Fan coil / terminal unit controller (preloaded application) · BACnet points list
Distech Controls ECY-PTU-107 preloaded applications BACnet points list
Updated 7 November 2026
The ECY-PTU-107 is a Distech Controls Eclypse terminal unit controller on BACnet IP that ships with preloaded fan coil, chilled beam/ceiling and heat pump applications, plus lighting and sunblind control. The preloaded program exposes a fixed set of value objects for setpoints, occupancy, mode, fan, valve, light and blind control. It is configured from the controller's web pages or the EC-gfxProgram Configuration Assistant.
This page lists 151 BACnet objects for the Distech Controls ECY-PTU-107 preloaded applications — 115 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Distech Controls’s own free documentation, linked below.
- Manufacturer
- Distech Controls
- Model
- ECY-PTU-107 preloaded applications
- Equipment
- Fan coil / terminal unit controller (preloaded application)
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 151 (115 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- ECY-PTU-107, Eclypse ECY-PTU-107
Reference only, provided as-is: verify against Distech Controls’s current documentation and the live device before use. Not official Distech Controls information. Terms of use.
BMS integration notes: Distech Controls ECY-PTU-107 preloaded applications
Command occupancy with MV 2 and the mode with MV 1, write the occupied setpoints AV 40 and AV 41, and read back MV 14, MV 11, AV 1 and MV 16. Leave MV 3 at Auto unless the BMS should pick the fan speed.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 2 | OccupancyCmd | Occupancy command from the BMS | Write |
| MV 1 | HvacModeCmd | HVAC mode command (auto, heat, cool, off) | Write |
| MV 3 | FanSpeedCmd | Fan speed command (auto, off, low, med, high) | Write |
| AV 40 | OccCoolSp | Occupied cooling setpoint | Write |
| AV 41 | OccHeatSp | Occupied heating setpoint | Write |
| MV 14 | OccupancyStatus | Effective occupancy state | Read |
| MV 11 | HvacModeStatus | Actual HVAC mode | Read |
| AV 1 | SpaceTemp | Space temperature used for control | Read |
| MV 16 | FanSpeedSt | Actual fan speed | Read |
| BV 2 | CondSensorSt | Condensation alarm; cooling valve closes | Read |
Enable & remote start
Write MV 2 OccupancyCmd for occupancy and MV 1 HvacModeCmd for the mode; any value other than Auto forces the unit into that mode. MV 3 FanSpeedCmd set to Auto leaves the fan to the control loop.
Sensors & values from the BMS
The guide says AV 1 SpaceTemp and other measured values can be overridden through the BACnet priority array (it calls this a testing feature). MV 5 MotionSensor can be written from the network; the guide says to use a priority lower than 14 to override local control.
Network setup
- Eclypse controllers connect over Ethernet; the guide reaches the configuration pages through the controller's IP address or factory host name.
- Master/slave and remote light/blind groups use room numbers (AV 81 CtrlRoom and the light/blind room values).
Watch out for
- Temperatures are in °C in this guide.
- Configuration values (system type, valve and fan types) are commissioning settings; don't write them cyclically.
