Hotel room controller (lighting, HVAC, room services) · BACnet points list

Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08 BACnet points list

Updated 12 November 2026

Short answer

The Legrand hotel room controller runs one guest room's lighting, shutters, power circuits, thermostats and room services and exposes them on BACnet IP. The object map is fixed: presence and PMS flags, power and lighting circuits, DALI and BUS SCS dimmer groups, up to four BUS SCS thermostats, do-not-disturb / make-up-room and ten scenario triggers.

This page lists 67 BACnet objects for the Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08 — 61 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Legrand’s own free documentation, linked below.

Manufacturer
Legrand
Model
BACnet IP hotel room controller 0 484 12 / 0 484 08
Equipment
Hotel room controller (lighting, HVAC, room services)
Equipment type
Thermostats, sensors & meters
BACnet objects
67 (61 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
0 484 12, 0 484 08, 048412, 048408, Legrand RCU, Legrand hotel room controller, bticino hotel room BACnet
Source document
Hotel Rooms BACnet IP Solutions - Installation and User Guide / Technical Guide · LE10699AF
Download CSV 67 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Legrand’s current documentation and the live device before use. Not official Legrand information. Terms of use.

BMS integration notes: Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08

Integration in brief

Read BI 0 for occupancy and write BV 14 from the PMS when the room is booked. Supervise each thermostat's mode, setpoint and ambient temperature, and the lighting circuits. Scenarios run on any change of the scenario BO value.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 14PMSRoom booked flag from the PMSWrite
MV 2ModeThermostat 1 mode: 0 = Comfort ... 4 = OFFWrite
AV 0Setpoint temperatureThermostat 1 setpointWrite
MV 5Fan SpeedThermostat 1 fan: 0 = auto, 1-3 = slow-fastWrite
BO 11Door contact for Virtual keycard functionDoor state for virtual keycard, 1 = closedWrite
BI 0PresenceRoom presence, 1 = presentRead
AI 8Ambient temperatureThermostat 1 room temperatureRead
MV 4Do not disturb/ Make up room0 = Do not disturb, 1 = Make up roomWrite
BV 13SOSSOS callWrite

Sensors & values from the BMS

With the virtual keycard function enabled, the access control system writes the door state to BO 11.

