- Home
- BACnet points lists
- Marley Engineered Products
- Smart Series Plus digital heater controller (BACnet MS/TP)
Thermostat / controller for cabinet unit heaters · BACnet points list
Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP) BACnet points list
Updated 12 November 2026
The Smart Series Plus is a wall-mount digital controller for Marley Engineered Products heaters, built on Honeywell's BACnet FF (TB3026B) platform with application 5 loaded. It joins BACnet MS/TP and exposes the platform's setpoint, display, occupancy and schedule objects plus the heater application's settings: output enable, fan mode, standby, heating loop gains, fan start/stop and BMS scheduling options.
This page lists 208 BACnet objects for the Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP) — 179 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Marley Engineered Products’s own free documentation, linked below.
- Manufacturer
- Marley Engineered Products
- Model
- Smart Series Plus digital heater controller (BACnet MS/TP)
- Equipment
- Thermostat / controller for cabinet unit heaters
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 208 (179 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 9999
- Also known as
- Smart Series Plus, Smart-Series Plus, 5200-11256-004, Marley unit heater BACnet controller
Reference only, provided as-is: verify against Marley Engineered Products’s current documentation and the live device before use. Not official Marley Engineered Products information. Terms of use.
BMS integration notes: Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP)
Set Output Enable (BV 2) ON, the MS/TP MAC and device instance (ISU 800-804), and decide between the internal schedule and BMS scheduling (BV 56). Then write occupancy (BV 40) and the occupied setpoint AV 90, and read the room temperature, active heating setpoint and occupied status.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 2 | Output Enable | Output enable; must be ON for the heater to run | Write |
| BV 56 | Enable BMS Scheduling | Enable BMS scheduling (overrides internal schedule) | Write |
| AV 90 | Setpoint (SP) | Occupied space setpoint | Write |
| AV 96 | Unoccupied Heating SP | Unoccupied heating setpoint | Write |
| BV 9 | Enable Communication Failure | Go occupied on MS/TP comm failure | Write |
| AV 104 | Sensed Room Temperature | Room temperature (built-in sensor) | Read |
| AV 100 | Current Heating SP | Active heating setpoint | Read |
| BV 67 | Occupied/Unoccupied Status | Occupied / unoccupied status | Read |
Enable & remote start
BV 2 Output Enable must be ON. With BV 56 active the BMS schedules occupancy (BV 40, priority array) instead of the internal schedule.
Heartbeat & communication loss
BV 9 Enable Communication Failure: when active the controller falls back to occupied if MS/TP communication fails.
Network setup
- Factory defaults: MS/TP MAC 0 (valid 0-127), device instance 0009999 (valid 0-4194302).
- MS/TP MAC is ISU 800 (0-127); device instance is entered in parts through ISU 801-804.
- Application selection AV 49 must stay at 5 for Marley heaters.
Watch out for
- Table 24 marks several display objects 'Do Not Change'; leave them at their defaults.
- SYSTEM block OFF (BV 102 visible) overrides scheduled occupied to unoccupied.
Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 90 | Setpoint (SP) | Occupied space setpoint | °F/°C | Write | |
| AV | 91 | Setpoint High Limit | Setpoint high limit | °F/°C | Write | |
| AV | 92 | Setpoint Low Limit | Setpoint low limit | °F/°C | Write | |
| AV | 93 | Cooling SP Offset | Cooling setpoint offset | °F/°C | Write | |
| AV | 94 | Heating SP Offset | Heating setpoint offset | °F/°C | Write | |
| AV | 95 | Unoccupied Cooling SP | Unoccupied cooling setpoint | °F/°C | Write | |
| AVmin | 96 | Unoccupied Heating SP | Unoccupied heating setpoint | °F/°C | Write | |
| AV | 97 | After Hours Timer Limit | After-hours override limit | h | Write | |