Distech Controls ECY-PTU-107 preloaded applications BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 1 | SpaceTemp | Range -10 to 50 °C | °C | Read | |
| AV | 2 | CoolingValveCtrl | Range 0 to 100% | % | Read | |
| AV | 3 | HeatingValveCtrl | Range 0 to 100% | % | Read | |
| AV | 4 | SpaceCO2 | ppm | Read | ||
| AV | 5 | ElectHeatCtrl | Range 0 to 100% | % | Read | |
| AV | 6 | SpaceTempSI4 | Range -10 to 50 °C | °C | Read | |
| AV | 7 | DischargeTemp | °C | Read | ||
| AV | 8 | ReturnTemp | °C | Read | ||
| AV | 9 | WaterTemp | °C | Read | ||
| AV | 10 | SpOffsetUI2 | Range -5 to 5 °C | °C | Read | |
| AV | 11 | MidSetpoint | °C | Read | ||
| AV | 14 | OptStartCoolFactor | min | Write | ||
| AV | 15 | OptStartHeatFactor | min | Write | ||
| AV | 17 | OptStartMaxStartupTime | min | Write | ||
| AV | 18 | OptStartFactorWeight | Range 1 to 99% | % | Write | |
| AV | 19 | APARStartupDelay | min | Write | ||
| AV | 20 | ModeActivDelay | min | Write | ||
| AV | 21 | RuleActiveDelay | min | Write | ||
| AV | 22 | ActiveRules | Read | |||
| AV | 26 | ElectHeatStatus | Range 0 to 100% | % | Read | |
| AV | 27 | SpOffsetRange | Range 0 to 10°K | K | Write | |
| AV | 28 | SetPtOffset | Range -10 to 10°K | K | Read | |
| AV | 30 | SpaceTempOffset | Range -5 to 5°K | K | Write | |
| AV | 31 | FloatingDriveTime | s | Write | ||
| AV | 33 | EffectSp | °C | Read | ||
| AV | 34 | SpaceHumidity | Range 0 to 100% | %RH | Read | |
| AV | 35 | FreezeProtSp | °C | Write | ||
| AV | 36 | ActCoolSp | °C | Read | ||
| AV | 37 | ActHeatSp | °C | Read | ||
| AV | 38 | UnoccCoolSp | °C | Write | ||
| AV | 39 | StandbyCoolSp | °C | Write | ||
| AVmin | 40 | OccCoolSp | °C | Write | ||
| AVmin | 41 | OccHeatSp | °C | Write | ||
| AV | 42 | StandbyHeatSp | °C | Write | ||
| AV | 43 | UnoccHeatSp | °C | Write | ||
| AV | 44 | TerminalLoad | Range -100 to 100% | % | Read | |
| AV | 45 | SensorSleepTime | s | Write | ||
| AV | 46 | ChgOverDelay | min | Write | ||
| AV | 47 | HoldTime | s | Write | ||
| AV | 48 | ByPassTime | min | Write | ||
| AV | 52 | WaterSpHeat | °C | Write | ||
| AV | 53 | WaterSpCool | °C | Write | ||
| AV | 54 | MaxDischAirSp | °C | Write | ||
| AV | 55 | MinDischAirSp | °C | Write | ||
| AV | 56 | BlindTransCmd | Range 0 to 100% | % | Write | |
| AV | 57 | BlindRotCmd | Range 0 to 360 deg | ° | Write | |
| AV | 58 | AuxHeatEnable | Range 0 to 100% | % | Write | |
| AV | 59 | ElectheatPeriod | Range 60 to 300 s | s | Write | |
| AV | 60 | FanOffDelay | s | Write | ||
| AV | 61 | FanCoolLow | Range 0 to 100% | % | Write | |
| AV | 62 | FanHeatLow | Range 0 to 100% | % | Write | |
| AV | 63 | CoolMaxFan | Range 0 to 100% | % | Write | |
| AV | 64 | HeatMaxFan | Range 0 to 100% | % | Write | |
| AV | 65 | CoolMinFan | Range 0 to 100% | % | Write | |
| AV | 66 | HeatMinFan | Range 0 to 100% | % | Write | |
| AV | 69 | VlvExerciseDelay | days | Write | ||
