Damper actuator · BACnet points list

Frakta DM.1.1-MB modulating damper actuators (BACnet MS/TP / Modbus RTU) BACnet points list

Updated 12 November 2026

Short answer

The DM.1.1-MB actuators are 24 V modulating air damper actuators from 8 to 32 Nm. A DIP switch selects BACnet MS/TP or Modbus RTU. Over BACnet the BMS overrides the analog control input (AI 0) to position the damper and reads position, run, blocked and dew point states; a watchdog decides what happens if the BMS stops writing.

This page lists 14 BACnet objects for the Frakta DM.1.1-MB modulating damper actuators (BACnet MS/TP / Modbus RTU) — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Frakta’s own free documentation, linked below.

Manufacturer
Frakta
Model
DM.1.1-MB modulating damper actuators (BACnet MS/TP / Modbus RTU)
Equipment
Damper actuator
Equipment type
Valves & actuators
BACnet objects
14 (7 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
DM.1.1-MB, DMS1.1-MB, DM1.1-MB, DML1.1-MB, DMG1.1-MB, Frakta DM1 MB, Frakta damper actuator BACnet
Source document
Modulating control actuators DM.1.1-MB Modbus / BACnet series · rev. Juli 2022
Download CSV 14 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Frakta’s current documentation and the live device before use. Not official Frakta information. Terms of use.

BMS integration notes: Frakta DM.1.1-MB modulating damper actuators (BACnet MS/TP / Modbus RTU)

Integration in brief

Switch DIP 4 to BACnet MS/TP, set the address on the address switches, then write the position command to AI 0 (0-10) at least every 60 s. Read AV 0 position and BV 3 for a blocked actuator. Set MV 1 and MV 2 to decide how the watchdog behaves.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 0Analog_InputPosition command, 0-10 (rewrite within 60 s)Write
AV 0PositisonDamper position, 0-100 %Read
BV 0RunMotor runningRead
BV 3BlockedActuator blockedRead

Enable & remote start

Mode switch position 4 selects BACnet MS/TP (the other setting is Modbus RTU).

Heartbeat & communication loss

AI 0 falls back to the physical analog input if not rewritten within 60 s. The watchdog (AV 1 WD_timeout, MV 1 WD_mode, MV 2 WD_action) can close, open, follow the analog input or do nothing when it trips; the manual also states the actuator closes if the control value doesn't change within 60 s.

Network setup

Watch out for

Frakta DM.1.1-MB modulating damper actuators (BACnet MS/TP / Modbus RTU) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

14 of 14 shown
Type
BinaryMulti-state
Access
Show
Frakta DM.1.1-MB modulating damper actuators (BACnet MS/TP / Modbus RTU) BACnet Points List
DescriptionStates
AImin0Analog_InputControl input 0-10; writable override, reverts after 60 s without a writeVWrite
AO0Analog_OutputPosition feedback outputVRead
AVmin0PositisonActual position from the potentiometer, 0-100%Read
AV1WD_timeoutWatchdog timeoutWrite
BVmin0RunMotor runningRead
BV1Ain_RangeControl range from jumpers (0-10 V or 2-10 V)Read
BV2ReverseDirection of rotation from jumpersRead
BVmin3BlockedActuator blocked; retries after 60 s or on reverse commandRead
BV4Dew_pointDew point sensor stateRead
MV0Bus speedBus speedWrite2.4 kbit, 4.8 kbit, 9.6 kbit (default), 14.4 kbit, 19.2 kbit, 28.8 kbit, 38.4 kbit, 57.6 kbit, 76.8 kbit, 115.2 kbit, 230.4 kbit, 250 kbit, 500 kbit
MV1WD_modeWhat resets the watchdogWriteSet command, Com online
MV2WD_actionAction when the watchdog tripsWriteClose, Open, Analog in, Nothing
MV3DP_configUse the analog input as a dew point sensorWriteInactive, Active Close, Active Open
MV4DP_polarityDew point signal polarityWriteNormal 0, Normal 1
Object ID lookup: Frakta DM.1.1-MB modulating damper actuators point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the DM.1.1-MB modulating damper actuators (BACnet MS/TP / Modbus RTU) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Frakta DM.1.1-MB modulating damper actuators (BACnet MS/TP / Modbus RTU)

How many BACnet points does the Frakta DM.1.1-MB modulating damper actuators (BACnet MS/TP / Modbus RTU) have?

This list has 14 BACnet objects: 1 analog input, 1 analog output, 2 analog values, 5 binary values, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Frakta DM.1.1-MB modulating damper actuators (BACnet MS/TP / Modbus RTU) BACnet points are writable?

7 of the 14 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Frakta DM.1.1-MB modulating damper actuators (BACnet MS/TP / Modbus RTU) BACnet documentation?

The source is Modulating control actuators DM.1.1-MB Modbus / BACnet series, revision Juli 2022, published free by Frakta at https://www.frakta.de/wp-content/uploads/2022/07/DM1_MB_englisch_new_190722.pdf.

What are the minimum BACnet points to integrate the Frakta DM.1.1-MB modulating damper actuators (BACnet MS/TP / Modbus RTU)?

Start with AI 0 Analog_Input (Position command, 0-10 (rewrite within 60 s)); AV 0 Positison (Damper position, 0-100 %); BV 0 Run (Motor running); BV 3 Blocked (Actuator blocked).

How do I enable BMS control of the Frakta DM.1.1-MB modulating damper actuators (BACnet MS/TP / Modbus RTU)?

Mode switch position 4 selects BACnet MS/TP (the other setting is Modbus RTU).

Does the Frakta DM.1.1-MB modulating damper actuators (BACnet MS/TP / Modbus RTU) need a BACnet heartbeat or have a communication timeout?

AI 0 falls back to the physical analog input if not rewritten within 60 s. The watchdog (AV 1 WD_timeout, MV 1 WD_mode, MV 2 WD_action) can close, open, follow the analog input or do nothing when it trips; the manual also states the actuator closes if the control value doesn't change within 60 s.

How do I check these points on the real DM.1.1-MB modulating damper actuators (BACnet MS/TP / Modbus RTU)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.