| AV | 98 | After Hours Timer | After-hours timer | Write | ||
| AV | 99 | Current Cooling SP | Active cooling setpoint | °F/°C | Read | |
| AVmin | 100 | Current Heating SP | Active heating setpoint | °F/°C | Read | |
| AV | 101 | Displayed Room Temperature | Room temperature shown on the display | °F/°C | Read | |
| AVmin | 104 | Sensed Room Temperature | Room temperature from the built-in sensor | °F/°C | Read | |
| AV | 105 | Sensed Room Humidity | Room humidity from the built-in sensor | %RH | Read | |
| AV | 106 | Demand Offset | Demand (standby) offset | Write | ||
| AV | 108 | SP Mode Cooling SP | Cooling setpoint in setpoint mode | °F/°C | Write | |
| AV | 109 | SP Mode Heating SP | Heating setpoint in setpoint mode | °F/°C | Write | |
| AV | 110 | SP Mode Setpoint Mode | Setpoint Mode: Chooses the setpoint model, and also selects the layout of... | Write | 0.0=use OFF Format (no setpoints shown), 1.0=use 1-setpoint format (cooling), 2.0=use 1-setpoint format (heating), 3.0=use 2-setpoint format Occupancy Mode: Ignored | |
| AV | 111 | SYSTEM Setpoint Model | Provides a compatible output from the SYSTEM control that can be... | Write | 0.0=OFF selected, 1.0=COOL selected, 2.0=HEAT/EM HEAT selected, 3.0=AUTO selected | |
| AV | 113 | SP Override Mode AV | In setpoint mode: setpoint override state | Write | 1.0=scheduled, 2.0=temporary, 3.0=permanent, 4.0=vacation, 5.0=initial | |
| AV | 114 | Filter Runtime | Current filter runtime hours | Hours | Write | |
| AV | 115 | Filter Runtime Limit | Filter runtime limit | Hours | Read | |
| AV | 117 | UV Lamp Runtime Limit | UV Lamp runtime limit | Hours | Read | |
| AV | 123 | Set system to Occupancy mode | Sets system to Occupancy mode | Write | ||
| AV | 124 | Filter Change Reminder | Enables the filter change reminder | Write | ||
| AV | 127 | Daylight savings | Sets Daylight savings to Off, pre-2007 scheme, or post-2007 scheme | Write | ||
| AV | 128 | Keypad lock | Locks the keypad | Write | ||
| AV | 129 | Weekday periods ISU value | Schedule periods per weekday (ISU 540) | Write | 2=Two schedule periods per day, 4=Four schedule periods per day | |
| AV | 130 | Hold until time | In setpoint mode: minute of the day (0-1440) at which a temporary or v | Minutes | Write | |
| AV | 131 | Vacation days remaining | In setpoint mode: number of days remaining in a vacation override | Days | Write | |
| AV | 132 | Field service mode security PIN | Allows access to Field Service mode only by authorized users | Write | ||
| AV | 133 | ISU mode security PIN | Allows access to ISU mode only by authorized users | Write | ||
| AV | 137 | Fan Setting Display Format | Selects the format in which fan settings are shown on the display | Write | ||
| AV | 138 | Sensed Temperature Offset | Limited to +/- 4 degrees F | °F/°C | Write | |
| AV | 210 | UHLH number | Custom screen field setting | Write | ||
| AV | 211 | ULHC left character | Custom screen field setting | Write | ||
| AV | 212 | ULHC right character | Custom screen field setting | Write | ||
| AV | 213 | URHC number | Custom screen field setting | Write | ||
| AV | 214 | URHC 10 char | Custom screen field setting | Write | ||
| AV | 215 | URHC 1 char | Custom screen field setting | Write | ||
| AV | 216 | URHC minimum | Custom screen field setting | Write | ||
| AV | 217 | URHC maximum | Custom screen field setting | Write | ||
| AV | 218 | URHC delta | Custom screen field setting | Write | ||
| AV | 219 | LLHC number | Custom screen field setting | Write | ||
| AV | 220 | LLHC 10 char | Custom screen field setting | Write | ||
| AV | 221 | LLHC 1 char | Custom screen field setting | Write | ||
| AV | 222 | LLHC minimum | Custom screen field setting | Write | ||
| AV | 223 | LLHC maximum | Custom screen field setting | Write | ||
| AV | 224 | LLHC delta | Custom screen field setting | Write | ||
| AV | 225 | LLHC 1000 char | Custom screen field setting | Write | ||
