- Home
- BACnet points lists
- EasyIO
- EasyIO FC-20 Controller (fixed BACnet object register)
Programmable I/O controller · BACnet points list
EasyIO FC-20 Controller (fixed BACnet object register) BACnet points list
Updated 7 November 2026
The FC-20 register lists the fixed BACnet objects the controller serves: 12 universal inputs (AI 1-12), 12 digital inputs (BI 1-12), 4 analog and 4 digital outputs, 64 analog value registers and 32 binary value registers for passing data to and from the program, and configuration objects for each input and output (signal type, scaling, offset, temperature table, digital on/off levels, linear and reverse settings, output interlock delays). What the registers mean depends on the program loaded in the controller.
This page lists 249 BACnet objects for the EasyIO FC-20 Controller (fixed BACnet object register) — 116 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from EasyIO’s own free documentation, linked below.
- Manufacturer
- EasyIO
- Model
- EasyIO FC-20 Controller (fixed BACnet object register)
- Equipment
- Programmable I/O controller
- Equipment type
- Other equipment
- BACnet objects
- 249 (116 writable)
- Transport
- —
- Firmware
- Not stated
- Also known as
- FC-20, FC20, EasyIO FC20, Johnson Controls EasyIO
- Source document
- EasyIO FC 20 BACnet Register · v1.3 · rev. 2018-01-17
Reference only, provided as-is: verify against EasyIO’s current documentation and the live device before use. Not official EasyIO information. Terms of use.
BMS integration notes: EasyIO FC-20 Controller (fixed BACnet object register)
Set each universal input type (MV 1-12) and analog output type (MV 13-16) to match the wiring, then read the inputs (AI 1-12, BI 1-12) and command the outputs (AO 1-4, BO 1-4) or exchange data with the program through the AV and BV registers.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 1 | DO 1 | Digital output 1 command | Command |
| AO 1 | AO 1 | Analog output 1 command | Command |
| AV 33 | AVOS 1 | First writable analog register to the program | Write |
| BV 18 | BO Reg 1 | First writable binary register to the program | Write |
| AI 1 | UI 1 | Universal input 1 value | Read |
| BI 1 | DI 1 | Digital input 1 state | Read |
| AV 1 | AVIS 1 | First read-only analog register from the program | Read |
Network setup
- UI n Type (MV 1-12): 1 = 0-10 V, 2 = 0-5 V, 3 = 0-20 mA, 4 = 4-20 mA, 5 = resistance, 6 = temperature sensor.
- AO n Type (MV 13-16): 1 = voltage, 2 = 0-20 mA, 3 = 4-20 mA.
Watch out for
- When a program in the controller drives an output, a BMS write to that output may be overwritten.
- The AV/BV registers carry no fixed meaning; get the program's point map from whoever wrote it.
EasyIO FC-20 Controller (fixed BACnet object register) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | UI 1 | Universal input 1 value | Read | ||
| AI | 2 | UI 2 | Universal input 2 value | Read | ||
| AI | 3 | UI 3 | Universal input 3 value | Read | ||
| AI | 4 | UI 4 | Universal input 4 value | Read | ||
| AI | 5 | UI 5 | Universal input 5 value | Read | ||
| AI | 6 | UI 6 | Universal input 6 value | Read | ||
| AI | 7 | UI 7 | Universal input 7 value | Read | ||
| AI | 8 | UI 8 | Universal input 8 value | Read | ||
| AI | 9 | UI 9 | Universal input 9 value | Read | ||
| AI | 10 | UI 10 | Universal input 10 value | Read | ||
| AI | 11 | UI 11 | Universal input 11 value | Read | ||
| AI | 12 | UI 12 | Universal input 12 value | Read | ||
