Walk-in cooler / freezer refrigeration controller · BACnet points list

Heatcraft intelliGen Integration Card (iIC) for the intelliGen Refrigeration Controller BACnet points list

Updated 12 November 2026

Short answer

The iIC is an add-on card for the intelliGen walk-in refrigeration controller that connects it to a BMS over RS-485 using BACnet MS/TP or Modbus RTU. System-wide (global) objects cover box temperature, operating mode, alarms, setpoints, defrost settings and schedules. Per-evaporator (local) objects come in blocks of 8, one per evaporator, for sensor values, EXV position, fan settings, alarms and refrigerant-detection (RDS) data.

This page lists 111 BACnet objects for the Heatcraft intelliGen Integration Card (iIC) for the intelliGen Refrigeration Controller — 71 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Heatcraft’s own free documentation, linked below.

Manufacturer
Heatcraft
Model
intelliGen Integration Card (iIC) for the intelliGen Refrigeration Controller
Equipment
Walk-in cooler / freezer refrigeration controller
Equipment type
Other equipment
BACnet objects
111 (71 writable)
Transport
BACnet MS/TP
Firmware
Standard BACnet objects need iRC firmware 01.03.xxxx or later
Also known as
intelliGen iIC, intelliGen Integration Card, iIC, intelliGen Refrigeration Controller, iRC, 25011901
Source document
intelliGen Integration Card (iIC) Installation & Operation Manual · Part No. 25011901 · rev. September 2026
Download CSV 111 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Heatcraft’s current documentation and the live device before use. Not official Heatcraft information. Terms of use.

BMS integration notes: Heatcraft intelliGen Integration Card (iIC) for the intelliGen Refrigeration Controller

Integration in brief

Select BACnet on the controller (Connectivity menu or the web page) with the external Modbus address set to 0, give the card an MS/TP address 1-127 and baud rate, then read box temperature, operating mode and alarms, and write the box setpoint if the BMS should own it.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 48Box Temperature SetpointBox temperature setpointWrite
AV 40Force DefrostWrite 1 to start a defrostWrite
AI 5Box temperatureBox temperatureRead
AI 4Operating modeOperating mode: off, cooling, defrost, drain...Read
AI 3System AlarmsSystem alarm bits, 0 = clearRead
AI 160Local AlarmsEvaporator 1 alarm bitsRead

Network setup

Watch out for

Heatcraft intelliGen Integration Card (iIC) for the intelliGen Refrigeration Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

