Easy BACnet
  1. Home
  2. BACnet points lists
  3. Dimplex
  4. WPM heat pump manager with NWPM Touch (BACnet IP)

Heat pump manager (controller) · BACnet points list

Dimplex WPM heat pump manager with NWPM Touch (BACnet IP) BACnet points list

Updated 12 November 2026

Short answer

The NWPM Touch card (article 378800) plugs into the Serial/BMS slot of the WPM heat pump manager and exposes it over BACnet IP. The published data point list (German names) covers status, lockout, fault and sensor-error codes, operating mode, temperatures and pressures, output states, run hours, heat quantities, heating-circuit settings, an outdoor temperature written by the BMS, Smart Grid control and BMS room-control inputs. All objects are Analog Values or Binary Values with instances 100000 / 200000 + key number.

This page lists 105 BACnet objects for the Dimplex WPM heat pump manager with NWPM Touch (BACnet IP) — 18 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Dimplex’s own free documentation, linked below.

Manufacturer
Dimplex
Model
WPM heat pump manager with NWPM Touch (BACnet IP)
Equipment
Heat pump manager (controller)
Equipment type
Heat pumps
BACnet objects
105 (18 writable)
Transport
BACnet IP
Firmware
WPM software M3.3 or later; NWPM Touch firmware A2.1.0 - B2.1.0 or later
Also known as
WPM Touch, WPM Econ5, WPM Econ, NWPM Touch, 378800, Dimplex Wärmepumpenmanager, Dimplex heat pump manager BACnet
Source document
BACnet/IP - Datenpunktliste (Dimplex Wiki, with sub-pages and BACnet/IP - Funktionsbeschreibungen)
Download CSV 105 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Dimplex’s current documentation and the live device before use. Not official Dimplex information. Terms of use.

BMS integration notes: Dimplex WPM heat pump manager with NWPM Touch (BACnet IP)

Integration in brief

Fit the NWPM Touch card and enable the network setting on the WPM. Read the status, lockout and fault codes and the main temperatures, and write the operating mode or circuit setpoints only if the BMS owns them. If the BMS supplies outdoor temperature or room values, the service technician must configure that on the WPM first.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 200014BetriebsmodusOperating mode command (writable)Write
AV 200036FestwertsolltemperaturFixed-value setpoint, 1st circuit, °CWrite
AV 100053Ruecklaufsolltemperatur (Hz/Khl)Return temperature setpoint in use, °CRead
AV 100103StatusmeldungenOperating state code (heating, hot water, defrost...)Read
AV 100001Außentemperatur (R1)Outdoor temperature, °CRead
AV 100002Ruecklauftemperatur (R2)Return water temperature, °CRead
AV 100003Warmwassertemperatur (R3)Hot water temperature, °CRead
BV 100041Verdichter 1Compressor 1 runningRead
AV 100104SperrmeldungenLockout code (why the heat pump is blocked)Read
AV 100105StoermeldungenFault code, 0 = no faultRead

Enable & remote start

Set the Netzwerk parameter on the WPM (home app setting) to activate the NWPM Touch extension. The list has no separate BMS enable; writes go straight to the mode and setpoint objects.

Sensors & values from the BMS

AV 100112 takes outdoor temperature from the BMS (configured by the service technician before WPM software M3.15). If no value is written after a power reset it stays at -99.9 °C and raises an outdoor sensor fault. For Smart-RTC+ room control (WPM_L23.1+), select a room address page with AV 200064, then write room temperature AV 100011, humidity AV 100013, room setpoint AV 200080 and release AV 100173 for up to 10 rooms per circuit.

