The nanodac is a compact paperless recorder with up to two PID loops, steam calculations and 30 virtual channels. Its BACnet object list is fixed: measured channels, loop setpoints and outputs, steam values and virtual channels as analog inputs; alarm thresholds, loop PV, setpoint, auto/manual, manual output and PID terms as writable analog values; alarm states as multistate inputs; and 30 user parameter address/value pairs that give indirect access to any other numeric parameter.
This page lists 210 BACnet objects for the Eurotherm (Schneider Electric) nanodac recorder / controller — 112 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Eurotherm (Schneider Electric)’s documentation hosted by BACnet International product catalog, not by Eurotherm (Schneider Electric) itself, so treat it as unofficial.
- Manufacturer
- Eurotherm (Schneider Electric)
- Model
- nanodac recorder / controller
- Equipment
- Other equipment (process recorder / PID controller)
- Equipment type
- Other equipment
- BACnet objects
- 210 (112 writable)
- Transport
- —
- Firmware
- V8.09
- Also known as
- nanodac, Eurotherm nanodac, nanodac recorder, HA033110
- Source document
- nanodac Recorder / Controller Protocol Implementation Conformance Statement · HA033110 Issue 1 · rev. 2017-09-12 (unofficial copy, hosted by BACnet International product catalog)
Reference only, provided as-is: verify against Eurotherm (Schneider Electric)’s current documentation and the live device before use. Not official Eurotherm (Schneider Electric) information. Terms of use.
BMS integration notes: Eurotherm (Schneider Electric) nanodac recorder / controller
Read the channel PVs (AI 1-8) and alarm states (MI 1-8) for monitoring. For control, write the loop target setpoint (AV 10), auto/manual (AV 11) and manual output (AV 12) for loop 1, or AV 17-19 for loop 2. Anything not in the list can be reached with the UserParameter address/value pairs.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 10 | Loop.1.Main.TargetSP | Loop 1 target setpoint | Write |
| AV 11 | Loop.1.Main.AutoMan | Loop 1 auto / manual select | Write |
| AV 12 | Loop.1.OP.ManualOutVal | Loop 1 output in manual | Write |
| AI 1 | Channel.1.Main.PV | Channel 1 measured value | Read |
| AI 2 | Channel.2.Main.PV | Channel 2 measured value | Read |
| AI 9 | Loop.1.Main.TargetSP | Loop 1 working setpoint | Read |
| AI 10 | Loop.1.Main.ActiveOP | Loop 1 active output | Read |
| MI 1 | Channel.1.Alarm1.Status | Channel 1 alarm 1 state | Read |
| MI 2 | Channel.1.Alarm2.Status | Channel 1 alarm 2 state | Read |
Network setup
- Up to 30 extra numeric parameters can be mapped through the UserParameter pairs (AV 53-112) using the parameter's Modbus address from the nanodac manual.
Watch out for
- AI 9 and AV 10 carry the same object name text (Loop.1.Main.TargetSP); AI 9 is the read-only working setpoint, AV 10 the writable target setpoint.
- Loop and alarm settings written over BACnet are instrument parameters; avoid cyclic writes.
Eurotherm (Schneider Electric) nanodac recorder / controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BI | 1 | DigitalIO.DI_LALC.Output | Indicates status of LALC output | Read | ON / OFF | |
| BI | 2 | DigitalIO.DI_LBLC.Output | Indicates status of LBLC output | Read | ON / OFF | |
| BI | 3 | DigitalIO.1A1B.Output | Indicates status of 1A1B output | Read | ON / OFF | |
| BI | 4 | DigitalIO.2A2B.Output | Indicates status of 2A2B output | Read | ON / OFF | |
| BI | 5 | DigitalIO.3A3B.Output | Indicates status of 3A3B output | Read | ON / OFF | |
| BI | 6 | DigitalIO.RELAY_4AC.Output | Indicates status of 4AC output | Read | ON / OFF | |
