- TA-Slider 160 / 500 / 750 / 1250 / 1600 BACnet MS/TP actuator
Valve actuator (digital, BACnet MS/TP) · BACnet points list
IMI Hydronic TA-Slider 160 / 500 / 750 / 1250 / 1600 BACnet MS/TP actuator BACnet points list
Updated 12 November 2026
Digitally configurable TA-Slider valve actuators (160 N to 1600 N) with BACnet MS/TP. Over the bus they take a relative setpoint, report position, interpolated flow and two optional temperature sensors, and expose stroke/flow limits, change-over regimes, temperature limitation and an error log. The 160/500 and the 750/1250/1600 documents print the same object table, except that only the larger actuators have the second relay (BV 4).
This page lists 90 BACnet objects for the IMI Hydronic TA-Slider 160 / 500 / 750 / 1250 / 1600 BACnet MS/TP actuator — 48 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from IMI Hydronic’s own free documentation, linked below.
- Manufacturer
- IMI Hydronic
- Model
- TA-Slider 160 / 500 / 750 / 1250 / 1600 BACnet MS/TP actuator
- Equipment
- Valve actuator (digital, BACnet MS/TP)
- Equipment type
- Valves & actuators
- BACnet objects
- 90 (48 writable)
- Transport
- BACnet MS/TP
- Firmware
- 2.5.0
- Also known as
- TA-Slider 750, TA-Slider 1250, TA-Slider 1600, TA-Slider 750 Plus, TA-Slider 1600 Plus, TA-Slider 750 2T, TA-Slider 1600 2T, 322226, 322227, 322228, TA-Slider 160, TA-Slider 500, TA-Slider 160 BACnet MS/TP, TA-Slider 500 BACnet MS/TP R24, TA-Slider 160 CO, IMI TA TA-Slider, 322224 13011, 322225 13011
Reference only, provided as-is: verify against IMI Hydronic’s current documentation and the live device before use. Not official IMI Hydronic information. Terms of use.
BMS integration notes: IMI Hydronic TA-Slider 160 / 500 / 750 / 1250 / 1600 BACnet MS/TP actuator
Configure the actuator with HyTune (device ID, baud, parity) and set Signal Source to BusCom, then write the relative setpoint AV 0 and read back position, flow and the motor status. Set AV 2 if you want an error when the BMS stops sending.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 0 | Control Setpoint | Relative setpoint, 0-100 % | Write |
| AI 0 | Actuator position Feedback | Actuator position, % | Read |
| MI 0 | Motor status | Motor status (7 = error) | Read |
| AI 7 | FlowFeedback SI | Interpolated flow, l/h (needs valve type) | Read |
| BI 0 | Override Status | Manual/electrical override active | Read |
| AV 10 | Errors code | Error code (0 = no error) | Read |
Enable & remote start
The actuator follows AV 0 only when Signal Source (MSI 11) is BusCom; that is set with the HyTune app and TA-Dongle.
Heartbeat & communication loss
AV 2 Cyclic control timeout (0-60 min, default 0 = off) raises a CyclicTime error if no control signal arrives within the time.
Network setup
- Baud rate Auto (default), 9600-115200; device ID, baud and parity are set with HyTune.
- Device instance defaults to a value computed from the serial number; Max_Master and Location are writable.
- RS-485 termination: switched on with HyTune on the 160/500; on the 750/1250/1600 remove the jumper behind the wire connector on the communication board.
Watch out for
- Flow objects need the valve type defined (AV 31 or HyTune), otherwise they are meaningless.
- Change-over by bus uses BV 2 (regime) and BV 3 (relay for a 6-way valve) and needs HyTune pre-configuration (FW 2.5.0+).