Network setup

Watch out for

Dimplex WPM heat pump manager with NWPM Touch (BACnet IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

105 of 105 shown
Type
AnalogBinary
Access
Show
Dimplex WPM heat pump manager with NWPM Touch (BACnet IP) BACnet Points List
DescriptionStates
AVmin100001Außentemperatur (R1)Outdoor temperature (sensor R1)°CRead
AVmin100002Ruecklauftemperatur (R2)Return temperature (R2)°CRead
AVmin100003Warmwassertemperatur (R3)Hot water temperature (R3)°CRead
AV100005Vorlauftemperatur (R9)Flow temperature (R9)°CRead
AV100006Waermequelleneintritt (R24)*Heat source inlet temperature (R24)°CRead
AV100007Waermequellenaustritt (R6)Heat source outlet temperature (R6)Read
AV100008HochdruckHigh pressurebarRead
AV100009Temperatur 2. Heizkreis (R5)2nd heating circuit temperature (R5)°CRead
AV100010Temperatur 3. Heizkreis3rd heating circuit temperature°CRead
AV100011Raumtemperatur 1 / RT-RTH EconRoom temperature 1; also BMS room temperature input (see notes)°CRead
AV100012Raumtemperatur 2Room temperature 2°CRead
AV100013Raumfeuchte 1 / RT-RTH EconRoom humidity 1; also BMS room humidity input (see notes)%RHRead
AV100014Raumfeuchte 2Room humidity 2%RHRead
AV100019Vorlauftemperatur (R11) Passiv KuehlenPassive cooling flow temperature (R11)°CRead
AV100020Ruecklauftemperatur (R4) Passiv KuehlenPassive cooling return temperature (R4)°CRead
AV100021Ruecklauftemperatur gemeinsamer Primaerkreis (R24)Shared primary circuit return temperature (R24)°CRead
AV1000046Raumtemperatur 1. HeizkreisRoom temperature, 1st heating circuit (instance as printed)°CWrite
AVmin100053Ruecklaufsolltemperatur (Hz/Khl)Return setpoint (heating/cooling)°CRead
AV100054Solltemperatur 2. HeizkreisSetpoint, 2nd heating circuit°CRead
AV100055Solltemperatur 3. HeizkreisSetpoint, 3rd heating circuit°CRead
AV100056Minimale Temperatur 2. HeizkreisMinimum temperature 2nd circuit (as printed)°CRead
AV100057Minimale Temperatur 2. HeizkreisSecond row printed with the same name°CRead
AV100058Aktuelle Warmwasser-SolltemperaturCurrent hot water setpoint°CRead
AV100060Leistungsstufe HeizenHeating output stageRead
AV100061Leistungsstufe KuehlenCooling output stageRead
AV100071Zusatzumwaelzpumpe (M16)Run hourshRead
AV100072Verdichter 1Run hourshRead
AV100073Verdichter 2Run hourshRead
AV100074Primaerpumpe /Ventilator (M11)Run hourshRead
AV1000752. Waermeerzeuger (E10)Run hourshRead
AV100076Heizungspumpe (M13)Run hourshRead
AV100077Warmwasserpumpe (M18)Run hourshRead
AV100078Flanschheizung (E9)Run hourshRead
AV100079Schwimmbadpumpe (M19)Run hourshRead
AV100080Internes 4-Wege-VentilRun hourshRead
AV100081Auswahl Stör-/ Sperrwert 1 - 10Write 100-190 (faults) or 200-290 (lockouts) to pick a stored entryWrite
AV100082StundeDate/time part of the selected stored entryhRead
AV100083MinuteDate/time part of the selected stored entryminRead
AV100084MonatDate/time part of the selected stored entrymonthRead
AV100085TagDate/time part of the selected stored entrydayRead
AV100086JahrDate/time part of the selected stored entryyearRead
AV100092Störwert (Siehe Störmeldungen)Stored fault or lockout code for the selected entryRead
AV100101NiederdruckLow pressurebarRead
AVmin100103StatusmeldungenOperating status code (see state list)Read0.0=Aus; 0.1=Aus; 0.2=Heizen; 0.3=Schwimmbad; 0.4=Warmwasser; 0.5=Kühlen; 1.0=Abtauen; 1.1=Durchflussüberwachung; 2.4=Verzögerung Betriebsmodusumschaltung; 3.0=Sperre (siehe Kapitel Sperrmeldungen)