| AV | 226 | LLHC 100 char | Custom screen field setting | Write | ||
| AV | 227 | LRHC number | Custom screen field setting | Write | ||
| AV | 228 | LRHC 10 char | Custom screen field setting | Write | ||
| AV | 229 | LRHC 1 char | Custom screen field setting | Write | ||
| AV | 230 | LRHC minimum | Custom screen field setting | Write | ||
| AV | 231 | LRHC maximum | Custom screen field setting | Write | ||
| AV | 232 | LRHC delta | Custom screen field setting | Write | ||
| BV | 64 | Time Schedule Output | Schedule output (occupied when on) | Read | ||
| BV | 65 | User ON/OFF in Occupied Mode | User on/off in occupied mode | Write | ||
| BV | 66 | After Hours Timer Status | After-hours timer running | Read | ||
| BVmin | 67 | Occupied/Unoccupied Status | Occupied / unoccupied status | Read | ||
| BV | 68 | Field service Lockout | Field service lockout | Write | ||
| BV | 69 | Swap English/Metric | Swap English / metric display | Write | ||
| BV | 71 | English (OFF) / Metric (ON) | English (off) or metric (on) | Write | ||
| BV | 72 | Fan stage 1 | Fan stage 1 output status | Read | ||
| BV | 73 | Fan stage 2 | Fan stage 2 output status | Read | ||
| BV | 74 | Fan stage 3 | Fan stage 3 output status | Read | ||
| BV | 77 | Heating ICON | Display 'heat on' icon | Write | ||
| BV | 78 | Cooling ICON | Display 'cool on' icon | Write | ||
| BV | 79 | Backlight ON | Backlight on | Write | ||
| BV | 80 | Enable Fan Speed Control | Allow the 'FAN' control to be visible to the end user | Write | ||
| BV | 81 | Select Hotel Mode | Hotel mode | Write | ||
| BV | 82 | Enable Time Display | Show time | Write | ||
| BV | 83 | 24Hr Time Format | 24-hour clock | Write | ||
| BV | 84 | Enable Space Humidity | Display space humidity as appropriate | Write | ||
| BV | 102 | Enable System Control | Allow the 'SYSTEM' control to be visible | Write | ||
| BV | 103 | Hide Fan and System | Hide the FAN and SYSTEM controls in unoccupied mode (regardless of other... | Write | ||
| BV | 104 | Enable DOW | Allow day of week to be shown is possible | Write | ||
| BV | 105 | Show Unocc Setpoints | Display the unoccupied heating/cooling setpoints in unoccupied mode | Write | ||
| BV | 106 | Show Wait | Display 'Wait' | Write | ||
| BV | 107 | Show Aux heat on | Display 'Aux heat on' | Write | ||
| BV | 111 | Force CHANGE FILTER | Force 'CHANGE FILTER' to be displayed (can also be automatically displayed... | Write | ||
| BV | 114 | Disable SCHED key | If set, the user is not allowed to view schedules | Write | ||
| BV | 115 | Disable Permanent HOLD key | Allow 'HOLD' key to be used to access the Permanent Hold UI | Write | ||
| BV | 116 | Disable CLOCK key | Allow 'CLOCK' key to be used to set clock (if appropriate) | Write | ||
| BV | 117 | Allow System OFF | Allow system OFF | Write | ||
| BV | 118 | Allow System HEAT | Allow system HEAT | Write | ||
| BV | 119 | Allow System COOL | Allow system COOL | Write | ||
| BV | 120 | Allow System AUTO | Allow system AUTO | Write | ||
| BV | 121 | Allow System EM HEAT | Allow system EM HEAT | Write | ||
| BV | 122 | System HEAT Mode | System HEAT mode | Write | ||
| BV | 123 | System COOL Mode | System COOL mode | Write | ||
| BV | 124 | System AUTO Mode | System AUTO mode | Write | ||
| BV | 125 | System EM HEAT Mode | System EM HEAT mode | Write | ||
| BV | 130 | Disable Vacation HOLD key | Allow 'HOLD' key to be used to access the standard Vacation Hold UI (if... | Write | ||
| BV | 131 | Hotel Standby Mode | Set Active by DDC to indicate to the display that DDC is controlling to... | Write | ||
| BV | 133 | Enable internal schedule | Internal 7-day scheduling is enabled (subject to other factors) | Write | ||
| BV | 134 | Filter Enable | Enable filter timer and automatic 'change filter' warning | Write | ||
| BV | 135 | Filter ON | Accumulator ON | Write | ||
| BV | 141 | Disable schedule edit | Inhibits screen EDIT key | Write | ||
| BV | 142 | Master OFF | No effect | Write | ||
