 shown
Type
AnalogBinaryMulti-state
Access
Show
Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP) BACnet Points List
DescriptionStates
AVmin90Setpoint (SP)Occupied space setpoint°F/°CWrite
AV91Setpoint High LimitSetpoint high limit°F/°CWrite
AV92Setpoint Low LimitSetpoint low limit°F/°CWrite
AV93Cooling SP OffsetCooling setpoint offset°F/°CWrite
AV94Heating SP OffsetHeating setpoint offset°F/°CWrite
AV95Unoccupied Cooling SPUnoccupied cooling setpoint°F/°CWrite
AVmin96Unoccupied Heating SPUnoccupied heating setpoint°F/°CWrite
AV97After Hours Timer LimitAfter-hours override limithWrite
AV98After Hours TimerAfter-hours timerWrite
AV99Current Cooling SPActive cooling setpoint°F/°CRead
AVmin100Current Heating SPActive heating setpoint°F/°CRead
AV101Displayed Room TemperatureRoom temperature shown on the display°F/°CRead
AVmin104Sensed Room TemperatureRoom temperature from the built-in sensor°F/°CRead
AV105Sensed Room HumidityRoom humidity from the built-in sensor%RHRead
AV106Demand OffsetDemand (standby) offsetWrite
AV108SP Mode Cooling SPCooling setpoint in setpoint mode°F/°CWrite
AV109SP Mode Heating SPHeating setpoint in setpoint mode°F/°CWrite
AV110SP Mode Setpoint ModeSetpoint Mode: Chooses the setpoint model, and also selects the layout of...Write0.0=use OFF Format (no setpoints shown), 1.0=use 1-setpoint format (cooling), 2.0=use 1-setpoint format (heating), 3.0=use 2-setpoint format Occupancy Mode: Ignored
AV111SYSTEM Setpoint ModelProvides a compatible output from the SYSTEM control that can be...Write0.0=OFF selected, 1.0=COOL selected, 2.0=HEAT/EM HEAT selected, 3.0=AUTO selected
AV113SP Override Mode AVIn setpoint mode: setpoint override stateWrite1.0=scheduled, 2.0=temporary, 3.0=permanent, 4.0=vacation, 5.0=initial
AV114Filter RuntimeCurrent filter runtime hoursHoursWrite
AV115Filter Runtime LimitFilter runtime limitHoursRead
AV117UV Lamp Runtime LimitUV Lamp runtime limitHoursRead
AV123Set system to Occupancy modeSets system to Occupancy modeWrite
AV124Filter Change ReminderEnables the filter change reminderWrite
AV127Daylight savingsSets Daylight savings to Off, pre-2007 scheme, or post-2007 schemeWrite
AV128Keypad lockLocks the keypadWrite
AV129Weekday periods ISU valueSchedule periods per weekday (ISU 540)Write2=Two schedule periods per day, 4=Four schedule periods per day
AV130Hold until timeIn setpoint mode: minute of the day (0-1440) at which a temporary or vMinutesWrite
AV131Vacation days remainingIn setpoint mode: number of days remaining in a vacation overrideDaysWrite
AV132Field service mode security PINAllows access to Field Service mode only by authorized usersWrite
AV133ISU mode security PINAllows access to ISU mode only by authorized usersWrite
AV137Fan Setting Display FormatSelects the format in which fan settings are shown on the displayWrite
AV138Sensed Temperature OffsetLimited to +/- 4 degrees F°F/°CWrite
AV210UHLH numberCustom screen field settingWrite
AV211ULHC left characterCustom screen field settingWrite
AV212ULHC right characterCustom screen field settingWrite
AV213URHC numberCustom screen field settingWrite
AV214URHC 10 charCustom screen field settingWrite
AV215URHC 1 charCustom screen field settingWrite
AV216URHC minimumCustom screen field settingWrite
AV217URHC maximumCustom screen field settingWrite
AV218URHC deltaCustom screen field settingWrite
AV219LLHC numberCustom screen field settingWrite
AV220LLHC 10 charCustom screen field settingWrite
AV221LLHC 1 charCustom screen field settingWrite
AV222LLHC minimumCustom screen field settingWrite
AV223LLHC maximumCustom screen field settingWrite
AV224LLHC deltaCustom screen field settingWrite
AV225LLHC 1000 charCustom screen field settingWrite
AV226LLHC 100 charCustom screen field settingWrite
AV227LRHC numberCustom screen field settingWrite
AV228LRHC 10 charCustom screen field settingWrite
AV229LRHC 1 charCustom screen field settingWrite
AV230LRHC minimumCustom screen field settingWrite
AV231LRHC maximumCustom screen field settingWrite
AV232LRHC deltaCustom screen field settingWrite
BV64Time Schedule OutputSchedule output (occupied when on)Read
BV65User ON/OFF in Occupied ModeUser on/off in occupied modeWrite
BV66After Hours Timer StatusAfter-hours timer runningRead
BVmin67Occupied/Unoccupied StatusOccupied / unoccupied statusRead
