- KN2 / KN4 / rAy boilers - HeatNet BACnet Bridge
Commercial boiler controller · BACnet points list
Hydrotherm KN2 / KN4 / rAy boilers - HeatNet BACnet Bridge BACnet points list
Updated 4 November 2026
On Hydrotherm KN2, KN4 and rAy boilers the HeatNet control is linked to BACnet through a HeatNet bridge that translates its Modbus registers into a fixed object list. The BMS writes heat demand, the system setpoint (with a countdown failsafe timer), outdoor-reset settings, DHW setpoint and the clock. Read-only objects give plant temperatures, boilers on, modulation, raw spare inputs and per-boiler run time, cycles, temperatures, modulation and status flags for up to 16 boilers.
This page lists 75 BACnet objects for the Hydrotherm KN2 / KN4 / rAy boilers - HeatNet BACnet Bridge — 18 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Hydrotherm’s own free documentation, linked below.
- Manufacturer
- Hydrotherm
- Model
- KN2 / KN4 / rAy boilers - HeatNet BACnet Bridge
- Equipment
- Commercial boiler controller
- Equipment type
- Boilers & water heaters
- BACnet objects
- 75 (18 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Bridge configuration 2.40+ (2.50+ for some points); HeatNet firmware 2.70 / 3.48+ for some points
- Also known as
- KN2, KN-2, KN4, KN-4, rAy, HeatNet, HeatNet bridge, KNSLM, Mestek
- Source document
- KN2/KN4/rAy BACnet Bridge Objects · v2.50
Instance calculator. This list prints one unit; the other units follow a formula. HeatNet V3 boiler control (Hydrotherm KN, RBI) instance calculator →
Reference only, provided as-is: verify against Hydrotherm’s current documentation and the live device before use. Not official Hydrotherm information. Terms of use.
BMS integration notes: Hydrotherm KN2 / KN4 / rAy boilers - HeatNet BACnet Bridge
Connect the BMS to the master (boiler 1) HeatNet control. Write BV 1 HeatDemand to call for heat and AV 2 Setpoint for the system setpoint, and keep reloading AV 1 SetpointTimer so the plant does not fall back to its local setpoint. Read header/supply/return temperatures, boilers on, modulation and the per-boiler alarm and failed flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | HeatDemand | Heat demand from the BMS (1 = heat) | Write |
| AV 2 | Setpoint | System setpoint, 40-220 °F | Write |
| AV 1 | SetpointTimer | Failsafe countdown; reload before it reaches 0 | Write |
| AI 144 | OperatingSetpoint | Active setpoint in use | Read |
| AI 3 | HeaderTemp | Header / system temperature, °F | Read |
| AI 1 | BoilersOn | Number of boilers running | Read |
| AI 2 | Modulation | System target modulation, % | Read |
| BV 1005 | Boiler##_Running | Boiler 1 firing (add 32 per boiler number) | Read |
| BV 1002 | Boiler##_Alarm | Boiler 1 alarm (add 32 per boiler number) | Read |
| BV 1003 | Boiler##_Failed | Boiler 1 failed (add 32 per boiler number) | Read |
Enable & remote start
BV 1 HeatDemand puts the boiler (plant) into heating mode when set to 1; 0 removes the demand. The setpoint the BMS writes is AV 2 Setpoint.
Heartbeat & communication loss
AV 1 SetpointTimer (0-65535 s) is a BMS failsafe countdown. The BMS must reload it periodically; if it reaches zero the control assumes the BMS has stopped and reloads its own saved local setpoint. Writing any read/write variable reloads the timer to 60 s if it is below 60 (on control firmware below 2.70 only writing the setpoint does this).
Sensors & values from the BMS
AV 3-7 and BV 2 set up outdoor air reset; there is no writable outdoor temperature or flow value on this bridge.
Network setup
- The HeatNet bridge comes as a BACnet IP or a BACnet MS/TP version (an extra-cost option); it translates the HeatNet Modbus registers to these objects.
- BACnet IP bridge defaults, from Mestek's separate 'HeatNet Communication Protocols' v1.01 document (not the object list): IP 192.168.1.24, mask 255.255.255.0, BACnet MAC 11, BACnet node 11.
- BACnet MS/TP bridge defaults (same HeatNet Communication Protocols document): MAC 11, BACnet node 11, 38400 baud.