| BI | 7 | DigitalIO.RELAY_5AC.Output | Indicates status of 5AC output | Read | ON / OFF | |
| AImin | 1 | Channel.1.Main.PV | Channel 1 PV | Read | ||
| AImin | 2 | Channel.2.Main.PV | Channel 2 PV | Read | ||
| AI | 3 | Channel.3.Main.PV | Channel 3 PV | Read | ||
| AI | 4 | Channel.4.Main.PV | Channel 4 PV | Read | ||
| AI | 5 | Channel.5.Main.PV | Channel 5 PV | Read | ||
| AI | 6 | Channel.6.Main.PV | Channel 6 PV | Read | ||
| AI | 7 | Channel.7.Main.PV | Channel 7 PV | Read | ||
| AI | 8 | Channel.8.Main.PV | Channel 8 PV | Read | ||
| AImin | 9 | Loop.1.Main.TargetSP | Loop 1 working setpoint | Read | ||
| AImin | 10 | Loop.1.Main.ActiveOP | Loop 1 active output | Read | ||
| AI | 11 | Loop.2.Main.TargetSP | Loop 2 working setpoint | Read | ||
| AI | 12 | Loop.2.Main.ActiveOP | Loop 2 active output | Read | ||
| AI | 13 | Steam.1.HeatFlow | Steam 1 Heat Flow | Read | ||
| AI | 14 | Steam1.MassFlow | Steam 1 Mass Flow | Read | ||
| AI | 15 | Steam.1.HeatConsumed | Steam 1 heat consumed | Read | ||
| AI | 16 | Steam.2.WaterEnth | Steam 2 water enthalpy | Read | ||
| AI | 17 | Steam.2.SteamEnth | Steam 2 steam enthalpy | Read | ||
| AI | 18 | Steam.2.CalcValue | Steam 2 calculation value | Read | ||
| AI | 19 | DigitalIO.1A1B.PV | 1A1B PV | Read | ||
| AI | 20 | DigitalIO.2A2B.PV | 1A1B PV | Read | ||
| AI | 21 | DigitalIO.3A3B.PV | 1A1B PV | Read | ||
| AI | 22 | VirtualChannel.1.Main.PV | Virtual channel 1 PV | Read | ||
| AI | 23 | VirtualChannel.2.Main.PV | Virtual channel 2 PV | Read | ||
| AI | 24 | VirtualChannel.3.Main.PV | Virtual channel 3 PV | Read | ||
| AI | 25 | VirtualChannel.4.Main.PV | Virtual channel 4 PV | Read | ||
| AI | 26 | VirtualChannel.5.Main.PV | Virtual channel 5 PV | Read | ||
| AI | 27 | VirtualChannel.6.Main.PV | Virtual channel 6 PV | Read | ||
| AI | 28 | VirtualChannel.7.Main.PV | Virtual channel 7 PV | Read | ||
| AI | 29 | VirtualChannel.8.Main.PV | Virtual channel 8 PV | Read | ||
| AI | 30 | VirtualChannel.9.Main.PV | Virtual channel 9 PV | Read | ||
| AI | 31 | VirtualChannel.10.Main.PV | Virtual channel 10 PV | Read | ||
| AI | 32 | VirtualChannel.11.Main.PV | Virtual channel 11 PV | Read | ||
| AI | 33 | VirtualChannel.12.Main.PV | Virtual channel 12 PV | Read | ||
| AI | 34 | VirtualChannel.13.Main.PV | Virtual channel 13 PV | Read | ||
| AI | 35 | VirtualChannel.14.Main.PV | Virtual channel 14 PV | Read | ||
| AI | 36 | VirtualChannel.15.Main.PV | Virtual channel 15 PV | Read | ||
| AI | 37 | VirtualChannel.16.Main.PV | Virtual channel 16 PV | Read | ||
| AI | 38 | VirtualChannel.17.Main.PV | Virtual channel 17 PV | Read | ||
| AI | 39 | VirtualChannel.18.Main.PV | Virtual channel 18 PV | Read | ||
| AI | 40 | VirtualChannel.19.Main.PV | Virtual channel 19 PV | Read | ||
| AI | 41 | VirtualChannel.20.Main.PV | Virtual channel 20 PV | Read | ||
| AI | 42 | VirtualChannel.21.Main.PV | Virtual channel 21 PV | Read | ||
| AI | 43 | VirtualChannel.22.Main.PV | Virtual channel 22 PV | Read | ||
| AI | 44 | VirtualChannel.23.Main.PV | Virtual channel 23 PV | Read | ||
| AI | 45 | VirtualChannel.24.Main.PV | Virtual channel 24 PV | Read | ||
| AI | 46 | VirtualChannel.25.Main.PV | Virtual channel 25 PV | Read | ||
| AI | 47 | VirtualChannel.26.Main.PV | Virtual channel 26 PV | Read | ||
| AI | 48 | VirtualChannel.27.Main.PV | Virtual channel 27 PV | Read | ||
| AI | 49 | VirtualChannel.28.Main.PV | Virtual channel 28 PV | Read | ||
| AI | 50 | VirtualChannel.29.Main.PV | Virtual channel 29 PV | Read | ||
| AI | 51 | VirtualChannel.30.Main.PV | Virtual channel 30 PV | Read | ||