| AOmin | 1 | AO 1 | Analog output 1 | Command | ||
| AO | 2 | AO 2 | Analog output 2 | Command | ||
| AO | 3 | AO 3 | Analog output 3 | Command | ||
| AO | 4 | AO 4 | Analog output 4 | Command | ||
| AVmin | 1 | AVIS 1 | Analog value register 1 (read only) | Read | ||
| AV | 2 | AVIS 2 | Analog value register 2 (read only) | Read | ||
| AV | 3 | AVIS 3 | Analog value register 3 (read only) | Read | ||
| AV | 4 | AVIS 4 | Analog value register 4 (read only) | Read | ||
| AV | 5 | AVIS 5 | Analog value register 5 (read only) | Read | ||
| AV | 6 | AVIS 6 | Analog value register 6 (read only) | Read | ||
| AV | 7 | AVIS 7 | Analog value register 7 (read only) | Read | ||
| AV | 8 | AVIS 8 | Analog value register 8 (read only) | Read | ||
| AV | 9 | AVIS 9 | Analog value register 9 (read only) | Read | ||
| AV | 10 | AVIS 10 | Analog value register 10 (read only) | Read | ||
| AV | 11 | AVIS 11 | Analog value register 11 (read only) | Read | ||
| AV | 12 | AVIS 12 | Analog value register 12 (read only) | Read | ||
| AV | 13 | AVIS 13 | Analog value register 13 (read only) | Read | ||
| AV | 14 | AVIS 14 | Analog value register 14 (read only) | Read | ||
| AV | 15 | AVIS 15 | Analog value register 15 (read only) | Read | ||
| AV | 16 | AVIS 16 | Analog value register 16 (read only) | Read | ||
| AV | 17 | AVIF 1 | Analog value register 1 (read only) | Read | ||
| AV | 18 | AVIF 2 | Analog value register 2 (read only) | Read | ||
| AV | 19 | AVIF 3 | Analog value register 3 (read only) | Read | ||
| AV | 20 | AVIF 4 | Analog value register 4 (read only) | Read | ||
| AV | 21 | AVIF 5 | Analog value register 5 (read only) | Read | ||
| AV | 22 | AVIF 6 | Analog value register 6 (read only) | Read | ||
| AV | 23 | AVIF 7 | Analog value register 7 (read only) | Read | ||
| AV | 24 | AVIF 8 | Analog value register 8 (read only) | Read | ||
| AV | 25 | AVIF 9 | Analog value register 9 (read only) | Read | ||
| AV | 26 | AVIF 10 | Analog value register 10 (read only) | Read | ||
| AV | 27 | AVIF 11 | Analog value register 11 (read only) | Read | ||
| AV | 28 | AVIF 12 | Analog value register 12 (read only) | Read | ||
| AV | 29 | AVIF 13 | Analog value register 13 (read only) | Read | ||
| AV | 30 | AVIF 14 | Analog value register 14 (read only) | Read | ||
| AV | 31 | AVIF 15 | Analog value register 15 (read only) | Read | ||
| AV | 32 | AVIF 16 | Analog value register 16 (read only) | Read | ||
| AVmin | 33 | AVOS 1 | Writable analog value register 1 | Write | ||
| AV | 34 | AVOS 2 | Writable analog value register 2 | Write | ||
| AV | 35 | AVOS 3 | Writable analog value register 3 | Write | ||
| AV | 36 | AVOS 4 | Writable analog value register 4 | Write | ||
| AV | 37 | AVOS 5 | Writable analog value register 5 | Write | ||
| AV | 38 | AVOS 6 | Writable analog value register 6 | Write | ||
| AV | 39 | AVOS 7 | Writable analog value register 7 | Write | ||
| AV | 40 | AVOS 8 | Writable analog value register 8 | Write | ||
| AV | 41 | AVOS 9 | Writable analog value register 9 | Write | ||
| AV | 42 | AVOS 10 | Writable analog value register 10 | Write | ||
| AV | 43 | AVOS 11 | Writable analog value register 11 | Write | ||
| AV | 44 | AVOS 12 | Writable analog value register 12 | Write | ||
| AV | 45 | AVOS 13 | Writable analog value register 13 | Write | ||
| AV | 46 | AVOS 14 | Writable analog value register 14 | Write | ||
| AV | 47 | AVOS 15 | Writable analog value register 15 | Write | ||
