Hotel room controller (lighting, HVAC, room services) · BACnet points list
Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08 BACnet points list
Updated 12 November 2026
The Legrand hotel room controller runs one guest room's lighting, shutters, power circuits, thermostats and room services and exposes them on BACnet IP. The object map is fixed: presence and PMS flags, power and lighting circuits, DALI and BUS SCS dimmer groups, up to four BUS SCS thermostats, do-not-disturb / make-up-room and ten scenario triggers.
This page lists 67 BACnet objects for the Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08 — 61 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Legrand’s own free documentation, linked below.
- Manufacturer
- Legrand
- Model
- BACnet IP hotel room controller 0 484 12 / 0 484 08
- Equipment
- Hotel room controller (lighting, HVAC, room services)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 67 (61 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- 0 484 12, 0 484 08, 048412, 048408, Legrand RCU, Legrand hotel room controller, bticino hotel room BACnet
Reference only, provided as-is: verify against Legrand’s current documentation and the live device before use. Not official Legrand information. Terms of use.
BMS integration notes: Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08
Read BI 0 for occupancy and write BV 14 from the PMS when the room is booked. Supervise each thermostat's mode, setpoint and ambient temperature, and the lighting circuits. Scenarios run on any change of the scenario BO value.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 14 | PMS | Room booked flag from the PMS | Write |
| MV 2 | Mode | Thermostat 1 mode: 0 = Comfort ... 4 = OFF | Write |
| AV 0 | Setpoint temperature | Thermostat 1 setpoint | Write |
| MV 5 | Fan Speed | Thermostat 1 fan: 0 = auto, 1-3 = slow-fast | Write |
| BO 11 | Door contact for Virtual keycard function | Door state for virtual keycard, 1 = closed | Write |
| BI 0 | Presence | Room presence, 1 = present | Read |
| AI 8 | Ambient temperature | Thermostat 1 room temperature | Read |
| MV 4 | Do not disturb/ Make up room | 0 = Do not disturb, 1 = Make up room | Write |
| BV 13 | SOS | SOS call | Write |
Sensors & values from the BMS
With the virtual keycard function enabled, the access control system writes the door state to BO 11.
Network setup
- Thermostats must be BUS SCS thermostats in MASTER mode; up to 4, numbered in declaration order.
- PMS, virtual keycard and external scenarios must be enabled in the "hotel functions" section of the configuration software.
Watch out for
- Range objects follow declaration order in the configuration tool, so instance numbers move if peripherals are declared in a different order.
- The unit BOs (°C/°F) change every temperature value of that thermostat.
Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08 BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 0 | Presence | Room presence from keycard reader or virtual keycard | Read | 0=absence, 1=presence | |
| BOmin | 11 | Door contact for Virtual keycard function | Door state written by the access control system | Write | 0=door open, 1=door closed | |
| BVmin | 14 | PMS | Room booked flag from the PMS | Write | 0=room not booked, 1=room booked | |
| BV | 0 | Power circuit | Power circuits: BV 0-3, BV 0 = output F2 ... BV 3 = output E1 | Write | 0=OFF, 1=ON | |