| AV | 1 | Channel.1.Alarm1.Threshold | Channel 1 alarm 1 threshold | Write | ||
| AV | 2 | Channel.1.Alarm2.Threshold | Channel 1 alarm 2 threshold | Write | ||
| AV | 3 | Channel.2.Alarm1.Threshold | Channel 2 alarm 1 threshold | Write | ||
| AV | 4 | Channel.2.Alarm2.Threshold | Channel 2 alarm 2 threshold | Write | ||
| AV | 5 | Channel.3.Alarm1.Threshold | Channel 3 alarm 1 threshold | Write | ||
| AV | 6 | Channel.3.Alarm2.Threshold | Channel 3 alarm 2 threshold | Write | ||
| AV | 7 | Channel.4.Alarm1.Threshold | Channel 4 alarm 1 threshold | Write | ||
| AV | 8 | Channel.4.Alarm2.Threshold | Channel 4 alarm 2 threshold | Write | ||
| AV | 9 | Loop1.Main.PV | Loop 1 PV | Write | ||
| AVmin | 10 | Loop.1.Main.TargetSP | Loop 1 target setpoint | Write | ||
| AVmin | 11 | Loop.1.Main.AutoMan | Loop 1 auto/manual | Write | ||
| AVmin | 12 | Loop.1.OP.ManualOutVal | Loop 1 manual output | Write | ||
| AV | 13 | Loop.1.PID.ProportionalBand | Loop 1 proportional band | Write | ||
| AV | 14 | Loop.1.PID.IntegralTime | Loop 1 integral time | Write | ||
| AV | 15 | Loop.1.PID.DerivativeTime | Loop 1 derivative time | Write | ||
| AV | 16 | Loop.2.Main.PV | Loop 1 PV | Write | ||
| AV | 17 | Loop.2.Main.TargetSP | Loop 1 target setpoint | Write | ||
| AV | 18 | Loop.2.Main.AutoMan | Loop 1 auto/manual | Write | ||
| AV | 19 | Loop.2.OP.ManualOutVal | Loop 1 manual output | Write | ||
| AV | 20 | Loop.2.PID.ProportionalBand | Loop 1 proportional band | Write | ||
| AV | 21 | Loop.2.PID.IntegralTime | Loop 1 integral time | Write | ||
| AV | 22 | Loop.2.PID.DerivativeTime | Loop 1 derivative time | Write | ||
| AV | 23 | VirtualChannel.1.Alarm1.Threshold | Virtual channel 1 alarm 1 threshold | Write | ||
| AV | 24 | VirtualChannel.1.Alarm2.Threshold | Virtual channel 1 alarm 2 threshold | Write | ||
| AV | 25 | VirtualChannel.2.Alarm1.Threshold | Virtual channel 2 alarm 1 threshold | Write | ||
| AV | 26 | VirtualChannel.2.Alarm2.Threshold | Virtual channel 2 alarm 2 threshold | Write | ||
| AV | 27 | VirtualChannel.3.Alarm1.Threshold | Virtual channel 3 alarm 1 threshold | Write | ||
| AV | 28 | VirtualChannel.3.Alarm2.Threshold | Virtual channel 3 alarm 2 threshold | Write | ||
| AV | 29 | VirtualChannel.4.Alarm1.Threshold | Virtual channel 4 alarm 1 threshold | Write | ||
| AV | 30 | VirtualChannel.4.Alarm2.Threshold | Virtual channel 4 alarm 2 threshold | Write | ||
| AV | 31 | VirtualChannel.5.Alarm1.Threshold | Virtual channel 5 alarm 1 threshold | Write | ||
| AV | 32 | VirtualChannel.5.Alarm2.Threshold | Virtual channel 5 alarm 2 threshold | Write | ||
| AV | 33 | VirtualChannel.6.Alarm1.Threshold | Virtual channel 6 alarm 1 threshold | Write | ||
| AV | 34 | VirtualChannel.6.Alarm2.Threshold | Virtual channel 6 alarm 2 threshold | Write | ||
| AV | 35 | VirtualChannel.7.Alarm1.Threshold | Virtual channel 7 alarm 1 threshold | Write | ||
| AV | 36 | VirtualChannel.7.Alarm2.Threshold | Virtual channel 7 alarm 2 threshold | Write | ||
| AV | 37 | VirtualChannel.8.Alarm1.Threshold | Virtual channel 8 alarm 1 threshold | Write | ||
| AV | 38 | VirtualChannel.8.Alarm2.Threshold | Virtual channel 8 alarm 2 threshold | Write | ||
| AV | 39 | VirtualChannel.9.Alarm1.Threshold | Virtual channel 9 alarm 1 threshold | Write | ||
| AV | 40 | VirtualChannel.9.Alarm2.Threshold | Virtual channel 9 alarm 2 threshold | Write | ||
| AV | 41 | VirtualChannel.10.Alarm1.Threshold | Virtual channel 10 alarm 1 threshold | Write | ||
| AV | 42 | VirtualChannel.10.Alarm2.Threshold | Virtual channel 10 alarm 2 threshold | Write | ||
| AV | 43 | VirtualChannel.11.Alarm1.Threshold | Virtual channel 11 alarm 1 threshold | Write | ||