BV68Field service LockoutField service lockoutWrite
BV69Swap English/MetricSwap English / metric displayWrite
BV71English (OFF) / Metric (ON)English (off) or metric (on)Write
BV72Fan stage 1Fan stage 1 output statusRead
BV73Fan stage 2Fan stage 2 output statusRead
BV74Fan stage 3Fan stage 3 output statusRead
BV77Heating ICONDisplay 'heat on' iconWrite
BV78Cooling ICONDisplay 'cool on' iconWrite
BV79Backlight ONBacklight onWrite
BV80Enable Fan Speed ControlAllow the 'FAN' control to be visible to the end userWrite
BV81Select Hotel ModeHotel modeWrite
BV82Enable Time DisplayShow timeWrite
BV8324Hr Time Format24-hour clockWrite
BV84Enable Space HumidityDisplay space humidity as appropriateWrite
BV102Enable System ControlAllow the 'SYSTEM' control to be visibleWrite
BV103Hide Fan and SystemHide the FAN and SYSTEM controls in unoccupied mode (regardless of other...Write
BV104Enable DOWAllow day of week to be shown is possibleWrite
BV105Show Unocc SetpointsDisplay the unoccupied heating/cooling setpoints in unoccupied modeWrite
BV106Show WaitDisplay 'Wait'Write
BV107Show Aux heat onDisplay 'Aux heat on'Write
BV111Force CHANGE FILTERForce 'CHANGE FILTER' to be displayed (can also be automatically displayed...Write
BV114Disable SCHED keyIf set, the user is not allowed to view schedulesWrite
BV115Disable Permanent HOLD keyAllow 'HOLD' key to be used to access the Permanent Hold UIWrite
BV116Disable CLOCK keyAllow 'CLOCK' key to be used to set clock (if appropriate)Write
BV117Allow System OFFAllow system OFFWrite
BV118Allow System HEATAllow system HEATWrite
BV119Allow System COOLAllow system COOLWrite
BV120Allow System AUTOAllow system AUTOWrite
BV121Allow System EM HEATAllow system EM HEATWrite
BV122System HEAT ModeSystem HEAT modeWrite
BV123System COOL ModeSystem COOL modeWrite
BV124System AUTO ModeSystem AUTO modeWrite
BV125System EM HEAT ModeSystem EM HEAT modeWrite
BV130Disable Vacation HOLD keyAllow 'HOLD' key to be used to access the standard Vacation Hold UI (if...Write
BV131Hotel Standby ModeSet Active by DDC to indicate to the display that DDC is controlling to...Write
BV133Enable internal scheduleInternal 7-day scheduling is enabled (subject to other factors)Write
BV134Filter EnableEnable filter timer and automatic 'change filter' warningWrite
BV135Filter ONAccumulator ONWrite
BV141Disable schedule editInhibits screen EDIT keyWrite
BV142Master OFFNo effectWrite
BV200AIn Current ModeAI 0: current mode selectWrite
BV201AIn Current ModeAI 1: current mode selectWrite
BV202AIn Current ModeAI 2: current mode selectWrite
BV210Custom 1 EnableCustom screen element / keyWrite
BV211ResetCustom screen element / keyWrite
BV212ULHC enableCustom screen element / keyWrite
BV213ULHC decimalCustom screen element / keyWrite
BV214ULHC lead zeroCustom screen element / keyWrite
BV215URHC enableCustom screen element / keyWrite
BV216URHC decimalCustom screen element / keyWrite
BV217URHC lead zeroCustom screen element / keyWrite
BV218URHC editCustom screen element / keyWrite
BV219LLHC enableCustom screen element / keyWrite
BV220LLHC lead zeroCustom screen element / keyWrite
BV221LLHC editCustom screen element / keyWrite
BV222LRHC enableCustom screen element / keyWrite
BV223LRHC decimalCustom screen element / keyWrite
BV224LRHC lead zeroCustom screen element / keyWrite
BV225LRHC editCustom screen element / keyWrite
BV226LRHC leading 1Custom screen element / keyWrite
BV227Day boxesCustom screen element / keyWrite
BV228Mon textCustom screen element / keyWrite
BV229Tue textCustom screen element / keyWrite
BV230Wed textCustom screen element / keyWrite
BV231Thu textCustom screen element / keyWrite
BV232Fri textCustom screen element / keyWrite
BV233Sat textCustom screen element / keyWrite
BV234Sun textCustom screen element / keyWrite
BV235Mon checkCustom screen element / keyWrite
BV236Tue checkCustom screen element / keyWrite
BV237Wed checkCustom screen element / keyWrite
BV238Thu checkCustom screen element / keyWrite
BV239Fri checkCustom screen element / keyWrite
BV240Sat checkCustom screen element / keyWrite
BV241Sun checkCustom screen element / keyWrite
BV242Ok to pickCustom screen element / keyWrite
BV243Screen lockedCustom screen element / keyWrite
BV244ChangeCustom screen element / keyWrite
