Lighting relay panel (via BACnet gateway) · BACnet points list

Cooper Lighting Solutions Greengate 344640003 Relay Panel (ProtoNode) BACnet points list

Updated 11 November 2026

Short answer

A ProtoNode FPC-N34 reads a Greengate lighting relay panel over IP and presents it as a BACnet IP or BACnet MS/TP device. The 344640003 profile has 3 relays, 44 switch inputs, 64 remote points, 3 analog inputs, plus a panel reset. Relays and remote points are Binary Values; switch input states are Binary Inputs. Cooper marks this guide as discontinued (watermark dated 13-10-2023), so the list is for existing Greengate installations.

This page lists 115 BACnet objects for the Cooper Lighting Solutions Greengate 344640003 Relay Panel (ProtoNode) — 68 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Cooper Lighting Solutions’s own free documentation, linked below.

Manufacturer
Cooper Lighting Solutions
Model
Greengate 344640003 Relay Panel (ProtoNode)
Equipment
Lighting relay panel (via BACnet gateway)
Equipment type
Other equipment
BACnet objects
115 (68 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
344640003, Greengate 344640003, Greengate relay panel, ProtoNode FPC-N34
Source document
ProtoNode FPC-N34 and FPC-N35 Startup Guide for Cooper Lighting Solutions Greengate and iLUMIN · rev. Document Revision 1.H, Template Revision 53
Download CSV 115 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Cooper Lighting Solutions’s current documentation and the live device before use. Not official Cooper Lighting Solutions information. Terms of use.

BMS integration notes: Cooper Lighting Solutions Greengate 344640003 Relay Panel (ProtoNode)

Integration in brief

Command lighting relays through the Relay BVs, use the Remote BVs as the panel's remote inputs, and read the switch input BIs for local switch states.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1Relay01Relay 1 on/off commandWrite
BV 101Remote01Remote point 1 (panel remote input)Write
BI 1Switch01Switch input 1 statusRead
AI 1AI01Analog input 1 valueRead

Network setup

Watch out for

Cooper Lighting Solutions Greengate 344640003 Relay Panel (ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