| AV | 44 | VirtualChannel.11.Alarm2.Threshold | Virtual channel 11 alarm 2 threshold | Write | ||
| AV | 45 | VirtualChannel.12.Alarm1.Threshold | Virtual channel 12 alarm 1 threshold | Write | ||
| AV | 46 | VirtualChannel.12.Alarm2.Threshold | Virtual channel 12 alarm 2 threshold | Write | ||
| AV | 47 | VirtualChannel.13.Alarm1.Threshold | Virtual channel 13 alarm 1 threshold | Write | ||
| AV | 48 | VirtualChannel.13.Alarm2.Threshold | Virtual channel 13 alarm 2 threshold | Write | ||
| AV | 49 | VirtualChannel.14.Alarm1.Threshold | Virtual channel 14 alarm 1 threshold | Write | ||
| AV | 50 | VirtualChannel.14.Alarm2.Threshold | Virtual channel 14 alarm 2 threshold | Write | ||
| AV | 51 | VirtualChannel.15.Alarm1.Threshold | Virtual channel 15 alarm 1 threshold | Write | ||
| AV | 52 | VirtualChannel.15.Alarm2.Threshold | Virtual channel 15 alarm 2 threshold | Write | ||
| AV | 53 | UserParameter.1.Address | User parameter 1 address | Write | ||
| AV | 54 | UserParameter.1.Value | User parameter 1 value | Write | ||
| AV | 55 | UserParameter.2.Address | User parameter 2 address | Write | ||
| AV | 56 | UserParameter.2.Value | User parameter 2 value | Write | ||
| AV | 57 | UserParameter.3.Address | User parameter 3 address | Write | ||
| AV | 58 | UserParameter.3.Value | User parameter 3 value | Write | ||
| AV | 59 | UserParameter.4.Address | User parameter 4 address | Write | ||
| AV | 60 | UserParameter.4.Value | User parameter 4 value | Write | ||
| AV | 61 | UserParameter.5.Address | User parameter 5 address | Write | ||
| AV | 62 | UserParameter.5.Value | User parameter 5 value | Write | ||
| AV | 63 | UserParameter.6.Address | User parameter 6 address | Write | ||
| AV | 64 | UserParameter.6.Value | User parameter 6 value | Write | ||
| AV | 65 | UserParameter.7.Address | User parameter 7 address | Write | ||
| AV | 66 | UserParameter.7.Value | User parameter 7 value | Write | ||
| AV | 67 | UserParameter.8.Address | User parameter 8 address | Write | ||
| AV | 68 | UserParameter.8.Value | User parameter 8 value | Write | ||
| AV | 69 | UserParameter.9.Address | User parameter 9 address | Write | ||
| AV | 70 | UserParameter.9.Value | User parameter 9 value | Write | ||
| AV | 71 | UserParameter.10.Address | User parameter 10 address | Write | ||
| AV | 72 | UserParameter.10.Value | User parameter 10 value | Write | ||
| AV | 73 | UserParameter.11.Address | User parameter 11 address | Write | ||
| AV | 74 | UserParameter.11.Value | User parameter 11 value | Write | ||
| AV | 75 | UserParameter.12.Address | User parameter 12 address | Write | ||
| AV | 76 | UserParameter.12.Value | User parameter 12 value | Write | ||
| AV | 77 | UserParameter.13.Address | User parameter 13 address | Write | ||
| AV | 78 | UserParameter.13.Value | User parameter 13 value | Write | ||
| AV | 79 | UserParameter.14.Address | User parameter 14 address | Write | ||
| AV | 80 | UserParameter.14.Value | User parameter 14 value | Write | ||
| AV | 81 | UserParameter.15.Address | User parameter 15 address | Write | ||
| AV | 82 | UserParameter.15.Value | User parameter 15 value | Write | ||
| AV | 83 | UserParameter.16Address | User parameter 16 address | Write | ||
| AV | 84 | UserParameter.16.Value | User parameter 16 value | Write | ||
| AV | 85 | UserParameter.17.Address | User parameter 17address | Write | ||
| AV | 86 | UserParameter.17.Value | User parameter 17 value | Write | ||
| AV | 87 | UserParameter.18.Address | User parameter 18 address | Write | ||
| AV | 88 | UserParameter.18.Value | User parameter 18 value | Write | ||