BV245FilterCustom screen element / keyWrite
BV250InsideCustom screen element / keyWrite
BV253Set toCustom screen element / keyWrite
BV254AuxCustom screen element / keyWrite
BV255Heat OnCustom screen element / keyWrite
BV256WaitCustom screen element / keyWrite
BV257Cool OnCustom screen element / keyWrite
BV258Heat AdjustCustom screen element / keyWrite
BV260FollowCustom screen element / keyWrite
BV262URHC Adj ArrowsCustom screen element / keyWrite
BV263PmCustom screen element / keyWrite
BV264AmCustom screen element / keyWrite
BV265DaysCustom screen element / keyWrite
BV266LLHC Adj ArrowsCustom screen element / keyWrite
BV268PermanentCustom screen element / keyWrite
BV269Hold UntilCustom screen element / keyWrite
BV270Cancel PeriodCustom screen element / keyWrite
BV271OutsideCustom screen element / keyWrite
BV272DECustom screen element / keyWrite
BV280VentCustom screen element / keyWrite
BV281Mon keyCustom screen element / keyWrite
BV282Tue keyCustom screen element / keyWrite
BV283Wed keyCustom screen element / keyWrite
BV284Thu keyCustom screen element / keyWrite
BV285Fri keyCustom screen element / keyWrite
BV286Sat keyCustom screen element / keyWrite
BV287Sun keyCustom screen element / keyWrite
BV292LLHC up keyCustom screen element / keyWrite
BV293LLHC dn keyCustom screen element / keyWrite
BV294RESET keyCustom screen element / keyWrite
BV295CANCEL PERIOD keyCustom screen element / keyWrite
BV297FAN keyCustom screen element / keyWrite
BV298SYSTEM keyCustom screen element / keyWrite
BV300AOn Current ModeAO 0: current mode detectedRead
BV301AOn Current ModeAO 1: current mode detectedRead
BV400AIn PullupAI 0: pull-up enableWrite
BV401AIn PullupAI 1: pull-up enableWrite
BV402AIn PullupAI 2: pull-up enableWrite
MV0Time ModeDevice's time handling capability: Normal clock operation willRead1=Time Of Day Unknown Mode, 2=Time Of Day Available Mode, 3=Date/Time Available Mode
MV1Schedule ModelDevice's schedule modelRead1=Setpoint, 2=Occupancy
MV2Keypad LockKeypad access levelRead1=full access, 2=setpoints only, 3=locked
MV3DLS ModeMode of Daylight Saving operationRead1=OFF, 2=Auto (pre-2007), 3=Auto (2007 and later)
MV4SP IncrementAmount of change in setpoint per arrow pressRead
MV5Schedule IncrementAmount of change in schedule times per arrow pressRead
MV6User SYSTEM selectionDisplay / screen settingRead
MV7Fan statusDisplay / screen settingRead
MV8Fan OFF textDisplay / screen settingRead
MV9Fan stage 1 textDisplay / screen settingRead
MV10Fan stage 2 textDisplay / screen settingRead
MV11Fan stage 3 textDisplay / screen settingRead
MV12Schedule FormatThis point is a human-friendly version of AV-129, ISU parameter 540 (see...Read1=2 commands per day, 2=4 commands per day
MV13SP Override ModeIn setpoint mode: setpoint override stateRead1=scheduled, 2=temporary, 3=permanent, 4=vacation
AV49Application SelectionApplication number, default 5 (0-18)Write
BVmin2Output EnableSet ON to enable the outputsWriteOFF, ON
AV17Fan 1=Cont 2=CycHtg 3=CycHtgClgFan mode: continuous or cyclingWrite1=Cont, 2=CycHtg, 3=CycHtgClg
AV19standby offsetStandby offset, 0-6 degrees; copied to AV 106°F/°CWrite
AV20Standby Delay SecondsStandby delay, default 180sWrite
BV27Heating LockoutHeating lockoutWriteInactive, Active
BVmin56Enable BMS SchedulingBMS scheduling instead of internal scheduleWriteInactive, Active
BVmin9Enable Communication FailureGo occupied on MS/TP comm failureWriteInactive, Active
BV10Enable System OFFAllow system OFFWriteInactive, Active
AV40AC HP Mode1 = thermostat emulation, 2 = analog to BIN controlWrite1, 2
AV41Heating Signal KpHeating loop proportional gain, default 20Write
AV42Heating Signal KiHeating loop integral gain, default 1Write
AV46Auto Fan Start Demand %Fan start demand, default 20%Write
AV53Auto Fan Stop Deadband SPFan stop deadband, default 5%Write
AV77Filter Alarm SPFilter alarm runtime, default 3000hWrite
AV782PVlvMode Set DB%Two-position valve set deadband, default 20%Write
AV792PVlvMode Reset DB%Two-position valve reset deadband, default 1%Write
Object ID lookup: Marley Engineered Products Smart Series Plus digital heater controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Smart Series Plus digital heater controller (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP)