| BV | 200 | AIn Current Mode | AI 0: current mode select | Write | ||
| BV | 201 | AIn Current Mode | AI 1: current mode select | Write | ||
| BV | 202 | AIn Current Mode | AI 2: current mode select | Write | ||
| BV | 210 | Custom 1 Enable | Custom screen element / key | Write | ||
| BV | 211 | Reset | Custom screen element / key | Write | ||
| BV | 212 | ULHC enable | Custom screen element / key | Write | ||
| BV | 213 | ULHC decimal | Custom screen element / key | Write | ||
| BV | 214 | ULHC lead zero | Custom screen element / key | Write | ||
| BV | 215 | URHC enable | Custom screen element / key | Write | ||
| BV | 216 | URHC decimal | Custom screen element / key | Write | ||
| BV | 217 | URHC lead zero | Custom screen element / key | Write | ||
| BV | 218 | URHC edit | Custom screen element / key | Write | ||
| BV | 219 | LLHC enable | Custom screen element / key | Write | ||
| BV | 220 | LLHC lead zero | Custom screen element / key | Write | ||
| BV | 221 | LLHC edit | Custom screen element / key | Write | ||
| BV | 222 | LRHC enable | Custom screen element / key | Write | ||
| BV | 223 | LRHC decimal | Custom screen element / key | Write | ||
| BV | 224 | LRHC lead zero | Custom screen element / key | Write | ||
| BV | 225 | LRHC edit | Custom screen element / key | Write | ||
| BV | 226 | LRHC leading 1 | Custom screen element / key | Write | ||
| BV | 227 | Day boxes | Custom screen element / key | Write | ||
| BV | 228 | Mon text | Custom screen element / key | Write | ||
| BV | 229 | Tue text | Custom screen element / key | Write | ||
| BV | 230 | Wed text | Custom screen element / key | Write | ||
| BV | 231 | Thu text | Custom screen element / key | Write | ||
| BV | 232 | Fri text | Custom screen element / key | Write | ||
| BV | 233 | Sat text | Custom screen element / key | Write | ||
| BV | 234 | Sun text | Custom screen element / key | Write | ||
| BV | 235 | Mon check | Custom screen element / key | Write | ||
| BV | 236 | Tue check | Custom screen element / key | Write | ||
| BV | 237 | Wed check | Custom screen element / key | Write | ||
| BV | 238 | Thu check | Custom screen element / key | Write | ||
| BV | 239 | Fri check | Custom screen element / key | Write | ||
| BV | 240 | Sat check | Custom screen element / key | Write | ||
| BV | 241 | Sun check | Custom screen element / key | Write | ||
| BV | 242 | Ok to pick | Custom screen element / key | Write | ||
| BV | 243 | Screen locked | Custom screen element / key | Write | ||
| BV | 244 | Change | Custom screen element / key | Write | ||
| BV | 245 | Filter | Custom screen element / key | Write | ||
| BV | 250 | Inside | Custom screen element / key | Write | ||
| BV | 253 | Set to | Custom screen element / key | Write | ||
| BV | 254 | Aux | Custom screen element / key | Write | ||
| BV | 255 | Heat On | Custom screen element / key | Write | ||
| BV | 256 | Wait | Custom screen element / key | Write | ||
| BV | 257 | Cool On | Custom screen element / key | Write | ||
| BV | 258 | Heat Adjust | Custom screen element / key | Write | ||
| BV | 260 | Follow | Custom screen element / key | Write | ||
| BV | 262 | URHC Adj Arrows | Custom screen element / key | Write | ||
| BV | 263 | Pm | Custom screen element / key | Write | ||
| BV | 264 | Am | Custom screen element / key | Write | ||
| BV | 265 | Days | Custom screen element / key | Write | ||
| BV | 266 | LLHC Adj Arrows | Custom screen element / key | Write | ||
| BV | 268 | Permanent | Custom screen element / key | Write | ||
| BV | 269 | Hold Until | Custom screen element / key | Write | ||
| BV | 270 | Cancel Period | Custom screen element / key | Write | ||
| BV | 271 | Outside | Custom screen element / key | Write | ||
| BV | 272 | DE | Custom screen element / key | Write | ||
| BV | 280 | Vent | Custom screen element / key | Write | ||
| BV | 281 | Mon key | Custom screen element / key | Write | ||
| BV | 282 | Tue key | Custom screen element / key | Write | ||