| BV | 4 | Lighting circuit | Lighting circuits: BV 4-11, BV 4 = output D4 ... BV 11 = output C1 | Write | 0=OFF, 1=ON | |
| BV | 48 | SCS ON/OFF circuit | BUS SCS on/off actuator outputs: BV 48-63, in order of declaration | Write | 0=OFF, 1=ON | |
| AV | 53 | DALI lighting circuit | DALI group level, %: AV 53-68 = groups 0-15 | % | Write | |
| BV | 64 | DALI lighting circuit | DALI group on/off: BV 64-79 = groups 0-15 | Write | 0=OFF, 1=ON | |
| AV | 21 | SCS dimmer lighting circuit | BUS SCS dimmer level, %: AV 21-52, in order of declaration | % | Write | |
| BV | 16 | SCS dimmer lighting circuit | BUS SCS dimmer on/off: BV 16-47, in order of declaration | Write | 0=OFF, 1=ON | |
| MV | 0 | Roller shutter/curtain circuit | Shutter/curtain on output block B | Write | 0=Up, 1=Down, 2=Undefined (Stop) | |
| MV | 1 | Roller shutter/curtain circuit | Shutter/curtain on output block A | Write | 0=Up, 1=Down, 2=Undefined (Stop) | |
| BI | 1 | Green sensitive PB | Chosen "green sensitive" control | Read | 0=Disable, 1=Enable | |
| AImin | 8 | Ambient temperature | Room temperature, thermostat 1 | °C or °F | Read | |
| AVmin | 0 | Setpoint temperature | Setpoint, thermostat 1 (3-40 °C) | °C or °F | Write | |
| MVmin | 2 | Mode | Operating mode, thermostat 1 | Write | 0=Comfort, 1=Comfort-2, 2=Eco, 3=Frost guard/thermal protection, 4=OFF, 5=Manual | |
| MV | 3 | Summer/Winter | Season, thermostat 1 | Write | 0=Winter, 1=Summer, 2=Hybrid | |
| MVmin | 5 | Fan Speed | Fan speed, thermostat 1 | Write | 0=Automatic, 1=Slow speed, 2=Medium speed, 3=Fast speed | |
| AV | 1 | Minimum setpoint in heating mode | Heating setpoint low limit, thermostat 1 | °C or °F | Write | |
| AV | 2 | Maximum setpoint in heating mode | Heating setpoint high limit, thermostat 1 | °C or °F | Write | |
| AV | 3 | Minimum setpoint in cooling mode | Cooling setpoint low limit, thermostat 1 | °C or °F | Write | |
| AV | 4 | Maximum setpoint in cooling mode | Cooling setpoint high limit, thermostat 1 | °C or °F | Write | |
| BO | 12 | Change of unit (°C/°F) | Temperature unit, thermostat 1 (write only) | Write | 0=°C unit, 1=°F unit | |
| AI | 9 | Ambient temperature | Room temperature, thermostat 2 | °C or °F | Read | |
| AV | 5 | Setpoint temperature | Setpoint, thermostat 2 (3-40 °C) | °C or °F | Write | |
| MV | 6 | Mode | Operating mode, thermostat 2 | Write | 0=Comfort, 1=Comfort-2, 2=Eco, 3=Frost guard/thermal protection, 4=OFF, 5=Manual | |
| MV | 7 | Summer/Winter | Season, thermostat 2 | Write | 0=Winter, 1=Summer, 2=Hybrid | |
| MV | 9 | Fan speed | Fan speed, thermostat 2 | Write | 0=Automatic, 1=Slow speed, 2=Medium speed, 3=Fast speed | |
| AV | 6 | Minimum setpoint in heating mode | Heating setpoint low limit, thermostat 2 | °C or °F | Write | |
| AV | 7 | Maximum setpoint in heating mode | Heating setpoint high limit, thermostat 2 | °C or °F | Write | |
| AV | 8 | Minimum setpoint in cooling mode | Cooling setpoint low limit, thermostat 2 | °C or °F | Write | |
| AV | 9 | Maximum setpoint in cooling mode | Cooling setpoint high limit, thermostat 2 | °C or °F | Write | |
| BO | 13 | Change of unit (°C/°F) | Temperature unit, thermostat 2 (write only) | Write | 0=°C unit, 1=°F unit | |
| AI | 10 | Ambient temperature | Room temperature, thermostat 3 | °C or °F | Read | |
| AV | 10 | Setpoint temperature | Setpoint, thermostat 3 (3-40 °C) | °C or °F | Write | |
