Valve actuator (bus, with energy functions) · BACnet points list
Kieback&Peter MD15-BUS / MD50-BUS small valve actuators (BACnet MS/TP) BACnet points list
Updated 12 November 2026
The Kieback&Peter MD15-BUS and MD50-BUS actuators take a position command or run their own control (room, return or differential temperature, or thermal power) over BACnet MS/TP. Objects cover the operating mode and change-over selection, setpoints, PI and limit settings, sensor input configuration for P1/P2, valve selection and hydraulic balancing, flushing and anti-seize timers, actual position, flow, temperatures, thermal power and energy, and status and fault flags.
This page lists 82 BACnet objects for the Kieback&Peter MD15-BUS / MD50-BUS small valve actuators (BACnet MS/TP) — 54 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Kieback&Peter’s own free documentation, linked below.
- Manufacturer
- Kieback&Peter
- Model
- MD15-BUS / MD50-BUS small valve actuators (BACnet MS/TP)
- Equipment
- Valve actuator (bus, with energy functions)
- Equipment type
- Valves & actuators
- BACnet objects
- 82 (54 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- MD15-BUS, MD15-BUS-HE, MD15-BUS-Q, MD15-BUS-N-Q, MD15-BUS-N-HE, MD50-BUS, MD50-BUS-N, Kieback Peter MD15, Kieback Peter MD50
Reference only, provided as-is: verify against Kieback&Peter’s current documentation and the live device before use. Not official Kieback&Peter information. Terms of use.
BMS integration notes: Kieback&Peter MD15-BUS / MD50-BUS small valve actuators (BACnet MS/TP)
Pick the operating mode with MV 4 (external position signal or one of the internal control modes) and the heating/cooling change-over with MV 9. In position mode write AV 1 (0-100 %); in room-temperature mode write AV 18 setpoint and the room temperature AV 17. Read AI 6 actual position, AI 7 flow and the fault flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 4 | Betriebmodus | Operating mode; 1 = external position signal AV 1 | Write |
| MV 9 | Auswahl HLK Modus (Change-Over) | Change-over: 1 shut, 2 heat, 3 cool, 4 auto | Write |
| AV 1 | Externes Stellsignal | Position command, 0-100 % | Write |
| AV 18 | Sollwert Raumtemperatur | Room temperature setpoint | Write |
| AV 17 | Istwert Raumtemperatur | Room temperature from the BMS | Write |
| AI 6 | Istwert Stellsignal | Actual relative flow, % | Read |
| AI 7 | Istwert Volumenstrom | Actual flow, l/h | Read |
| BI 6 | Fehler: Ventil ist blockiert | Valve blocked | Read |
| BI 4 | Störung Hardware | Hardware fault | Read |
Enable & remote start
MV 4 Betriebmodus selects position control from AV 1 or an internal control mode; MV 9 sets heating, cooling or shut-off.
Heartbeat & communication loss
MV 6 sets the reaction to a 300 s bus communication loss: no change, close, open, go to the emergency position (AV 8, default 30 %) or follow the 0-10 V input.
Sensors & values from the BMS
Room (AV 17), supply (AV 4) and return (AV 5) temperatures can be written by the BMS when MV 10 / MV 5 select the bus as their source.
Network setup
- MAC address comes from the DIP switches; with switch setting 63 it can be written through AV 28. MV 7 sets the baud rate (default 38400).
Watch out for
- MV 6 decides what the actuator does after 300 s without bus communication (no change, close, open, emergency position AV 8, or follow the 0-10 V input).
- Write bus temperatures (AV 4, AV 5, AV 17) no more than once an hour; they are stored persistently.