111 of 111 shown
Type
Access
Show
Heatcraft intelliGen Integration Card (iIC) for the intelliGen Refrigeration Controller BACnet Points List
DescriptionStates
AI1DST OffsetDaylight saving offsetRead
AI2Number Of Unit RecordsNumber of evaporators in the systemRead
AImin3System AlarmsSystem alarm bits (AL01... see manual bit table)ReadBit-mapped, 0=Clear, 1=Set
AImin4Operating modeSystem operating modeReadOP_OFF-0, OP_COOLING-1, OP_PUMPDOWN-2, OP_DEFROST-3, OP_DRAIN-4, OP_DELAY-5, OP_BOXLOAD-6, OP_MANUAL_EXV-7 OP_REFREEZE-10, OP_SERVICE-11, OP_A2L_OVERRIDE-12
AImin5Box temperatureBox (room) temperature°FRead
AI6Date/Time TypeDate/time format codeRead
AI16Box Temperature Sensor CalibrationEvaporator 1; evaporators 1-8 = AI 16-23°FRead
AI24EV Suction Temperature Sensor CalibrationEvaporator 1; evaporators 1-8 = AI 24-31°FRead
AI32EV Suction Pressure Sensor CalibrationEvaporator 1; evaporators 1-8 = AI 32-39psigRead
AI40EV Auxiliary Temperature Sensor CalibrationEvaporator 1; evaporators 1-8 = AI 40-47°FRead
AI48EV Coil Temperature Sensor CalibrationEvaporator 1; evaporators 1-8 = AI 48-55°FRead
AI56EXV Step PositionEvaporator 1; evaporators 1-8 = AI 56-63Read
AI64Evap suction tempearatureEvaporator 1; evaporators 1-8 = AI 64-71°FRead
AI72SSTEvaporator 1; evaporators 1-8 = AI 72-79°FRead
AI80Evap Suction pressureEvaporator 1; evaporators 1-8 = AI 80-87psiaRead
AI88Evap superheatEvaporator 1; evaporators 1-8 = AI 88-95°FRead
AI96Primary Temperature Sensor ValueEvaporator 1; evaporators 1-8 = AI 96-103°FRead
AI104Auxiliary Temperature Sensor ValueEvaporator 1; evaporators 1-8 = AI 104-111°FRead
AI112Coil Temperature Sensor ValueEvaporator 1; evaporators 1-8 = AI 112-119°FRead
AI128Unit AddressEvaporator 1; evaporators 1-8 = AI 128-135Read
AI136Object Installed/EnableEvaporator 1; evaporators 1-8 = AI 136-143Read
AI144EV Length of Last DefrostEvaporator 1; evaporators 1-8 = AI 144-151Read
AI152EV RCB Control VoltageEvaporator 1; evaporators 1-8 = AI 152-159Read
AImin160Local AlarmsEvaporator 1; evaporators 1-8 = AI 160-167ReadBit-mapped, 0=Clear, 1=Set
CSV14RDS SW VersionEvaporator 1; evaporators 1-8 = CSV 14-21Read
AI168EXV TypeEvaporator 1; evaporators 1-8 = AI 168-175Read0 - Carel(0 to 255), 1 - Sporlan(0 to 2500) 2 - TXV 3 - EXV-CCMT 3L 5L 8L 4 - EXV-Emerson CV4-7 5 - EXV-CCMT 2 4 8 6 - EXV-CCMT 16 7 - EXV-CCMT 24 8 - EXV-CCMT 30 9 - EXV-CCMT 42
AI176RDS Mitigation Controller Communication StatusEvaporator 1; evaporators 1-8 = AI 176-183Read1 - Initializing, 2 - Active, 3 - Communication Failure
AI184RDS Mitigation Controller Sensor countEvaporator 1; evaporators 1-8 = AI 184-191Read
AI192RDS Mitigation Controller stateEvaporator 1; evaporators 1-8 = AI 192-199Read0 - Null, 1- Initializing, 2 - Monitoring, 3 - Mitigating, 4 - Servicing, 5 - Fault, 6 - User Test, 7 - Factory Reset
AI200RDS Sensor x statusBlock 200-223 (8 units x 3 sensors); first objectRead0 - Normal, 1 - Service, 2 - Fault, 3 - Mitigation
AI224RDS Sensor x %LFLBlock 224-247 (8 units x 3 sensors); first object%Read
AI248RDS Sensor x TemperatureBlock 248-271 (8 units x 3 sensors); first object°CRead
AI272RDS Sensor x Relative HumidityBlock 272-295 (8 units x 3 sensors); first object%Read
AI296RDS Sensor x Supported RefrigerantBlock 296-319 (8 units x 3 sensors); first objectReadBit-mapped, 0=Clear, 1=Set
AI320RDS Sensor x Mitigation ThresholdBlock 320-343 (8 units x 3 sensors); first object%Read
AI344RDS Model NumberEvaporator 1; evaporators 1-8 = AI 344-351Read
AI352A2L Unit alarmEvaporator 1; evaporators 1-8 = AI 352-359ReadBit-mapped, 0=Clear, 1=Set
AV1Defrost StyleWriteTIMED-0, SMART-1, DEMAND-2
AV2Box Temperature Differential°FWrite
AV3Product Load Mode Time DelayminWrite
AV4Product Load Mode TimerProduct load mode maximum timeminWrite
AV5Low Superheat Setpoint°FWrite
AV6Minimum RuntimeminWrite
AV7Minimum OfftimeminWrite
AV8Drain Down PeriodminWrite
AV9Number of DefrostsDefrosts per dayWrite
AV10Defrost 1 ScheduleminWrite
AV11Defrost 2 ScheduleminWrite
AV12Defrost 3 ScheduleminWrite
AV13Defrost 4 ScheduleminWrite
AV14Defrost 5 ScheduleminWrite
AV15Defrost 6 ScheduleminWrite
AV16Defrost 7 ScheduleminWrite
AV17Defrost 8 ScheduleminWrite
AV18Defrost 9 ScheduleminWrite
AV19Defrost 10 ScheduleminWrite
AV20Defrost 11 ScheduleminWrite
AV21Defrost 12 ScheduleminWrite
AV22Defrost Failsafe TimeminWrite
AV23Defrost End Setpoint°FWrite
AV24Refreeze Time SafetyminWrite
AV25Refreeze Suction Setpoint°FWrite
AV26Alarm High Box Temperature setpoint°FWrite
AV27Alarm Low Box Temperature setpoint°FWrite
AV28Alarm Delay TimeminWrite
AV29Alarm Door Open TimeminWrite
AV30CountryWrite0-USA, 1-CANADA
AV31Time ZoneWriteMST-0, NST-1, AST-2, EST-3, CST-4, MST-5, PST-6, AKST-7, HAST-8, SST-9, CHST-10, WAKT-11
AV32UTC OffsetWrite
AV33Follow DST (DayLight Savings)WriteProprietary: Yes, No Standard: 0 -No, 1 - Yes
AV34Defrost TypeWriteAIR -0, MTEL -1, LTEL - 2
AV35RefrigerantWriteR404A - 0, R507A - 1, R407A - 2, R407C - 3, R407F - 4, R22 - 5, R448A - 6, R449A - 7 R-744(CO2) - 8, R454A(A2L) - 9, R454C(A2L) - 10, R455A(A2L) - 11
AV36Temperature UnitsWriteFAHRENHEIT - 0, CELSIUS - 1
AV37Pressure UnitsWritePSIG – 0, KPA -1, BAR – 2
AV38Dual Coil TerminationWriteYes, No
AV3912/24 Hour ClockWrite0 -12H, 1 -24H
AVmin40Force DefrostWrite 1 to start a defrostWrite
AV41Primary EV AddressWrite
AV42BACnet Baud rateWrite0 - 9600, 2 - 38400
AV43Enter Service modeService mode on/offWrite0-Exit Service Mode 1-Enter Service Mode
AV44Light Bar EnableWriteProprietary: True - On, False - Off Standard: 0 - Off, 1 - On
AV45external MODbus addressRead
AV46externalBACnet addressWrite
AV47Condensing unit wiredWrite0 - NO , NON-ZERO - RCB address
AVmin48Box Temperature SetpointBox temperature setpoint°FWrite
AV49EXV Control Algorithm ResetWrite 1 to reset EXV controlWrite
AV50Digital Scroll Comp Support EnableWrite0 - Disable, 1 - Enable
AV51DSC Rolling Average PeriodsWrite
AV52DSC EXV Update RatesWrite
AV53CO2 System TypeWrite0 - Low Temp 1 - Medium Temp
AV54CO2 Max Operating PressureWrite
AV55Lead Lag Alarm Delay PeriodminWrite
AV56Lead Lag Slope Set Point°/minWrite
AV57Lead Lag Box Temp Set Point°FWrite
AV58Lead Lag Differential°FWrite
AV61EV Fan Control StyleEvaporator 1; evaporators 1-8 = AV 61-68Write0 - Standard, 1 - Two Speed, 2 - Variable, 3 - Off
AV69EV Fan Stir EnableEvaporator 1; evaporators 1-8 = AV 69-76Write0 - Off, 1 - On
AV77EV Fan Stir Cycle FrequencyEvaporator 1; evaporators 1-8 = AV 77-84minWrite
AV85EV Fan Stir Duty CycleEvaporator 1; evaporators 1-8 = AV 85-92%Write
AV93EV Fan Speed (Off Cycle)Evaporator 1; evaporators 1-8 = AV 93-100%Write
AV101Door Switch ConfigurationEvaporator 1; evaporators 1-8 = AV 101-108Write0 - None, 1 - Normally Closed, 2 - Normally Open
AV109Pressure Transducer TypeEvaporator 1; evaporators 1-8 = AV 109-116Write0 - 139.7 psia 1 - 300 psia 2 - 500 psia 3 - 650 psia (Emerson 800-2650) 4 - 0 to 652 psig (Sporlan 952579) 5 - 870.2 psia (Danfoss 060G6342) 6 - 1000 psia (Emerson 800-2710) 7 - 2000 psig (Sporlan 9520010)
AV117EV Superheat SetpointEvaporator 1; evaporators 1-8 = AV 117-124°FWrite
CSV2Lead Lag Group NameRead
CSV5Short Unit NameEvaporator 1; block printed as CSV 5-13Read
DTV1Date/TimeController date and timeWrite
AV59Enter Manual EXV ModeWrite0 - Exit Manual EXV Mode, 1 - Enter Manual EXV Mode
AV60RDS Mitigation Controller Early warning Threshold value (%LFL)%Write
AV125Adjust EXV Step PositionEvaporator 1; evaporators 1-8 = AV 125-132Write
AV133RDS Installed?Evaporator 1; evaporators 1-8 = AV 133-140Write0 - No, 1 - Yes
AV1001LanguageDisplay languageWrite1-English, 2-Spanish, 3-French
Object ID lookup: Heatcraft intelliGen Integration Card for the intelliGen Refrigeration Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the intelliGen Integration Card (iIC) for the intelliGen Refrigeration Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Heatcraft intelliGen Integration Card (iIC) for the intelliGen Refrigeration Controller

