Boiler cascade controller via ProtoNode gateway · BACnet points list

Hamilton Engineering BDB-CDB (ProtoNode FPC-N54) BACnet points list

Updated 28 October 2026

Short answer

Hamilton Engineering's BDB-CDB control is read over Modbus RTU by a ProtoNode FPC-N54 and served on BACnet IP or BACnet MS/TP. The 99-object profile has writable central heating, DHW, indirect DHW, pool and spa setpoints, cascade sensor readings and an anomaly code, then a 9-object block for each of BCB1 to BCB8. This file lists the cascade objects and the BCB1 block.

This page lists 36 BACnet objects for the Hamilton Engineering BDB-CDB (ProtoNode FPC-N54) — 18 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Hamilton Engineering’s own free documentation, linked below.

Manufacturer
Hamilton Engineering
Model
BDB-CDB (ProtoNode FPC-N54)
Equipment
Boiler cascade controller via ProtoNode gateway
Equipment type
Boilers & water heaters
BACnet objects
36 (18 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
50032 (Node_Offset default 50,000 + the BDB-CDB Node-ID 32)
Also known as
BDB-CDB, BDB, CDB, ProtoNode FPC-N54, FPC-N54-1776, Hamilton ProtoNode
Source document
ProtoNode FPC-N54 Start-up Guide for Interfacing Hamilton Engineering Products: BDB-CDB · Document Revision 2.A (Web Configurator Template Revision 3) · rev. 2019-06
Download CSV 36 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Hamilton Engineering BDB-CDB (ProtoNode FPC-N54)

Integration in brief

Wire the BDB-CDB Modbus port (9600, 8N1) to the ProtoNode R1 port, pick BACnet IP or BACnet MS/TP in the Web Configurator, add the BDB-CDB profile with Node-ID 32, and discover the device at 50032. Setpoints are the writable analog values; status and fault information comes from the cascade anomaly and the per-board working status and anomaly codes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 2CH RequestsCentral heating request; values not defined in the guideWrite
AV 11Boiler For Heating SetpointBoiler setpoint for the heating loadWrite
AV 12Dhw SP TempDomestic hot water setpointWrite
AI 31BCB1 Working StatusBCB1 working statusRead
AI 21Cascade S1 Temp Sensor ValueCascade sensor S1 temperatureRead
AI 27Cascade AnomalyCascade-level anomaly (fault) codeRead
AI 32BCB1 Anom Code 1BCB1 anomaly codeRead

Network setup

Watch out for

Hamilton Engineering BDB-CDB (ProtoNode FPC-N54) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

36 of 36 shown
Type
Multi-state
Access
Show
Hamilton Engineering BDB-CDB (ProtoNode FPC-N54) BACnet Points List
DescriptionStates
AI1System ConfigurationSystem configuration valueRead
AVmin2CH RequestsCentral heating requestsWrite
AV3CH SP / CH Offset 1CH setpoint or CH offset 1Write
AV4CH SP / CH Offset 2CH setpoint or CH offset 2Write
AV5CH SP / CH Offset 3CH setpoint or CH offset 3Write
AV6CH SP / CH Offset 4CH setpoint or CH offset 4Write
AV7CH SP / CH Offset 5CH setpoint or CH offset 5Write
AV8CH SP / CH Offset 6CH setpoint or CH offset 6Write
AV9CH SP / CH Offset 7CH setpoint or CH offset 7Write
AV10CH SP / CH Offset 8CH setpoint or CH offset 8Write
AVmin11Boiler For Heating SetpointBoiler setpoint for heatingWrite
AVmin12Dhw SP TempDomestic hot water setpointWrite
AV13Recirculation SP For Cascade RegRecirculation setpoint for cascade regulationWrite
AV14Idhw SP TempIndirect DHW setpointWrite
AV15Boiler For Idhw Load SetpointBoiler setpoint for indirect DHW loadWrite
AV16Ispa SP TempSpa setpointWrite
AV17Boiler For Pool Load SetpointBoiler setpoint for pool loadWrite
AV18Ipool SP TempPool setpointWrite
AV19Boiler For Spa Load SetpointBoiler setpoint for spa loadWrite
AI20Cascade Temp Sensors StateCascade sensor statusRead
AImin21Cascade S1 Temp Sensor ValueCascade sensor S1 temperatureRead
AI22Cascade S2 Temp Sensor ValueCascade sensor S2 temperatureRead
AI23Cascade S3 Temp Sensor ValueCascade sensor S3 temperatureRead
AI24Cascade S4 Temp Sensor ValueCascade sensor S4 temperatureRead
AI25Cascade S5 Temp Sensor ValueCascade sensor S5 temperatureRead
AI26Cascade S6 Temp Sensor ValueCascade sensor S6 temperatureRead
AImin27Cascade AnomalyCascade anomaly (fault) codeRead
AI28BCB1 Temp Sensors StateBCB1 sensor statusRead
AI29BCB1 T1 Temp Sensor ValueBCB1 sensor T1 temperatureRead
AI30BCB1 T2 Temp Sensor ValueBCB1 sensor T2 temperatureRead
AImin31BCB1 Working StatusBCB1 working statusRead
AImin32BCB1 Anom Code 1BCB1 anomaly code 1Read
MI33BCB1 Anom Code 2 PrefixBCB1 anomaly code 2, prefixRead
MI34BCB1 Anom Code 2 SuffixBCB1 anomaly code 2, suffixRead
AI35BCB1 Fan Modulation Relative PerBCB1 fan modulation, relative%Read
AI36BCB1 Fan Modulation Absolute PerBCB1 fan modulation, absolute%Read

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BDB-CDB (ProtoNode FPC-N54) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Hamilton Engineering BDB-CDB (ProtoNode FPC-N54)

How many BACnet points does the Hamilton Engineering BDB-CDB (ProtoNode FPC-N54) have?

This list has 36 BACnet objects: 16 analog inputs, 18 analog values, 2 multi-state inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Hamilton Engineering BDB-CDB (ProtoNode FPC-N54) BACnet points are writable?

18 of the 36 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Hamilton Engineering BDB-CDB (ProtoNode FPC-N54) BACnet documentation?

The source is ProtoNode FPC-N54 Start-up Guide for Interfacing Hamilton Engineering Products: BDB-CDB (Document Revision 2.A (Web Configurator Template Revision 3)), revision 2019-06, published free by Hamilton Engineering at https://hamiltonengineering.com/wp-content/uploads/ProtoNode-FPC-N54-Start-up-Guide-06.19.pdf.

What are the minimum BACnet points to integrate the Hamilton Engineering BDB-CDB (ProtoNode FPC-N54)?

Start with AV 2 CH Requests (Central heating request; values not defined in the guide); AV 11 Boiler For Heating Setpoint (Boiler setpoint for the heating load); AV 12 Dhw SP Temp (Domestic hot water setpoint); AI 31 BCB1 Working Status (BCB1 working status); AI 21 Cascade S1 Temp Sensor Value (Cascade sensor S1 temperature); AI 27 Cascade Anomaly (Cascade-level anomaly (fault) code); AI 32 BCB1 Anom Code 1 (BCB1 anomaly code).

How do I check these points on the real BDB-CDB (ProtoNode FPC-N54)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: ProtoNode FPC-N54 Start-up Guide for Interfacing Hamilton Engineering Products: BDB-CDB · Document Revision 2.A (Web Configurator Template Revision 3) · rev. 2019-06. Object names, instances and units are reproduced as published; descriptions are our own.