IMI Hydronic TA-Slider 160 / 500 / 750 / 1250 / 1600 BACnet MS/TP actuator BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 0 | Actuator position Feedback | Current actuator position, % of stroke | % | Read | |
| AI | 1 | Calibrated stroke SI | Stroke found by calibration, µm | µm | Read | |
| AI | 2 | Calibrated stroke US | Stroke found by calibration, inches | in | Read | |
| AI | 3 | Motor ontime | Total motor running time since first power-up | s | Read | |
| AI | 4 | Actuator ontime | Total time in service since first power-up | s | Read | |
| AI | 5 | Actuator distance SI | Total travel since first power-up, mm | mm | Read | |
| AI | 6 | Actuator distance US | Total travel since first power-up, inches | in | Read | |
| AImin | 7 | FlowFeedback SI | Interpolated flow, l/h (needs valve type) | l/h | Read | |
| AI | 8 | FlowFeedback US | Interpolated flow, USGPM (needs valve type) | USGPM | Read | |
| AI | 9 | Temperature 1 SI | Sensor 1 temperature, °C (10000/10001 = fault) | °C | Read | |
| AI | 10 | Temperature 1 US | Sensor 1 temperature, °F (10000/10001 = fault) | °F | Read | |
| AI | 11 | Temperature 2 SI | Sensor 2 temperature, °C (10000/10001 = fault) | °C | Read | |
| AI | 12 | Temperature 2 US | Sensor 2 temperature, °F (10000/10001 = fault) | °F | Read | |
| AVmin | 0 | Control Setpoint | Relative setpoint, % of the active maximum | % | Write | |
| AV | 1 | Communication address | MS/TP address of the actuator | Write | ||
| AV | 2 | Cyclic control timeout | Error if no control signal within this time (0 = off) | min | Write | |
| AV | 3 | Max Stroke Limitation R1 SI | Max stroke in regime 1, µm | µm | Write | |
| AV | 4 | Max Stroke Limitation R1 US | Max stroke in regime 1, inches | in | Write | |
| AV | 5 | Max Stroke Limitation R2 SI | Max stroke in regime 2, µm | µm | Write | |
| AV | 6 | Max Stroke Limitation R2 US | Max stroke in regime 2, inches | in | Write | |
| AV | 7 | Min stroke limitation R1 SI | Min stroke in regime 1, µm | µm | Write | |
| AV | 8 | Min stroke limitation R1 US | Min stroke in regime 1, inches | in | Write | |
| AVmin | 10 | Errors code | Active error code (0 = no error) | Read | ||
| AV | 11 | Error 1 | Error log, oldest entry | Read | ||
| AV | 12 | Error 2 | Error log entry 2 | Read | ||
| AV | 13 | Error 3 | Error log entry 3 | Read | ||
| AV | 14 | Error 4 | Error log entry 4 | Read | ||
| AV | 15 | Error 5 | Error log entry 5 | Read | ||
| AV | 16 | Error 6 | Error log entry 6 | Read | ||
| AV | 17 | Error 7 | Error log entry 7 | Read | ||
| AV | 18 | Error 8 | Error log entry 8 | Read | ||
| AV | 19 | Error 9 | Error log entry 9 | Read | ||
| AV | 20 | Error 10 | Error log, newest entry | Read | ||
| AV | 21 | Min stroke limitation R2 SI | Min stroke in regime 2, µm | µm | Write | |
| AV | 22 | Min stroke limitation R2 US | Min stroke in regime 2, inches | in | Write | |
| AV | 23 | Max Flow limitation R1 SI | Max flow in regime 1, l/h | l/h | Write | |
| AV | 24 | Max Flow limitation R1 US | Max flow in regime 1, USGPM | USGPM | Write | |
| AV | 25 | Max Flow limitation R2 SI | Max flow in regime 2, l/h | l/h | Write | |
| AV | 26 | Max Flow limitation R2 US | Max flow in regime 2, USGPM | USGPM | Write | |
| AV | 27 | Min Flow limitation R1 SI | Min flow in regime 1, l/h | l/h | Write | |
| AV | 28 | Min Flow limitation R1 US | Min flow in regime 1, USGPM | USGPM | Write | |
| AV | 29 | Min Flow limitation R2 SI | Min flow in regime 2, l/h | l/h | Write | |
| AV | 30 | Min Flow limitation R2 US | Min flow in regime 2, USGPM | USGPM | Write | |
| AV | 31 | Valve | Valve type the actuator is mounted on | Write | ||
| AV | 32 | DeltaT Setpoint R1 | Delta T limitation setpoint, regime 1 | K | Write | |