| AV | 48 | AVOS 16 | Writable analog value register 16 | Write | ||
| AV | 49 | AVOF 1 | Writable analog value register 1 | Write | ||
| AV | 50 | AVOF 2 | Writable analog value register 2 | Write | ||
| AV | 51 | AVOF 3 | Writable analog value register 3 | Write | ||
| AV | 52 | AVOF 4 | Writable analog value register 4 | Write | ||
| AV | 53 | AVOF 5 | Writable analog value register 5 | Write | ||
| AV | 54 | AVOF 6 | Writable analog value register 6 | Write | ||
| AV | 55 | AVOF 7 | Writable analog value register 7 | Write | ||
| AV | 56 | AVOF 8 | Writable analog value register 8 | Write | ||
| AV | 57 | AVOF 9 | Writable analog value register 9 | Write | ||
| AV | 58 | AVOF 10 | Writable analog value register 10 | Write | ||
| AV | 59 | AVOF 11 | Writable analog value register 11 | Write | ||
| AV | 60 | AVOF 12 | Writable analog value register 12 | Write | ||
| AV | 61 | AVOF 13 | Writable analog value register 13 | Write | ||
| AV | 62 | AVOF 14 | Writable analog value register 14 | Write | ||
| AV | 63 | AVOF 15 | Writable analog value register 15 | Write | ||
| AV | 64 | AVOF 16 | Writable analog value register 16 | Write | ||
| AV | 65 | UI 1 Scale Low | Input 1 scaling, low end | Read | ||
| AV | 66 | UI 2 Scale Low | Input 2 scaling, low end | Read | ||
| AV | 67 | UI 3 Scale Low | Input 3 scaling, low end | Read | ||
| AV | 68 | UI 4 Scale Low | Input 4 scaling, low end | Read | ||
| AV | 69 | UI 5 Scale Low | Input 5 scaling, low end | Read | ||
| AV | 70 | UI 6 Scale Low | Input 6 scaling, low end | Read | ||
| AV | 71 | UI 7 Scale Low | Input 7 scaling, low end | Read | ||
| AV | 72 | UI 8 Scale Low | Input 8 scaling, low end | Read | ||
| AV | 73 | UI 9 Scale Low | Input 9 scaling, low end | Read | ||
| AV | 74 | UI 10 Scale Low | Input 10 scaling, low end | Read | ||
| AV | 75 | UI 11 Scale Low | Input 11 scaling, low end | Read | ||
| AV | 76 | UI 12 Scale Low | Input 12 scaling, low end | Read | ||
| AV | 77 | UI 1 Scale High | Input 1 scaling, high end | Read | ||
| AV | 78 | UI 2 Scale High | Input 2 scaling, high end | Read | ||
| AV | 79 | UI 3 Scale High | Input 3 scaling, high end | Read | ||
| AV | 80 | UI 4 Scale High | Input 4 scaling, high end | Read | ||
| AV | 81 | UI 5 Scale High | Input 5 scaling, high end | Read | ||
| AV | 82 | UI 6 Scale High | Input 6 scaling, high end | Read | ||
| AV | 83 | UI 7 Scale High | Input 7 scaling, high end | Read | ||
| AV | 84 | UI 8 Scale High | Input 8 scaling, high end | Read | ||
| AV | 85 | UI 9 Scale High | Input 9 scaling, high end | Read | ||
| AV | 86 | UI 10 Scale High | Input 10 scaling, high end | Read | ||
| AV | 87 | UI 11 Scale High | Input 11 scaling, high end | Read | ||
| AV | 88 | UI 12 Scale High | Input 12 scaling, high end | Read | ||
| AV | 89 | UI 1 Offset | Input 1 calibration offset | Read | ||
| AV | 90 | UI 2 Offset | Input 2 calibration offset | Read | ||
| AV | 91 | UI 3 Offset | Input 3 calibration offset | Read | ||
| AV | 92 | UI 4 Offset | Input 4 calibration offset | Read | ||
| AV | 93 | UI 5 Offset | Input 5 calibration offset | Read | ||
| AV | 94 | UI 6 Offset | Input 6 calibration offset | Read | ||
| AV | 95 | UI 7 Offset | Input 7 calibration offset | Read | ||
| AV | 96 | UI 8 Offset | Input 8 calibration offset | Read | ||
| AV | 97 | UI 9 Offset | Input 9 calibration offset | Read | ||
| AV | 98 | UI 10 Offset | Input 10 calibration offset | Read | ||
| AV | 99 | UI 11 Offset | Input 11 calibration offset | Read | ||