115 of 115 shown
Type
Analog
Access
Show
Cooper Lighting Solutions Greengate 344640003 Relay Panel (ProtoNode) BACnet Points List
DescriptionStates
AImin1AI01Analog input valueRead
AI2AI02Analog input valueRead
AI3AI03Analog input valueRead
BImin1Switch01Switch input 1 statusRead
BI2Switch02Switch input 2 statusRead
BI3Switch03Switch input 3 statusRead
BI4Switch04Switch input 4 statusRead
BI5Switch05Switch input 5 statusRead
BI6Switch06Switch input 6 statusRead
BI7Switch07Switch input 7 statusRead
BI8Switch08Switch input 8 statusRead
BI9Switch09Switch input 9 statusRead
BI10Switch010Switch input 10 statusRead
BI11Switch011Switch input 11 statusRead
BI12Switch012Switch input 12 statusRead
BI13Switch013Switch input 13 statusRead
BI14Switch014Switch input 14 statusRead
BI15Switch015Switch input 15 statusRead
BI16Switch016Switch input 16 statusRead
BI17Switch017Switch input 17 statusRead
BI18Switch018Switch input 18 statusRead
BI19Switch019Switch input 19 statusRead
BI20Switch020Switch input 20 statusRead
BI21Switch021Switch input 21 statusRead
BI22Switch022Switch input 22 statusRead
BI23Switch023Switch input 23 statusRead
BI24Switch024Switch input 24 statusRead
BI25Switch025Switch input 25 statusRead
BI26Switch026Switch input 26 statusRead
BI27Switch027Switch input 27 statusRead
BI28Switch028Switch input 28 statusRead
BI29Switch029Switch input 29 statusRead
BI30Switch030Switch input 30 statusRead
BI31Switch031Switch input 31 statusRead
BI32Switch032Switch input 32 statusRead
BI33Switch033Switch input 33 statusRead
BI34Switch034Switch input 34 statusRead
BI35Switch035Switch input 35 statusRead
BI36Switch036Switch input 36 statusRead
BI37Switch037Switch input 37 statusRead
BI38Switch038Switch input 38 statusRead
BI39Switch039Switch input 39 statusRead
BI40Switch040Switch input 40 statusRead
BI41Switch041Switch input 41 statusRead
BI42Switch042Switch input 42 statusRead
BI43Switch043Switch input 43 statusRead
BI44Switch044Switch input 44 statusRead
BVmin1Relay01Relay 1 on/offWrite
BV2Relay02Relay 2 on/offWrite
BV3Relay03Relay 3 on/offWrite
BVmin101Remote01Remote point 1Write
BV102Remote02Remote point 2Write
BV103Remote03Remote point 3Write
BV104Remote04Remote point 4Write
BV105Remote05Remote point 5Write
BV106Remote06Remote point 6Write
BV107Remote07Remote point 7Write
BV108Remote08Remote point 8Write
BV109Remote09Remote point 9Write
BV110Remote010Remote point 10Write
BV111Remote011Remote point 11Write
BV112Remote012Remote point 12Write
BV113Remote013Remote point 13Write
BV114Remote014Remote point 14Write
BV115Remote015Remote point 15Write
BV116Remote016Remote point 16Write
BV117Remote017Remote point 17Write
BV118Remote018Remote point 18Write
BV119Remote019Remote point 19Write
BV120Remote020Remote point 20Write
BV121Remote021Remote point 21Write
BV122Remote022Remote point 22Write
BV123Remote023Remote point 23Write
BV124Remote024Remote point 24Write
BV125Remote025Remote point 25Write
BV126Remote026Remote point 26Write
BV127Remote027Remote point 27Write
BV128Remote028Remote point 28Write
BV129Remote029Remote point 29Write
BV130Remote030Remote point 30Write
BV131Remote031Remote point 31Write
BV132Remote032Remote point 32Write
BV133Remote033Remote point 33Write
BV134Remote034Remote point 34Write
BV135Remote035Remote point 35Write
BV136Remote036Remote point 36Write
BV137Remote037Remote point 37Write
BV138Remote038Remote point 38Write
BV139Remote039Remote point 39Write
BV140Remote040Remote point 40Write
BV141Remote041Remote point 41Write
BV142Remote042Remote point 42Write
BV143Remote043Remote point 43Write
BV144Remote044Remote point 44Write
BV145Remote045Remote point 45Write
BV146Remote046Remote point 46Write
BV147Remote047Remote point 47Write
BV148Remote048Remote point 48Write
BV149Remote049Remote point 49Write
BV150Remote050Remote point 50Write
BV151Remote051Remote point 51Write
BV152Remote052Remote point 52Write
BV153Remote053Remote point 53Write
BV154Remote054Remote point 54Write
BV155Remote055Remote point 55Write
BV156Remote056Remote point 56Write
BV157Remote057Remote point 57Write
BV158Remote058Remote point 58Write
BV159Remote059Remote point 59Write
BV160Remote060Remote point 60Write
BV161Remote061Remote point 61Write
BV162Remote062Remote point 62Write
BV163Remote063Remote point 63Write
BV164Remote064Remote point 64Write
BV1001ResetPanel reset commandWrite
Object ID lookup: Cooper Lighting Solutions Greengate 344640003 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Greengate 344640003 Relay Panel (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Cooper Lighting Solutions Greengate 344640003 Relay Panel (ProtoNode)

How many BACnet points does the Cooper Lighting Solutions Greengate 344640003 Relay Panel (ProtoNode) have?

This list has 115 BACnet objects: 3 analog inputs, 44 binary inputs, 68 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Cooper Lighting Solutions Greengate 344640003 Relay Panel (ProtoNode) BACnet points are writable?

68 of the 115 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Cooper Lighting Solutions Greengate 344640003 Relay Panel (ProtoNode) BACnet documentation?

The source is ProtoNode FPC-N34 and FPC-N35 Startup Guide for Cooper Lighting Solutions Greengate and iLUMIN, revision Document Revision 1.H, Template Revision 53, published free by Cooper Lighting Solutions at https://cooperlighting.com/api/assets/v1/file/Signify/content/1e56df1e31ec4bcc8d6bad40006c1682/ProtoNode-Startup-Guide-for-CLS.

What are the minimum BACnet points to integrate the Cooper Lighting Solutions Greengate 344640003 Relay Panel (ProtoNode)?

Start with BV 1 Relay01 (Relay 1 on/off command); BV 101 Remote01 (Remote point 1 (panel remote input)); BI 1 Switch01 (Switch input 1 status); AI 1 AI01 (Analog input 1 value).

How do I check these points on the real Greengate 344640003 Relay Panel (ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Cooper Lighting Solutions BACnet points lists

Source: ProtoNode FPC-N34 and FPC-N35 Startup Guide for Cooper Lighting Solutions Greengate and iLUMIN · rev. Document Revision 1.H, Template Revision 53. Object names, instances and units are reproduced as published; descriptions are our own.