| AV | 33 | DeltaT Setpoint R2 | Delta T limitation setpoint, regime 2 | K | Write | |
| AV | 34 | Return T Setpoint R1 SI | Return temperature limit, regime 1, °C | °C | Write | |
| AV | 35 | Return T Setpoint R1 US | Return temperature limit, regime 1, °F | °F | Write | |
| AV | 36 | Return T Setpoint R2 SI | Return temperature limit, regime 2, °C | °C | Write | |
| AV | 37 | Return T Setpoint R2 US | Return temperature limit, regime 2, °F | °F | Write | |
| AV | 38 | Min Flow threshold R1 SI | Flow below which temp limitation stops, regime 1 | l/h | Write | |
| AV | 39 | Min Flow threshold R1 US | Flow below which temp limitation stops, regime 1 | USGPM | Write | |
| AV | 40 | Min Flow threshold R2 SI | Flow below which temp limitation stops, regime 2 | l/h | Write | |
| AV | 41 | Min Flow threshold R2 US | Flow below which temp limitation stops, regime 2 | USGPM | Write | |
| AV | 42 | Min stroke threshold R1 SI | Stroke below which temp limitation stops, regime 1 | µm | Write | |
| AV | 43 | Min stroke threshold R1 US | Stroke below which temp limitation stops, regime 1 | in | Write | |
| AV | 44 | Min stroke threshold R2 SI | Stroke below which temp limitation stops, regime 2 | µm | Write | |
| AV | 45 | Min stroke threshold R2 US | Stroke below which temp limitation stops, regime 2 | in | Write | |
| AV | 46 | Heating reference Supply DT | Reference supply delta T for heating return-temp limit | K | Write | |
| AV | 47 | Cooling reference Supply DT | Reference supply delta T for cooling return-temp limit | K | Write | |
| AV | 48 | ChangeOver Temp Switch R1 SI | Supply temp that switches to cooling, °C | °C | Write | |
| AV | 49 | ChangeOver Temp Switch R1 US | Supply temp that switches to cooling, °F | °F | Write | |
| AV | 50 | ChangeOver Temp Switch R2 SI | Supply temp that switches to heating, °C | °C | Write | |
| AV | 51 | ChangeOver Temp Switch R2 US | Supply temp that switches to heating, °F | °F | Write | |
| AV | 52 | CoRegime switching DT | Temperature difference needed to switch regimes | K | Write | |
| BImin | 0 | Override Status | Mechanical or electrical override active | Read | 0=No, 1=Yes | |
| BI | 1 | Physical Binary Input | State of the physical binary input | Read | 0=Off, 1=On | |
| BI | 2 | Temp Limitation Status | Current status of the temperature limitation | Read | 0=Inactive, 1=Active | |
| BI | 3 | Temp 1 Used | Defines whether the Temperature sensor 1 is used or not | Read | 0=Not used, 1=Used | |
| BI | 4 | Temp 2 Used | Defines whether the Temperature sensor 2 is used or not | Read | 0=Not used, 1=Used | |
| BV | 0 | Valve opening type | Valve direction (push-to-close or push-to-open) | Read | 0=Push-to-close, 1=Push-to-open | |
| BV | 1 | Force calibration | Request forced calibration | Write | 0=Off, 1=On | |
| BV | 2 | Bus Binary input | Regime or flushing request from the bus (see MSI 10) | Write | 0=Regime1 / No flushing, 1=Regime2 / Flushing | |
| BV | 3 | Relay1 | Relay 1 command when its trigger is BusCom | Write | 0=Deactivated, 1=Activated | |
| BV | 4 | Relay2 | Relay 2 command when its trigger is BusCom | Write | 0=Deactivated, 1=Activated | |
| BV | 5 | Enable Limited Stroke | Enable stroke limits (read-only with some change-over types) | Write | 0=Deactivated, 1=Activated | |
| MImin | 0 | Motor status | Motor status | Read | 1=Stopped, 2=Retracting, 3=Extending, 4=Calibration, 5=Manual-override, 6=Clogging, 7=Error | |
| MI | 1 | Power type | Power type | Read | 1=Low, 2=High, 3=USB | |
| MI | 2 | Actuator Control Characteristics | Characteristic of the actuator | Read | 1=Linear, 2=Equal Percentage Modified (EQM), 3=Inverted EQM | |