| AV | 100 | UI 12 Offset | Input 12 calibration offset | Read | ||
| AV | 101 | UI 1 TempTable | Input 1 temperature sensor table number | Write | ||
| AV | 102 | UI 2 TempTable | Input 2 temperature sensor table number | Write | ||
| AV | 103 | UI 3 TempTable | Input 3 temperature sensor table number | Write | ||
| AV | 104 | UI 4 TempTable | Input 4 temperature sensor table number | Write | ||
| AV | 105 | UI 5 TempTable | Input 5 temperature sensor table number | Write | ||
| AV | 106 | UI 6 TempTable | Input 6 temperature sensor table number | Write | ||
| AV | 107 | UI 7 TempTable | Input 7 temperature sensor table number | Write | ||
| AV | 108 | UI 8 TempTable | Input 8 temperature sensor table number | Write | ||
| AV | 109 | UI 9 TempTable | Input 9 temperature sensor table number | Write | ||
| AV | 110 | UI 10 TempTable | Input 10 temperature sensor table number | Write | ||
| AV | 111 | UI 11 TempTable | Input 11 temperature sensor table number | Write | ||
| AV | 112 | UI 12 TempTable | Input 12 temperature sensor table number | Write | ||
| AV | 113 | UI 1 DI On Lvl | Input 1 level that reads as digital on | Read | ||
| AV | 114 | UI 2 DI On Lvl | Input 2 level that reads as digital on | Read | ||
| AV | 115 | UI 3 DI On Lvl | Input 3 level that reads as digital on | Read | ||
| AV | 116 | UI 4 DI On Lvl | Input 4 level that reads as digital on | Read | ||
| AV | 117 | UI 5 DI On Lvl | Input 5 level that reads as digital on | Read | ||
| AV | 118 | UI 6 DI On Lvl | Input 6 level that reads as digital on | Read | ||
| AV | 119 | UI 7 DI On Lvl | Input 7 level that reads as digital on | Read | ||
| AV | 120 | UI 8 DI On Lvl | Input 8 level that reads as digital on | Read | ||
| AV | 121 | UI 9 DI On Lvl | Input 9 level that reads as digital on | Read | ||
| AV | 122 | UI 10 DI On Lvl | Input 10 level that reads as digital on | Read | ||
| AV | 123 | UI 11 DI On Lvl | Input 11 level that reads as digital on | Read | ||
| AV | 124 | UI 12 DI On Lvl | Input 12 level that reads as digital on | Read | ||
| AV | 125 | UI 1 DI Off Lvl | Input 1 level that reads as digital off | Read | ||
| AV | 126 | UI 2 DI Off Lvl | Input 2 level that reads as digital off | Read | ||
| AV | 127 | UI 3 DI Off Lvl | Input 3 level that reads as digital off | Read | ||
| AV | 128 | UI 4 DI Off Lvl | Input 4 level that reads as digital off | Read | ||
| AV | 129 | UI 5 DI Off Lvl | Input 5 level that reads as digital off | Read | ||
| AV | 130 | UI 6 DI Off Lvl | Input 6 level that reads as digital off | Read | ||
| AV | 131 | UI 7 DI Off Lvl | Input 7 level that reads as digital off | Read | ||
| AV | 132 | UI 8 DI Off Lvl | Input 8 level that reads as digital off | Read | ||
| AV | 133 | UI 9 DI Off Lvl | Input 9 level that reads as digital off | Read | ||
| AV | 134 | UI 10 DI Off Lvl | Input 10 level that reads as digital off | Read | ||
| AV | 135 | UI 11 DI Off Lvl | Input 11 level that reads as digital off | Read | ||
| AV | 136 | UI 12 DI Off Lvl | Input 12 level that reads as digital off | Read | ||
| AV | 137 | AO 1 Scale Low | Output 1 scaling, low end | Write | ||
| AV | 138 | AO 2 Scale Low | Output 2 scaling, low end | Write | ||
| AV | 139 | AO 3 Scale Low | Output 3 scaling, low end | Write | ||
| AV | 140 | AO 4 Scale Low | Output 4 scaling, low end | Write | ||
| AV | 141 | AO 1 Scale High | Output 1 scaling, high end | Write | ||
| AV | 142 | AO 2 Scale High | Output 2 scaling, high end | Write | ||