Network setup

Watch out for

Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

67 of 67 shown
Type
Multi-state
Access
Show
Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08 BACnet Points List
DescriptionStates
BImin0PresenceRoom presence from keycard reader or virtual keycardRead0=absence, 1=presence
BOmin11Door contact for Virtual keycard functionDoor state written by the access control systemWrite0=door open, 1=door closed
BVmin14PMSRoom booked flag from the PMSWrite0=room not booked, 1=room booked
BV0Power circuitPower circuits: BV 0-3, BV 0 = output F2 ... BV 3 = output E1Write0=OFF, 1=ON
BV4Lighting circuitLighting circuits: BV 4-11, BV 4 = output D4 ... BV 11 = output C1Write0=OFF, 1=ON
BV48SCS ON/OFF circuitBUS SCS on/off actuator outputs: BV 48-63, in order of declarationWrite0=OFF, 1=ON
AV53DALI lighting circuitDALI group level, %: AV 53-68 = groups 0-15%Write
BV64DALI lighting circuitDALI group on/off: BV 64-79 = groups 0-15Write0=OFF, 1=ON
AV21SCS dimmer lighting circuitBUS SCS dimmer level, %: AV 21-52, in order of declaration%Write
BV16SCS dimmer lighting circuitBUS SCS dimmer on/off: BV 16-47, in order of declarationWrite0=OFF, 1=ON
MV0Roller shutter/curtain circuitShutter/curtain on output block BWrite0=Up, 1=Down, 2=Undefined (Stop)
MV1Roller shutter/curtain circuitShutter/curtain on output block AWrite0=Up, 1=Down, 2=Undefined (Stop)
BI1Green sensitive PBChosen "green sensitive" controlRead0=Disable, 1=Enable
AImin8Ambient temperatureRoom temperature, thermostat 1°C or °FRead
AVmin0Setpoint temperatureSetpoint, thermostat 1 (3-40 °C)°C or °FWrite
MVmin2ModeOperating mode, thermostat 1Write0=Comfort, 1=Comfort-2, 2=Eco, 3=Frost guard/thermal protection, 4=OFF, 5=Manual
MV3Summer/WinterSeason, thermostat 1Write0=Winter, 1=Summer, 2=Hybrid
MVmin5Fan SpeedFan speed, thermostat 1Write0=Automatic, 1=Slow speed, 2=Medium speed, 3=Fast speed
AV1Minimum setpoint in heating modeHeating setpoint low limit, thermostat 1°C or °FWrite
AV2Maximum setpoint in heating modeHeating setpoint high limit, thermostat 1°C or °FWrite
AV3Minimum setpoint in cooling modeCooling setpoint low limit, thermostat 1°C or °FWrite
AV4Maximum setpoint in cooling modeCooling setpoint high limit, thermostat 1°C or °FWrite
BO12Change of unit (°C/°F)Temperature unit, thermostat 1 (write only)Write0=°C unit, 1=°F unit
AI9Ambient temperatureRoom temperature, thermostat 2°C or °FRead
AV5Setpoint temperatureSetpoint, thermostat 2 (3-40 °C)°C or °FWrite
MV6ModeOperating mode, thermostat 2Write0=Comfort, 1=Comfort-2, 2=Eco, 3=Frost guard/thermal protection, 4=OFF, 5=Manual
MV7Summer/WinterSeason, thermostat 2Write0=Winter, 1=Summer, 2=Hybrid
MV9Fan speedFan speed, thermostat 2Write0=Automatic, 1=Slow speed, 2=Medium speed, 3=Fast speed
AV6Minimum setpoint in heating modeHeating setpoint low limit, thermostat 2°C or °FWrite
AV7Maximum setpoint in heating modeHeating setpoint high limit, thermostat 2°C or °FWrite
AV8Minimum setpoint in cooling modeCooling setpoint low limit, thermostat 2°C or °FWrite
AV9Maximum setpoint in cooling modeCooling setpoint high limit, thermostat 2°C or °FWrite
BO13Change of unit (°C/°F)Temperature unit, thermostat 2 (write only)Write0=°C unit, 1=°F unit
AI10Ambient temperatureRoom temperature, thermostat 3°C or °FRead
AV10Setpoint temperatureSetpoint, thermostat 3 (3-40 °C)°C or °FWrite
MV10ModeOperating mode, thermostat 3Write0=Comfort, 1=Comfort-2, 2=Eco, 3=Frost guard/thermal protection, 4=OFF, 5=Manual
MV11Summer/WinterSeason, thermostat 3Write0=Winter, 1=Summer, 2=Hybrid
MV13Fan SpeedFan speed, thermostat 3Write0=Automatic, 1=Slow speed, 2=Medium speed, 3=Fast speed
AV11Minimum setpoint in heating modeHeating setpoint low limit, thermostat 3°C or °FWrite
AV12Maximum setpoint in heating modeHeating setpoint high limit, thermostat 3°C or °FWrite
AV13Minimum setpoint in cooling modeCooling setpoint low limit, thermostat 3°C or °FWrite
AV14Maximum setpoint in cooling modeCooling setpoint high limit, thermostat 3°C or °FWrite
BO14Change of unit (°C/°F)Temperature unit, thermostat 3 (write only)Write0=°C unit, 1=°F unit
AI11Ambient temperatureRoom temperature, thermostat 4°C or °FRead
AV15Setpoint temperatureSetpoint, thermostat 4 (3-40 °C)°C or °FWrite
MV14ModeOperating mode, thermostat 4Write0=Comfort, 1=Comfort-2, 2=Eco, 3=Frost guard/thermal protection, 4=OFF, 5=Manual
MV15Summer/WinterSeason, thermostat 4Write0=Winter, 1=Summer, 2=Hybrid
MV17Fan speedFan speed, thermostat 4Write0=Automatic, 1=Slow speed, 2=Medium speed, 3=Fast speed
AV16Minimum setpoint in heating modeHeating setpoint low limit, thermostat 4°C or °FWrite
AV17Maximum setpoint in heating modeHeating setpoint high limit, thermostat 4°C or °FWrite
AV18Minimum setpoint in cooling modeCooling setpoint low limit, thermostat 4°C or °FWrite
AV19Maximum setpoint in cooling modeCooling setpoint high limit, thermostat 4°C or °FWrite
BO15Change of unit (°C/°F)Temperature unit, thermostat 4 (write only)Write0=°C unit, 1=°F unit
MVmin4Do not disturb/ Make up roomHousekeeping state (room controller or corridor display)Write0=Do not disturb, 1=Make up room, 2=Stop/no housekeeping
BV12Ward + room numberChosen "room service" controlWrite0=Disable, 1=Enable
BVmin13SOSChosen SOS controlWrite0=Disable, 1=Enable
BV15Generic room serviceGeneric room service (UX Touch corridor display)Write0=Disable, 1=Enable
BO1Internal scenario no. 1Change of value launches internal scenarioWrite
BO2Internal scenario no. 2Change of value launches internal scenarioWrite
BO3Internal scenario no. 3Change of value launches internal scenarioWrite
BO4Internal scenario no. 4Change of value launches internal scenarioWrite
BO5Internal scenario no. 5Change of value launches internal scenarioWrite
BO6External scenario no. 1Change of value launches external scenarioWrite
BO7External scenario no. 2Change of value launches external scenarioWrite
BO8External scenario no. 3Change of value launches external scenarioWrite
BO9External scenario no. 4Change of value launches external scenarioWrite
BO10External scenario no. 5Change of value launches external scenarioWrite
Object ID lookup: Legrand Hotel room controller (RCU) point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BACnet IP hotel room controller 0 484 12 / 0 484 08 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08

