Power and energy meter (BACnet MS/TP) · BACnet points list

Continental Control Systems WattNode BACnet electric power meter (WNC-...-BN) BACnet points list

Updated 4 November 2026

Short answer

The WattNode BACnet is a three-phase power and energy meter with BACnet MS/TP on board. It has a fixed object list: Analog Inputs for energy, power, voltage, current, frequency, power factor and demand; Analog Values for error history, diagnostics and setup (CT amps, demand period, PT ratio, gain and phase trims); Binary Values for CT polarity and reset commands; and Multi-state Values for service type, averaging and demand reset.

This page lists 107 BACnet objects for the Continental Control Systems WattNode BACnet electric power meter (WNC-...-BN) — 50 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Continental Control Systems’s own free documentation, linked below.

Manufacturer
Continental Control Systems
Model
WattNode BACnet electric power meter (WNC-...-BN)
Equipment
Power and energy meter (BACnet MS/TP)
Equipment type
Thermostats, sensors & meters
BACnet objects
107 (50 writable)
Transport
BACnet MS/TP
Firmware
1.13 and 1.20 (manual WNC-BN-1.20)
Default device instance
Meter serial number
Also known as
WattNode BACnet, WNC-3Y-208-BN, WNC-3Y-480-BN, WNC-3D-240-BN, RWNC-3Y-208-BN, WattNode Revenue BACnet, CCS WattNode, WattNode BACnet object list
Source document
WattNode BACnet Electric Power Meter - Reference Manual · WNC-BN-1.20 · rev. 2017-08-25
Download CSV 107 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Continental Control Systems’s current documentation and the live device before use. Not official Continental Control Systems information. Terms of use.

BMS integration notes: Continental Control Systems WattNode BACnet electric power meter (WNC-...-BN)

Integration in brief

Set the MS/TP address and baud rate on the DIP switch, then set CtAmpsA/B/C (AV 12-14) to the rated amps of the CTs and pick the service type (MV 0). After that, read total power (AI 3), net energy (AI 0 or the resettable AI 38), demand (AI 31) and the phase voltages and currents. ErrorStatus1 (AV 0) holds the newest error code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 3PowerSumTotal real power, WRead
AI 0EnergySumNRNet energy total, kWh, never resetsRead
AI 31DemandSumReal power demand, WRead
AI 15VoltAvgLNAverage line-to-neutral voltageRead
AI 24CurrentAPhase A current, ARead
AI 27PowerFactorAvgAverage power factorRead
AI 23FreqLine frequency, HzRead
AV 0ErrorStatus1Newest error code, 0 = no errorsRead

Network setup

Watch out for

Continental Control Systems WattNode BACnet electric power meter (WNC-...-BN) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