| AV | 70 | VlvExerciseUnoccDelay | h | Write | ||
| AV | 71 | Light1Room | Write | |||
| AV | 74 | Light4Room | Write | |||
| AV | 75 | Sblnd1Room | Write | |||
| AV | 76 | Sblnd2Room | Write | |||
| AV | 77 | Sblnd3Room | Write | |||
| AV | 78 | Sblnd4Room | Write | |||
| AV | 79 | VlvExerciseCycle | s | Write | ||
| AV | 80 | Elevation | m | Write | ||
| AV | 81 | CtrlRoom | Range 0 to 127 | Write | ||
| AV | 82 | UnoccTranslation | % | Write | ||
| AV | 83 | OccTranslation | Range 0 to 100% | % | Write | |
| AV | 84 | UnoccRotation | ° | Write | ||
| AV | 85 | OccRotation | Range -90 to 90 deg | ° | Write | |
| AV | 86 | InfraRedZone | Range 0 to 12 | Write | ||
| AV | 87 | BlindCtrlInfo | Read | |||
| AV | 88 | LightCtrlInfo | Read | |||
| AV | 89 | RemoteCtrlInfo | Read | |||
| AV | 90 | MasterInfo | Read | |||
| AV | 91 | SlaveInfo | Read | |||
| AV | 92 | SendSpaceTempCO2 | Read | |||
| AV | 93 | LuxSetpoint | lux | Write | ||
| AV | 94 | ReflexFactor | Write | |||
| AV | 95 | LightPower | lux | Write | ||
| AV | 96 | MinLightCmd | % | Write | ||
| AV | 97 | LightOffset | lux | Write | ||
| AV | 98 | LuxRampUpTime | s | Write | ||
| AV | 99 | LuxRampDownTime | s | Write | ||
| BV | 1 | WindowStatus | Read | Open/Close | ||
| BVmin | 2 | CondSensorSt | Read | Alarm/Normal | ||
| BV | 3 | WindowContact | Default Close | Read | Open/close | |
| BV | 4 | AuxContact | Default Off | Read | On/Off | |
| BV | 5 | ChgOverSt | Default Cool | Read | Heat/Cool | |
| BV | 11 | MS1.Occupancy | Default Unoccupied | Write | Occupied/Unoccupied | |
| BV | 12 | RoomOccupancy | Default Unoccupied | Read | Occupied/Unoccupied | |
| BV | 13 | HeatValveConfig | Default NormClose | Write | NormOpen/NormClose | |
| BV | 14 | CoolValveConfig | Default NormClose | Write | NormOpen/NormClose | |
| BV | 16 | EnableRoomUnocc | Default Yes | Write | Yes/No | |
| BV | 17 | ECSmartComfortExt | Default Light | Write | Light/Blind | |
| BV | 18 | NetChgOver | Default Cool | Write | Heat/Cool | |
| BV | 19 | ComSensorUnits | Default deg.C | Write | deg.C/deg.F | |
| BV | 26 | EnableAPARRules | Default TRUE | Write | TRUE/FALSE | |
| BV | 31 | CtrlGroupLight1 | Default Window | Write | Window/Corridor | |
| BV | 32 | CtrlGroupLight2 | Default Window | Write | Window/Corridor | |
| BV | 33 | CtrlGroupLight3 | Default Window | Write | Window/Corridor | |
| BV | 34 | CtrlGroupLight4 | Default Window | Write | Window/Corridor | |
| BV | 35 | LightType1 | Default Dimming | Write | Dimming/OnOff | |
| BV | 36 | LightType2 | Default Dimming | Write | Dimming/OnOff | |
| BV | 37 | LightType3 | Default Dimming | Write | Dimming/OnOff | |
| BV | 38 | LightType4 | Default Dimming | Write | Dimming/OnOff | |
| BV | 39 | LightCtrlMode | Default Local | Write | Local/Master | |
| BV | 40 | BlindCtrlMode | Default Local | Write | Local/Master | |
| BV | 41 | BlindType1 | Default Exterior | Write | Interior/Exterior | |
