Short answer

The nanodac is a compact paperless recorder with up to two PID loops, steam calculations and 30 virtual channels. Its BACnet object list is fixed: measured channels, loop setpoints and outputs, steam values and virtual channels as analog inputs; alarm thresholds, loop PV, setpoint, auto/manual, manual output and PID terms as writable analog values; alarm states as multistate inputs; and 30 user parameter address/value pairs that give indirect access to any other numeric parameter.

This page lists 210 BACnet objects for the Eurotherm (Schneider Electric) nanodac recorder / controller — 112 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Eurotherm (Schneider Electric)’s documentation hosted by BACnet International product catalog, not by Eurotherm (Schneider Electric) itself, so treat it as unofficial.

Manufacturer
Eurotherm (Schneider Electric)
Model
nanodac recorder / controller
Equipment
Other equipment (process recorder / PID controller)
Equipment type
Other equipment
BACnet objects
210 (112 writable)
Transport
—
Firmware
V8.09
Also known as
nanodac, Eurotherm nanodac, nanodac recorder, HA033110
Source document
nanodac Recorder / Controller Protocol Implementation Conformance Statement · HA033110 Issue 1 · rev. 2017-09-12 (unofficial copy, hosted by BACnet International product catalog)
Download CSV 210 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Eurotherm (Schneider Electric)’s current documentation and the live device before use. Not official Eurotherm (Schneider Electric) information. Terms of use.

BMS integration notes: Eurotherm (Schneider Electric) nanodac recorder / controller

Integration in brief

Read the channel PVs (AI 1-8) and alarm states (MI 1-8) for monitoring. For control, write the loop target setpoint (AV 10), auto/manual (AV 11) and manual output (AV 12) for loop 1, or AV 17-19 for loop 2. Anything not in the list can be reached with the UserParameter address/value pairs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 10Loop.1.Main.TargetSPLoop 1 target setpointWrite
AV 11Loop.1.Main.AutoManLoop 1 auto / manual selectWrite
AV 12Loop.1.OP.ManualOutValLoop 1 output in manualWrite
AI 1Channel.1.Main.PVChannel 1 measured valueRead
AI 2Channel.2.Main.PVChannel 2 measured valueRead
AI 9Loop.1.Main.TargetSPLoop 1 working setpointRead
AI 10Loop.1.Main.ActiveOPLoop 1 active outputRead
MI 1Channel.1.Alarm1.StatusChannel 1 alarm 1 stateRead
MI 2Channel.1.Alarm2.StatusChannel 1 alarm 2 stateRead

Network setup

Watch out for

Eurotherm (Schneider Electric) nanodac recorder / controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