How many BACnet points does the Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08 have?

This list has 67 BACnet objects: 4 analog inputs, 22 analog values, 2 binary inputs, 15 binary outputs, 9 binary values, 15 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08 BACnet points are writable?

61 of the 67 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08 BACnet documentation?

The source is Hotel Rooms BACnet IP Solutions - Installation and User Guide / Technical Guide (LE10699AF), published free by Legrand at https://assets.legrand.com/pim/NP-FT-GT/LE10699AF_EN.pdf.

What are the minimum BACnet points to integrate the Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08?

Start with BV 14 PMS (Room booked flag from the PMS); MV 2 Mode (Thermostat 1 mode: 0 = Comfort ... 4 = OFF); AV 0 Setpoint temperature (Thermostat 1 setpoint); MV 5 Fan Speed (Thermostat 1 fan: 0 = auto, 1-3 = slow-fast); BO 11 Door contact for Virtual keycard function (Door state for virtual keycard, 1 = closed); BI 0 Presence (Room presence, 1 = present); AI 8 Ambient temperature (Thermostat 1 room temperature); MV 4 Do not disturb/ Make up room (0 = Do not disturb, 1 = Make up room); BV 13 SOS (SOS call).

Can the BMS supply sensor values to the Legrand BACnet IP hotel room controller 0 484 12 / 0 484 08?

With the virtual keycard function enabled, the access control system writes the door state to BO 11.

How do I check these points on the real BACnet IP hotel room controller 0 484 12 / 0 484 08?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Hotel Rooms BACnet IP Solutions - Installation and User Guide / Technical Guide · LE10699AF. Object names, instances and units are reproduced as published; descriptions are our own.