- To set the clock, write AV 8-14 (month, day, year, hour, minute, second, weekday) and then write 1 to BV 3 SetClock.
Watch out for
- If SetpointTimer runs out, the plant quietly returns to its local setpoint.
- Per-boiler objects are listed at the boiler 1 instance; offset them by boiler number using the formulas in the notes. Boiler 1 is the master or stand-alone boiler.
- Per-boiler modulation (AI 128-143) does not work in AA/High Fire, T1 or T2 modes.
- The bridge polls the HeatNet Modbus registers continuously; a few less important registers are not carried over to BACnet.
Hydrotherm KN2 / KN4 / rAy boilers - HeatNet BACnet Bridge BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 1 | SetpointTimer | BMS failsafe countdown; reload before it reaches zero; 0 – 65535 seconds | s | Write | |
| AVmin | 2 | Setpoint | System setpoint written by the BMS; 40 - 220 °F (4.5 – 104.4 °C) | °F | Write | |
| AV | 3 | OARSetpoint | Outdoor temperature at which the boiler shuts down; 40 – 100 °F (4.5 – 37.8 °C) | °F | Write | |
| AV | 4 | OARHighWaterTemp | Water setpoint at the high outdoor temperature; 60 – 190 °F (15.6 – 87.8 °C) | °F | Write | |
| AV | 5 | OARHighAirTemp | High outdoor air temperature reset point; 50 – 90 °F (10 – 32.2 °C) | °F | Write | |
| AV | 6 | OARLowWaterTemp | Header/supply setpoint at the low outdoor temperature; 70 – 220 °F (21.1 – 104.4 °C) | °F | Write | |
| AV | 7 | OARLowAirTemp | Low outdoor air temperature reset point; -35 – 40 °F (-37.2 – 4.4 °C) | °F | Write | |
| AV | 8 | SetMonth | Clock set value: month (0 = January); 0 (January) – 11 (December) | months | Write | |
| AV | 9 | SetDay | Clock set value: day; 1 – 31 | days | Write | |
| AV | 10 | SetYear | Clock set value: year (0-99); 0 – 99 | years | Write | |
| AV | 11 | SetHour | Clock set value: hour; 0 – 23 | h | Write | |
| AV | 12 | SetMinute | Clock set value: minute; 0 – 59 | min | Write | |
| AV | 13 | SetSecond | Clock set value: second; 0 – 59 | s | Write | |
| AV | 14 | SetWeekday | Clock set value: weekday; 1 (Monday) – 7 (Sunday) | Write | ||
| AV | 15 | DHWSetpoint | DHW setpoint; 40 – 200 °F (4.4 – 93.3 °C) | °F | Write | |
| BVmin | 1 | HeatDemand | BMS heat demand: 1 puts the boiler plant into heating | Write | 0=no heat demand, 1=heat demand | |
| BV | 2 | OAResetEnable | Enable outdoor air reset | Write | 0=disabled, 1=enabled | |
| BV | 3 | SetClock | Write 1 to load the Set... values into the clock | Write | 1=set the clock | |
| BV | 1000 | Boiler##_Disabled | Boiler is disabled | Read | 0=enabled, 1=disabled | |
| BV | 1001 | Boiler##_LocalOverride | Local Override (member boilers only) | Read | 0=no override, 1=override | |
| BVmin | 1002 | Boiler##_Alarm | Boiler Alarm | Read | 0=ok, 1=alarm | |
| BVmin | 1003 | Boiler##_Failed | Boiler Failed | Read | 0=ok, 1=failed | |
| BV | 1004 | Boiler##_MemberError | Member Alarm or Failed | Read | 0=ok, 1=error | |
| BVmin | 1005 | Boiler##_Running | Boiler is running/firing | Read | 0=off, 1=running (firing) | |
| BV | 1006 | Boiler##_PumpOn | Local pump is on/running | Read | 0=off, 1=on (running) | |
| BV | 1011 | Boiler##_Spare4Interlock | Spare 4 (application defined) Interlock | Read | 0=open, 1=closed | |
| BV | 1013 | Boiler##_FlowInterlock | Local Flow Interlock | Read | 0=open, 1=closed | |
| BV | 1015 | Boiler##_MainValve | Main Valve | Read | 0=closed, 1=open | |
| BV | 1017 | Boiler##_BlowerOn | Blower is on/running | Read | 0=off, 1=on (running) | |
| BV | 1018 | Boiler##_IgnitionAlarm | Ignition Circuit Alarm | Read | 0=ok, 1=alarm | |
| BV | 1020 | Boiler##_HighLimit | High Limit | Read | 0=ok, 1=tripped | |
| BV | 1023 | Boiler##_SoftwareOperator | Software Operator Tripped | Read | 0=not tripped, 1=tripped | |