| AV | 143 | AO 3 Scale High | Output 3 scaling, high end | Write | ||
| AV | 144 | AO 4 Scale High | Output 4 scaling, high end | Write | ||
| AV | 145 | DO 1 Inter delay | Digital output 1 interlock delay | Write | ||
| AV | 146 | DO 2 Inter delay | Digital output 2 interlock delay | Write | ||
| AV | 147 | DO 3 Inter delay | Digital output 3 interlock delay | Write | ||
| AV | 148 | DO 4 Inter delay | Digital output 4 interlock delay | Write | ||
| BImin | 1 | DI 1 | Digital input 1 state | Read | ||
| BI | 2 | DI 2 | Digital input 2 state | Read | ||
| BI | 3 | DI 3 | Digital input 3 state | Read | ||
| BI | 4 | DI 4 | Digital input 4 state | Read | ||
| BI | 5 | DI 5 | Digital input 5 state | Read | ||
| BI | 6 | DI 6 | Digital input 6 state | Read | ||
| BI | 7 | DI 7 | Digital input 7 state | Read | ||
| BI | 8 | DI 8 | Digital input 8 state | Read | ||
| BI | 9 | DI9 | Read | |||
| BI | 10 | DI 10 | Digital input 10 state | Read | ||
| BI | 11 | DI 11 | Digital input 11 state | Read | ||
| BI | 12 | DI 12 | Digital input 12 state | Read | ||
| BOmin | 1 | DO 1 | Digital output 1 | Command | ||
| BO | 2 | DO 2 | Digital output 2 | Command | ||
| BO | 3 | DO 3 | Digital output 3 | Command | ||
| BO | 4 | DO 4 | Digital output 4 | Command | ||
| BV | 1 | Reserve | Reserved | Read | ||
| BV | 2 | BI Reg 1 | Binary value register 1 (read only) | Read | ||
| BV | 3 | BI Reg 2 | Binary value register 2 (read only) | Read | ||
| BV | 4 | BI Reg 3 | Binary value register 3 (read only) | Read | ||
| BV | 5 | BI Reg 4 | Binary value register 4 (read only) | Read | ||
| BV | 6 | BI Reg 5 | Binary value register 5 (read only) | Read | ||
| BV | 7 | BI Reg 6 | Binary value register 6 (read only) | Read | ||
| BV | 8 | BI Reg 7 | Binary value register 7 (read only) | Read | ||
| BV | 9 | BI Reg 8 | Binary value register 8 (read only) | Read | ||
| BV | 10 | BI Reg 9 | Binary value register 9 (read only) | Read | ||
| BV | 11 | BI Reg 10 | Binary value register 10 (read only) | Read | ||
| BV | 12 | BI Reg 11 | Binary value register 11 (read only) | Read | ||
| BV | 13 | BI Reg 12 | Binary value register 12 (read only) | Read | ||
| BV | 14 | BI Reg 13 | Binary value register 13 (read only) | Read | ||
| BV | 15 | BI Reg 14 | Binary value register 14 (read only) | Read | ||
| BV | 16 | BI Reg 15 | Binary value register 15 (read only) | Read | ||
| BV | 17 | BI Reg 16 | Binary value register 16 (read only) | Read | ||
| BVmin | 18 | BO Reg 1 | Writable binary value register 1 | Write | ||
| BV | 19 | BO Reg 2 | Writable binary value register 2 | Write | ||
| BV | 20 | BO Reg 3 | Writable binary value register 3 | Write | ||
| BV | 21 | BO Reg 4 | Writable binary value register 4 | Write | ||
| BV | 22 | BO Reg 5 | Writable binary value register 5 | Write | ||
| BV | 23 | BO Reg 6 | Writable binary value register 6 | Write | ||
| BV | 24 | BO Reg 7 | Writable binary value register 7 | Write | ||
| BV | 25 | BO Reg 8 | Writable binary value register 8 | Write | ||
| BV | 26 | BO Reg 9 | Writable binary value register 9 | Write | ||
| BV | 27 | BO Reg 10 | Writable binary value register 10 | Write | ||
| BV | 28 | BO Reg 11 | Writable binary value register 11 | Write | ||
| BV | 29 | BO Reg 12 | Writable binary value register 12 | Write | ||
| BV | 30 | BO Reg 13 | Writable binary value register 13 | Write | ||
| BV | 31 | BO Reg 14 | Writable binary value register 14 | Write | ||
| BV | 32 | BO Reg 15 | Writable binary value register 15 | Write | ||