| AV | 89 | UserParameter.19.Address | User parameter 19 address | Write | ||
| AV | 90 | UserParameter.19.Value | User parameter 19 value | Write | ||
| AV | 91 | UserParameter.20.Address | User parameter 20 address | Write | ||
| AV | 92 | UserParameter.20.Value | User parameter 20 value | Write | ||
| AV | 93 | UserParameter.21.Address | User parameter 21 address | Write | ||
| AV | 94 | UserParameter.21.Value | User parameter 21 value | Write | ||
| AV | 95 | UserParameter.22.Address | User parameter 22 address | Write | ||
| AV | 96 | UserParameter.22.Value | User parameter 22 value | Write | ||
| AV | 97 | UserParameter.23.Address | User parameter 23 address | Write | ||
| AV | 98 | UserParameter.23.Value | User parameter 23 value | Write | ||
| AV | 99 | UserParameter.24.Address | User parameter 24 address | Write | ||
| AV | 100 | UserParameter.24.Value | User parameter 24 value | Write | ||
| AV | 101 | UserParameter.25.Address | User parameter 25 address | Write | ||
| AV | 102 | UserParameter.25.Value | User parameter 25 value | Write | ||
| AV | 103 | UserParameter.26.Address | User parameter 26 address | Write | ||
| AV | 104 | UserParameter.26.Value | User parameter 26 value | Write | ||
| AV | 105 | UserParameter.27.Address | User parameter 27 address | Write | ||
| AV | 106 | UserParameter.27.Value | User parameter 27 value | Write | ||
| AV | 107 | UserParameter.28.Address | User parameter 28 address | Write | ||
| AV | 108 | UserParameter.28.Value | User parameter 28 value | Write | ||
| AV | 109 | UserParameter.29.Address | User parameter 29 address | Write | ||
| AV | 110 | UserParameter.29.Value | User parameter 29 value | Write | ||
| AV | 111 | UserParameter.30.Address | User parameter 30 address | Write | ||
| AV | 112 | UserParameter.30.Value | User parameter 30 value | Write | ||
| MImin | 1 | Channel.1.Alarm1.Status | Channel 1 alarm 1 status | Read | ||
| MImin | 2 | Channel.1.Alarm2.Status | Channel 1 alarm 2 status | Read | ||
| MI | 3 | Channel.2.Alarm1.Status | Channel 2 alarm 1 status | Read | ||
| MI | 4 | Channel.2.Alarm2.Status | Channel 2 alarm 2 status | Read | ||
| MI | 5 | Channel.3.Alarm1.Status | Channel 3 alarm 1 status | Read | ||
| MI | 6 | Channel.3.Alarm2.Status | Channel 3 alarm 2 status | Read | ||
| MI | 7 | Channel.4.Alarm1.Status | Channel 4 alarm 1 status | Read | ||
| MI | 8 | Channel.4.Alarm2.Status | Channel 4 alarm 2 status | Read | ||
| MI | 9 | VirtualChannel.1.Alarm1.Status | Virtual channel 1 alarm 1 status | Read | ||
| MI | 10 | VirtualChannel.1.Alarm2.Status | Virtual channel 1 alarm 2 status | Read | ||
| MI | 11 | VirtualChannel.2.Alarm1.Status | Virtual channel 2 alarm 1 status | Read | ||
| MI | 12 | VirtualChannel.2.Alarm2.Status | Virtual channel 2 alarm 2 status | Read | ||
| MI | 13 | VirtualChannel.3.Alarm1.Status | Virtual channel 3 alarm 1 status | Read | ||
| MI | 14 | VirtualChannel.3.Alarm2.Status | Virtual channel 3 alarm 2 status | Read | ||
| MI | 15 | VirtualChannel.4.Alarm1.Status | Virtual channel 4 alarm 1 status | Read | ||
| MI | 16 | VirtualChannel.4.Alarm2.Status | Virtual channel 4 alarm 2 status | Read | ||
| MI | 17 | VirtualChannel.5.Alarm1.Status | Virtual channel 5 alarm 1 status | Read | ||
| MI | 18 | VirtualChannel.5.Alarm2.Status | Virtual channel 5 alarm 2 status | Read | ||
| MI | 19 | VirtualChannel.6.Alarm1.Status | Virtual channel 6 alarm 1 status | Read | ||
| MI | 20 | VirtualChannel.6.Alarm2.Status | Virtual channel 6 alarm 2 status | Read | ||
| MI | 21 | VirtualChannel.7.Alarm1.Status | Virtual channel 7 alarm 1 status | Read | ||
| MI | 22 | VirtualChannel.7.Alarm2.Status | Virtual channel 7 alarm 2 status | Read | ||