| BV | 1024 | Boiler##_HeaderSensorNA | Header Sensor not available (detected) | Read | 0=detected, 1=not available | |
| BV | 1025 | Boiler##_SupplySensorNA | Supply/Outlet Sensor not available (detected) | Read | 0=detected, 1=not available | |
| BV | 1026 | Boiler##_ReturnSensorNA | Return/Inlet Sensor not available (detected) | Read | 0=detected, 1=not available | |
| BV | 1027 | Boiler##_OutsideSensorNA | Header Sensor not available (detected) | Read | 0=detected, 1=not available | |
| BV | 1029 | Boiler##_DamperProve1 | Combustion Air Damper Prove (J10B) | Read | 0=not proven, 1=proven | |
| BV | 1030 | Boiler##_Master | This is the Master Boiler | Read | 0=member, 1=master | |
| BV | 1031 | Boiler##_Detected | Boiler ## is detected (present) | Read | 0=not detected, 1=detected | |
| BV | 2000 | Boiler##_AAHighFire | AA/High Fire Input | Read | 0=open, 1=closed | |
| BV | 2001 | Boiler##_HeatDemand | Heat Demand (Local Override) Input | Read | 0=open, 1=closed | |
| BV | 2002 | Boiler##_4to20Remote | 4 to 20ma Remote Input | Read | 0=open, 1=closed | |
| BV | 3000 | Boiler##_DHWSensorEnabled | DHW Sensor has been enabled in the menus | Read | 0=disabled, 1=enabled | |
| BV | 3001 | Boiler##_DamperProve2 | Combustion Air Damper Prove | Read | 0=not proven, 1=proven | |
| BV | 3003 | Boiler##_BlowerFault | Blower fault | Read | 0=ok, 1=fault | |
| BV | 3004 | Boiler##_BlockedInlet | Blocked Inlet | Read | 0=blocked, 1=ok | |
| BV | 3005 | Boiler##_BlockedFlue | Blocked Flue | Read | 0=blocked, 1=ok | |
| BV | 3006 | Boiler##_DHWInput | DHW Input | Read | ||
| BV | 3007 | Boiler##_LowFireInput | Low Fire Input | Read | ||
| BV | 3008 | Boiler##_DHWFault | DHW Fault | Read | 0=ok, 1=fault | |
| BV | 3009 | Boiler##_DHWSensorNA | DHW Sensor is not available (detected) | Read | 0=detected, 1=not available | |
| BV | 3011 | Boiler##_OpLimitClamp | Boiler input is limited (clamped) due to high supply (outlet) temperature | Read | 0=not clamped, 1=clamped | |
| AImin | 1 | BoilersOn | Number of boilers running | Read | ||
| AImin | 2 | Modulation | System target modulation | % | Read | |
| AImin | 3 | HeaderTemp | Header / system temperature | °F | Read | |
| AI | 4 | SupplyTemp | Supply temperature | °F | Read | |
| AI | 5 | ReturnTemp | Return temperature | °F | Read | |
| AI | 6 | OutsideTemp | Outside air temperature | °F | Read | |
| AI | 7 | Spare1 | Raw A/D value of spare input 1 | Read | ||
| AI | 8 | Spare2 | Raw A/D value of spare input 2 | Read | ||
| AI | 9 | Month | Clock: month (0-11) | months | Read | |
| AI | 10 | Day | Clock: day | days | Read | |
| AI | 11 | Year | Clock: year (0-99) | years | Read | |
| AI | 12 | Hour | Clock: hour | h | Read | |
| AI | 13 | Minute | Clock: minute | min | Read | |
| AI | 14 | Second | Clock: second | s | Read | |
| AI | 15 | Weekday | Clock: weekday | Read | ||
| AI | 16 | DHWTemp | DHW temperature | °F | Read | |
| AI | 48 | Boiler01_Runtime | Boiler 1 run time on the current board (boiler n = 47 + n) | min | Read | |
| AI | 64 | Boiler01_Cycles | Boiler 1 cycle count (boiler n = 63 + n) | Read | ||
| AI | 80 | Boiler01_SupplyTemp | Boiler 1 supply (outlet) temperature (boiler n = 79 + n) | °F | Read | |
| AI | 96 | Boiler01_ReturnTemp | Boiler 1 return (inlet) temperature (boiler n = 95 + n) | °F | Read | |
| AI | 112 | Boiler01_DHWTemp | Boiler 1 DHW sensor temperature (boiler n = 111 + n) | °F | Read | |
| AI | 128 | Boiler01_Modulation | Boiler 1 modulation (boiler n = 127 + n) | % | Read | |
| AImin | 144 | OperatingSetpoint | Active setpoint in use (heating, DHW, reset or 4-20 mA) | °F | Read |
No points match these filters.