210 of 210 shown
Type
BinaryMulti-stateOther
Access
Show
Eurotherm (Schneider Electric) nanodac recorder / controller BACnet Points List
DescriptionStates
BI1DigitalIO.DI_LALC.OutputIndicates status of LALC outputReadON / OFF
BI2DigitalIO.DI_LBLC.OutputIndicates status of LBLC outputReadON / OFF
BI3DigitalIO.1A1B.OutputIndicates status of 1A1B outputReadON / OFF
BI4DigitalIO.2A2B.OutputIndicates status of 2A2B outputReadON / OFF
BI5DigitalIO.3A3B.OutputIndicates status of 3A3B outputReadON / OFF
BI6DigitalIO.RELAY_4AC.OutputIndicates status of 4AC outputReadON / OFF
BI7DigitalIO.RELAY_5AC.OutputIndicates status of 5AC outputReadON / OFF
AImin1Channel.1.Main.PVChannel 1 PVRead
AImin2Channel.2.Main.PVChannel 2 PVRead
AI3Channel.3.Main.PVChannel 3 PVRead
AI4Channel.4.Main.PVChannel 4 PVRead
AI5Channel.5.Main.PVChannel 5 PVRead
AI6Channel.6.Main.PVChannel 6 PVRead
AI7Channel.7.Main.PVChannel 7 PVRead
AI8Channel.8.Main.PVChannel 8 PVRead
AImin9Loop.1.Main.TargetSPLoop 1 working setpointRead
AImin10Loop.1.Main.ActiveOPLoop 1 active outputRead
AI11Loop.2.Main.TargetSPLoop 2 working setpointRead
AI12Loop.2.Main.ActiveOPLoop 2 active outputRead
AI13Steam.1.HeatFlowSteam 1 Heat FlowRead
AI14Steam1.MassFlowSteam 1 Mass FlowRead
AI15Steam.1.HeatConsumedSteam 1 heat consumedRead
AI16Steam.2.WaterEnthSteam 2 water enthalpyRead
AI17Steam.2.SteamEnthSteam 2 steam enthalpyRead
AI18Steam.2.CalcValueSteam 2 calculation valueRead
AI19DigitalIO.1A1B.PV1A1B PVRead
AI20DigitalIO.2A2B.PV1A1B PVRead
AI21DigitalIO.3A3B.PV1A1B PVRead
AI22VirtualChannel.1.Main.PVVirtual channel 1 PVRead
AI23VirtualChannel.2.Main.PVVirtual channel 2 PVRead
AI24VirtualChannel.3.Main.PVVirtual channel 3 PVRead
AI25VirtualChannel.4.Main.PVVirtual channel 4 PVRead
AI26VirtualChannel.5.Main.PVVirtual channel 5 PVRead
AI27VirtualChannel.6.Main.PVVirtual channel 6 PVRead
AI28VirtualChannel.7.Main.PVVirtual channel 7 PVRead
AI29VirtualChannel.8.Main.PVVirtual channel 8 PVRead
AI30VirtualChannel.9.Main.PVVirtual channel 9 PVRead
AI31VirtualChannel.10.Main.PVVirtual channel 10 PVRead
AI32VirtualChannel.11.Main.PVVirtual channel 11 PVRead
AI33VirtualChannel.12.Main.PVVirtual channel 12 PVRead
AI34VirtualChannel.13.Main.PVVirtual channel 13 PVRead
AI35VirtualChannel.14.Main.PVVirtual channel 14 PVRead
AI36VirtualChannel.15.Main.PVVirtual channel 15 PVRead
AI37VirtualChannel.16.Main.PVVirtual channel 16 PVRead
AI38VirtualChannel.17.Main.PVVirtual channel 17 PVRead
AI39VirtualChannel.18.Main.PVVirtual channel 18 PVRead
AI40VirtualChannel.19.Main.PVVirtual channel 19 PVRead
AI41VirtualChannel.20.Main.PVVirtual channel 20 PVRead
AI42VirtualChannel.21.Main.PVVirtual channel 21 PVRead
AI43VirtualChannel.22.Main.PVVirtual channel 22 PVRead
AI44VirtualChannel.23.Main.PVVirtual channel 23 PVRead
AI45VirtualChannel.24.Main.PVVirtual channel 24 PVRead
AI46VirtualChannel.25.Main.PVVirtual channel 25 PVRead
AI47VirtualChannel.26.Main.PVVirtual channel 26 PVRead
AI48VirtualChannel.27.Main.PVVirtual channel 27 PVRead
AI49VirtualChannel.28.Main.PVVirtual channel 28 PVRead
AI50VirtualChannel.29.Main.PVVirtual channel 29 PVRead
AI51VirtualChannel.30.Main.PVVirtual channel 30 PVRead
AV1Channel.1.Alarm1.ThresholdChannel 1 alarm 1 thresholdWrite
AV2Channel.1.Alarm2.ThresholdChannel 1 alarm 2 thresholdWrite
