Other equipment (sanitary flush control gateway) · BACnet points list

Geberit Connect (Geberit Gateway + GEBUS end devices) BACnet points list

Updated 12 November 2026

Short answer

The Geberit Gateway publishes every connected end device as its own set of BACnet IP objects, plus collective groups per zone and device type. Each object has a fixed object number (000-399); the real instance adds the device position, device type and zone. Status objects give connectivity, warnings, errors and usage; counters give flushes and water use; control objects start flushes, set flush volumes and cleaning mode.

This page lists 36 BACnet objects for the Geberit Connect (Geberit Gateway + GEBUS end devices) — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Geberit’s own free documentation, linked below.

Manufacturer
Geberit
Model
Geberit Connect (Geberit Gateway + GEBUS end devices)
Equipment
Other equipment (sanitary flush control gateway)
Equipment type
Other equipment
BACnet objects
36 (8 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
Geberit Connect, Geberit Gateway, GEBUS, Geberit Hygiene System, GHS, 971.816.00.0
Source document
Geberit Connect System Manual · 971.816.00.0(02) · rev. 04-2024
Download CSV 36 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Geberit’s current documentation and the live device before use. Not official Geberit information. Terms of use.

BMS integration notes: Geberit Connect (Geberit Gateway + GEBUS end devices)

Integration in brief

Map ConnectionStatus, GenericWarning and GenericError for each device or collective group and alarm on them; trend WaterUsage and FlushCount. The BMS can start flushes and switch cleaning mode.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 205FlushStart a flush (WC / urinal)Write
MV 207CleaningCleaning mode on/offWrite
PIV 170WaterUsageWater use, lRead
PIV 141FlushCountFlush countRead
BV 107UsageActiveDevice in useRead
MV 101ConnectionStatusNormal / UnreachableRead
BV 103GenericWarningDevice warningRead
BV 104GenericErrorDevice faultRead

Network setup

Watch out for

Geberit Connect (Geberit Gateway + GEBUS end devices) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

36 of 36 shown
Type
BinaryMulti-state
Access
Show
Geberit Connect (Geberit Gateway + GEBUS end devices) BACnet Points List
DescriptionStates
CSV1DeviceSerialSerial number (all)Read
CSV2ZoneNameZone the device is assigned to (all)Read
MVmin101ConnectionStatusConnectivity to the end device (WT/WC/UR/SE/HS)ReadNormal, Unreachable
BV102GenericInfoGateway shows an information message (GW)Read
BVmin103GenericWarningDevice or gateway shows a warning (all)Read
BVmin104GenericErrorDevice or gateway shows a fault (all)Read
BV105GenericFatalErrorFatal fault (HS)Read
BV106LowBatteryEnd device battery almost empty (WT/WC/UR)Read
BVmin107UsageActiveDevice in use (all)Read
BV108ValveOpenSolenoid valve (V1) open (WT/WC/UR/HS)Read
BV109Valve2OpenSolenoid valve V2 open (HS)Read
BV110LevelSensorBackpressure sensor reports backpressure (HS)Read
MV111GHSStatusGeberit Hygiene System status over all flush programmes (GW)ReadOff, Active, Blocked, Delayed, Draining, Error
PIV140UsageCountNumber of uses since install/reset (WT/WC/UR)Read
PIVmin141FlushCountNumber of flushes since install/reset (WT/WC/UR/HS)Read
PIV142Flush2CountFlushes with valve V2 (HS)Read
PIV143AutomaticFlushCountAutomatic WC flushes (WC)Read
PIV144ManualFlushCountManual WC flushes (WC)Read
PIV145FullFlushCountFull WC flushes (WC)Read
PIV146PartialFlushCountPartial WC flushes (WC)Read
PIV147HygieneFlushCountFlushes from internal hygiene programmes (WT/WC/UR/HS)Read
PIV148HygieneFlushCount2Hygiene programme flushes with valve V2 (HS)Read
PIVmin170WaterUsageWater use since install/reset (WT/WC/UR/HS)lRead
PIV171WaterUsage2Water use of stack V2 (HS)lRead
PIV172WaterTemperatureWater temperature (SE/HS)°CRead
PIV173WaterTemperature2Water temperature, stack V2 (HS)°CRead
PIV174WaterFlowFlow rate (SE/HS)ml/sRead
PIV175WaterFlow2Flow rate, stack V2 (HS)ml/sRead
MV201LocateOn = device LED flashes (gateway: Bluetooth LED) (all)WriteUnknown, On, Off
MV202DisableRadioTurns off the Bluetooth interface (GW/WT/WC/UR/HS)WriteFalse, True, Indeterminate (groups only)
PIV203DrainVolumeDrain (flush) volume, V1 (WT/WC/UR/HS)lWrite
PIV204DrainVolume2Drain (flush) volume, V2 (HS)lWrite
BVmin205FlushStarts a flush (WC full flush, urinal for FlushTime) (WC/UR)Write
PIV206FlushTimeUrinal flush time (UR)sWrite
MVmin207CleaningCleaning mode on/off; ends automatically (WT/WC/UR)WriteInactive, Active, Indeterminate (groups only)
MV208GHSOperatingModeActive Geberit Hygiene System mode (GW)WriteOff, Mode 1, Mode 2
Object ID lookup: Geberit Connect point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Geberit Connect (Geberit Gateway + GEBUS end devices) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Geberit Connect (Geberit Gateway + GEBUS end devices)

How many BACnet points does the Geberit Connect (Geberit Gateway + GEBUS end devices) have?

This list has 36 BACnet objects: 10 binary values, 6 multi-state values, 2 characterstring values, 18 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Geberit Connect (Geberit Gateway + GEBUS end devices) BACnet points are writable?

8 of the 36 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Geberit Connect (Geberit Gateway + GEBUS end devices) BACnet documentation?

The source is Geberit Connect System Manual (971.816.00.0(02)), revision 04-2024, published free by Geberit at https://cdn.data.geberit.com/documents/971.816.00.0_02.pdf.

What are the minimum BACnet points to integrate the Geberit Connect (Geberit Gateway + GEBUS end devices)?

Start with BV 205 Flush (Start a flush (WC / urinal)); MV 207 Cleaning (Cleaning mode on/off); PIV 170 WaterUsage (Water use, l); PIV 141 FlushCount (Flush count); BV 107 UsageActive (Device in use); MV 101 ConnectionStatus (Normal / Unreachable); BV 103 GenericWarning (Device warning); BV 104 GenericError (Device fault).

How do I check these points on the real Geberit Connect (Geberit Gateway + GEBUS end devices)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Geberit Connect System Manual · 971.816.00.0(02) · rev. 04-2024. Object names, instances and units are reproduced as published; descriptions are our own.