EC fan network gateway (fan speed control) · BACnet points list

ebm-papst BACnet Gateway ECCN02-CT0 (EC fan network) BACnet points list

Updated 6 November 2026

Short answer

The ECCN02-CT0 gateway links up to 18 ebm-papst EC fans (addressed over Modbus RS-485 with EC-Control) to a BACnet IP (Ethernet, the default port) or BACnet MS/TP network. Once 'BMS Control' is switched on at the gateway and written to the fans, the BMS sets each fan's speed as a 0-100 % PWM value through one analog value per fan. The manual's BACnet table lists only these speed commands.

This page lists 18 BACnet objects for the ebm-papst BACnet Gateway ECCN02-CT0 (EC fan network) — 18 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ebm-papst’s own free documentation, linked below.

Manufacturer
ebm-papst
Model
BACnet Gateway ECCN02-CT0 (EC fan network)
Equipment
EC fan network gateway (fan speed control)
Equipment type
Other equipment
BACnet objects
18 (18 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
47000
Also known as
ECCN02-CT0, ECCN02, ebm-papst BACnet gateway, EC fan gateway, ECCN06-CT0
Source document
BACnet Gateway Manual - User Manual for ECCN02-CT0, ECCN06-CT0 · Version 1.0 · rev. 2021-01-28
Download CSV 18 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against ebm-papst’s current documentation and the live device before use. Not official ebm-papst information. Terms of use.

BMS integration notes: ebm-papst BACnet Gateway ECCN02-CT0 (EC fan network)

Integration in brief

Address the fans with EC-Control first, pick Ethernet TCP/IP (default) or MS/TP under Settings > BMS Config > Comm. Settings, set the IP or MS/TP parameters and reboot. Turn BMS MASTER on under Settings > BMS Config > BMS Control and write the values to the fans; then write each fan's PWM AV.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 180BAV0_FAN_1_BMS_PWMFan 1 speed command, 0-100 %Write
AV 181BAV0_FAN_1_BMS_PWMFan 2 speed command, 0-100 %Write

Enable & remote start

BMS control is switched on at the gateway (Settings > BMS Config > BMS Control > BMS MASTER = ON), then written into the fans with WRITE VALUES = YES. The fans then ignore their 0-10 V analog input and take the %PWM written over BACnet.

Network setup

Watch out for

ebm-papst BACnet Gateway ECCN02-CT0 (EC fan network) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

18 of 18 shown
Type
Analog
Show
ebm-papst BACnet Gateway ECCN02-CT0 (EC fan network) BACnet Points List
DescriptionStates
AVmin180BAV0_FAN_1_BMS_PWMFan 1 speed command (PWM), 0-100 %%Write
AVmin181BAV0_FAN_1_BMS_PWMFan 2 speed command (PWM), 0-100 %%Write
AV182BAV0_FAN_2_BMS_PWMFan 3 speed command (PWM), 0-100 %%Write
AV183BAV0_FAN_3_BMS_PWMFan 4 speed command (PWM), 0-100 %%Write
AV184BAV0_FAN_4_BMS_PWMFan 5 speed command (PWM), 0-100 %%Write
AV185BAV0_FAN_5_BMS_PWMFan 6 speed command (PWM), 0-100 %%Write
AV186BAV0_FAN_6_BMS_PWMFan 7 speed command (PWM), 0-100 %%Write
AV187BAV0_FAN_7_BMS_PWMFan 8 speed command (PWM), 0-100 %%Write
AV188BAV0_FAN_8_BMS_PWMFan 9 speed command (PWM), 0-100 %%Write
AV189BAV0_FAN_9_BMS_PWMFan 10 speed command (PWM), 0-100 %%Write
AV190BAV0_FAN_10_BMS_PWMFan 11 speed command (PWM), 0-100 %%Write
AV191BAV0_FAN_12_BMS_PWMFan 12 speed command (PWM), 0-100 %%Write
AV192BAV0_FAN_13_BMS_PWMFan 13 speed command (PWM), 0-100 %%Write
AV193BAV0_FAN_14_BMS_PWMFan 14 speed command (PWM), 0-100 %%Write
AV194BAV0_FAN_15_BMS_PWMFan 15 speed command (PWM), 0-100 %%Write
AV195BAV0_FAN_16_BMS_PWMFan 16 speed command (PWM), 0-100 %%Write
AV196BAV0_FAN_17_BMS_PWMFan 17 speed command (PWM), 0-100 %%Write
AV197BAV0_FAN_18_BMS_PWMFan 18 speed command (PWM), 0-100 %%Write
Object ID lookup: ebm-papst BACnet Gateway ECCN02-CT0 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BACnet Gateway ECCN02-CT0 (EC fan network) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the ebm-papst BACnet Gateway ECCN02-CT0 (EC fan network)

How many BACnet points does the ebm-papst BACnet Gateway ECCN02-CT0 (EC fan network) have?

This list has 18 BACnet objects: 18 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which ebm-papst BACnet Gateway ECCN02-CT0 (EC fan network) BACnet points are writable?

18 of the 18 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official ebm-papst BACnet Gateway ECCN02-CT0 (EC fan network) BACnet documentation?

The source is BACnet Gateway Manual - User Manual for ECCN02-CT0, ECCN06-CT0 (Version 1.0), revision 2021-01-28, published free by ebm-papst at https://www.ebmpapst.com/content/dam/ebm-papst/loc/apac/australia/operating-instructions/eccn-2---6/ECCN02_ECCN06_Manual.pdf.

What are the minimum BACnet points to integrate the ebm-papst BACnet Gateway ECCN02-CT0 (EC fan network)?

Start with AV 180 BAV0_FAN_1_BMS_PWM (Fan 1 speed command, 0-100 %); AV 181 BAV0_FAN_1_BMS_PWM (Fan 2 speed command, 0-100 %).

How do I enable BMS control of the ebm-papst BACnet Gateway ECCN02-CT0 (EC fan network)?

BMS control is switched on at the gateway (Settings > BMS Config > BMS Control > BMS MASTER = ON), then written into the fans with WRITE VALUES = YES. The fans then ignore their 0-10 V analog input and take the %PWM written over BACnet.

How do I check these points on the real BACnet Gateway ECCN02-CT0 (EC fan network)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More ebm-papst BACnet points lists

Source: BACnet Gateway Manual - User Manual for ECCN02-CT0, ECCN06-CT0 · Version 1.0 · rev. 2021-01-28. Object names, instances and units are reproduced as published; descriptions are our own.