Kieback&Peter MD15-BUS / MD50-BUS small valve actuators (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Software-Version | Software version (123 = 1.23) | Read | ||
| AI | 2 | Analoger Eingang P1 | Input P1 value; unit follows sensor type; only MD15/MD15-HE/MD15-Q/MD50 | Read | ||
| AI | 3 | Analoger Eingang P2 | Input P2 value; unit follows sensor type; only MD15/MD15-HE/MD15-Q/MD50 | Read | ||
| AI | 4 | Sollposition | Target stem position | mm | Read | |
| AI | 5 | Ist Position | Actual stem position | mm | Read | |
| AImin | 6 | Istwert Stellsignal | Actual relative flow | % | Read | |
| AImin | 7 | Istwert Volumenstrom | Actual flow from valve data; only MD15-Q/-N types/MD50 | l/h | Read | |
| AI | 8 | Istwert Differenztemperatur | Supply minus return temperature | K | Read | |
| AI | 9 | Spueltimer aktuell | Hours to next flush, or minutes left while flushing | Read | ||
| AI | 10 | Ventilblockierschutz-Timer aktuell | Hours until anti-seize run | h | Read | |
| AI | 11 | Betriebsstunden | Total operating hours | h | Read | |
| AI | 12 | Wegzähler | Total stem travel | mm | Read | |
| AI | 13 | Gesamt-Stellhub | Learned stroke between end positions | mm | Read | |
| AI | 15 | Aktuelle Volumenstrombegrenzung | Active flow limit (heating or cooling); only MD15-Q/-N types/MD50 | l/h | Read | |
| AI | 16 | Istwert der thermischen Leistung | Thermal power (pressure-independent valves); only MD15-Q/-N types/MD50 | kW | Read | |
| AI | 17 | Energie seit 0:00 Uhr | Energy since midnight; only MD15-Q/-N types/MD50 | kWh | Read | |
| AI | 18 | Energie in den letzten 24 h | Energy in the last 24 h; only MD15-Q/-N types/MD50 | kWh | Read | |
| AI | 20 | Gültigkeitsdauer kontinuierlicher Energiezähler | Time since continuous energy counter reset; only MD15-Q/-N types/MD50 | h | Read | |
| AO | 1 | Analoger Ausgang P2 | Output P2 value when P2 is a 0-10 V output; only MD15/MD15-HE/MD15-Q/MD50 | % | Write | |
| AVmin | 1 | Externes Stellsignal | Position command (relative flow) | % | Write | |
| AV | 2 | Minimaler Stellhub | Lower limit of the position signal | % | Write | |
| AV | 3 | Maximaler Stellhub | Upper limit of the position signal | % | Write | |
| AV | 4 | Istwert Vorlauftemperatur | Supply temperature (write from BMS if bus source) | °C | Write | |
| AV | 5 | Istwert Rücklauftemperatur | Return temperature (write from BMS if bus source) | °C | Write | |
| AV | 6 | Korrekturwert P1 | Offset for sensor P1; only MD15/MD15-HE/MD15-Q/MD50 | K | Write | |
| AV | 7 | Korrekturwert P2 | Offset for sensor P2; only MD15/MD15-HE/MD15-Q/MD50 | K | Write | |
| AV | 8 | Notposition | Emergency position on bus loss or control fault | % | Write | |
| AV | 9 | Spültimer | Flush timer in minutes (old; use AV 35) | min | Write | |
| AV | 10 | Timer Ventilblockierschutz | Anti-seize timer; 0 = off | h | Write | |
| AV | 11 | Hydraulischer Abgleich Heizen | Flow limit, heating; only MD15-Q/-N types/MD50 | l/h | Write | |
| AV | 12 | Hydraulischer Abgleich Kühlen | Flow limit, cooling; only MD15-Q/-N types/MD50 | l/h | Write | |
| AV | 13 | Federweg Ventil | Valve stroke; change triggers relearn; only MD15-HE/MD15-Q/-N types | mm | Write | |
| AV | 14 | Medium-Energiekonstante | Medium heat capacity (water 4183) | J/(kg·K) | Write | |
| AV | 15 | Xp | PI controller proportional band | Write | ||
| AV | 16 | Tn | PI controller reset time | s | Write | |
| AVmin | 17 | Istwert Raumtemperatur | Room temperature (write from BMS if bus source) | °C | Write | |
