Multi-sensor room sensor hub · BACnet points list

Delta Controls O3 Sensor Hub BACnet points list

Updated 6 November 2026

Short answer

The O3 is a ceiling-mounted room sensor hub that reports temperature, humidity, occupancy (motion plus sound), light level and color, and sound level as BACnet objects. It also has a light ring, speaker, IR blaster and two universal I/O points. Most objects are readings; the AVs set sensitivities, timers and the light ring or sound behaviour.

This page lists 66 BACnet objects for the Delta Controls O3 Sensor Hub — 40 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Delta Controls’s own free documentation, linked below.

Manufacturer
Delta Controls
Model
O3 Sensor Hub
Equipment
Multi-sensor room sensor hub
Equipment type
Thermostats, sensors & meters
BACnet objects
66 (40 writable)
Transport
BACnet IP
Firmware
2.0 or later (objects note their own minimum version)
Also known as
O3, Delta O3, O3 sensor hub
Source document
BACnet Objects in the O3 (Delta Controls O3 support article) · 4427505298963 · rev. 2025-04-10
Download CSV 66 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Delta Controls’s current documentation and the live device before use. Not official Delta Controls information. Terms of use.

BMS integration notes: Delta Controls O3 Sensor Hub

Integration in brief

Enable BACnet IP on the O3 (it ships on BACnet/Ethernet), discover it, and read the occupant-height temperature and humidity, the combined occupancy signal and light level. Tune occupancy with AV 23-26 if the space needs it.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 3Occupant TemperatureRoom temperature at occupant heightRead
AI 6Occupant HumidityRoom humidity at occupant height, %Read
BI 8OccupancyOccupied: motion plus soundRead
AV 40Occupancy EstimationEstimated number of peopleRead
AI 12Light LevelAmbient light levelRead
AI 17Sound LevelAmbient sound level, dBRead

Network setup

Watch out for

Delta Controls O3 Sensor Hub BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