| BV | 283 | Wed key | Custom screen element / key | Write | ||
| BV | 284 | Thu key | Custom screen element / key | Write | ||
| BV | 285 | Fri key | Custom screen element / key | Write | ||
| BV | 286 | Sat key | Custom screen element / key | Write | ||
| BV | 287 | Sun key | Custom screen element / key | Write | ||
| BV | 292 | LLHC up key | Custom screen element / key | Write | ||
| BV | 293 | LLHC dn key | Custom screen element / key | Write | ||
| BV | 294 | RESET key | Custom screen element / key | Write | ||
| BV | 295 | CANCEL PERIOD key | Custom screen element / key | Write | ||
| BV | 297 | FAN key | Custom screen element / key | Write | ||
| BV | 298 | SYSTEM key | Custom screen element / key | Write | ||
| BV | 300 | AOn Current Mode | AO 0: current mode detected | Read | ||
| BV | 301 | AOn Current Mode | AO 1: current mode detected | Read | ||
| BV | 400 | AIn Pullup | AI 0: pull-up enable | Write | ||
| BV | 401 | AIn Pullup | AI 1: pull-up enable | Write | ||
| BV | 402 | AIn Pullup | AI 2: pull-up enable | Write | ||
| MV | 0 | Time Mode | Device's time handling capability: Normal clock operation will | Read | 1=Time Of Day Unknown Mode, 2=Time Of Day Available Mode, 3=Date/Time Available Mode | |
| MV | 1 | Schedule Model | Device's schedule model | Read | 1=Setpoint, 2=Occupancy | |
| MV | 2 | Keypad Lock | Keypad access level | Read | 1=full access, 2=setpoints only, 3=locked | |
| MV | 3 | DLS Mode | Mode of Daylight Saving operation | Read | 1=OFF, 2=Auto (pre-2007), 3=Auto (2007 and later) | |
| MV | 4 | SP Increment | Amount of change in setpoint per arrow press | Read | ||
| MV | 5 | Schedule Increment | Amount of change in schedule times per arrow press | Read | ||
| MV | 6 | User SYSTEM selection | Display / screen setting | Read | ||
| MV | 7 | Fan status | Display / screen setting | Read | ||
| MV | 8 | Fan OFF text | Display / screen setting | Read | ||
| MV | 9 | Fan stage 1 text | Display / screen setting | Read | ||
| MV | 10 | Fan stage 2 text | Display / screen setting | Read | ||
| MV | 11 | Fan stage 3 text | Display / screen setting | Read | ||
| MV | 12 | Schedule Format | This point is a human-friendly version of AV-129, ISU parameter 540 (see... | Read | 1=2 commands per day, 2=4 commands per day | |
| MV | 13 | SP Override Mode | In setpoint mode: setpoint override state | Read | 1=scheduled, 2=temporary, 3=permanent, 4=vacation | |
| AV | 49 | Application Selection | Application number, default 5 (0-18) | Write | ||
| BVmin | 2 | Output Enable | Set ON to enable the outputs | Write | OFF, ON | |
| AV | 17 | Fan 1=Cont 2=CycHtg 3=CycHtgClg | Fan mode: continuous or cycling | Write | 1=Cont, 2=CycHtg, 3=CycHtgClg | |
| AV | 19 | standby offset | Standby offset, 0-6 degrees; copied to AV 106 | °F/°C | Write | |
| AV | 20 | Standby Delay Seconds | Standby delay, default 180 | s | Write | |
| BV | 27 | Heating Lockout | Heating lockout | Write | Inactive, Active | |
| BVmin | 56 | Enable BMS Scheduling | BMS scheduling instead of internal schedule | Write | Inactive, Active | |
| BVmin | 9 | Enable Communication Failure | Go occupied on MS/TP comm failure | Write | Inactive, Active | |
| BV | 10 | Enable System OFF | Allow system OFF | Write | Inactive, Active | |
| AV | 40 | AC HP Mode | 1 = thermostat emulation, 2 = analog to BIN control | Write | 1, 2 | |
| AV | 41 | Heating Signal Kp | Heating loop proportional gain, default 20 | Write | ||
| AV | 42 | Heating Signal Ki | Heating loop integral gain, default 1 | Write | ||
| AV | 46 | Auto Fan Start Demand % | Fan start demand, default 20 | % | Write | |
| AV | 53 | Auto Fan Stop Deadband SP | Fan stop deadband, default 5 | % | Write | |
| AV | 77 | Filter Alarm SP | Filter alarm runtime, default 3000 | h | Write | |
| AV | 78 | 2PVlvMode Set DB% | Two-position valve set deadband, default 20 | % | Write | |
| AV | 79 | 2PVlvMode Reset DB% | Two-position valve reset deadband, default 1 | % | Write |
No points match these filters.