| BV | 42 | BlindType2 | Default Exterior | Write | Interior/Exterior | |
| BV | 43 | BlindType3 | Default Exterior | Write | Interior/Exterior | |
| BV | 44 | BlindType4 | Default Exterior | Write | Interior/Exterior | |
| MVmin | 1 | HvacModeCmd | Default Auto | Write | 1=Auto, 2=Heat, 3=Cool, 4=Off | |
| MVmin | 2 | OccupancyCmd | Write | 1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby | ||
| MVmin | 3 | FanSpeedCmd | Default Auto | Write | 1=Auto, 2=Off, 3=Low, 4=Med, 5=High | |
| MV | 4 | OptStartMode | Default Auto | Write | 1=Auto, 2=HeatOnly, 3=CoolOnly, 4=Disable | |
| MV | 5 | MotionSensor | Default Unused | Write | 1=Occupied, 2=Unoccupied, 3=Unused | |
| MV | 6 | ChangeOverInput | Default Unused | Read | 1=Unused, 2=Heat, 3=Cool | |
| MVmin | 11 | HvacModeStatus | Default Auto | Read | 1=Auto, 2=Heat, 3=Cool, 4=Off | |
| MV | 13 | MS1.FanSpeed | Default Auto | Write | 1=Auto, 2=Off, 3=Low, 4=Med, 5=High | |
| MVmin | 14 | OccupancyStatus | Read | 1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby | ||
| MV | 15 | EcoVue | Read | 1=1 Leaf, 2=2 Leaves, 3=3 Leaves, 4=4 Leaves | ||
| MVmin | 16 | FanSpeedSt | Read | 1=Off, 2=Low, 3=Med, 4=High | ||
| MV | 17 | FanCtrlMode | Write | 1=On, 2=Auto, 3=Smart | ||
| MV | 18 | UI2Config | Default SpOffset | Write | 1=Unused, 2=Discharge Temp, 3=Return Temp, 4=Water Temp, 5=SpOffset | |
| MV | 19 | UI3Config | Default WindowContactNO | Write | 1=Unused, 2=WindowContactNO, 3=WindowContactNC | |
| MV | 20 | SI4Config | Default SpaceTemp | Write | 1=Unused, 2=Discharge Temp, 3=Return Temp, 4=Water Temp, 5=SpaceTemp | |
| MV | 21 | DI5Config | Default Unused | Write | 1=Unused, 2=AuxContactNO, 3=AuxContactNC, 4=ChangOverHtg, 5=ChangOverClg, 6=CondSensorNO, 7=CondSensorNC | |
| MV | 22 | DI6Config | Default AuxContactNO | Write | 1=Unused, 2=AuxContactNO, 3=AuxContactNC, 4=ChangOverHtg, 5=ChangOverClg, 6=OccSensorNO, 7=OccSensorNC | |
| MV | 23 | ConfigOccSensor | Write | 1=Unused, 2=Multi-Sensor, 3=ComSensor, 4=DigitaInput, 5=Auto/All | ||
| MV | 24 | SystemType | Default CoolHeat | Write | 1=Cool, 2=CoolElectHeat, 3=ChgOver, 4=ChgOverElectHeat, 5=Heat, 6=HeatElectHeat, 7=CoolHeat, 8=CoolHeatElectHeat | |
| MV | 25 | FanType | Default VarSpeed | Write | 1=None, 2=VarSpeed, 3=3Speed | |
| MV | 26 | CoolValveType | Default Thermal | Write | 1=Unused, 2=0-10V, 3=Thermal, 4=On-Off, 5=Floating | |
| MV | 27 | HeatValveType | Default Thermal | Write | 1=Unused, 2=0-10V, 3=Thermal, 4=On-Off, 5=Floating | |
| MV | 28 | SpaceTempCtrl | Write | 1=Local, 2=Master, 3=Slave, 4=Auto | ||
| MV | 29 | ComSensorDisplay | Default SpaceTemp | Write | 1=SpaceTemp, 2=SpOffset, 3=MidSetpoint, 4=EffectSp | |
| MV | 30 | ComSensorLock | Write | 1=All, 2=Sp and override, 3=Sp Only, 4=No access | ||
| MV | 31 | DischAirLimitType | Default NotLimited | Write | 1=NotLimited, 2=LowLimit, 3=HighLimit, 4=HighLowLimit | |