| AVmin | 18 | Sollwert Raumtemperatur | Room temperature setpoint | °C | Write | |
| AV | 19 | Sollwert thermische Leistung | Thermal power setpoint; only MD15-Q/-N types/MD50 | kW | Write | |
| AV | 20 | Sollwert Rücklauftemperatur | Return temperature setpoint | °C | Write | |
| AV | 21 | Sollwert Differenztemperatur | Differential temperature setpoint | °C | Write | |
| AV | 22 | Grenzwert maximale thermische Leistung | Maximum thermal power limit; 0 = off; only MD15-Q/-N types/MD50 | kW | Write | |
| AV | 23 | Grenzwert Ruecklauftemperatur | Return temperature limit; 0 = off | °C | Write | |
| AV | 24 | Grenzwert Differenztemperatur | Minimum differential temperature limit; 0 = off | K | Write | |
| AV | 28 | MAC-Adresse | MS/TP MAC address (writable at DIP setting 63) | Write | ||
| AV | 29 | Schließen wenn Stellbereich | Band near end positions that drives fully open/closed | % | Write | |
| AV | 30 | Kvs Wert des ausgewaehlten Ventils | Kvs of the selected valve; only MD15-Q/-N types/MD50 | l/h | Write | |
| AV | 31 | Sensitivität Begrenzung thermische Leistung | Power limit sensitivity; only MD15-Q/-N types/MD50 | Write | ||
| AV | 32 | Sensitivität Begrenzung Rücklauftemperatur | Return temperature limit sensitivity | Write | ||
| AV | 33 | Sensitivität Begrenzung Differenztemperatur | Differential temperature limit sensitivity | Write | ||
| AV | 34 | Kontinuierlicher Energiezähler | Continuous energy counter; write 0 to reset; only MD15-Q/-N types/MD50 | kWh | Write | |
| AV | 35 | Spültimer | Flush timer in hours; 0 = off | h | Write | |
| AV | 36 | Spültimer Öffnungszeit | Time held fully open while flushing | min | Write | |
| AV | 37 | Startwert externes Stellsignal | Start value of the position signal at power-up | % | Write | |
| BI | 1 | Binaerer Eingang P1 | Binary input P1; only MD15/MD15-HE/MD15-Q/MD50 | Read | 0=Aus, 1=Ein | |
| BI | 2 | Binaerer Eingang P2 | Binary input P2; only MD15/MD15-HE/MD15-Q/MD50 | Read | 0=Aus, 1=Ein | |
| BI | 3 | Antrieb ist beschaeftigt | Actuator busy (also set while flushing) (status word bit) | Read | 0=Normal, 1=Active | |
| BImin | 4 | Störung Hardware | Hardware fault (status word bit) | Read | 0=Normal, 1=Active | |
| BI | 5 | Fehler beim Anlernen des Ventils | Valve learning failed (status word bit) | Read | 0=Normal, 1=Active | |
| BImin | 6 | Fehler: Ventil ist blockiert | Valve blocked (status word bit) | Read | 0=Normal, 1=Active | |
| BI | 7 | Warnung: Leckage erkannt | Leak warning (dT over 8 K with valve closed 6 h) | Read | 0=keine Warnung, 1=Leckage erkannt (Differenztemperatur ueber 8 K während Ventil min. 6 h geschlossen) | |
| BI | 8 | Begrenzung thermische Leistung aktiv | Power, return or dT limit active (status word bit) | Read | 0=Normal, 1=Active | |
| BI | 9 | Taupunkt/Frostschutzwächter aktiv | Dew point or frost monitor active (status word bit) | Read | 0=Normal, 1=Active | |
| BV | 1 | P1 Invertierung (binaerer Eingang) | Invert binary input P1; only MD15/MD15-HE/MD15-Q/MD50 | Write | 0=Normal, 1=Invertiert | |
| BV | 2 | P2 Invertierung (binaerer Eingang) | Invert binary input P2; only MD15/MD15-HE/MD15-Q/MD50 | Write | 0=Normal, 1=Invertiert | |
| BV | 3 | P2 Invertierung (analoger Ausgang) | Invert analog output P2; only MD15/MD15-HE/MD15-Q/MD50 | Write | 0=Normal, 1=Invertiert | |
| BV | 4 | Invertierung der Ventilstellrichtung | Invert valve direction | Write | 0=Normal, 1=Invertiert | |
| MI | 1 | Status HLK Modus (Change-Over) | Change-over status | Read | 1=Aus (Absperren), 2=Heizen, 3=Kühlen | |