Object ID lookup: Marley Engineered Products Smart Series Plus digital heater controller point IDs by name
AV90Setpoint (SP)AV91Setpoint High LimitAV92Setpoint Low LimitAV93Cooling SP OffsetAV94Heating SP OffsetAV95Unoccupied Cooling SPAV96Unoccupied Heating SPAV97After Hours Timer LimitAV98After Hours TimerAV99Current Cooling SPAV100Current Heating SPAV101Displayed Room TemperatureAV104Sensed Room TemperatureAV105Sensed Room HumidityAV106Demand OffsetAV108SP Mode Cooling SPAV109SP Mode Heating SPAV110SP Mode Setpoint ModeAV111SYSTEM Setpoint ModelAV113SP Override Mode AVAV114Filter RuntimeAV115Filter Runtime LimitAV117UV Lamp Runtime LimitAV123Set system to Occupancy modeAV124Filter Change ReminderAV127Daylight savingsAV128Keypad lockAV129Weekday periods ISU valueAV130Hold until timeAV131Vacation days remainingAV132Field service mode security PINAV133ISU mode security PINAV137Fan Setting Display FormatAV138Sensed Temperature OffsetAV210UHLH numberAV211ULHC left characterAV212ULHC right characterAV213URHC numberAV214URHC 10 charAV215URHC 1 charAV216URHC minimumAV217URHC maximumAV218URHC deltaAV219LLHC numberAV220LLHC 10 charAV221LLHC 1 charAV222LLHC minimumAV223LLHC maximumAV224LLHC deltaAV225LLHC 1000 charAV226LLHC 100 charAV227LRHC numberAV228LRHC 10 charAV229LRHC 1 charAV230LRHC minimumAV231LRHC maximumAV232LRHC deltaBV64Time Schedule OutputBV65User ON/OFF in Occupied ModeBV66After Hours Timer StatusBV67Occupied/Unoccupied StatusBV68Field service LockoutBV69Swap English/MetricBV71English (OFF) / Metric (ON)BV72Fan stage 1BV73Fan stage 2BV74Fan stage 3BV77Heating ICONBV78Cooling ICONBV79Backlight ONBV80Enable Fan Speed ControlBV81Select Hotel ModeBV82Enable Time DisplayBV8324Hr Time FormatBV84Enable Space HumidityBV102Enable System ControlBV103Hide Fan and SystemBV104Enable DOWBV105Show Unocc SetpointsBV106Show WaitBV107Show Aux heat onBV111Force CHANGE FILTERBV114Disable SCHED keyBV115Disable Permanent HOLD keyBV116Disable CLOCK keyBV117Allow System OFFBV118Allow System HEATBV119Allow System COOLBV120Allow System AUTOBV121Allow System EM HEATBV122System HEAT ModeBV123System COOL ModeBV124System AUTO ModeBV125System EM HEAT ModeBV130Disable Vacation HOLD keyBV131Hotel Standby ModeBV133Enable internal scheduleBV134Filter EnableBV135Filter ONBV141Disable schedule editBV142Master OFFBV200AIn Current ModeBV201AIn Current ModeBV202AIn Current ModeBV210Custom 1 EnableBV211ResetBV212ULHC enableBV213ULHC decimalBV214ULHC lead zeroBV215URHC enableBV216URHC decimalBV217URHC lead zeroBV218URHC editBV219LLHC enableBV220LLHC lead zeroBV221LLHC editBV222LRHC enableBV223LRHC decimalBV224LRHC lead zeroBV225LRHC editBV226LRHC leading 1BV227Day boxesBV228Mon textBV229Tue textBV230Wed textBV231Thu textBV232Fri textBV233Sat textBV234Sun textBV235Mon checkBV236Tue checkBV237Wed checkBV238Thu checkBV239Fri checkBV240Sat checkBV241Sun checkBV242Ok to pickBV243Screen lockedBV244ChangeBV245FilterBV250InsideBV253Set toBV254AuxBV255Heat OnBV256WaitBV257Cool OnBV258Heat AdjustBV260FollowBV262URHC Adj ArrowsBV263PmBV264AmBV265DaysBV266LLHC Adj ArrowsBV268PermanentBV269Hold UntilBV270Cancel PeriodBV271OutsideBV272DEBV280VentBV281Mon keyBV282Tue keyBV283Wed keyBV284Thu keyBV285Fri keyBV286Sat keyBV287Sun keyBV292LLHC up keyBV293LLHC dn keyBV294RESET keyBV295CANCEL PERIOD keyBV297FAN keyBV298SYSTEM keyBV300AOn Current ModeBV301AOn Current ModeBV400AIn PullupBV401AIn PullupBV402AIn PullupMV0Time ModeMV1Schedule ModelMV2Keypad LockMV3DLS ModeMV4SP IncrementMV5Schedule IncrementMV6User SYSTEM selectionMV7Fan statusMV8Fan OFF textMV9Fan stage 1 textMV10Fan stage 2 textMV11Fan stage 3 textMV12Schedule FormatMV13SP Override ModeAV49Application SelectionBV2Output EnableAV17Fan 1=Cont 2=CycHtg 3=CycHtgClgAV19standby offsetAV20Standby Delay SecondsBV27Heating LockoutBV56Enable BMS SchedulingBV9Enable Communication FailureBV10Enable System OFFAV40AC HP ModeAV41Heating Signal KpAV42Heating Signal KiAV46Auto Fan Start Demand %AV53Auto Fan Stop Deadband SPAV77Filter Alarm SPAV782PVlvMode Set DB%AV792PVlvMode Reset DB%