| MI | 23 | VirtualChannel.8.Alarm1.Status | Virtual channel 8 alarm 1 status | Read | ||
| MI | 24 | VirtualChannel.8.Alarm2.Status | Virtual channel 8 alarm 2 status | Read | ||
| MI | 25 | VirtualChannel.9.Alarm1.Status | Virtual channel 9 alarm 1 status | Read | ||
| MI | 26 | VirtualChannel.9.Alarm2.Status | Virtual channel 9 alarm 2 status | Read | ||
| MI | 27 | VirtualChannel.10.Alarm1.Status | Virtual channel 10 alarm 1 status | Read | ||
| MI | 28 | VirtualChannel.10.Alarm2.Status | Virtual channel 10 alarm 2 status | Read | ||
| MI | 29 | VirtualChannel.11.Alarm1.Status | Virtual channel 11 alarm 1 status | Read | ||
| MI | 30 | VirtualChannel.11.Alarm2.Status | Virtual channel 11 alarm 2 status | Read | ||
| MI | 31 | VirtualChannel.12.Alarm1.Status | Virtual channel 12 alarm 1 status | Read | ||
| MI | 32 | VirtualChannel.12.Alarm2.Status | Virtual channel 12 alarm 2 status | Read | ||
| MI | 33 | VirtualChannel.13.Alarm1.Status | Virtual channel 13 alarm 1 status | Read | ||
| MI | 34 | VirtualChannel.13.Alarm2.Status | Virtual channel 13 alarm 2 status | Read | ||
| MI | 35 | VirtualChannel.14.Alarm1.Status | Virtual channel 14 alarm 1 status | Read | ||
| MI | 36 | VirtualChannel.14.Alarm2.Status | Virtual channel 14 alarm 2 status | Read | ||
| MI | 37 | VirtualChannel.15.Alarm1.Status | Virtual channel 15 alarm 1 status | Read | ||
| MI | 38 | VirtualChannel.15.Alarm2.Status | Virtual channel 15 alarm 2 status | Read | ||
| CSV | 1 | Loop.1.Setup.LoopName | Loop 1 name | Read | ||
| CSV | 2 | Loop.2.Setup.LoopName | Loop 2 name | Read |
No points match these filters.
Object ID lookup: Eurotherm (Schneider Electric) nanodac recorder / controller point IDs by name
BI1DigitalIO.DI_LALC.OutputBI2DigitalIO.DI_LBLC.OutputBI3DigitalIO.1A1B.OutputBI4DigitalIO.2A2B.OutputBI5DigitalIO.3A3B.OutputBI6DigitalIO.RELAY_4AC.OutputBI7DigitalIO.RELAY_5AC.OutputAI1Channel.1.Main.PVAI2Channel.2.Main.PVAI3Channel.3.Main.PVAI4Channel.4.Main.PVAI5Channel.5.Main.PVAI6Channel.6.Main.PVAI7Channel.7.Main.PVAI8Channel.8.Main.PVAI9Loop.1.Main.TargetSPAI10Loop.1.Main.ActiveOPAI11Loop.2.Main.TargetSPAI12Loop.2.Main.ActiveOPAI13Steam.1.HeatFlowAI14Steam1.MassFlowAI15Steam.1.HeatConsumedAI16Steam.2.WaterEnthAI17Steam.2.SteamEnthAI18Steam.2.CalcValueAI19DigitalIO.1A1B.PVAI20DigitalIO.2A2B.PVAI21DigitalIO.3A3B.PVAI22VirtualChannel.1.Main.PVAI23VirtualChannel.2.Main.PVAI24VirtualChannel.3.Main.PVAI25VirtualChannel.4.Main.PVAI26VirtualChannel.5.Main.PVAI27VirtualChannel.6.Main.PVAI28VirtualChannel.7.Main.PVAI29VirtualChannel.8.Main.PVAI30VirtualChannel.9.Main.PVAI31VirtualChannel.10.Main.PVAI32VirtualChannel.11.Main.PVAI33VirtualChannel.12.Main.PVAI34VirtualChannel.13.Main.PVAI35VirtualChannel.14.Main.PVAI36VirtualChannel.15.Main.PVAI37VirtualChannel.16.Main.PVAI38VirtualChannel.17.Main.PVAI39VirtualChannel.18.Main.PVAI40VirtualChannel.19.Main.PVAI41VirtualChannel.20.Main.PVAI42VirtualChannel.21.Main.PVAI43VirtualChannel.22.Main.PVAI44VirtualChannel.23.Main.PVAI45VirtualChannel.24.Main.PVAI46VirtualChannel.25.Main.PVAI47VirtualChannel.26.Main.PVAI48VirtualChannel.27.Main.PVAI49VirtualChannel.28.Main.PVAI50VirtualChannel.29.Main.PVAI51VirtualChannel.30.Main.PVAV1Channel.1.Alarm1.ThresholdAV2Channel.1.Alarm2.ThresholdAV3Channel.2.Alarm1.ThresholdAV4Channel.2.Alarm2.ThresholdAV5Channel.3.Alarm1.ThresholdAV6Channel.3.Alarm2.ThresholdAV7Channel.4.Alarm1.ThresholdAV8Channel.4.Alarm2.ThresholdAV9Loop1.Main.PVAV10Loop.1.Main.TargetSPAV11Loop.1.Main.AutoManAV12Loop.1.OP.ManualOutValAV13Loop.1.PID.ProportionalBandAV14Loop.1.PID.IntegralTimeAV15Loop.1.PID.DerivativeTimeAV16Loop.2.Main.PVAV17Loop.2.Main.TargetSPAV18Loop.2.Main.AutoManAV19Loop.2.OP.ManualOutValAV20Loop.2.PID.ProportionalBandAV21Loop.2.PID.IntegralTimeAV22Loop.2.PID.DerivativeTimeAV23VirtualChannel.1.Alarm1.ThresholdAV24VirtualChannel.1.Alarm2.ThresholdAV25VirtualChannel.2.Alarm1.ThresholdAV26VirtualChannel.2.Alarm2.ThresholdAV27VirtualChannel.3.Alarm1.ThresholdAV28VirtualChannel.3.Alarm2.ThresholdAV29VirtualChannel.4.Alarm1.ThresholdAV30VirtualChannel.4.Alarm2.ThresholdAV31VirtualChannel.5.Alarm1.ThresholdAV32VirtualChannel.5.Alarm2.ThresholdAV33VirtualChannel.6.Alarm1.ThresholdAV34VirtualChannel.6.Alarm2.ThresholdAV35VirtualChannel.7.Alarm1.ThresholdAV36VirtualChannel.7.Alarm2.ThresholdAV37VirtualChannel.8.Alarm1.ThresholdAV38VirtualChannel.8.Alarm2.ThresholdAV39VirtualChannel.9.Alarm1.ThresholdAV40VirtualChannel.9.Alarm2.ThresholdAV41VirtualChannel.10.Alarm1.ThresholdAV42VirtualChannel.10.Alarm2.ThresholdAV43VirtualChannel.11.Alarm1.ThresholdAV44VirtualChannel.11.Alarm2.ThresholdAV45VirtualChannel.12.Alarm1.ThresholdAV46VirtualChannel.12.Alarm2.ThresholdAV47VirtualChannel.13.Alarm1.ThresholdAV48VirtualChannel.13.Alarm2.ThresholdAV49VirtualChannel.14.Alarm1.ThresholdAV50VirtualChannel.14.Alarm2.ThresholdAV51VirtualChannel.15.Alarm1.ThresholdAV52VirtualChannel.15.Alarm2.ThresholdAV53UserParameter.1.AddressAV54UserParameter.1.ValueAV55UserParameter.2.AddressAV56UserParameter.2.ValueAV57UserParameter.3.AddressAV58UserParameter.3.ValueAV59UserParameter.4.AddressAV60UserParameter.4.ValueAV61UserParameter.5.AddressAV62UserParameter.5.ValueAV63UserParameter.6.AddressAV64UserParameter.6.ValueAV65UserParameter.7.AddressAV66UserParameter.7.ValueAV67UserParameter.8.AddressAV68UserParameter.8.ValueAV69UserParameter.9.AddressAV70UserParameter.9.ValueAV71UserParameter.10.AddressAV72UserParameter.10.ValueAV73UserParameter.11.AddressAV74UserParameter.11.ValueAV75UserParameter.12.AddressAV76UserParameter.12.ValueAV77UserParameter.13.AddressAV78UserParameter.13.ValueAV79UserParameter.14.AddressAV80UserParameter.14.ValueAV81UserParameter.15.AddressAV82UserParameter.15.ValueAV83UserParameter.16AddressAV84UserParameter.16.ValueAV85UserParameter.17.AddressAV86UserParameter.17.ValueAV87UserParameter.18.AddressAV88UserParameter.18.ValueAV89UserParameter.19.AddressAV90UserParameter.19.ValueAV91UserParameter.20.AddressAV92UserParameter.20.ValueAV93UserParameter.21.AddressAV94UserParameter.21.ValueAV95UserParameter.22.AddressAV96UserParameter.22.ValueAV97UserParameter.23.AddressAV98UserParameter.23.ValueAV99UserParameter.24.AddressAV100UserParameter.24.ValueAV101UserParameter.25.AddressAV102UserParameter.25.ValueAV103UserParameter.26.AddressAV104UserParameter.26.ValueAV105UserParameter.27.AddressAV106UserParameter.27.ValueAV107UserParameter.28.AddressAV108UserParameter.28.ValueAV109UserParameter.29.AddressAV110UserParameter.29.ValueAV111UserParameter.30.AddressAV112UserParameter.30.ValueMI1Channel.1.Alarm1.StatusMI2Channel.1.Alarm2.StatusMI3Channel.2.Alarm1.StatusMI4Channel.2.Alarm2.StatusMI5Channel.3.Alarm1.StatusMI6Channel.3.Alarm2.StatusMI7Channel.4.Alarm1.StatusMI8Channel.4.Alarm2.StatusMI9VirtualChannel.1.Alarm1.StatusMI10VirtualChannel.1.Alarm2.StatusMI11VirtualChannel.2.Alarm1.StatusMI12VirtualChannel.2.Alarm2.StatusMI13VirtualChannel.3.Alarm1.StatusMI14VirtualChannel.3.Alarm2.StatusMI15VirtualChannel.4.Alarm1.StatusMI16VirtualChannel.4.Alarm2.StatusMI17VirtualChannel.5.Alarm1.StatusMI18VirtualChannel.5.Alarm2.StatusMI19VirtualChannel.6.Alarm1.StatusMI20VirtualChannel.6.Alarm2.StatusMI21VirtualChannel.7.Alarm1.StatusMI22VirtualChannel.7.Alarm2.StatusMI23VirtualChannel.8.