Object ID lookup: Hydrotherm KN2 / KN4 / rAy boilers point IDs by name
AV1SetpointTimerAV2SetpointAV3OARSetpointAV4OARHighWaterTempAV5OARHighAirTempAV6OARLowWaterTempAV7OARLowAirTempAV8SetMonthAV9SetDayAV10SetYearAV11SetHourAV12SetMinuteAV13SetSecondAV14SetWeekdayAV15DHWSetpointBV1HeatDemandBV2OAResetEnableBV3SetClockBV1000Boiler##_DisabledBV1001Boiler##_LocalOverrideBV1002Boiler##_AlarmBV1003Boiler##_FailedBV1004Boiler##_MemberErrorBV1005Boiler##_RunningBV1006Boiler##_PumpOnBV1011Boiler##_Spare4InterlockBV1013Boiler##_FlowInterlockBV1015Boiler##_MainValveBV1017Boiler##_BlowerOnBV1018Boiler##_IgnitionAlarmBV1020Boiler##_HighLimitBV1023Boiler##_SoftwareOperatorBV1024Boiler##_HeaderSensorNABV1025Boiler##_SupplySensorNABV1026Boiler##_ReturnSensorNABV1027Boiler##_OutsideSensorNABV1029Boiler##_DamperProve1BV1030Boiler##_MasterBV1031Boiler##_DetectedBV2000Boiler##_AAHighFireBV2001Boiler##_HeatDemandBV2002Boiler##_4to20RemoteBV3000Boiler##_DHWSensorEnabledBV3001Boiler##_DamperProve2BV3003Boiler##_BlowerFaultBV3004Boiler##_BlockedInletBV3005Boiler##_BlockedFlueBV3006Boiler##_DHWInputBV3007Boiler##_LowFireInputBV3008Boiler##_DHWFaultBV3009Boiler##_DHWSensorNABV3011Boiler##_OpLimitClampAI1BoilersOnAI2ModulationAI3HeaderTempAI4SupplyTempAI5ReturnTempAI6OutsideTempAI7Spare1AI8Spare2AI9MonthAI10DayAI11YearAI12HourAI13MinuteAI14SecondAI15WeekdayAI16DHWTempAI48Boiler01_RuntimeAI64Boiler01_CyclesAI80Boiler01_SupplyTempAI96Boiler01_ReturnTempAI112Boiler01_DHWTempAI128Boiler01_ModulationAI144OperatingSetpoint
Integration notes
- Per-boiler binary values are printed once as Boiler##_<name> with an instance formula and are listed here at the boiler 1 instance: 1000-series base + (n - 1) x 32, 2000/3000-series base + (n - 1) x 16. Boiler 1 is the master or stand-alone boiler; members are 2-16.
- Per-boiler analog inputs are printed as ranges and listed here for boiler 1 only: Runtime AI 48-63, Cycles AI 64-79, SupplyTemp AI 80-95, ReturnTemp AI 96-111, DHWTemp AI 112-127, Modulation AI 128-143 (boiler n = boiler 1 instance + n - 1).
- Bridge configuration 2.50+ is needed for AV 15 (with HeatNet firmware 2.70+) and for AI 112-144 and BV 3000-3011 (with HeatNet firmware 3.48+).