| MV | 1 | Service- und Wartungsfunktionen auswählen | Service functions (learn, test run, reset ...) | Write | 1=Normalbetrieb, 2=Anlernen des Ventils, 3=Testlauf, 4=Ventil synchronisieren, 5=Fehlermeldungen zuruecksetzen, 6=Bus-Neustart, 7=Auf Werkseinstellungen zuruecksetzen | |
| MV | 2 | Sensortyp P1 | Sensor type on P1; only MD15/MD15-HE/MD15-Q/MD50 | Write | 1=Aus, 2=Binaerer Eingang, 3=0..10 V Eingang, 4=KP10, 5=NI1000-DIN, 6=NI1000-LG, 7=PT1000, 8=Potentiometer 10k, 9=Potentiometer 10k Sollwertkorrektur +/-3 K, 10=Potentiometer 10k Sollwertkorrektur +/-5 K | |
| MV | 3 | Sensor-/Ausgangstyp P2 | Sensor or output type on P2; only MD15/MD15-HE/MD15-Q/MD50 | Write | 1=Aus, 2=Binaerer Eingang, 3=0..10 V Eingang, 4=KP10, 5=NI1000-DIN, 6=NI1000-LG, 7=PT1000, 8=Potentiometer 10k, 9=0..10 V Ausgang (nach Register 426/AO1), 10=0..10 V Stellungsrueckmeldung (nach Register 401/AI6), 11=Change-Over-Ausgang für 6-Wege Ventil (nach Register 201/MV9) | |
| MVmin | 4 | Betriebmodus | Operating mode | Write | 1=Steuerung über externes Stellsignal / (Register 400/AV1), 2=Auf (100 %), 3=Zu (0 %), 4=Min. Pos (Register 312/AV2), 5=res., 6=Max. Pos (Register 313/AV3), 7=Regelung nach Raumtemperatur (Register 403/AV17 und 300/AV18), 8=Regelung nach thermischer Leistung (Register 410/AI16 und 301/AV19), 9=Regelung nach Ruecklauftemperatur (Register 405/AV5 und 302/AV20), 10=Regelung nach Differenztemperatur (Register 406/AI8 und 303/AV21), 11=Steuerung über YIN 0..10V (P1), 12=Steuerung über YIN 0..10V (P2) | |
| MV | 5 | Quellen für Vor- und Ruecklauftemperatur | Source of supply and return temperature; only MD15/MD15-HE/MD15-Q/MD50 | Write | 1=Buswerte über Register 404/AV4 und / 405/AV5, 2=Vorlauf: P1, Rücklauf: P2, 3=Vorlauf: P2, Rücklauf: P1, 4=Vorlauf: P1, Rücklauf: Bus, 5=Vorlauf: P2, Rücklauf: Bus, 6=Vorlauf: Bus, Rücklauf: P1, 7=Vorlauf: Bus, Rücklauf: P2 | |
| MV | 6 | Modus Kommunikationsausfall | Reaction to bus communication loss (300 s) | Write | 1=Keine Aenderung, 2=Zu (0%) Zeitüberschreitung (300s), 3=Auf (100%) bei Zeitüberschreitung (300s), 4=Notposition (Register 134/AV8) bei Zeitüberschreitung (300s), 5=Nach YIN 0..10V (P1) bei Zeitüberschreitung (300s), 6=Nach YIN 0..10V (P2) bei Zeitüberschreitung (300s) | |
| MV | 7 | RS485 Baudrate | RS-485 baud rate | Write | 1=Default (38400), 2=9600, 3=19200, 4=38400, 5=57600, 6=76800, 7=115200 | |
| MV | 8 | Ventiltyp Auswahl | Valve type; list depends on actuator model | Write | ||
| MVmin | 9 | Auswahl HLK Modus (Change-Over) | Change-over: shut, heat, cool or auto | Write | 1=Absperren, 2=Heizen, 3=Kühlen, 4=Automatisch über Vorlauftemperatur (keine Ansteuerung des Change-Over Ausgangs (P2)) | |
| MV | 10 | Quelle fuer Raumtemperatur auswählen | Source of room temperature; only MD15/MD15-HE/MD15-Q/MD50 | Write | 1=Buswert über Register 403/AV17, 2=P1, 3=P2 | |
| MV | 11 | LED Modus | LED mode | Write | 1=LED aus, 2=Betriebsstatus ohne Bus, 3=Betriebsstatus mit Bus | |
| MV | 12 | Stellgeschwindigkeit | Actuator speed | Write | 1=Normal: 22 s/mm, 2=Langsam: 28 s/mm, 3=Schnell: 16 s/mm | |
| MV | 13 | Stellsignal Charakteristik | Control signal characteristic | Write | 1=Linear, 3=Gleichprozentig, 4=Gleichprozentig (Invertiert) | |
| MV | 14 | Taupunktwächter | Dew point monitor | Write | 1=Off, 2=P1 (Zu = 0%), 3=P2 (Zu = 0%), 4=P1 (Notposition AV8), 5=P2 (Notposition AV8) | |
| MV | 15 | Froschutzwächter | Frost protection monitor | Write | 1=Off, 2=P1 (Auf = 100%), 3=P2 (Auf = 100%), 4=P1 (Notposition AV8), 5=P2 (Notposition AV8) |
No points match these filters.