AVmin100104SperrmeldungenLockout (block) message codeRead0.2=Volumenstrom; 0.5=Funktionskontrolle; 0.6=Einsatzgrenze HT; 0.7=Systemkontrolle; 0.8=Verzögerung Betriebsartenumschaltung; 0.9=Pumpenvorlauf; 1.0=Mindeststandzeit; 1.1=Netzbelastung; 1.2=Schaltspielsperre; 1.3=Warmwasser Nacherwärmung; 1.4=Regenerativ; 1.5=EVU-Sperre; 1.6=Sanftanlasser; 1.7=Durchfluss; 1.8=Einsatzgrenze Wärmepumpe (2. Wärmeerzeuger); 1.9=Hochdruck; 2.0=Niederdruck; 2.1=Einsatzgrenze Wärmequelle; 2.3=System Grenze; 2.4=Last Primärkreis; 2.5=Sperre Extern; 2.9=Inverter; 3.1=Aufwärmen; 3.3=EvD Initialisierung; 3.4=2.Wärmeerzeuger freigegeben; 3.5=Störung (siehe Wert für Störmeldungen); 5.1=Minimale Wärmequellentemperatur; 5.2=Maximale Wärmequellentemperatur; 5.3=Minimale Rücklauftemperatur; 5.4=Maximale Rücklauftemperatur; 5.5=Minimale Vorlauftemperatur; 5.6=Maximale Vorlauftemperatur; 5.7=Kommunikation Propansensor
AVmin100105StoermeldungenFault message codeRead0=kein Fehler; 0.1=Fehler N17.1; 0.2=Fehler N17.2; 0.3=Fehler N17.3; 0.4=Fehler N17.4; 0.5=Fehler N17; 0.6=Elektronisches Ex.Ventil; 0.7=Raumregler RTM Econ; 0.8=Fehler ODU; 0.9=Durchfluss Frostschutz; 1.0=Erweiterung WPIO; 1.2=Inverter; 1.3=Erweiterung WQIF; 1.4=Nasslauf; 1.5=Sensorik (siehe Wert für Sensorik); 1.6=Niederdruck Sole; 1.9=Primärkreis; 2.0=Abtauen; 2.1=Niederdruck Sole; 2.2=Warmwasser; 2.3=Last Verdichter; 2.4=Codierung; 2.5=Niederdruck; 2.6=Frostschutz; 2.8=Hochdruck; 2.9=Temperatur Differenz; 3.0=Heisgasthermostat; 3.1=Durchfluss; 3.2=Aufwärmen; 3.3=Abtauung Frostschutz; 5.0=Propan Alarm; 5.1=Propan Sensor Fehler
AV100106SensormeldungenSensor fault codeRead0.1=Außenfühler (R1); 0.2=Rücklauffühler (R2); 0.3=Warmwasserfühler (R3); 0.4=Codierung (R7); 0.5=Vorlauffühler (R9); 0.6=2.Heizkreisfühler (R5); 0.7=3.Heizkreisfühler (R13); 0.8=Regenerativfühler (R13); 0.9=Raumfühler 1; 1.0=Raumfühler 2; 1.1=Fühler Wärmequellenaustritt (R6); 1.2=Fühler Wärmequelleneintritt (R24); 1.4=Kollektorfühler (R23); 1.5=Niederdrucksensor (R25); 1.6=Hochdrucksensor (R26); 1.7=Raumfeuchte 1; 1.8=Raumfeuchte 2; 1.9=Fühler Frostschutz-Kälte; 2.0=Heißgas; 2.1=Rücklauffühler (R2.1); 2.2=Schwimmbadfühler (R20); 2.3=Vorlauffühler Kühlen Passiv (R11); 2.4=Rücklauffühler Kühlen Passiv (R4); 2.6=Fühler Solarspeicher (R22); 2.8=Anforderungsfühler Heizen (R2.2); 2.9=RTM Econ; 3.0=Anforderungsfühler Kühlen (R39); 3.7=Öltemperaturfühler Verdichter 1; 3.9=Öltemperaturfühler Verdichter 2; 4.1=Heißgasfühler Verdichter 1; 4.3=Heißgasfühler Verdichter 2; 4.5=Verdampfer Lufteintrittsfühler; 4.8=Durchflusssensor Sekundärkreis; 4.9=Drucksensor Sekundärkreis; 5.0=Durchflusssensor Primärkreis; 5.1=Drucksensor Primärkreis; 5.2=Sauggasfühler
AV100112Aussentemperatur über BMSOutdoor temperature written by the BMSWrite
AV100120AußenlufttemperaturVentilation: outdoor air temperature°CRead
AV100121ZulufttemperaturVentilation: supply air temperature°CRead
AV100122AblufttemperaturVentilation: extract air temperature°CRead
AV100123FortlufttemperaturVentilation: exhaust air temperature°CRead
AV100125Drehzahl ZuluftventilatorVentilation: supply fan speedrpmRead
AV100126Drehzahl AbluftventilatorVentilation: extract fan speedrpmRead
AV100173Raumfreigabe 50-79 BMSRoom release for selected room addressWrite1=Heizen (Kühlen gesperrt); 3=Heizen und Kühlen
AVmin200014BetriebsmodusOperating mode (state texts not published)Write
AV200035ParallelverschiebungHeating curve parallel shift, 1st circuitWrite
