Easy BACnet
  1. Home
  2. BACnet points lists
  3. Fireye
  4. Nexus NX6100 / PPC6000 burner control (NXTSD104 / NX6330 touchscreen, BACnet IP)

Burner management / boiler control · BACnet points list

Fireye Nexus NX6100 / PPC6000 burner control (NXTSD104 / NX6330 touchscreen, BACnet IP) BACnet points list

Updated 12 November 2026

Short answer

The NXTSD104/NX6330 touchscreen acts as a BACnet IP router for the Fireye 6000-series burner control. A Who-Is finds three devices: the router device (the main or left-hand burner control) and devices +1 (right-hand burner on twin-fired boilers) and +2 (62xx water-level expansion unit) on virtual network 2709. Each device has the same object set: 60 read-only AVs of main values, 16 selectable AIs, override AOs and BOs.

This page lists 57 BACnet objects for the Fireye Nexus NX6100 / PPC6000 burner control (NXTSD104 / NX6330 touchscreen, BACnet IP) — 20 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Fireye’s own free documentation, linked below.

Manufacturer
Fireye
Model
Nexus NX6100 / PPC6000 burner control (NXTSD104 / NX6330 touchscreen, BACnet IP)
Equipment
Burner management / boiler control
Equipment type
Boilers & water heaters
BACnet objects
57 (20 writable)
Transport
BACnet IP
Firmware
Touchscreen 2.200 or later
Also known as
NX6100, PPC6000, Nexus NX6100, Fireye Nexus, NXTSD104, NX6330, MOD-6001, Fireye PPC6000, Fireye 6000 series
Source document
MOD-6001 Nexus NX6100 / PPC6000 Modbus and BACnet Communications (chapter 6 BACNET/IP interface) · MOD-6001 · rev. 2018-09-24
Download CSV 57 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Fireye’s current documentation and the live device before use. Not official Fireye information. Terms of use.

BMS integration notes: Fireye Nexus NX6100 / PPC6000 burner control (NXTSD104 / NX6330 touchscreen, BACnet IP)

Integration in brief

Enable BACnet and set the device instance on the touchscreen, discover the router device, then read the AVs (status, setpoint, measured value, fault number, flame signal). To control, clear Out_Of_Service on the AO/BO you need and write it; Burner ON/OFF (BO 7) and Setpoint 1 Control Value (AO 0) are the usual commands.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 7Burner ON/OFFWrite 0 to hold the burner offCommand
BO 1Release to IgniteMust be 1 to allow ignition (if used)Command
AO 0Setpoint 1 Control ValueSetpoint 1 overrideCommand
BO 4Mute / ResetFault reset: 1 for ~5 s, then 0Command
AV 19Burner StatusBurner statusRead
AV 12Measured ValueMeasured pressure/temperatureRead
AV 21SetpointSetpoint in useRead
AV 30Modulation RateFiring rateRead
AV 37Flame SignalFlame signalRead
AV 23Fault NumberActive fault numberRead

Enable & remote start

AOs and BOs are Out_Of_Service by default; clear the flag, then writes override the control as long as it is in AUTO and REMOTE. BO 1 Release to Ignite, if used, must be 1 for the burner to light.

Network setup

Watch out for

Fireye Nexus NX6100 / PPC6000 burner control (NXTSD104 / NX6330 touchscreen, BACnet IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

