Cosmogas Argus boiler control via ProtoNode RER / LER BACnet points list

Updated 6 November 2026

Short answer

A ProtoNode RER (FPC-N34) reads a Cosmogas Argus managing or standalone boiler over Modbus RTU and serves it on BACnet MS/TP or BACnet IP. The 41 objects cover heating and DHW setpoints and modes, outdoor-reset parameters, supply/return/DHW/flue temperatures, firing rate, flame current, water pressure, error codes and per-burner state, status, error and firing rate for four dependent burners, plus a control register that must be set before writes.

This page lists 41 BACnet objects for the Cosmogas Argus boiler control via ProtoNode RER / LER — 11 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Cosmogas’s own free documentation, linked below.

Manufacturer
Cosmogas
Model
Argus boiler control via ProtoNode RER / LER
Equipment
Boiler controller gateway (ProtoNode)
Equipment type
Boilers & water heaters
BACnet objects
41 (11 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Cosmogas Argus BACnet, Argus managing boiler, Argus dependent boiler, RBI Infinite Energy 2 BACnet, ProtoNode RER FPC-N34-1626, ProtoNode LER FPC-N35-1625
Source document
ProtoNode RER and ProtoNode LER Startup Guide - For Interfacing Cosmogas Products: Argus Managing/Standalone Boiler and Dependent Boiler · Instruction 62403594 R08 · rev. Jun. 06, 2017
Download CSV 41 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Cosmogas’s current documentation and the live device before use. Not official Cosmogas information. Terms of use.

BMS integration notes: Cosmogas Argus boiler control via ProtoNode RER / LER

Integration in brief

Set the boilers to Modbus RTU 9600 8-N-1 with unique Node-IDs, wire them to the ProtoNode, select BACnet MS/TP or BACnet IP on the S DIP switches and run auto-discovery. Before any write, set MV 95 to 1, then write setpoints and modes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 7CH ModeHeating mode (RT, outdoor reset, 0-10 V...)Write
AV 5Boiler CH SPHeating setpoint, 68-179 °FWrite
AV 6Boiler DHW SPIndirect DHW setpoint, 104-140 °FWrite
MV 95Control RegisterSet to 1 before any writeWrite
AI 2StateBurner stateRead
AI 9Supply TempSupply water temperatureRead
AI 10Return TempReturn water temperatureRead
AI 14Firing RateFiring rate, %Read
AI 4Error CodeFault code (255 = no error)Read

Enable & remote start

MV 95 Control Register must be written to 1 before any value change is accepted.

Network setup

Watch out for

Cosmogas Argus boiler control via ProtoNode RER / LER BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