How many BACnet points does the Heatcraft intelliGen Integration Card (iIC) for the intelliGen Refrigeration Controller have?

This list has 111 BACnet objects: 36 analog inputs, 71 analog values, 3 characterstring values, 1 datetime value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Heatcraft intelliGen Integration Card (iIC) for the intelliGen Refrigeration Controller BACnet points are writable?

71 of the 111 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Heatcraft intelliGen Integration Card (iIC) for the intelliGen Refrigeration Controller BACnet documentation?

The source is intelliGen Integration Card (iIC) Installation & Operation Manual (Part No. 25011901), revision September 2026, published free by Heatcraft at https://www.heatcraftrpd.com/dA/0784ac1446/intelliGen%20iIC%20I&O%20Manual%202023.pdf.

What are the minimum BACnet points to integrate the Heatcraft intelliGen Integration Card (iIC) for the intelliGen Refrigeration Controller?

Start with AV 48 Box Temperature Setpoint (Box temperature setpoint); AV 40 Force Defrost (Write 1 to start a defrost); AI 5 Box temperature (Box temperature); AI 4 Operating mode (Operating mode: off, cooling, defrost, drain); AI 3 System Alarms (System alarm bits, 0 = clear); AI 160 Local Alarms (Evaporator 1 alarm bits).

How do I check these points on the real intelliGen Integration Card (iIC) for the intelliGen Refrigeration Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Heatcraft BACnet points lists

Source: intelliGen Integration Card (iIC) Installation & Operation Manual · Part No. 25011901 · rev. September 2026. Object names, instances and units are reproduced as published; descriptions are our own.