| MV | 10 | Mode | Operating mode, thermostat 3 | Write | 0=Comfort, 1=Comfort-2, 2=Eco, 3=Frost guard/thermal protection, 4=OFF, 5=Manual | |
| MV | 11 | Summer/Winter | Season, thermostat 3 | Write | 0=Winter, 1=Summer, 2=Hybrid | |
| MV | 13 | Fan Speed | Fan speed, thermostat 3 | Write | 0=Automatic, 1=Slow speed, 2=Medium speed, 3=Fast speed | |
| AV | 11 | Minimum setpoint in heating mode | Heating setpoint low limit, thermostat 3 | °C or °F | Write | |
| AV | 12 | Maximum setpoint in heating mode | Heating setpoint high limit, thermostat 3 | °C or °F | Write | |
| AV | 13 | Minimum setpoint in cooling mode | Cooling setpoint low limit, thermostat 3 | °C or °F | Write | |
| AV | 14 | Maximum setpoint in cooling mode | Cooling setpoint high limit, thermostat 3 | °C or °F | Write | |
| BO | 14 | Change of unit (°C/°F) | Temperature unit, thermostat 3 (write only) | Write | 0=°C unit, 1=°F unit | |
| AI | 11 | Ambient temperature | Room temperature, thermostat 4 | °C or °F | Read | |
| AV | 15 | Setpoint temperature | Setpoint, thermostat 4 (3-40 °C) | °C or °F | Write | |
| MV | 14 | Mode | Operating mode, thermostat 4 | Write | 0=Comfort, 1=Comfort-2, 2=Eco, 3=Frost guard/thermal protection, 4=OFF, 5=Manual | |
| MV | 15 | Summer/Winter | Season, thermostat 4 | Write | 0=Winter, 1=Summer, 2=Hybrid | |
| MV | 17 | Fan speed | Fan speed, thermostat 4 | Write | 0=Automatic, 1=Slow speed, 2=Medium speed, 3=Fast speed | |
| AV | 16 | Minimum setpoint in heating mode | Heating setpoint low limit, thermostat 4 | °C or °F | Write | |
| AV | 17 | Maximum setpoint in heating mode | Heating setpoint high limit, thermostat 4 | °C or °F | Write | |
| AV | 18 | Minimum setpoint in cooling mode | Cooling setpoint low limit, thermostat 4 | °C or °F | Write | |
| AV | 19 | Maximum setpoint in cooling mode | Cooling setpoint high limit, thermostat 4 | °C or °F | Write | |
| BO | 15 | Change of unit (°C/°F) | Temperature unit, thermostat 4 (write only) | Write | 0=°C unit, 1=°F unit | |
| MVmin | 4 | Do not disturb/ Make up room | Housekeeping state (room controller or corridor display) | Write | 0=Do not disturb, 1=Make up room, 2=Stop/no housekeeping | |
| BV | 12 | Ward + room number | Chosen "room service" control | Write | 0=Disable, 1=Enable | |
| BVmin | 13 | SOS | Chosen SOS control | Write | 0=Disable, 1=Enable | |
| BV | 15 | Generic room service | Generic room service (UX Touch corridor display) | Write | 0=Disable, 1=Enable | |
| BO | 1 | Internal scenario no. 1 | Change of value launches internal scenario | Write | ||
| BO | 2 | Internal scenario no. 2 | Change of value launches internal scenario | Write | ||
| BO | 3 | Internal scenario no. 3 | Change of value launches internal scenario | Write | ||
| BO | 4 | Internal scenario no. 4 | Change of value launches internal scenario | Write | ||
| BO | 5 | Internal scenario no. 5 | Change of value launches internal scenario | Write | ||
| BO | 6 | External scenario no. 1 | Change of value launches external scenario | Write | ||
| BO | 7 | External scenario no. 2 | Change of value launches external scenario | Write | ||
| BO | 8 | External scenario no. 3 | Change of value launches external scenario | Write | ||
| BO | 9 | External scenario no. 4 | Change of value launches external scenario | Write | ||
| BO | 10 | External scenario no. 5 | Change of value launches external scenario | Write |
No points match these filters.