AV3Channel.2.Alarm1.ThresholdChannel 2 alarm 1 thresholdWrite
AV4Channel.2.Alarm2.ThresholdChannel 2 alarm 2 thresholdWrite
AV5Channel.3.Alarm1.ThresholdChannel 3 alarm 1 thresholdWrite
AV6Channel.3.Alarm2.ThresholdChannel 3 alarm 2 thresholdWrite
AV7Channel.4.Alarm1.ThresholdChannel 4 alarm 1 thresholdWrite
AV8Channel.4.Alarm2.ThresholdChannel 4 alarm 2 thresholdWrite
AV9Loop1.Main.PVLoop 1 PVWrite
AVmin10Loop.1.Main.TargetSPLoop 1 target setpointWrite
AVmin11Loop.1.Main.AutoManLoop 1 auto/manualWrite
AVmin12Loop.1.OP.ManualOutValLoop 1 manual outputWrite
AV13Loop.1.PID.ProportionalBandLoop 1 proportional bandWrite
AV14Loop.1.PID.IntegralTimeLoop 1 integral timeWrite
AV15Loop.1.PID.DerivativeTimeLoop 1 derivative timeWrite
AV16Loop.2.Main.PVLoop 1 PVWrite
AV17Loop.2.Main.TargetSPLoop 1 target setpointWrite
AV18Loop.2.Main.AutoManLoop 1 auto/manualWrite
AV19Loop.2.OP.ManualOutValLoop 1 manual outputWrite
AV20Loop.2.PID.ProportionalBandLoop 1 proportional bandWrite
AV21Loop.2.PID.IntegralTimeLoop 1 integral timeWrite
AV22Loop.2.PID.DerivativeTimeLoop 1 derivative timeWrite
AV23VirtualChannel.1.Alarm1.ThresholdVirtual channel 1 alarm 1 thresholdWrite
AV24VirtualChannel.1.Alarm2.ThresholdVirtual channel 1 alarm 2 thresholdWrite
AV25VirtualChannel.2.Alarm1.ThresholdVirtual channel 2 alarm 1 thresholdWrite
AV26VirtualChannel.2.Alarm2.ThresholdVirtual channel 2 alarm 2 thresholdWrite
AV27VirtualChannel.3.Alarm1.ThresholdVirtual channel 3 alarm 1 thresholdWrite
AV28VirtualChannel.3.Alarm2.ThresholdVirtual channel 3 alarm 2 thresholdWrite
AV29VirtualChannel.4.Alarm1.ThresholdVirtual channel 4 alarm 1 thresholdWrite
AV30VirtualChannel.4.Alarm2.ThresholdVirtual channel 4 alarm 2 thresholdWrite
AV31VirtualChannel.5.Alarm1.ThresholdVirtual channel 5 alarm 1 thresholdWrite
AV32VirtualChannel.5.Alarm2.ThresholdVirtual channel 5 alarm 2 thresholdWrite
AV33VirtualChannel.6.Alarm1.ThresholdVirtual channel 6 alarm 1 thresholdWrite
AV34VirtualChannel.6.Alarm2.ThresholdVirtual channel 6 alarm 2 thresholdWrite
AV35VirtualChannel.7.Alarm1.ThresholdVirtual channel 7 alarm 1 thresholdWrite
AV36VirtualChannel.7.Alarm2.ThresholdVirtual channel 7 alarm 2 thresholdWrite
AV37VirtualChannel.8.Alarm1.ThresholdVirtual channel 8 alarm 1 thresholdWrite
AV38VirtualChannel.8.Alarm2.ThresholdVirtual channel 8 alarm 2 thresholdWrite
AV39VirtualChannel.9.Alarm1.ThresholdVirtual channel 9 alarm 1 thresholdWrite
AV40VirtualChannel.9.Alarm2.ThresholdVirtual channel 9 alarm 2 thresholdWrite
AV41VirtualChannel.10.Alarm1.ThresholdVirtual channel 10 alarm 1 thresholdWrite
AV42VirtualChannel.10.Alarm2.ThresholdVirtual channel 10 alarm 2 thresholdWrite
AV43VirtualChannel.11.Alarm1.ThresholdVirtual channel 11 alarm 1 thresholdWrite
AV44VirtualChannel.11.Alarm2.ThresholdVirtual channel 11 alarm 2 thresholdWrite
AV45VirtualChannel.12.Alarm1.ThresholdVirtual channel 12 alarm 1 thresholdWrite
AV46VirtualChannel.12.Alarm2.ThresholdVirtual channel 12 alarm 2 thresholdWrite
AV47VirtualChannel.13.Alarm1.ThresholdVirtual channel 13 alarm 1 thresholdWrite
AV48VirtualChannel.13.Alarm2.ThresholdVirtual channel 13 alarm 2 thresholdWrite
AV49VirtualChannel.14.Alarm1.ThresholdVirtual channel 14 alarm 1 thresholdWrite
AV50VirtualChannel.14.Alarm2.ThresholdVirtual channel 14 alarm 2 thresholdWrite