| BV | 33 | BO Reg 16 | Writable binary value register 16 | Write | ||
| BV | 34 | UI 1 Linear | Input 1 linear scaling enable | Write | ||
| BV | 35 | UI 2 Linear | Input 2 linear scaling enable | Write | ||
| BV | 36 | UI 3 Linear | Input 3 linear scaling enable | Write | ||
| BV | 37 | UI 4 Linear | Input 4 linear scaling enable | Write | ||
| BV | 38 | UI 5 Linear | Input 5 linear scaling enable | Write | ||
| BV | 39 | UI 6 Linear | Input 6 linear scaling enable | Write | ||
| BV | 40 | UI 7 Linear | Input 7 linear scaling enable | Write | ||
| BV | 41 | UI 8 Linear | Input 8 linear scaling enable | Write | ||
| BV | 42 | UI 9 Linear | Input 9 linear scaling enable | Write | ||
| BV | 43 | UI 10 Linear | Input 10 linear scaling enable | Write | ||
| BV | 44 | UI 11 Linear | Input 11 linear scaling enable | Write | ||
| BV | 45 | UI 12 Linear | Input 12 linear scaling enable | Write | ||
| BV | 46 | AO 1 Linear | Output 1 linear scaling enable | Write | ||
| BV | 47 | AO 2 Linear | Output 2 linear scaling enable | Write | ||
| BV | 48 | AO 3 Linear | Output 3 linear scaling enable | Write | ||
| BV | 49 | AO 4 Linear | Output 4 linear scaling enable | Write | ||
| BV | 50 | AO 1 Reverse | Output 1 reverse acting | Write | ||
| BV | 51 | AO 2 Reverse | Output 2 reverse acting | Write | ||
| BV | 52 | AO 3 Reverse | Output 3 reverse acting | Write | ||
| BV | 53 | AO 4 Reverse | Output 4 reverse acting | Write | ||
| MV | 1 | UI 1 Type | Input 1 signal type | Write | 1=0-10V, 2=0-5V, 3=0-20mA, 4=4-20mA, 5=Resistance, 6=Temperature Sensor | |
| MV | 2 | UI 2 Type | Input 2 signal type | Write | 1=0-10V, 2=0-5V, 3=0-20mA, 4=4-20mA, 5=Resistance, 6=Temperature Sensor | |
| MV | 3 | UI 3 Type | Input 3 signal type | Write | 1=0-10V, 2=0-5V, 3=0-20mA, 4=4-20mA, 5=Resistance, 6=Temperature Sensor | |
| MV | 4 | UI 4 Type | Input 4 signal type | Write | 1=0-10V, 2=0-5V, 3=0-20mA, 4=4-20mA, 5=Resistance, 6=Temperature Sensor | |
| MV | 5 | UI 5 Type | Input 5 signal type | Write | 1=0-10V, 2=0-5V, 3=0-20mA, 4=4-20mA, 5=Resistance, 6=Temperature Sensor | |
| MV | 6 | UI 6 Type | Input 6 signal type | Write | 1=0-10V, 2=0-5V, 3=0-20mA, 4=4-20mA, 5=Resistance, 6=Temperature Sensor | |
| MV | 7 | UI 7 Type | Input 7 signal type | Write | 1=0-10V, 2=0-5V, 3=0-20mA, 4=4-20mA, 5=Resistance, 6=Temperature Sensor | |
| MV | 8 | UI 8 Type | Input 8 signal type | Write | 1=0-10V, 2=0-5V, 3=0-20mA, 4=4-20mA, 5=Resistance, 6=Temperature Sensor | |
| MV | 9 | UI 9 Type | Input 9 signal type | Write | 1=0-10V, 2=0-5V, 3=0-20mA, 4=4-20mA, 5=Resistance, 6=Temperature Sensor | |
| MV | 10 | UI 10 Type | Input 10 signal type | Write | 1=0-10V, 2=0-5V, 3=0-20mA, 4=4-20mA, 5=Resistance, 6=Temperature Sensor | |
| MV | 11 | UI 11 Type | Input 11 signal type | Write | 1=0-10V, 2=0-5V, 3=0-20mA, 4=4-20mA, 5=Resistance, 6=Temperature Sensor | |
| MV | 12 | UI 12 Type | Input 12 signal type | Write | 1=0-10V, 2=0-5V, 3=0-20mA, 4=4-20mA, 5=Resistance, 6=Temperature Sensor | |
| MV | 13 | AO 1 Type | Output 1 signal type | Write | 1=Voltage, 2=Current 0-20mA, 3=Current 4-20mA | |
| MV | 14 | AO 2 Type | Output 2 signal type | Write | 1=Voltage, 2=Current 0-20mA, 3=Current 4-20mA | |
| MV | 15 | AO 3 Type | Output 3 signal type | Write | 1=Voltage, 2=Current 0-20mA, 3=Current 4-20mA | |
| MV | 16 | AO 4 Type | Output 4 signal type | Write | 1=Voltage, 2=Current 0-20mA, 3=Current 4-20mA |
No points match these filters.