Integration notes
- The appendix gives each object a label in an 'Object Name' column, but its property tables say the Object_Name property reads 'AV-nnn' / 'BV-nnn' / 'MV-nnn' for most objects. The labels are used as names here; a scan may show the AV-nnn form.
- Physical I/O objects (AI 0-2, AO 0-7, BI 0-2, BO 0-5) and the general-use AV 0-89 / BV 0-63 depend on the loaded application (DDC file); they are not listed here except where the guide names them.
- BV 40 (general-use range) is the occupancy command and supports a priority array.
- Access comes from the appendix where it has an access column; otherwise it is inferred (displayed/sensed/current/status points and multistates read-only, others writable).
- The ordered list in this guide marks the humidity, UV-lamp and several display objects RESERVED; they are left out. Application points (AV 17-79, BV 2-56) come from the guide's setup tables (Tables 21, 23 and 24), with defaults in the descriptions.
- Output Enable (BV 2) must be set ON at start-up or the relays stay off.
- The object set is the Honeywell BACnet FF platform; see the Honeywell TB3026B list for the full platform including humidity objects.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Smart Series Plus digital heater controller (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP)
How many BACnet points does the Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP) have?
This list has 208 BACnet objects: 69 analog values, 125 binary values, 14 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP) BACnet points are writable?
179 of the 208 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP) BACnet documentation?
The source is Smart Series Plus Installation and Operations Guide (English section, Appendix A and B) (5200-11256-004), revision 10/23, published free by Marley Engineered Products at https://www.marleymep.com/wp-content/uploads/5200-11256-004.pdf.
What are the minimum BACnet points to integrate the Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP)?
Start with BV 2 Output Enable (Output enable; must be ON for the heater to run); BV 56 Enable BMS Scheduling (Enable BMS scheduling (overrides internal schedule)); AV 90 Setpoint (SP) (Occupied space setpoint); AV 96 Unoccupied Heating SP (Unoccupied heating setpoint); BV 9 Enable Communication Failure (Go occupied on MS/TP comm failure); AV 104 Sensed Room Temperature (Room temperature (built-in sensor)); AV 100 Current Heating SP (Active heating setpoint); BV 67 Occupied/Unoccupied Status (Occupied / unoccupied status).
How do I enable BMS control of the Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP)?
BV 2 Output Enable must be ON. With BV 56 active the BMS schedules occupancy (BV 40, priority array) instead of the internal schedule.
Does the Marley Engineered Products Smart Series Plus digital heater controller (BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?
BV 9 Enable Communication Failure: when active the controller falls back to occupied if MS/TP communication fails.
How do I check these points on the real Smart Series Plus digital heater controller (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: Smart Series Plus Installation and Operations Guide (English section, Appendix A and B) · 5200-11256-004 · rev. 10/23. Object names, instances and units are reproduced as published; descriptions are our own.