Alarm1.StatusMI24VirtualChannel.8.Alarm2.StatusMI25VirtualChannel.9.Alarm1.StatusMI26VirtualChannel.9.Alarm2.StatusMI27VirtualChannel.10.Alarm1.StatusMI28VirtualChannel.10.Alarm2.StatusMI29VirtualChannel.11.Alarm1.StatusMI30VirtualChannel.11.Alarm2.StatusMI31VirtualChannel.12.Alarm1.StatusMI32VirtualChannel.12.Alarm2.StatusMI33VirtualChannel.13.Alarm1.StatusMI34VirtualChannel.13.Alarm2.StatusMI35VirtualChannel.14.Alarm1.StatusMI36VirtualChannel.14.Alarm2.StatusMI37VirtualChannel.15.Alarm1.StatusMI38VirtualChannel.15.Alarm2.StatusCSV1Loop.1.Setup.LoopNameCSV2Loop.2.Setup.LoopName
Integration notes
- Units are not printed (shown as a dash) for every analog object; they follow the channel and loop configuration.
- AV 53-112 are 30 UserParameter Address/Value pairs: write a parameter's Modbus address to the Address object, then read or write its value in the Value object. 32-bit integers cannot be reached this way; integers read with a resolution of 1.0.
- The Out_Of_Service property is writable on the BI, AI, AV and multistate objects.
- AI 20 and AI 21 (DigitalIO.2A2B.PV, DigitalIO.3A3B.PV) are both described as '1A1B PV' in the PICS; AV 16-22 (loop 2) are described as loop 1. The object names are given as printed.
- AI 14 is printed as 'Steam1.MassFlow' and AV 9 as 'Loop1.Main.PV' (no dot), unlike their neighbours.
- The PICS does not name the data link; vendor ID 10 (Schneider Electric), protocol revision 14, B-ASC.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the nanodac recorder / controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Eurotherm (Schneider Electric) nanodac recorder / controller
How many BACnet points does the Eurotherm (Schneider Electric) nanodac recorder / controller have?
This list has 210 BACnet objects: 51 analog inputs, 112 analog values, 7 binary inputs, 38 multi-state inputs, 2 characterstring values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Eurotherm (Schneider Electric) nanodac recorder / controller BACnet points are writable?
112 of the 210 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Eurotherm (Schneider Electric) nanodac recorder / controller BACnet documentation?
Eurotherm (Schneider Electric) does not publish it on its own website. This list comes from nanodac Recorder / Controller Protocol Implementation Conformance Statement (HA033110 Issue 1), revision 2017-09-12, a copy hosted by BACnet International product catalog at https://www.bacnetinternational.net/catalog/manu/eurotherm%20by%20schneider%20electric/HA033110_1_nanodac_BACnet_PICS_document.pdf. Ask Eurotherm (Schneider Electric) or its representative for the current revision.
What are the minimum BACnet points to integrate the Eurotherm (Schneider Electric) nanodac recorder / controller?
Start with AV 10 Loop.1.Main.TargetSP (Loop 1 target setpoint); AV 11 Loop.1.Main.AutoMan (Loop 1 auto / manual select); AV 12 Loop.1.OP.ManualOutVal (Loop 1 output in manual); AI 1 Channel.1.Main.PV (Channel 1 measured value); AI 2 Channel.2.Main.PV (Channel 2 measured value); AI 9 Loop.1.Main.TargetSP (Loop 1 working setpoint); AI 10 Loop.1.Main.ActiveOP (Loop 1 active output); MI 1 Channel.1.Alarm1.Status (Channel 1 alarm 1 state); MI 2 Channel.1.Alarm2.Status (Channel 1 alarm 2 state).
How do I check these points on the real nanodac recorder / controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Eurotherm (Schneider Electric) BACnet points lists
Source: nanodac Recorder / Controller Protocol Implementation Conformance Statement · HA033110 Issue 1 · rev. 2017-09-12. Object names, instances and units are reproduced as published; descriptions are our own.