| MI | 3 | Actuator Speed | Actuator speed (set with HyTune) | s/mm | Read | |
| MI | 4 | Operating Mode | Heating or cooling mode (sets defaults and limits) | Read | 1=Heating, 2=Cooling | |
| MI | 5 | Current CoRegime | Current change-over regime status | Read | 1=Regime1, 2=Regime2 | |
| MI | 6 | CoRegime switching | Switching mode between regimes 1 and 2 | Read | 1=None, 2=Dual-Range input Signal, 3=BusCom, 4=Temperature detection, 6=Delta Temperature Detection, 7=Binary input | |
| MI | 7 | Temp 1 location | Location on which the Temperature sensor 1 is installed | Read | 1=Supply side, 2=Return side | |
| MI | 8 | Temp 2 location | Location on which the Temperature sensor 2 is installed | Read | 1=Supply side, 2=Return side | |
| MI | 9 | Temp Limitation Type | Temperature limitation type to be chosen between DT or return temperature | Read | 1=None, 2=DT limitation, 3=T return limitation | |
| MI | 10 | Bus Binary Action | What BV 2 does when regime switching is BusCom | Read | 1=None, 2=Change-Over, 3=Flushing | |
| MI | 11 | Signal Source | SignalSource used to control the TA-Slider | Read | 1=Analog (V), 5=BusCom | |
| MV | 0 | RS-485 Baud rate | Baud rate for the BACnet MS/TP communication | Write | ||
| MV | 1 | Valve Control Char | Control characteristic of the valve type | Write | 1=Linear, 2=EQM |
No points match these filters.
Object ID lookup: IMI Hydronic TA-Slider 160 / 500 / 750 / 1250 / 1600 BACnet MS/TP actuator point IDs by name
AI0Actuator position FeedbackAI1Calibrated stroke SIAI2Calibrated stroke USAI3Motor ontimeAI4Actuator ontimeAI5Actuator distance SIAI6Actuator distance USAI7FlowFeedback SIAI8FlowFeedback USAI9Temperature 1 SIAI10Temperature 1 USAI11Temperature 2 SIAI12Temperature 2 USAV0Control SetpointAV1Communication addressAV2Cyclic control timeoutAV3Max Stroke Limitation R1 SIAV4Max Stroke Limitation R1 USAV5Max Stroke Limitation R2 SIAV6Max Stroke Limitation R2 USAV7Min stroke limitation R1 SIAV8Min stroke limitation R1 USAV10Errors codeAV11Error 1AV12Error 2AV13Error 3AV14Error 4AV15Error 5AV16Error 6AV17Error 7AV18Error 8AV19Error 9AV20Error 10AV21Min stroke limitation R2 SIAV22Min stroke limitation R2 USAV23Max Flow limitation R1 SIAV24Max Flow limitation R1 USAV25Max Flow limitation R2 SIAV26Max Flow limitation R2 USAV27Min Flow limitation R1 SIAV28Min Flow limitation R1 USAV29Min Flow limitation R2 SIAV30Min Flow limitation R2 USAV31ValveAV32DeltaT Setpoint R1AV33DeltaT Setpoint R2AV34Return T Setpoint R1 SIAV35Return T Setpoint R1 USAV36Return T Setpoint R2 SIAV37Return T Setpoint R2 USAV38Min Flow threshold R1 SIAV39Min Flow threshold R1 USAV40Min Flow threshold R2 SIAV41Min Flow threshold R2 USAV42Min stroke threshold R1 SIAV43Min stroke threshold R1 USAV44Min stroke threshold R2 SIAV45Min stroke threshold R2 USAV46Heating reference Supply DTAV47Cooling reference Supply DTAV48ChangeOver Temp Switch R1 SIAV49ChangeOver Temp Switch R1 USAV50ChangeOver Temp Switch R2 SIAV51ChangeOver Temp Switch R2 USAV52CoRegime switching DTBI0Override StatusBI1Physical Binary InputBI2Temp Limitation StatusBI3Temp 1 UsedBI4Temp 2 UsedBV0Valve opening typeBV1Force calibrationBV2Bus Binary inputBV3Relay1BV4Relay2BV5Enable Limited StrokeMI0Motor statusMI1Power typeMI2Actuator Control CharacteristicsMI3Actuator SpeedMI4Operating ModeMI5Current CoRegimeMI6CoRegime switchingMI7Temp 1 locationMI8Temp 2 locationMI9Temp Limitation TypeMI10Bus Binary ActionMI11Signal SourceMV0RS-485 Baud rateMV1Valve Control Char
Integration notes
- Taken from the protocol implementation tables (object, name, access, unit, value range, default, resolution) of both TA-Slider documents; footnote markers after names are removed.