AV51VirtualChannel.15.Alarm1.ThresholdVirtual channel 15 alarm 1 thresholdWrite
AV52VirtualChannel.15.Alarm2.ThresholdVirtual channel 15 alarm 2 thresholdWrite
AV53UserParameter.1.AddressUser parameter 1 addressWrite
AV54UserParameter.1.ValueUser parameter 1 valueWrite
AV55UserParameter.2.AddressUser parameter 2 addressWrite
AV56UserParameter.2.ValueUser parameter 2 valueWrite
AV57UserParameter.3.AddressUser parameter 3 addressWrite
AV58UserParameter.3.ValueUser parameter 3 valueWrite
AV59UserParameter.4.AddressUser parameter 4 addressWrite
AV60UserParameter.4.ValueUser parameter 4 valueWrite
AV61UserParameter.5.AddressUser parameter 5 addressWrite
AV62UserParameter.5.ValueUser parameter 5 valueWrite
AV63UserParameter.6.AddressUser parameter 6 addressWrite
AV64UserParameter.6.ValueUser parameter 6 valueWrite
AV65UserParameter.7.AddressUser parameter 7 addressWrite
AV66UserParameter.7.ValueUser parameter 7 valueWrite
AV67UserParameter.8.AddressUser parameter 8 addressWrite
AV68UserParameter.8.ValueUser parameter 8 valueWrite
AV69UserParameter.9.AddressUser parameter 9 addressWrite
AV70UserParameter.9.ValueUser parameter 9 valueWrite
AV71UserParameter.10.AddressUser parameter 10 addressWrite
AV72UserParameter.10.ValueUser parameter 10 valueWrite
AV73UserParameter.11.AddressUser parameter 11 addressWrite
AV74UserParameter.11.ValueUser parameter 11 valueWrite
AV75UserParameter.12.AddressUser parameter 12 addressWrite
AV76UserParameter.12.ValueUser parameter 12 valueWrite
AV77UserParameter.13.AddressUser parameter 13 addressWrite
AV78UserParameter.13.ValueUser parameter 13 valueWrite
AV79UserParameter.14.AddressUser parameter 14 addressWrite
AV80UserParameter.14.ValueUser parameter 14 valueWrite
AV81UserParameter.15.AddressUser parameter 15 addressWrite
AV82UserParameter.15.ValueUser parameter 15 valueWrite
AV83UserParameter.16AddressUser parameter 16 addressWrite
AV84UserParameter.16.ValueUser parameter 16 valueWrite
AV85UserParameter.17.AddressUser parameter 17addressWrite
AV86UserParameter.17.ValueUser parameter 17 valueWrite
AV87UserParameter.18.AddressUser parameter 18 addressWrite
AV88UserParameter.18.ValueUser parameter 18 valueWrite
AV89UserParameter.19.AddressUser parameter 19 addressWrite
AV90UserParameter.19.ValueUser parameter 19 valueWrite
AV91UserParameter.20.AddressUser parameter 20 addressWrite
AV92UserParameter.20.ValueUser parameter 20 valueWrite
AV93UserParameter.21.AddressUser parameter 21 addressWrite
AV94UserParameter.21.ValueUser parameter 21 valueWrite
AV95UserParameter.22.AddressUser parameter 22 addressWrite
AV96UserParameter.22.ValueUser parameter 22 valueWrite
AV97UserParameter.23.AddressUser parameter 23 addressWrite
AV98UserParameter.23.ValueUser parameter 23 valueWrite
AV99UserParameter.24.AddressUser parameter 24 addressWrite
AV100UserParameter.24.ValueUser parameter 24 valueWrite
AV101UserParameter.25.AddressUser parameter 25 addressWrite
AV102UserParameter.25.ValueUser parameter 25 valueWrite
AV103UserParameter.26.AddressUser parameter 26 addressWrite
AV104UserParameter.26.ValueUser parameter 26 valueWrite
AV105UserParameter.27.AddressUser parameter 27 addressWrite
AV106UserParameter.27.ValueUser parameter 27 valueWrite