| MV | 33 | MS1.LightBlind | Write | 1=LightStop, 2=LightUp, 3=LightDown, 4=BlindUp, 5=BlindDown, 6=BlindRotUp, 7=BlindRotDown, 8=BlindStop | ||
| MV | 34 | MS1.GroupCtrl | Write | 1=Grp1-8, 2=Grp1, 3=Grp2, 4=Grp3, 5=Grp4, 6=Grp5, 7=Grp6, 8=Grp7, 9=Grp8, 10=Grp1-2, 11=Grp1-4 | ||
| MV | 35 | RemoteCtrlGrpLight1 | Write | 1=Group1, 2=Group2, 3=Group3, 4=Group4, 5=Group5, 6=Group6, 7=Group7, 8=Group8 | ||
| MV | 36 | RemoteCtrlGrpLight2 | Write | 1=Group1, 2=Group2, 3=Group3, 4=Group4, 5=Group5, 6=Group6, 7=Group7, 8=Group8 | ||
| MV | 37 | RemoteCtrlGrpLight3 | Write | 1=Group1, 2=Group2, 3=Group3, 4=Group4, 5=Group5, 6=Group6, 7=Group7, 8=Group8 | ||
| MV | 38 | RemoteCtrlGrpLight4 | Write | 1=Group1, 2=Group2, 3=Group3, 4=Group4, 5=Group5, 6=Group6, 7=Group7, 8=Group8 | ||
| MV | 39 | RemoteCtrlGrpSblnd1 | Write | 1=Group1, 2=Group2, 3=Group3, 4=Group4, 5=Group5, 6=Group6, 7=Group7, 8=Group8 | ||
| MV | 40 | RemoteCtrlGrpSblnd2 | Write | 1=Group1, 2=Group2, 3=Group3, 4=Group4, 5=Group5, 6=Group6, 7=Group7, 8=Group8 | ||
| MV | 41 | RemoteCtrlGrpSblnd3 | Default Group3 | Write | 1=Group1, 2=Group2, 3=Group3, 4=Group4, 5=Group5, 6=Group6, 7=Group7, 8=Group8 | |
| MV | 42 | RemoteCtrlGrpSblnd4 | Default Group4 | Write | 1=Group1, 2=Group2, 3=Group3, 4=Group4, 5=Group5, 6=Group6, 7=Group7, 8=Group8 | |
| MV | 43 | SmartLight1Group | Default Grp1 | Write | 1=Grp1-8, 2=Grp1, 3=Grp2, 4=Grp3, 5=Grp4, 6=Grp5, 7=Grp6, 8=Grp7, 9=Grp8, 10=Grp1-2, 11=Grp1-4 | |
| MV | 44 | SmartBlind1Group | Default Grp1-8 | Write | 1=Grp1-8, 2=Grp1, 3=Grp2, 4=Grp3, 5=Grp4, 6=Grp5, 7=Grp6, 8=Grp7, 9=Grp8, 10=Grp1-2, 11=Grp1-4 | |
| MV | 50 | ControlMode | Default Local | Write | 1=Local, 2=Master, 3=Slave |
No points match these filters.
Object ID lookup: Distech Controls ECY-PTU-107 preloaded applications point IDs by name
AV1SpaceTempAV2CoolingValveCtrlAV3HeatingValveCtrlAV4SpaceCO2AV5ElectHeatCtrlAV6SpaceTempSI4AV7DischargeTempAV8ReturnTempAV9WaterTempAV10SpOffsetUI2AV11MidSetpointAV14OptStartCoolFactorAV15OptStartHeatFactorAV17OptStartMaxStartupTimeAV18OptStartFactorWeightAV19APARStartupDelayAV20ModeActivDelayAV21RuleActiveDelayAV22ActiveRulesAV26ElectHeatStatusAV27SpOffsetRangeAV28SetPtOffsetAV30SpaceTempOffsetAV31FloatingDriveTimeAV33EffectSpAV34SpaceHumidityAV35FreezeProtSpAV36ActCoolSpAV37ActHeatSpAV38UnoccCoolSpAV39StandbyCoolSpAV40OccCoolSpAV41OccHeatSpAV42StandbyHeatSpAV43UnoccHeatSpAV44TerminalLoadAV45SensorSleepTimeAV46ChgOverDelayAV47HoldTimeAV48ByPassTimeAV52WaterSpHeatAV53WaterSpCoolAV54MaxDischAirSpAV55MinDischAirSpAV56BlindTransCmdAV57BlindRotCmdAV58AuxHeatEnableAV59ElectheatPeriodAV60FanOffDelayAV61FanCoolLowAV62FanHeatLowAV63CoolMaxFanAV64HeatMaxFanAV65CoolMinFanAV66HeatMinFanAV69VlvExerciseDelayAV70VlvExerciseUnoccDelayAV71Light1RoomAV74Light4RoomAV75Sblnd1RoomAV76Sblnd2RoomAV77Sblnd3RoomAV78Sblnd4RoomAV79VlvExerciseCycleAV80ElevationAV81CtrlRoomAV82UnoccTranslationAV83OccTranslationAV84UnoccRotationAV85OccRotationAV86InfraRedZoneAV87BlindCtrlInfoAV88LightCtrlInfoAV89RemoteCtrlInfoAV90MasterInfoAV91SlaveInfoAV92SendSpaceTempCO2AV93LuxSetpointAV94ReflexFactorAV95LightPowerAV96MinLightCmdAV97LightOffsetAV98LuxRampUpTimeAV99LuxRampDownTimeBV1WindowStatusBV2CondSensorStBV3WindowContactBV4AuxContactBV5ChgOverStBV11MS1.OccupancyBV12RoomOccupancyBV13HeatValveConfigBV14CoolValveConfigBV16EnableRoomUnoccBV17ECSmartComfortExtBV18NetChgOverBV19ComSensorUnitsBV26EnableAPARRulesBV31CtrlGroupLight1BV32CtrlGroupLight2BV33CtrlGroupLight3BV34CtrlGroupLight4BV35LightType1BV36LightType2BV37LightType3BV38LightType4BV39LightCtrlModeBV40BlindCtrlModeBV41BlindType1BV42BlindType2BV43BlindType3BV44BlindType4MV1HvacModeCmdMV2OccupancyCmdMV3FanSpeedCmdMV4OptStartModeMV5MotionSensorMV6ChangeOverInputMV11HvacModeStatusMV13MS1.FanSpeedMV14OccupancyStatusMV15EcoVueMV16FanSpeedStMV17FanCtrlModeMV18UI2ConfigMV19UI3ConfigMV20SI4ConfigMV21DI5ConfigMV22DI6ConfigMV23ConfigOccSensorMV24SystemTypeMV25FanTypeMV26CoolValveTypeMV27HeatValveTypeMV28SpaceTempCtrlMV29ComSensorDisplayMV30ComSensorLockMV31DischAirLimitTypeMV33MS1.LightBlindMV34MS1.GroupCtrlMV35RemoteCtrlGrpLight1MV36RemoteCtrlGrpLight2MV37RemoteCtrlGrpLight3MV38RemoteCtrlGrpLight4MV39RemoteCtrlGrpSblnd1MV40RemoteCtrlGrpSblnd2MV41RemoteCtrlGrpSblnd3MV42RemoteCtrlGrpSblnd4MV43SmartLight1GroupMV44SmartBlind1GroupMV50ControlMode
Integration notes
- Objects are documented one per section in the guide's Variables chapter; hardware inputs and outputs are described there too but are not listed here.
- The guide has no read/write column, so access is inferred from each object's description: values the guide says are set, configured or received from the BMS are marked writable; values it describes as displayed (measured or calculated) are read-only, although the guide allows overriding some of them for testing.
- Which objects are used depends on the configured system type, fan type, valve types and input configuration.
- Left out because the guide prints two different instance numbers for them (section heading vs table row): UnoccOccDelay (AV 32), Light2Room (AV 72), Light3Room (AV 73), AppVersion (AV 100), SendAutoLightBlind (AV 103), RulesNumber (MV 8).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ECY-PTU-107 preloaded applications and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Distech Controls ECY-PTU-107 preloaded applications
How many BACnet points does the Distech Controls ECY-PTU-107 preloaded applications have?
This list has 151 BACnet objects: 84 analog values, 28 binary values, 39 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Distech Controls ECY-PTU-107 preloaded applications BACnet points are writable?
115 of the 151 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Distech Controls ECY-PTU-107 preloaded applications BACnet documentation?