AVmin200036FestwertsolltemperaturFixed-value setpoint temperature, 1st circuit°CWrite
AV200037HeizkurvenendpunktHeating curve end point, 1st circuitWrite
AV200042Sollwert dyn. Kuehlung bei 15°CDynamic cooling setpoint at 15 °C outdoor°CWrite
AV200064Raumadressen 1.Heiz/KühlkreisRoom address page: 50-59, 60-69 or 70-79 for circuit 1, 2 or 3Write
AV200080Raumsolltemperatur 50-79 BMSRoom setpoint for selected room address (x10)Write
AV200081Auswahl Heizkreis 2Selects circuit for writes: 2 = 2nd, 3 = 3rdWrite2=2. Heizkreis; 3=3. Heizkreis
AV200083HeizkurvenendpunktHeating curve end point, selected circuit°CWrite
AV200084FestwertemperaturFixed temperature, selected circuit°CWrite
AV200085ParallelverschiebungParallel shift, selected circuitKWrite
AV200087Maximale TemperaturMaximum temperature, selected circuit°CWrite
AV200095Heizen 1-4Energy counter digits 1-4 (combine 3 parts)kWhRead
AV200096Heizen 5-8Energy counter digits 5-8 (combine 3 parts)kWhRead
AV200097Heizen 9-12Energy counter digits 9-12 (combine 3 parts)kWhRead
AV200098Warmwasser 1-4Energy counter digits 1-4 (combine 3 parts)kWhRead
AV200099Warmwasser 5-8Energy counter digits 5-8 (combine 3 parts)kWhRead
AV200100Warmwasser 9-12Energy counter digits 9-12 (combine 3 parts)kWhRead
AV200101Schwimmbad 1-4Energy counter digits 1-4 (combine 3 parts)kWhRead
AV200102Schwimmbad 5-8Energy counter digits 5-8 (combine 3 parts)kWhRead
AV200103Schwimmbad 9-12Energy counter digits 9-12 (combine 3 parts)kWhRead
AV200126Umweltenergie 1-4Energy counter digits 1-4 (combine 3 parts)kWhRead
AV200127Umweltenergie 5-8Energy counter digits 5-8 (combine 3 parts)kWhRead
AV200128Umweltenergie 9-12Energy counter digits 9-12 (combine 3 parts)kWhRead
AV200133Sollwert dyn. Kuehlung bei 30°CDynamic cooling setpoint at 30 °C outdoor°CWrite
AV200166Smart GridSmart Grid state from the BMSWrite0=Hardwareeingang; 10=Zustand gelb; 11=Zustand grün; 12=Zustand rot; 13=Zustand dunkelgrün
BV177Zustand StellventilControl valve stateRead0=geschlossen; 1=geöffnet
BV100003Smart-Grid 1Input state (read-only)Read
BV100004Smart-Grid 2Input state (read-only)Read
BV100005EVU SperreInput state (read-only)Read
BV100006Sperre externInput state (read-only)Read
BVmin100041Verdichter 1Output stateRead
BV100042Verdichter 2Output stateRead
BV100043Primaerpumpe (M11) /Ventilator (M2)Output stateRead
BV1000442.Waermeerzeuger (E10)Output stateRead
BV100045Heizungspumpe (M13)Output stateRead
BV100046Warmwasserpumpe (M18)Output stateRead
BV100047Mischer Auf 3.Heizkreis (M21)Output stateRead
BV100048Mischer Zu 3.Heizkreis (M21)Output stateRead
BV100050Flanschheizung (E9)Output stateRead
BV100051Heizungspumpe 2.Heizkreis (M15)Output stateRead
BV100052Mischer Auf 2.Heizkreis (M22)Output stateRead
BV100053Mischer Zu 2.Heizkreis (M22)Output stateRead
BV100056Schwimmbadumwaelzpumpe (M19)Output stateRead
BV100057Stoerfernanzeige (h5)Output stateRead
BV100058Zirkulationspumpe (M24)Output stateRead
BV100060Kuehlumwaelzpumpe (M17)Output stateRead
BV100061Heizungsumwaelzpumpe 3. Heizkreis (M20)Output stateRead
BV100066Umschaltung Raumthermostate Heizen/Kuehlen (N9)Output stateRead
BV100068Primaerpumpe Kuehlen (M12)Output stateRead
Object ID lookup: Dimplex WPM heat pump manager with NWPM Touch point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the WPM heat pump manager with NWPM Touch (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Dimplex WPM heat pump manager with NWPM Touch (BACnet IP)