AV107UserParameter.28.AddressUser parameter 28 addressWrite
AV108UserParameter.28.ValueUser parameter 28 valueWrite
AV109UserParameter.29.AddressUser parameter 29 addressWrite
AV110UserParameter.29.ValueUser parameter 29 valueWrite
AV111UserParameter.30.AddressUser parameter 30 addressWrite
AV112UserParameter.30.ValueUser parameter 30 valueWrite
MImin1Channel.1.Alarm1.StatusChannel 1 alarm 1 statusRead
MImin2Channel.1.Alarm2.StatusChannel 1 alarm 2 statusRead
MI3Channel.2.Alarm1.StatusChannel 2 alarm 1 statusRead
MI4Channel.2.Alarm2.StatusChannel 2 alarm 2 statusRead
MI5Channel.3.Alarm1.StatusChannel 3 alarm 1 statusRead
MI6Channel.3.Alarm2.StatusChannel 3 alarm 2 statusRead
MI7Channel.4.Alarm1.StatusChannel 4 alarm 1 statusRead
MI8Channel.4.Alarm2.StatusChannel 4 alarm 2 statusRead
MI9VirtualChannel.1.Alarm1.StatusVirtual channel 1 alarm 1 statusRead
MI10VirtualChannel.1.Alarm2.StatusVirtual channel 1 alarm 2 statusRead
MI11VirtualChannel.2.Alarm1.StatusVirtual channel 2 alarm 1 statusRead
MI12VirtualChannel.2.Alarm2.StatusVirtual channel 2 alarm 2 statusRead
MI13VirtualChannel.3.Alarm1.StatusVirtual channel 3 alarm 1 statusRead
MI14VirtualChannel.3.Alarm2.StatusVirtual channel 3 alarm 2 statusRead
MI15VirtualChannel.4.Alarm1.StatusVirtual channel 4 alarm 1 statusRead
MI16VirtualChannel.4.Alarm2.StatusVirtual channel 4 alarm 2 statusRead
MI17VirtualChannel.5.Alarm1.StatusVirtual channel 5 alarm 1 statusRead
MI18VirtualChannel.5.Alarm2.StatusVirtual channel 5 alarm 2 statusRead
MI19VirtualChannel.6.Alarm1.StatusVirtual channel 6 alarm 1 statusRead
MI20VirtualChannel.6.Alarm2.StatusVirtual channel 6 alarm 2 statusRead
MI21VirtualChannel.7.Alarm1.StatusVirtual channel 7 alarm 1 statusRead
MI22VirtualChannel.7.Alarm2.StatusVirtual channel 7 alarm 2 statusRead
MI23VirtualChannel.8.Alarm1.StatusVirtual channel 8 alarm 1 statusRead
MI24VirtualChannel.8.Alarm2.StatusVirtual channel 8 alarm 2 statusRead
MI25VirtualChannel.9.Alarm1.StatusVirtual channel 9 alarm 1 statusRead
MI26VirtualChannel.9.Alarm2.StatusVirtual channel 9 alarm 2 statusRead
MI27VirtualChannel.10.Alarm1.StatusVirtual channel 10 alarm 1 statusRead
MI28VirtualChannel.10.Alarm2.StatusVirtual channel 10 alarm 2 statusRead
MI29VirtualChannel.11.Alarm1.StatusVirtual channel 11 alarm 1 statusRead
MI30VirtualChannel.11.Alarm2.StatusVirtual channel 11 alarm 2 statusRead
MI31VirtualChannel.12.Alarm1.StatusVirtual channel 12 alarm 1 statusRead
MI32VirtualChannel.12.Alarm2.StatusVirtual channel 12 alarm 2 statusRead
MI33VirtualChannel.13.Alarm1.StatusVirtual channel 13 alarm 1 statusRead
MI34VirtualChannel.13.Alarm2.StatusVirtual channel 13 alarm 2 statusRead
MI35VirtualChannel.14.Alarm1.StatusVirtual channel 14 alarm 1 statusRead
MI36VirtualChannel.14.Alarm2.StatusVirtual channel 14 alarm 2 statusRead
MI37VirtualChannel.15.Alarm1.StatusVirtual channel 15 alarm 1 statusRead
MI38VirtualChannel.15.Alarm2.StatusVirtual channel 15 alarm 2 statusRead
CSV1Loop.1.Setup.LoopNameLoop 1 nameRead
CSV2Loop.2.Setup.LoopNameLoop 2 nameRead
Object ID lookup: Eurotherm (Schneider Electric) nanodac recorder / controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the nanodac recorder / controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Eurotherm (Schneider Electric) nanodac recorder / controller