Object ID lookup: Legrand Hotel room controller (RCU) point IDs by name
BI0PresenceBO11Door contact for Virtual keycard functionBV14PMSBV0Power circuitBV4Lighting circuitBV48SCS ON/OFF circuitAV53DALI lighting circuitBV64DALI lighting circuitAV21SCS dimmer lighting circuitBV16SCS dimmer lighting circuitMV0Roller shutter/curtain circuitMV1Roller shutter/curtain circuitBI1Green sensitive PBAI8Ambient temperatureAV0Setpoint temperatureMV2ModeMV3Summer/WinterMV5Fan SpeedAV1Minimum setpoint in heating modeAV2Maximum setpoint in heating modeAV3Minimum setpoint in cooling modeAV4Maximum setpoint in cooling modeBO12Change of unit (°C/°F)AI9Ambient temperatureAV5Setpoint temperatureMV6ModeMV7Summer/WinterMV9Fan speedAV6Minimum setpoint in heating modeAV7Maximum setpoint in heating modeAV8Minimum setpoint in cooling modeAV9Maximum setpoint in cooling modeBO13Change of unit (°C/°F)AI10Ambient temperatureAV10Setpoint temperatureMV10ModeMV11Summer/WinterMV13Fan SpeedAV11Minimum setpoint in heating modeAV12Maximum setpoint in heating modeAV13Minimum setpoint in cooling modeAV14Maximum setpoint in cooling modeBO14Change of unit (°C/°F)AI11Ambient temperatureAV15Setpoint temperatureMV14ModeMV15Summer/WinterMV17Fan speedAV16Minimum setpoint in heating modeAV17Maximum setpoint in heating modeAV18Minimum setpoint in cooling modeAV19Maximum setpoint in cooling modeBO15Change of unit (°C/°F)MV4Do not disturb/ Make up roomBV12Ward + room numberBV13SOSBV15Generic room serviceBO1Internal scenario no. 1BO2Internal scenario no. 2BO3Internal scenario no. 3BO4Internal scenario no. 4BO5Internal scenario no. 5BO6External scenario no. 1BO7External scenario no. 2BO8External scenario no. 3BO9External scenario no. 4BO10External scenario no. 5
Integration notes
- Object table "Standard BACnet objects" and "Description of values", guide LE10699AF pages 229-235.
- Circuit groups are printed as instance ranges with one name; only the first object of each range is listed, the range is in the description (e.g. lighting BV 4-11, DALI groups AV 53-68 / BV 64-79).
- BUS SCS objects are numbered in the order peripherals were declared during configuration.
- The BUS SCS roller shutter/curtain object has no instance in the table and is marked "under construction"; it is left out.
- The text calls the ambient temperature objects Analog Values (0); type code 0 and the table say Analog Input.
- Scenario BOs are listed as write-only; a change of value 0->1 or 1->0 launches the scenario. Up to 128 simultaneous COV subscriptions.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BACnet IP hotel room controller 0 484 12 / 0 484 08 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08
How many BACnet points does the Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08 have?
This list has 67 BACnet objects: 4 analog inputs, 22 analog values, 2 binary inputs, 15 binary outputs, 9 binary values, 15 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08 BACnet points are writable?
61 of the 67 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08 BACnet documentation?
The source is Hotel Rooms BACnet IP Solutions - Installation and User Guide / Technical Guide (LE10699AF), published free by Legrand at https://assets.legrand.com/pim/NP-FT-GT/LE10699AF_EN.pdf.
What are the minimum BACnet points to integrate the Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08?
Start with BV 14 PMS (Room booked flag from the PMS); MV 2 Mode (Thermostat 1 mode: 0 = Comfort ... 4 = OFF); AV 0 Setpoint temperature (Thermostat 1 setpoint); MV 5 Fan Speed (Thermostat 1 fan: 0 = auto, 1-3 = slow-fast); BO 11 Door contact for Virtual keycard function (Door state for virtual keycard, 1 = closed); BI 0 Presence (Room presence, 1 = present); AI 8 Ambient temperature (Thermostat 1 room temperature); MV 4 Do not disturb/ Make up room (0 = Do not disturb, 1 = Make up room); BV 13 SOS (SOS call).
Can the BMS supply sensor values to the Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08?
With the virtual keycard function enabled, the access control system writes the door state to BO 11.
How do I check these points on the real BACnet IP hotel room controller 0 484 12 / 0 484 08?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: Hotel Rooms BACnet IP Solutions - Installation and User Guide / Technical Guide · LE10699AF. Object names, instances and units are reproduced as published; descriptions are our own.