How many BACnet points does the Dimplex WPM heat pump manager with NWPM Touch (BACnet IP) have?

This list has 105 BACnet objects: 81 analog values, 24 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Dimplex WPM heat pump manager with NWPM Touch (BACnet IP) BACnet points are writable?

18 of the 105 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Dimplex WPM heat pump manager with NWPM Touch (BACnet IP) BACnet documentation?

The source is BACnet/IP - Datenpunktliste (Dimplex Wiki, with sub-pages and BACnet/IP - Funktionsbeschreibungen), published free by Dimplex at https://dimplex.atlassian.net/wiki/spaces/DW/pages/3451355137/BACnet+IP+-+Datenpunktliste.

What are the minimum BACnet points to integrate the Dimplex WPM heat pump manager with NWPM Touch (BACnet IP)?

Start with AV 200014 Betriebsmodus (Operating mode command (writable)); AV 200036 Festwertsolltemperatur (Fixed-value setpoint, 1st circuit, °C); AV 100053 Ruecklaufsolltemperatur (Hz/Khl) (Return temperature setpoint in use, °C); AV 100103 Statusmeldungen (Operating state code (heating, hot water, defrost...)); AV 100001 Außentemperatur (R1) (Outdoor temperature, °C); AV 100002 Ruecklauftemperatur (R2) (Return water temperature, °C); AV 100003 Warmwassertemperatur (R3) (Hot water temperature, °C); BV 100041 Verdichter 1 (Compressor 1 running); AV 100104 Sperrmeldungen (Lockout code (why the heat pump is blocked)); AV 100105 Stoermeldungen (Fault code, 0 = no fault).

How do I enable BMS control of the Dimplex WPM heat pump manager with NWPM Touch (BACnet IP)?

Set the Netzwerk parameter on the WPM (home app setting) to activate the NWPM Touch extension. The list has no separate BMS enable; writes go straight to the mode and setpoint objects.

Can the BMS supply sensor values to the Dimplex WPM heat pump manager with NWPM Touch (BACnet IP)?

AV 100112 takes outdoor temperature from the BMS (configured by the service technician before WPM software M3.15). If no value is written after a power reset it stays at -99.9 °C and raises an outdoor sensor fault. For Smart-RTC+ room control (WPM_L23.1+), select a room address page with AV 200064, then write room temperature AV 100011, humidity AV 100013, room setpoint AV 200080 and release AV 100173 for up to 10 rooms per circuit.

How do I check these points on the real WPM heat pump manager with NWPM Touch (BACnet IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.