How many BACnet points does the Eurotherm (Schneider Electric) nanodac recorder / controller have?

This list has 210 BACnet objects: 51 analog inputs, 112 analog values, 7 binary inputs, 38 multi-state inputs, 2 characterstring values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Eurotherm (Schneider Electric) nanodac recorder / controller BACnet points are writable?

112 of the 210 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Eurotherm (Schneider Electric) nanodac recorder / controller BACnet documentation?

Eurotherm (Schneider Electric) does not publish it on its own website. This list comes from nanodac Recorder / Controller Protocol Implementation Conformance Statement (HA033110 Issue 1), revision 2017-09-12, a copy hosted by BACnet International product catalog at https://www.bacnetinternational.net/catalog/manu/eurotherm%20by%20schneider%20electric/HA033110_1_nanodac_BACnet_PICS_document.pdf. Ask Eurotherm (Schneider Electric) or its representative for the current revision.

What are the minimum BACnet points to integrate the Eurotherm (Schneider Electric) nanodac recorder / controller?

Start with AV 10 Loop.1.Main.TargetSP (Loop 1 target setpoint); AV 11 Loop.1.Main.AutoMan (Loop 1 auto / manual select); AV 12 Loop.1.OP.ManualOutVal (Loop 1 output in manual); AI 1 Channel.1.Main.PV (Channel 1 measured value); AI 2 Channel.2.Main.PV (Channel 2 measured value); AI 9 Loop.1.Main.TargetSP (Loop 1 working setpoint); AI 10 Loop.1.Main.ActiveOP (Loop 1 active output); MI 1 Channel.1.Alarm1.Status (Channel 1 alarm 1 state); MI 2 Channel.1.Alarm2.Status (Channel 1 alarm 2 state).

How do I check these points on the real nanodac recorder / controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Eurotherm (Schneider Electric) BACnet points lists

Source: nanodac Recorder / Controller Protocol Implementation Conformance Statement · HA033110 Issue 1 · rev. 2017-09-12. Object names, instances and units are reproduced as published; descriptions are our own.