Object ID lookup: Kieback&Peter MD15-BUS / MD50-BUS small valve actuators point IDs by name
AI1Software-VersionAI2Analoger Eingang P1AI3Analoger Eingang P2AI4SollpositionAI5Ist PositionAI6Istwert StellsignalAI7Istwert VolumenstromAI8Istwert DifferenztemperaturAI9Spueltimer aktuellAI10Ventilblockierschutz-Timer aktuellAI11BetriebsstundenAI12WegzählerAI13Gesamt-StellhubAI15Aktuelle VolumenstrombegrenzungAI16Istwert der thermischen LeistungAI17Energie seit 0:00 UhrAI18Energie in den letzten 24 hAI20Gültigkeitsdauer kontinuierlicher EnergiezählerAO1Analoger Ausgang P2AV1Externes StellsignalAV2Minimaler StellhubAV3Maximaler StellhubAV4Istwert VorlauftemperaturAV5Istwert RücklauftemperaturAV6Korrekturwert P1AV7Korrekturwert P2AV8NotpositionAV9SpültimerAV10Timer VentilblockierschutzAV11Hydraulischer Abgleich HeizenAV12Hydraulischer Abgleich KühlenAV13Federweg VentilAV14Medium-EnergiekonstanteAV15XpAV16TnAV17Istwert RaumtemperaturAV18Sollwert RaumtemperaturAV19Sollwert thermische LeistungAV20Sollwert RücklauftemperaturAV21Sollwert DifferenztemperaturAV22Grenzwert maximale thermische LeistungAV23Grenzwert RuecklauftemperaturAV24Grenzwert DifferenztemperaturAV28MAC-AdresseAV29Schließen wenn StellbereichAV30Kvs Wert des ausgewaehlten VentilsAV31Sensitivität Begrenzung thermische LeistungAV32Sensitivität Begrenzung RücklauftemperaturAV33Sensitivität Begrenzung DifferenztemperaturAV34Kontinuierlicher EnergiezählerAV35SpültimerAV36Spültimer ÖffnungszeitAV37Startwert externes StellsignalBI1Binaerer Eingang P1BI2Binaerer Eingang P2BI3Antrieb ist beschaeftigtBI4Störung HardwareBI5Fehler beim Anlernen des VentilsBI6Fehler: Ventil ist blockiertBI7Warnung: Leckage erkanntBI8Begrenzung thermische Leistung aktivBI9Taupunkt/Frostschutzwächter aktivBV1P1 Invertierung (binaerer Eingang)BV2P2 Invertierung (binaerer Eingang)BV3P2 Invertierung (analoger Ausgang)BV4Invertierung der VentilstellrichtungMI1Status HLK Modus (Change-Over)MV1Service- und Wartungsfunktionen auswählenMV2Sensortyp P1MV3Sensor-/Ausgangstyp P2MV4BetriebmodusMV5Quellen für Vor- und RuecklauftemperaturMV6Modus KommunikationsausfallMV7RS485 BaudrateMV8Ventiltyp AuswahlMV9Auswahl HLK Modus (Change-Over)MV10Quelle fuer Raumtemperatur auswählenMV11LED ModusMV12StellgeschwindigkeitMV13Stellsignal CharakteristikMV14TaupunktwächterMV15Froschutzwächter
Integration notes
- The source is a German manual; object names are the German parameter names from its data point list (Bezeichnung). The live Object_Name in the actuator may differ.