41 of 41 shown
Type
Multi-state
Access
Show
Cosmogas Argus boiler control via ProtoNode RER / LER BACnet Points List
DescriptionStates
AV1Modbus UnitsUnit flags: bit 0 °C/°F, bit 1 bar/psiWrite
AImin2StateBurner state (single-burner units)Read
AI3StatusBurner status (single-burner units)Read
AImin4Error CodeError code, 255 = no error (single-burner units)Read
AVmin5Boiler CH SPHeating setpoint, 68-179 °F°FWrite
AVmin6Boiler DHW SPIndirect water heater setpoint, 104-140 °F°FWrite
AVmin7CH ModeCentral heating modeWrite0=CH with RT, 1=CH with RT and outdoor reset, 2=CH with full outdoor reset, 3=CH with permanent heat demand, 4=CH with 0-10 Vcc input
AV8DHW ModeDomestic hot water modeWrite0=no DHW, 1=DHW store with sensor, 2=DHW store with thermostat, 3=N/A, 4=N/A, 5=N/A
AImin9Supply TempSupply temperature, burner 1 (master)Read
AImin10Return TempReturn temperature, burner 1 (master)Read
AI11DHW TempDHW tank temperatureRead
AI12Flue Gas TempFlue gas temperature, burner 1 (master)Read
AI13Heat Exchanger TempHeader temperature at the back of the heaterRead
AImin14Firing RateFiring rate (single-burner units)%Read
AI15Flame CurrentFlame current, burner 1 (master)Read
AI16Water PressureWater pressureRead
AI17Analog inAnalog input (doc: firing rate, single-burner units)Read
AI18CH pumpBurner 1 (master) motorized valve stateRead
AI19Dependent_1 StateState, burner 1 (master)Read
AI20Dependent_1 StatusStatus, burner 1 (master)Read
AI21Dependent_1 Error CodeError code, burner 1 (master)Read
AI22Dependent_1 Firing RateFiring rate, burner 1 (master)%Read
AI23Dependent_2 StateState, burner 2Read
AI24Dependent_2 StatusStatus, burner 2Read
AI25Dependent_2 Error CodeError code, burner 2Read
AI26Dependent_2 Firing RateFiring rate, burner 2%Read
AI27Dependent_3 StateState, burner 3Read
AI28Dependent_3 SatusStatus, burner 3Read
AI29Dependent_3 Error CodeError code, burner 3Read
AI30Dependent_3 Firing RateFiring rate, burner 3%Read
AI31Dependent_4 StateState, burner 4Read
AI32Dependent_4 StatusStatus, burner 4Read
AI33Dependent_4 Error CodeError code, burner 4Read
AI34Dependent_4 Firing RateFiring rate, burner 4%Read
AV35Spring Outdoor Air TempOutdoor reset: spring outdoor temperature (par. 2023)Write
AV36Spring Supply TempOutdoor reset: spring supply temperature (par. 2024)Write
AV37Winter Supply TempOutdoor reset: winter supply temperature (par. 2022)Write
AV38Warm Weather Shutdown TempWarm weather shutdown temperature (par. 2020)Write
AV39Night Setback TempNight setback temperature (par. 2027)Write
AI40Outdoor TempOutdoor temperatureRead
MVmin95Control RegisterSet to 1 before changing any valueWrite
Object ID lookup: Cosmogas Argus boiler control via ProtoNode RER / LER point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Argus boiler control via ProtoNode RER / LER and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Cosmogas Argus boiler control via ProtoNode RER / LER

How many BACnet points does the Cosmogas Argus boiler control via ProtoNode RER / LER have?

This list has 41 BACnet objects: 30 analog inputs, 10 analog values, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Cosmogas Argus boiler control via ProtoNode RER / LER BACnet points are writable?

11 of the 41 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Cosmogas Argus boiler control via ProtoNode RER / LER BACnet documentation?

The source is ProtoNode RER and ProtoNode LER Startup Guide - For Interfacing Cosmogas Products: Argus Managing/Standalone Boiler and Dependent Boiler (Instruction 62403594 R08), revision Jun. 06, 2017, published free by Cosmogas at https://www.literature.mestek.com/dms/RBI%20Water%20Heaters/Infinite%20Energy%202/ProtoCessor-FieldServer%20IOM%20(R08).pdf.

What are the minimum BACnet points to integrate the Cosmogas Argus boiler control via ProtoNode RER / LER?

Start with AV 7 CH Mode (Heating mode (RT, outdoor reset, 0-10 V...)); AV 5 Boiler CH SP (Heating setpoint, 68-179 °F); AV 6 Boiler DHW SP (Indirect DHW setpoint, 104-140 °F); MV 95 Control Register (Set to 1 before any write); AI 2 State (Burner state); AI 9 Supply Temp (Supply water temperature); AI 10 Return Temp (Return water temperature); AI 14 Firing Rate (Firing rate, %); AI 4 Error Code (Fault code (255 = no error)).

How do I enable BMS control of the Cosmogas Argus boiler control via ProtoNode RER / LER?

MV 95 Control Register must be written to 1 before any value change is accepted.

How do I check these points on the real Argus boiler control via ProtoNode RER / LER?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: ProtoNode RER and ProtoNode LER Startup Guide - For Interfacing Cosmogas Products: Argus Managing/Standalone Boiler and Dependent Boiler · Instruction 62403594 R08 · rev. Jun. 06, 2017. Object names, instances and units are reproduced as published; descriptions are our own.