- This list has fewer per-boiler flags than the KNSX and KN HeatNet V3 lists (no LWCO, VFD, gas-prove or operator interlocks), and adds BV 3004-3008 (blocked inlet/flue, DHW input, low-fire input, DHW fault).
- The document describes Boiler##_OutsideSensorNA with the same text as HeaderSensorNA ('Header Sensor not available'); the name suggests the outside sensor.
- Weekday values here run 1 (Monday) to 7 (Sunday).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the KN2 / KN4 / rAy boilers - HeatNet BACnet Bridge and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Hydrotherm KN2 / KN4 / rAy boilers - HeatNet BACnet Bridge
How many BACnet points does the Hydrotherm KN2 / KN4 / rAy boilers - HeatNet BACnet Bridge have?
This list has 75 BACnet objects: 23 analog inputs, 15 analog values, 37 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Hydrotherm KN2 / KN4 / rAy boilers - HeatNet BACnet Bridge BACnet points are writable?
18 of the 75 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Hydrotherm KN2 / KN4 / rAy boilers - HeatNet BACnet Bridge BACnet documentation?
The source is KN2/KN4/rAy BACnet Bridge Objects (v2.50), published free by Hydrotherm at https://www.literature.mestek.com/dms/Hydrotherm%20Boilers/HeatNet/KNSLM%20BACnet%20Objects%20v2-50.pdf.
What are the minimum BACnet points to integrate the Hydrotherm KN2 / KN4 / rAy boilers - HeatNet BACnet Bridge?
Start with BV 1 HeatDemand (Heat demand from the BMS (1 = heat)); AV 2 Setpoint (System setpoint, 40-220 °F); AV 1 SetpointTimer (Failsafe countdown; reload before it reaches 0); AI 144 OperatingSetpoint (Active setpoint in use); AI 3 HeaderTemp (Header / system temperature, °F); AI 1 BoilersOn (Number of boilers running); AI 2 Modulation (System target modulation, %); BV 1005 Boiler##_Running (Boiler 1 firing (add 32 per boiler number)); BV 1002 Boiler##_Alarm (Boiler 1 alarm (add 32 per boiler number)); BV 1003 Boiler##_Failed (Boiler 1 failed (add 32 per boiler number)).
How do I enable BMS control of the Hydrotherm KN2 / KN4 / rAy boilers - HeatNet BACnet Bridge?
BV 1 HeatDemand puts the boiler (plant) into heating mode when set to 1; 0 removes the demand. The setpoint the BMS writes is AV 2 Setpoint.
Does the Hydrotherm KN2 / KN4 / rAy boilers - HeatNet BACnet Bridge need a BACnet heartbeat or have a communication timeout?
AV 1 SetpointTimer (0-65535 s) is a BMS failsafe countdown. The BMS must reload it periodically; if it reaches zero the control assumes the BMS has stopped and reloads its own saved local setpoint. Writing any read/write variable reloads the timer to 60 s if it is below 60 (on control firmware below 2.70 only writing the setpoint does this).
Can the BMS supply sensor values to the Hydrotherm KN2 / KN4 / rAy boilers - HeatNet BACnet Bridge?
AV 3-7 and BV 2 set up outdoor air reset; there is no writable outdoor temperature or flow value on this bridge.
How do I check these points on the real KN2 / KN4 / rAy boilers - HeatNet BACnet Bridge?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Hydrotherm BACnet points lists
- Commercial boiler controller
Hydrotherm KN / KN+ Series boilers with HeatNet V3 control
Hydrotherm (Mestek) KN and KN+ Series condensing boilers with a HeatNet V3 control board (firmware 4.20+), including HeatNet cascades of up to 16 boilers.
Also known as: HeatNet V3, HeatNet, KN Series, KN+, KN-Series, ATH, Mestek, KN BACnet Objects - Commercial boiler controller
Hydrotherm KN Series (KNSX) boilers - HeatNet BACnet Bridge
Hydrotherm (Mestek) KN Series boilers covered by the KNSX object list, with a HeatNet control and a HeatNet BACnet IP or BACnet MS/TP bridge.
Also known as: KNSX, KN Series, HeatNet, HeatNet bridge, Mestek
Source: KN2/KN4/rAy BACnet Bridge Objects · v2.50. Object names, instances and units are reproduced as published; descriptions are our own.