- Differences between the two documents: BV 4 Relay2 exists only on the 750/1250/1600; the 160/500 document prints AV 0 as "ControlSetpoint" and MSI 1 state 2 as reserved; stroke and flow ranges are model-specific.
- Many objects come in SI and US pairs (µm/in, l/h/USGPM, °C/°F); read the one that matches your units.
- Several limits and temperature functions only apply when the change-over regime, valve type (AV 31) or temperature limitation is configured, usually with the HyTune app and TA-Dongle. Access [RW] (relay, limited stroke) is writable only in some configurations.
- Some objects need firmware 1.1.0 (main board 4.0.0), 2.4.4/2.4.5 or 2.5.0 per the footnotes; BV 3/BV 4 relays need the relay option.
- TA-Slider 160/500 document (dated 29/01/2024): https://assets.imi-hydronic.com/Documents/Instructions/IMI_TA/Low/TA-Slider_160-500_BACnet_MS-TP_Protocol_Implementation.pdf
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TA-Slider 160 / 500 / 750 / 1250 / 1600 BACnet MS/TP actuator and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the IMI Hydronic TA-Slider 160 / 500 / 750 / 1250 / 1600 BACnet MS/TP actuator
How many BACnet points does the IMI Hydronic TA-Slider 160 / 500 / 750 / 1250 / 1600 BACnet MS/TP actuator have?
This list has 90 BACnet objects: 13 analog inputs, 52 analog values, 5 binary inputs, 6 binary values, 12 multi-state inputs, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which IMI Hydronic TA-Slider 160 / 500 / 750 / 1250 / 1600 BACnet MS/TP actuator BACnet points are writable?
48 of the 90 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official IMI Hydronic TA-Slider 160 / 500 / 750 / 1250 / 1600 BACnet MS/TP actuator BACnet documentation?
The source is TA-Slider 750/1250/1600 BACnet MS/TP Protocol Implementation Conformance Statement - PICS, revision 11.2024, published free by IMI Hydronic at https://assets.imi-hydronic.com/Documents/Instructions/IMI_TA/Low/TA-Slider_750-1250-1600_BACnet_MS-TP_Protocol_Implementation.pdf.
What are the minimum BACnet points to integrate the IMI Hydronic TA-Slider 160 / 500 / 750 / 1250 / 1600 BACnet MS/TP actuator?
Start with AV 0 Control Setpoint (Relative setpoint, 0-100 %); AI 0 Actuator position Feedback (Actuator position, %); MI 0 Motor status (Motor status (7 = error)); AI 7 FlowFeedback SI (Interpolated flow, l/h (needs valve type)); BI 0 Override Status (Manual/electrical override active); AV 10 Errors code (Error code (0 = no error)).
How do I enable BMS control of the IMI Hydronic TA-Slider 160 / 500 / 750 / 1250 / 1600 BACnet MS/TP actuator?
The actuator follows AV 0 only when Signal Source (MSI 11) is BusCom; that is set with the HyTune app and TA-Dongle.
Does the IMI Hydronic TA-Slider 160 / 500 / 750 / 1250 / 1600 BACnet MS/TP actuator need a BACnet heartbeat or have a communication timeout?
AV 2 Cyclic control timeout (0-60 min, default 0 = off) raises a CyclicTime error if no control signal arrives within the time.
How do I check these points on the real TA-Slider 160 / 500 / 750 / 1250 / 1600 BACnet MS/TP actuator?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More IMI Hydronic BACnet points lists
Source: TA-Slider 750/1250/1600 BACnet MS/TP Protocol Implementation Conformance Statement - PICS · rev. 11.2024. Object names, instances and units are reproduced as published; descriptions are our own.