57 of 57 shown
Type
Binary
Access
Show
Fireye Nexus NX6100 / PPC6000 burner control (NXTSD104 / NX6330 touchscreen, BACnet IP) BACnet Points List
DescriptionStates
AV0Drive 0 PositionRead
AV1Drive 1 PositionRead
AV2Drive 2 PositionRead
AV3Drive 3 PositionRead
AV4Drive 4 PositionRead
AV5Drive 5 PositionRead
AV6Drive 6 PositionRead
AV7Drive 7 PositionRead
AV8Drive 8 PositionRead
AV9Drive 9 PositionRead
AVmin12Measured ValueRead
AV13EfficiencyRead
AV14Inlet TempRead
AV15O2 LevelRead
AV16CO2 LevelRead
AV17Spare / CO levelRead
AV18Hours RunRead
AVmin19Burner StatusRead
AV20Oxygen TrimRead
AVmin21SetpointRead
AV22Flue TempRead
AVmin23Fault NumberRead
AV27Profile NumberRead
AVmin30Modulation RateRead
AV31Analog Input 1Read
AV32Analog Input 2Read
AV35Gas PressureRead
AV36Valve Prove StatusRead
AVmin37Flame SignalRead
AV382nd Flame SignalRead
AV39Combustion air pressureRead
AV40Second Gas pressureRead
AV50Water-level (from waterlevel expansion unit)Read
AV51TDS (total dissolved solids – from waterlevel expansion unit)Read
AV52Feed-water flow (from waterlevel expansion unit)Read
AV53Feed-water temperature (from waterlevel expansion unit)Read
AV54Steam flow (from waterlevel expansion unit)Read
AOmin0Setpoint 1 Control ValueOverride value (clear Out_Of_Service first)Command
AO1Setpoint 2 Control ValueOverride value (clear Out_Of_Service first)Command
AO2Setpoint 1 Low Control LimitOverride value (clear Out_Of_Service first)Command
AO3Setpoint 2 Low Control LimitOverride value (clear Out_Of_Service first)Command
AO4Setpoint 1 High Control LimitOverride value (clear Out_Of_Service first)Command
AO5Setpoint 2 High Control LimitOverride value (clear Out_Of_Service first)Command
AO6Modulation RateOverride value (clear Out_Of_Service first)Command
BO0Setpoint Select0 = setpoint 1, 1 = setpoint 2 (e.g. night setback)Command
BOmin1Release to IgniteMust be 1 to let the burner ignite (if used)Command
BO2Low Fire Hold1 = hold low fireCommand
BO3Lead boiler SelectMake this the lead boiler when sequencingCommand
BOmin4Mute / ResetMute alarms and reset fault: 1 for about 5 s, then 0Command
BO5Oxygen Trim Enable1 = allow oxygen trimCommand
BO6Boiler Sequencing Enable1 = enable lead-lag sequencingCommand
BOmin7Burner ON/OFFWrite 0 to hold the burner offCommand
BO8Fault Mute Only1 = mute fault alarms onlyCommand
BO11Select Profile 11 = force profile 1Command
BO12Select Profile 21 = force profile 2Command
BO13Select Profile 31 = force profile 3Command
BO14Select Profile 41 = force profile 4Command
Object ID lookup: Fireye Nexus NX6100 / PPC6000 burner control point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Nexus NX6100 / PPC6000 burner control (NXTSD104 / NX6330 touchscreen, BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Fireye Nexus NX6100 / PPC6000 burner control (NXTSD104 / NX6330 touchscreen, BACnet IP)

How many BACnet points does the Fireye Nexus NX6100 / PPC6000 burner control (NXTSD104 / NX6330 touchscreen, BACnet IP) have?

This list has 57 BACnet objects: 7 analog outputs, 37 analog values, 13 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Fireye Nexus NX6100 / PPC6000 burner control (NXTSD104 / NX6330 touchscreen, BACnet IP) BACnet points are writable?

20 of the 57 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Fireye Nexus NX6100 / PPC6000 burner control (NXTSD104 / NX6330 touchscreen, BACnet IP) BACnet documentation?

The source is MOD-6001 Nexus NX6100 / PPC6000 Modbus and BACnet Communications (chapter 6 BACNET/IP interface) (MOD-6001), revision 2018-09-24, published free by Fireye at https://www.fireye.com/wp-content/uploads/sites/10/2025/04/MOD-6001-Nexus_NX6100_PPC6000_Modbus_BACnet_Communications_English_2018-09-24.pdf.

What are the minimum BACnet points to integrate the Fireye Nexus NX6100 / PPC6000 burner control (NXTSD104 / NX6330 touchscreen, BACnet IP)?

Start with BO 7 Burner ON/OFF (Write 0 to hold the burner off); BO 1 Release to Ignite (Must be 1 to allow ignition (if used)); AO 0 Setpoint 1 Control Value (Setpoint 1 override); BO 4 Mute / Reset (Fault reset: 1 for ~5 s, then 0); AV 19 Burner Status (Burner status); AV 12 Measured Value (Measured pressure/temperature); AV 21 Setpoint (Setpoint in use); AV 30 Modulation Rate (Firing rate); AV 37 Flame Signal (Flame signal); AV 23 Fault Number (Active fault number).

How do I enable BMS control of the Fireye Nexus NX6100 / PPC6000 burner control (NXTSD104 / NX6330 touchscreen, BACnet IP)?

AOs and BOs are Out_Of_Service by default; clear the flag, then writes override the control as long as it is in AUTO and REMOTE. BO 1 Release to Ignite, if used, must be 1 for the burner to light.

How do I check these points on the real Nexus NX6100 / PPC6000 burner control (NXTSD104 / NX6330 touchscreen, BACnet IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: MOD-6001 Nexus NX6100 / PPC6000 Modbus and BACnet Communications (chapter 6 BACNET/IP interface) · MOD-6001 · rev. 2018-09-24. Object names, instances and units are reproduced as published; descriptions are our own.