Object ID lookup: EasyIO EasyIO FC-20 point IDs by name
AI1UI 1AI2UI 2AI3UI 3AI4UI 4AI5UI 5AI6UI 6AI7UI 7AI8UI 8AI9UI 9AI10UI 10AI11UI 11AI12UI 12AO1AO 1AO2AO 2AO3AO 3AO4AO 4AV1AVIS 1AV2AVIS 2AV3AVIS 3AV4AVIS 4AV5AVIS 5AV6AVIS 6AV7AVIS 7AV8AVIS 8AV9AVIS 9AV10AVIS 10AV11AVIS 11AV12AVIS 12AV13AVIS 13AV14AVIS 14AV15AVIS 15AV16AVIS 16AV17AVIF 1AV18AVIF 2AV19AVIF 3AV20AVIF 4AV21AVIF 5AV22AVIF 6AV23AVIF 7AV24AVIF 8AV25AVIF 9AV26AVIF 10AV27AVIF 11AV28AVIF 12AV29AVIF 13AV30AVIF 14AV31AVIF 15AV32AVIF 16AV33AVOS 1AV34AVOS 2AV35AVOS 3AV36AVOS 4AV37AVOS 5AV38AVOS 6AV39AVOS 7AV40AVOS 8AV41AVOS 9AV42AVOS 10AV43AVOS 11AV44AVOS 12AV45AVOS 13AV46AVOS 14AV47AVOS 15AV48AVOS 16AV49AVOF 1AV50AVOF 2AV51AVOF 3AV52AVOF 4AV53AVOF 5AV54AVOF 6AV55AVOF 7AV56AVOF 8AV57AVOF 9AV58AVOF 10AV59AVOF 11AV60AVOF 12AV61AVOF 13AV62AVOF 14AV63AVOF 15AV64AVOF 16AV65UI 1 Scale LowAV66UI 2 Scale LowAV67UI 3 Scale LowAV68UI 4 Scale LowAV69UI 5 Scale LowAV70UI 6 Scale LowAV71UI 7 Scale LowAV72UI 8 Scale LowAV73UI 9 Scale LowAV74UI 10 Scale LowAV75UI 11 Scale LowAV76UI 12 Scale LowAV77UI 1 Scale HighAV78UI 2 Scale HighAV79UI 3 Scale HighAV80UI 4 Scale HighAV81UI 5 Scale HighAV82UI 6 Scale HighAV83UI 7 Scale HighAV84UI 8 Scale HighAV85UI 9 Scale HighAV86UI 10 Scale HighAV87UI 11 Scale HighAV88UI 12 Scale HighAV89UI 1 OffsetAV90UI 2 OffsetAV91UI 3 OffsetAV92UI 4 OffsetAV93UI 5 OffsetAV94UI 6 OffsetAV95UI 7 OffsetAV96UI 8 OffsetAV97UI 9 OffsetAV98UI 10 OffsetAV99UI 11 OffsetAV100UI 12 OffsetAV101UI 1 TempTableAV102UI 2 TempTableAV103UI 3 TempTableAV104UI 4 TempTableAV105UI 5 TempTableAV106UI 6 TempTableAV107UI 7 TempTableAV108UI 8 TempTableAV109UI 9 TempTableAV110UI 10 TempTableAV111UI 11 TempTableAV112UI 12 TempTableAV113UI 1 DI On LvlAV114UI 2 DI On LvlAV115UI 3 DI On LvlAV116UI 4 DI On LvlAV117UI 5 DI On LvlAV118UI 6 DI On LvlAV119UI 7 DI On LvlAV120UI 8 DI On LvlAV121UI 9 DI On LvlAV122UI 10 DI On LvlAV123UI 11 DI On LvlAV124UI 12 DI On LvlAV125UI 1 DI Off LvlAV126UI 2 DI Off LvlAV127UI 3 DI Off LvlAV128UI 4 DI Off LvlAV129UI 5 DI Off LvlAV130UI 6 DI Off LvlAV131UI 7 DI Off LvlAV132UI 8 DI Off LvlAV133UI 9 DI Off LvlAV134UI 10 DI Off LvlAV135UI 11 DI Off LvlAV136UI 12 DI Off LvlAV137AO 1 Scale LowAV138AO 2 Scale LowAV139AO 3 Scale LowAV140AO 4 Scale LowAV141AO 1 Scale HighAV142AO 2 Scale HighAV143AO 3 Scale HighAV144AO 4 Scale HighAV145DO 1 Inter delayAV146DO 2 Inter delayAV147DO 3 Inter delayAV148DO 4 Inter delayBI1DI 1BI2DI 2BI3DI 3BI4DI 4BI5DI 5BI6DI 6BI7DI 7BI8DI 8BI9DI9BI10DI 10BI11DI 11BI12DI 12BO1DO 1BO2DO 2BO3DO 3BO4DO 4BV1ReserveBV2BI Reg 1BV3BI Reg 2BV4BI Reg 3BV5BI Reg 4BV6BI Reg 5BV7BI Reg 6BV8BI Reg 7BV9BI Reg 8BV10BI Reg 9BV11BI Reg 10BV12BI Reg 11BV13BI Reg 12BV14BI Reg 13BV15BI Reg 14BV16BI Reg 15BV17BI Reg 16BV18BO Reg 1BV19BO Reg 2BV20BO Reg 3BV21BO Reg 4BV22BO Reg 5BV23BO Reg 6BV24BO Reg 7BV25BO Reg 8BV26BO Reg 9BV27BO Reg 10BV28BO Reg 11BV29BO Reg 12BV30BO Reg 13BV31BO Reg 14BV32BO Reg 15BV33BO Reg 16BV34UI 1 LinearBV35UI 2 LinearBV36UI 3 LinearBV37UI 4 LinearBV38UI 5 LinearBV39UI 6 LinearBV40UI 7 LinearBV41UI 8 LinearBV42UI 9 LinearBV43UI 10 LinearBV44UI 11 LinearBV45UI 12 LinearBV46AO 1 LinearBV47AO 2 LinearBV48AO 3 LinearBV49AO 4 LinearBV50AO 1 ReverseBV51AO 2 ReverseBV52AO 3 ReverseBV53AO 4 ReverseMV1UI 1 TypeMV2UI 2 TypeMV3UI 3 TypeMV4UI 4 TypeMV5UI 5 TypeMV6UI 6 TypeMV7UI 7 TypeMV8UI 8 TypeMV9UI 9 TypeMV10UI 10 TypeMV11UI 11 TypeMV12UI 12 TypeMV13AO 1 TypeMV14AO 2 TypeMV15AO 3 TypeMV16AO 4 Type