66 of 66 shown
Type
Multi-stateOther
Access
Show
Delta Controls O3 Sensor Hub BACnet Points List
DescriptionStates
AI1Universal IO Channel 1 AIAnalog input on I/O point xP1Read
AI2Universal IO Channel 2 AIAnalog input on I/O point xP2Read
AImin3Occupant TemperatureTemperature at 1 m above floor (composite)Read
AI4IR TemperatureAverage surface temperature in viewRead
AI5Internal TemperatureTemperature at ceiling heightRead
AImin6Occupant HumidityHumidity at 1 m above floor (calculated)%Read
AI7Internal HumidityHumidity at ceiling height%Read
AI10Acoustic Activity LevelFiltered audio levelRead
AImin12Light LevelAmbient light level (lx or fc)Read
AI13Color TemperatureColor temperature of ambient lightKRead
AI14Light Sensor Red ComponentRed light component, 0-65535Read
AI15Light Sensor Green ComponentGreen light component, 0-65535Read
AI16Light Sensor Blue ComponentBlue light component, 0-65535Read
AImin17Sound LevelUnfiltered ambient noise leveldBRead
AO1Universal IO Channel 1 AOAnalog output on I/O point xP1Write
AO2Universal IO Channel 2 AOAnalog output on I/O point xP2Write
AV2Light Ring Pattern RepeatsTimes the light ring pattern repeatsWrite
AV3Light Ring Custom Color RedCustom ring color red (BV 7 on)%Write
AV4Light Ring Custom Color GreenCustom ring color green (BV 7 on)%Write
AV5Light Ring Custom Color BlueCustom ring color blue (BV 7 on)%Write
AV6Light Ring BrightnessLight ring brightness (default 50 %)%Write
AV10IR Code RepeatsTimes each IR code is sentWrite
AV23Motion SensitivityPIR sensitivity%Write
AV24Occupancy Audio SensitivityAcoustic occupancy sensitivity%Write
AV25Occupancy Audio Retrigger PeriodSound keeps occupied state after motion (default 1200)sWrite
AV26Occupancy Inactivity PeriodTime to unoccupied with no motion or sound (default 300)sWrite
AV29Sound RepeatsTimes a sound is playedWrite
AV30Sound VolumeSpeaker volume (default 75 %)%Write
AV33Temperature SetpointUser-entered temperature from the mobile appWrite
AV34Light Level SetpointUser-entered light level from the mobile appWrite
AV39Occupancy Remaining Latch TimeTime left before BI 8 goes inactivesRead
AVmin40Occupancy EstimationEstimated number of occupantsRead
AV41Sound Level Rollup10 s filtered average sound leveldBRead
AV52Adjustment VariablePIR latch time adjustment, 1-10 ssWrite
AV251Occupancy Estimation - MeanOccupancy estimation meanRead
AV252Occupancy Estimation - MinOccupancy estimation minimumRead
AV253Occupancy Estimation - MaxOccupancy estimation maximumRead
BI1Universal IO Channel 1 BIBinary input on I/O point xP1Read
BI2Universal IO Channel 2 BIBinary input on I/O point xP2Read
BImin8OccupancyCombined motion and sound occupancyRead
BI9Motion SensorMotion occupancyRead
BI11Acoustic OccupancySound level above the acoustic thresholdRead
BO1Universal IO Channel 1 BOBinary output on I/O point xP1Write
BO2Universal IO Channel 2 BOBinary output on I/O point xP2Write
BV7Light Ring Activate Custom ColorsUse AV 3-5 custom color, overrides MV 1Write
BV8Power On Self Test EnableRun power-on self testWrite
BV44Startup Sound EnablePlay a sound at restart (default off)Write
MV1Play Light Ring PatternLight ring pattern 1-13 (1 = Off)Write
MV9Send IR CodeSend IR code 1-12 (default 1)Write
MV28Play SoundPlay one of the default or custom soundsWrite
CSV11IR Code 1IR code, Pronto hexWrite
CSV12IR Code 2IR code, Pronto hexWrite
CSV13IR Code 3IR code, Pronto hexWrite
CSV14IR Code 4IR code, Pronto hexWrite
CSV15IR Code 5IR code, Pronto hexWrite
CSV16IR Code 6IR code, Pronto hexWrite
CSV17IR Code 7IR code, Pronto hexWrite
CSV18IR Code 8IR code, Pronto hexWrite
CSV19IR Code 9IR code, Pronto hexWrite
CSV20IR Code 10IR code, Pronto hexWrite
CSV21IR Code 11IR code, Pronto hexWrite
CSV22IR Code 12IR code, Pronto hexWrite
CSV32Bluetooth Beacon MAC AddressBLE beacon MAC addressRead
CSV43Firmware UpgradeStarts a firmware upgradeWrite
CSV45BLE PIN6-digit Bluetooth access code (default 000000)Write
CSV46MQTT PasswordInternal MQTT broker passwordWrite
Object ID lookup: Delta Controls O3 Sensor Hub point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the O3 Sensor Hub and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Delta Controls O3 Sensor Hub

How many BACnet points does the Delta Controls O3 Sensor Hub have?

This list has 66 BACnet objects: 14 analog inputs, 2 analog outputs, 21 analog values, 5 binary inputs, 2 binary outputs, 3 binary values, 3 multi-state values, 16 characterstring values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Delta Controls O3 Sensor Hub BACnet points are writable?

40 of the 66 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Delta Controls O3 Sensor Hub BACnet documentation?

The source is BACnet Objects in the O3 (Delta Controls O3 support article) (4427505298963), revision 2025-04-10, published free by Delta Controls at https://delta-o3.zendesk.com/hc/en-us/articles/4427505298963-BACnet-Objects-in-the-O3.

What are the minimum BACnet points to integrate the Delta Controls O3 Sensor Hub?

Start with AI 3 Occupant Temperature (Room temperature at occupant height); AI 6 Occupant Humidity (Room humidity at occupant height, %); BI 8 Occupancy (Occupied: motion plus sound); AV 40 Occupancy Estimation (Estimated number of people); AI 12 Light Level (Ambient light level); AI 17 Sound Level (Ambient sound level, dB).

How do I check these points on the real O3 Sensor Hub?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: BACnet Objects in the O3 (Delta Controls O3 support article) · 4427505298963 · rev. 2025-04-10. Object names, instances and units are reproduced as published; descriptions are our own.