How many BACnet points does the Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP) have?

This list has 208 BACnet objects: 69 analog values, 125 binary values, 14 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP) BACnet points are writable?

179 of the 208 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP) BACnet documentation?

The source is Smart Series Plus Installation and Operations Guide (English section, Appendix A and B) (5200-11256-004), revision 10/23, published free by Marley Engineered Products at https://www.marleymep.com/wp-content/uploads/5200-11256-004.pdf.

What are the minimum BACnet points to integrate the Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP)?

Start with BV 2 Output Enable (Output enable; must be ON for the heater to run); BV 56 Enable BMS Scheduling (Enable BMS scheduling (overrides internal schedule)); AV 90 Setpoint (SP) (Occupied space setpoint); AV 96 Unoccupied Heating SP (Unoccupied heating setpoint); BV 9 Enable Communication Failure (Go occupied on MS/TP comm failure); AV 104 Sensed Room Temperature (Room temperature (built-in sensor)); AV 100 Current Heating SP (Active heating setpoint); BV 67 Occupied/Unoccupied Status (Occupied / unoccupied status).

How do I enable BMS control of the Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP)?

BV 2 Output Enable must be ON. With BV 56 active the BMS schedules occupancy (BV 40, priority array) instead of the internal schedule.

Does the Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?

BV 9 Enable Communication Failure: when active the controller falls back to occupied if MS/TP communication fails.

How do I check these points on the real Smart Series Plus digital heater controller (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Smart Series Plus Installation and Operations Guide (English section, Appendix A and B) · 5200-11256-004 · rev. 10/23. Object names, instances and units are reproduced as published; descriptions are our own.