Integration notes
- AVIS/AVIF (AV 1-32) and BI Reg (BV 2-17) are read-only registers; AVOS/AVOF (AV 33-64) and BO Reg (BV 18-33) are writable. Their meaning is set by the controller program.
- The register shows multistate objects as MSV; they are listed here as MV. The change log says the multistate objects became read/write in January 2015.
- The UI scaling, offset and DI level AVs are marked read only in the register, while the TempTable, AO scaling and DO delay AVs are read/write.
- The register does not state the BACnet transport or device instance.
- The register is published by EasyIO on the Johnson Controls documentation site.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EasyIO FC-20 Controller (fixed BACnet object register) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the EasyIO FC-20 Controller (fixed BACnet object register)
How many BACnet points does the EasyIO FC-20 Controller (fixed BACnet object register) have?
This list has 249 BACnet objects: 12 analog inputs, 4 analog outputs, 148 analog values, 12 binary inputs, 4 binary outputs, 53 binary values, 16 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which EasyIO FC-20 Controller (fixed BACnet object register) BACnet points are writable?
116 of the 249 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official EasyIO FC-20 Controller (fixed BACnet object register) BACnet documentation?
The source is EasyIO FC 20 BACnet Register (v1.3), revision 2018-01-17, published free by EasyIO at https://docs.johnsoncontrols.com/bas/api/khub/documents/BrE3~ppu1b~p2ibfJarlEQ/content.
What are the minimum BACnet points to integrate the EasyIO FC-20 Controller (fixed BACnet object register)?
Start with BO 1 DO 1 (Digital output 1 command); AO 1 AO 1 (Analog output 1 command); AV 33 AVOS 1 (First writable analog register to the program); BV 18 BO Reg 1 (First writable binary register to the program); AI 1 UI 1 (Universal input 1 value); BI 1 DI 1 (Digital input 1 state); AV 1 AVIS 1 (First read-only analog register from the program).
How do I check these points on the real EasyIO FC-20 Controller (fixed BACnet object register)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More EasyIO BACnet points lists
- I/O module
EasyIO FD-20i I/O Module (BACnet objects)
The EasyIO FD-20i: 10 analog (thermistor) inputs and 20 digital inputs, with per-input resistance, offset and temperature table objects.
Also known as: FD-20i, FD20i, EasyIO FD20i, Johnson Controls EasyIO - VAV terminal unit controller
EasyIO FW-08V VAV Controller (pre-built VAV application)
VAV boxes (cooling only, electric or hot water reheat, parallel or series fan) and pressure-dependent VVT zone dampers run by the EasyIO FW-08V with its factory VAV application.
Also known as: FW-08V, FW08V, EasyIO FW-08V, EasyIoUnivVAV, Johnson Controls EasyIO
Source: EasyIO FC 20 BACnet Register · v1.3 · rev. 2018-01-17. Object names, instances and units are reproduced as published; descriptions are our own.