The source is ECY-PTU-107 Preloaded Applications User Guide (ECY-PTU-107 Preloaded_UG_10_EN), revision 2016-11 (version 1.0), published free by Distech Controls at https://docs.distech-controls.com/api/khub/documents/e_61tL2Fod11LBZ3m1MTDw/content.
What are the minimum BACnet points to integrate the Distech Controls ECY-PTU-107 preloaded applications?
Start with MV 2 OccupancyCmd (Occupancy command from the BMS); MV 1 HvacModeCmd (HVAC mode command (auto, heat, cool, off)); MV 3 FanSpeedCmd (Fan speed command (auto, off, low, med, high)); AV 40 OccCoolSp (Occupied cooling setpoint); AV 41 OccHeatSp (Occupied heating setpoint); MV 14 OccupancyStatus (Effective occupancy state); MV 11 HvacModeStatus (Actual HVAC mode); AV 1 SpaceTemp (Space temperature used for control); MV 16 FanSpeedSt (Actual fan speed); BV 2 CondSensorSt (Condensation alarm; cooling valve closes).
How do I enable BMS control of the Distech Controls ECY-PTU-107 preloaded applications?
Write MV 2 OccupancyCmd for occupancy and MV 1 HvacModeCmd for the mode; any value other than Auto forces the unit into that mode. MV 3 FanSpeedCmd set to Auto leaves the fan to the control loop.
Can the BMS supply sensor values to the Distech Controls ECY-PTU-107 preloaded applications?
The guide says AV 1 SpaceTemp and other measured values can be overridden through the BACnet priority array (it calls this a testing feature). MV 5 MotionSensor can be written from the network; the guide says to use a priority lower than 14 to override local control.
How do I check these points on the real ECY-PTU-107 preloaded applications?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Distech Controls BACnet points lists
- Fan coil / terminal unit controller (preloaded application)
Distech Controls ECB-PTU-107 preloaded applications
Fan coil, chilled ceiling/beam and heat pump terminal units run by an ECB-PTU-107 with its factory application.
Also known as: ECB-PTU-107, ECB-PTU 107 - Fan coil / terminal unit controller (preloaded application)
Distech Controls ECB-PTU-207 preloaded applications
Fan coil, chilled ceiling/beam and heat pump terminal units run by an ECB-PTU-207 with its factory application.
Also known as: ECB-PTU-207, ECB-PTU 207 - Fan coil / terminal unit controller (preloaded application)
Distech Controls ECB-PTU-208 / ECB-PTU-308 preloaded applications
Fan coil, chilled ceiling/beam and heat pump terminal units run by an ECB-PTU-208 or ECB-PTU-308 with the factory application.
Also known as: ECB-PTU-208, ECB-PTU-308 - Fan coil / terminal unit controller (preloaded application)
Distech Controls ECB-PTU-307 preloaded applications
Fan coil, chilled ceiling/beam and heat pump terminal units run by an ECB-PTU-307 with its factory application.
Also known as: ECB-PTU-307, ECB-PTU 307 - Rooftop unit controller (preloaded application)
Distech Controls ECY-303 preloaded applications (rooftop unit)
Packaged rooftop units (staged cooling and heating, heat pump, economizer, humidity) run by an Eclypse ECY-303 with its factory application.
Also known as: ECY-303, Eclypse Connected Equipment Controller, ECY-303 Roof Top Unit - Fan coil / terminal unit controller (preloaded application)
Distech Controls ECY-PTU-207 / 208 and ECY-TU-203 preloaded applications (Eclypse Facilities)
Fan coil, chilled beam/ceiling and heat pump terminal units run by Eclypse ECY-PTU-207, ECY-PTU-208 or ECY-TU-203 controllers with the factory application.
Also known as: ECY-PTU-207, ECY-PTU-208, ECY-TU-203
Source: ECY-PTU-107 Preloaded Applications User Guide · ECY-PTU-107 Preloaded_UG_10_EN · rev. 2016-11 (version 1.0). Object names, instances and units are reproduced as published; descriptions are our own.