- Many objects exist only on some models (marked "only ..."): power, energy and flow values need the pressure-independent MD15-Q / -N / MD50 types. P1/P2 inputs are not on the -N types.
- BI 3-9 are not named in the table; they are bits of the operating status word (register 318) and are listed with the bit text. BI 3 and BI 8 each carry more than one condition (busy/flushing, three limit functions).
- MV 8 valve type selection has a different valve list per model; see the manual.
- Temperatures written by the BMS (AV 4, AV 5, AV 17) are read-only when a P1/P2 sensor is assigned as their source; the manual says to write them at most once per hour (persistent memory).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MD15-BUS / MD50-BUS small valve actuators (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Kieback&Peter MD15-BUS / MD50-BUS small valve actuators (BACnet MS/TP)
How many BACnet points does the Kieback&Peter MD15-BUS / MD50-BUS small valve actuators (BACnet MS/TP) have?
This list has 82 BACnet objects: 18 analog inputs, 1 analog output, 34 analog values, 9 binary inputs, 4 binary values, 1 multi-state input, 15 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Kieback&Peter MD15-BUS / MD50-BUS small valve actuators (BACnet MS/TP) BACnet points are writable?
54 of the 82 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Kieback&Peter MD15-BUS / MD50-BUS small valve actuators (BACnet MS/TP) BACnet documentation?
The source is Handbuch Konfiguration und Anwendungsbeispiele MD50-BUS und MD15-BUS-xx (AppNotes), ch. 2.5 Datenpunktliste fuer Bus-Stellantriebe, revision Rev. 1.10, published free by Kieback&Peter at https://kieback-peter.com/fileadmin/downloads/produkte/aktoren/Betriebsanleitungen/MD50/MD50-BUS/AppNotes_DE_MD50-BUS__MD15-BUS-xx_Rev._1.10.pdf.
What are the minimum BACnet points to integrate the Kieback&Peter MD15-BUS / MD50-BUS small valve actuators (BACnet MS/TP)?
Start with MV 4 Betriebmodus (Operating mode; 1 = external position signal AV 1); MV 9 Auswahl HLK Modus (Change-Over) (Change-over: 1 shut, 2 heat, 3 cool, 4 auto); AV 1 Externes Stellsignal (Position command, 0-100 %); AV 18 Sollwert Raumtemperatur (Room temperature setpoint); AV 17 Istwert Raumtemperatur (Room temperature from the BMS); AI 6 Istwert Stellsignal (Actual relative flow, %); AI 7 Istwert Volumenstrom (Actual flow, l/h); BI 6 Fehler: Ventil ist blockiert (Valve blocked); BI 4 Störung Hardware (Hardware fault).
How do I enable BMS control of the Kieback&Peter MD15-BUS / MD50-BUS small valve actuators (BACnet MS/TP)?
MV 4 Betriebmodus selects position control from AV 1 or an internal control mode; MV 9 sets heating, cooling or shut-off.
Does the Kieback&Peter MD15-BUS / MD50-BUS small valve actuators (BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?
MV 6 sets the reaction to a 300 s bus communication loss: no change, close, open, go to the emergency position (AV 8, default 30 %) or follow the 0-10 V input.
Can the BMS supply sensor values to the Kieback&Peter MD15-BUS / MD50-BUS small valve actuators (BACnet MS/TP)?
Room (AV 17), supply (AV 4) and return (AV 5) temperatures can be written by the BMS when MV 10 / MV 5 select the bus as their source.
How do I check these points on the real MD15-BUS / MD50-BUS small valve actuators (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: Handbuch Konfiguration und Anwendungsbeispiele MD50-BUS und MD15-BUS-xx (AppNotes), ch. 2.5 Datenpunktliste fuer Bus-Stellantriebe · rev. Rev. 1.10. Object names, instances and units are reproduced as published; descriptions are our own.