Fume hood airflow monitor / controller · BACnet points list

Critical Room Control CRC-FHM / CRC-FHC fume hood monitor / controller BACnet points list

Updated 12 November 2026

Short answer

The CRC-FHM/FHC is a touch-screen fume hood monitor and controller for face velocity, constant volume or sash-sensing volumetric control, driving CRC-CLV valves, exhaust terminals or drives. Its BACnet MS/TP map is all Analog Values: face velocity and flow, sash area and position, hood mode and alarm condition, setpoints and alarm limits, and PI tuning and valve commissioning values.

This page lists 22 BACnet objects for the Critical Room Control CRC-FHM / CRC-FHC fume hood monitor / controller — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Critical Room Control’s own free documentation, linked below.

Manufacturer
Critical Room Control
Model
CRC-FHM / CRC-FHC fume hood monitor / controller
Equipment
Fume hood airflow monitor / controller
Equipment type
Thermostats, sensors & meters
BACnet objects
22 (12 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
CRC-FHM, CRC-FHC, CRC-FHM/C, CRC-FHC-01-B, Critical Room Control fume hood controller
Source document
CRC-FHM/C Fume Hood Monitor / Controller data sheet, BACnet Point Map · rev. Rev 6.0
Download CSV 22 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Critical Room Control’s current documentation and the live device before use. Not official Critical Room Control information. Terms of use.

BMS integration notes: Critical Room Control CRC-FHM / CRC-FHC fume hood monitor / controller

Integration in brief

Set the MS/TP baud, MAC address and device instance on the touch screen. Write AV 9 to switch the hood between in use, standby and emergency, read AV 5 for face velocity or flow and AV 7 for exhaust CFM, and alarm on AV 10.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 9ModeMode: 1 in use, 2 standby, 3 emergencyWrite
AV 4In Use Set PointIn-use face velocity / flow setpointWrite
AV 6Standby Set PointStandby setpointWrite
AV 5Current Air Flow/VelocityFace velocity or flow, per control typeRead
AV 7Current CFMHood exhaust flow, CFMRead
AV 14Current Sash Open PercentSash opening, %Read
AV 10ConditionHood alarm: 1 normal, 2 caution, 3 alarmRead

Network setup

Watch out for

Critical Room Control CRC-FHM / CRC-FHC fume hood monitor / controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

22 of 22 shown
Type
Analog
Access
Show
Critical Room Control CRC-FHM / CRC-FHC fume hood monitor / controller BACnet Points List
DescriptionStates
AV0Analog in 1Raw signal, analog input 1 (wiring check)%Read
AV1Analog in 2Raw signal, analog input 2 (wiring check)%Read
AV2Analog in 3Raw signal, analog input 3 (wiring check)%Read
AV3Analog in 4Raw signal, analog input 4 (wiring check)%Read
AVmin4In Use Set PointIn-use setpoint (face velocity or flow)FPM/CFMWrite
AVmin5Current Air Flow/VelocityHood face velocity or flow, per control typeFPM/CFMRead
AVmin6Standby Set PointStandby (unoccupied) setpointFPM/CFMWrite
AVmin7Current CFMActual hood exhaust flowCFMRead
AV8Current Sash AreaSash open areaSQFTRead
AVmin9ModeHood modeWrite1=In use, 2=Standby, 3=Emergency Override, 4=Decommission
AVmin10ConditionHood alarm conditionRead1=Hood Normal (no alarm), 2=Caution, 3=Alarm
AV11Alarm HighHigh alarm setpoint above the control setpointFPM/CFMWrite
AV12Alarm LowLow alarm setpoint below the control setpointFPM/CFMWrite
AV13Pass through CFM INSummed flow from other hoods, passed to the lab controllerCFMRead
AVmin14Current Sash Open PercentSash position, % of full open%Read
AV15K FactorK-factor of the CRC-CLV exhaust valveWrite
AV16Valve Sensor HighValve flow transducer range, high"WCWrite
AV17Valve Sensor LowValve flow transducer range, low"WCWrite
AV18P GainPI loop proportional gainWrite
AV19I GainPI loop integral gainWrite
AV20Min FlowMinimum hood flowCFMWrite
AV21Max FlowMaximum hood flowCFMWrite
Object ID lookup: Critical Room Control CRC-FHM / CRC-FHC fume hood monitor / controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CRC-FHM / CRC-FHC fume hood monitor / controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Critical Room Control CRC-FHM / CRC-FHC fume hood monitor / controller

How many BACnet points does the Critical Room Control CRC-FHM / CRC-FHC fume hood monitor / controller have?

This list has 22 BACnet objects: 22 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Critical Room Control CRC-FHM / CRC-FHC fume hood monitor / controller BACnet points are writable?

12 of the 22 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Critical Room Control CRC-FHM / CRC-FHC fume hood monitor / controller BACnet documentation?

The source is CRC-FHM/C Fume Hood Monitor / Controller data sheet, BACnet Point Map, revision Rev 6.0, published free by Critical Room Control at https://storage.googleapis.com/wzukusers/user-29384423/documents/5a4bb9c11adeea01CgDW/FHC%20Data%20Sheet.pdf.

What are the minimum BACnet points to integrate the Critical Room Control CRC-FHM / CRC-FHC fume hood monitor / controller?

Start with AV 9 Mode (Mode: 1 in use, 2 standby, 3 emergency); AV 4 In Use Set Point (In-use face velocity / flow setpoint); AV 6 Standby Set Point (Standby setpoint); AV 5 Current Air Flow/Velocity (Face velocity or flow, per control type); AV 7 Current CFM (Hood exhaust flow, CFM); AV 14 Current Sash Open Percent (Sash opening, %); AV 10 Condition (Hood alarm: 1 normal, 2 caution, 3 alarm).

How do I check these points on the real CRC-FHM / CRC-FHC fume hood monitor / controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: CRC-FHM/C Fume Hood Monitor / Controller data sheet, BACnet Point Map · rev. Rev 6.0. Object names, instances and units are reproduced as published; descriptions are our own.