107 of 107 shown
Type
BinaryMulti-stateOther
Access
Show
Continental Control Systems WattNode BACnet electric power meter (WNC-...-BN) BACnet Points List
DescriptionStates
AImin0EnergySumNRNet energy, all phases, not resettablekWhRead
AI1EnergyPosSumNRPositive energy, all phases, not resettablekWhRead
AI2EnergyNegSumNRNegative energy, all phases, not resettablekWhRead
AImin3PowerSumReal power, sum of phasesWRead
AI4PowerAReal power, phase AWRead
AI5PowerBReal power, phase BWRead
AI6PowerCReal power, phase CWRead
AI7PowerReacSumReactive power, sum of phasesVARRead
AI8PowerReacAReactive power, phase AVARRead
AI9PowerReacBReactive power, phase BVARRead
AI10PowerReacCReactive power, phase CVARRead
AI11PowerAppSumApparent power, sum of phasesVARead
AI12PowerAppAApparent power, phase AVARead
AI13PowerAppBApparent power, phase BVARead
AI14PowerAppCApparent power, phase CVARead
AImin15VoltAvgLNAverage line-to-neutral voltageVRead
AI16VoltAVoltage, phase A to neutralVRead
AI17VoltBVoltage, phase B to neutralVRead
AI18VoltCVoltage, phase C to neutralVRead
AI19VoltAvgLLAverage line-to-line voltageVRead
AI20VoltABVoltage, A to BVRead
AI21VoltBCVoltage, B to CVRead
AI22VoltACVoltage, A to CVRead
AImin23FreqLine frequencyHzRead
AImin24CurrentACurrent, phase AARead
AI25CurrentBCurrent, phase BARead
AI26CurrentCCurrent, phase CARead
AImin27PowerFactorAvgAverage power factorRead
AI28PowerFactorAPower factor, phase ARead
AI29PowerFactorBPower factor, phase BRead
AI30PowerFactorCPower factor, phase CRead
AImin31DemandSumReal power demand, sum of phasesWRead
AI32DemandAppApparent power demand, sum of phasesWRead
AI33DemandAReal power demand, phase AWRead
AI34DemandBReal power demand, phase BWRead
AI35DemandCReal power demand, phase CWRead
AI36DemandMinLowest power sum demand (resettable)WWrite
AI37DemandMaxHighest power sum demand (resettable)WWrite
AI38EnergySumNet energy, all phases; resettable, can be presetkWhWrite
AI39EnergyPosSumPositive energy, all phases; resettable, can be presetkWhWrite
AI40EnergyNegSumNegative energy, all phases; resettable, can be presetkWhWrite
AI41EnergyANet energy, phase A; resettable, can be presetkWhWrite
AI42EnergyBNet energy, phase B; resettable, can be presetkWhWrite
AI43EnergyCNet energy, phase C; resettable, can be presetkWhWrite
AI44EnergyPosAPositive energy, phase A; resettable, can be presetkWhWrite
AI45EnergyPosBPositive energy, phase B; resettable, can be presetkWhWrite
AI46EnergyPosCPositive energy, phase C; resettable, can be presetkWhWrite
AI47EnergyNegANegative energy, phase A; resettable, can be presetkWhWrite
AI48EnergyNegBNegative energy, phase B; resettable, can be presetkWhWrite
AI49EnergyNegCNegative energy, phase C; resettable, can be presetkWhWrite
AI50EnergyReacSumReactive energy, sum of phases; resettable, can be presetkVARhWrite
AI51EnergyReacAReactive energy, phase A; resettable, can be presetkVARhWrite
AI52EnergyReacBReactive energy, phase B; resettable, can be presetkVARhWrite
AI53EnergyReacCReactive energy, phase C; resettable, can be presetkVARhWrite
AI54EnergyAppSumApparent energy, sum of phases; resettable, can be presetkVAhWrite
AI55EnergyAppAApparent energy, phase A; resettable, can be presetkVAhWrite
AI56EnergyAppBApparent energy, phase B; resettable, can be presetkVAhWrite
AI57EnergyAppCApparent energy, phase C; resettable, can be presetkVAhWrite
AI58ThermistorTempExternal thermistor temperature (Option TM1 only)°CRead
AVmin0ErrorStatus1Newest error code (0 = no errors)Read
AV1ErrorStatus2Error history entry 2Read
AV2ErrorStatus3Error history entry 3Read
AV3ErrorStatus4Error history entry 4Read
AV4ErrorStatus5Error history entry 5Read
AV5ErrorStatus6Error history entry 6Read
AV6ErrorStatus7Error history entry 7Read
AV7ErrorStatus8Oldest stored error codeRead
AV8UptimeSecsSeconds since last power-upsRead
AV9TotalSecsTotal seconds of operationsRead
AV10PowerFailCountNumber of power cyclesRead
AV11ConfigPasscodeOptional passcode that locks configurationWrite
AV12CtAmpsACT rated current, phase A (0-60000, default 5)AWrite
AV13CtAmpsBCT rated current, phase B (0-60000, default 5)AWrite
AV14CtAmpsCCT rated current, phase C (0-60000, default 5)AWrite
AV15DemPerMinsDemand period, 1-720 (default 15)minWrite
AV16DemSubintsNumber of demand subintervals, 1-10 (default 1)Write
AV17GainAdjustAPower/energy gain trim, phase A (5000-20000)1/10000Write
AV18GainAdjustBPower/energy gain trim, phase B (5000-20000)1/10000Write
AV19GainAdjustCPower/energy gain trim, phase C (5000-20000)1/10000Write
AV20PhaseAdjustACT phase angle trim, phase A (-8000 to 8000)0.001 degWrite
AV21PhaseAdjustBCT phase angle trim, phase B (-8000 to 8000)0.001 degWrite
AV22PhaseAdjustCCT phase angle trim, phase C (-8000 to 8000)0.001 degWrite
AV23CreepLimitMinimum power for non-zero readings (default 1500)Write
AV24PtRatioPotential transformer ratio (default 1.0)Write
AV25CalibrateFactory calibration object; not for customer useWrite
AV26Rs485CollisionCountRS-485 collision countRead
AV27Rs485FramingErrorCountRS-485 framing error countRead
AV28FrameSizeErrorCountInvalid MS/TP frame data length countRead
AV29HeaderCRCErrorCountHeader CRC error countRead
AV30DataCRCErrorCountData CRC error countRead
AV31IncompleteFrameCountReceived frames missing bytesRead
AV32Rs485BreakCountRS-485 break condition countRead
AV33BadByteCountUnexpected received bytes countRead
AV34LostTokenToken not received (timeout) countRead
AV35ThermistorCoeffASteinhart-Hart coefficient A (Option TM1)Write
AV36ThermistorCoeffBSteinhart-Hart coefficient B (Option TM1)Write
AV37ThermistorCoeffCSteinhart-Hart coefficient C (Option TM1)Write
BV0InvertCtAInvert CT polarity, phase AWrite0=Inactive, 1=Active
BV1InvertCtBInvert CT polarity, phase BWrite0=Inactive, 1=Active
BV2InvertCtCInvert CT polarity, phase CWrite0=Inactive, 1=Active
BV3ClearErrorsWrite active to clear all ErrorStatus objectsWrite0=Inactive, 1=Active
BV4ZeroEnergyWrite active to zero all resettable energy objectsWrite0=Inactive, 1=Active
BV5WinkShows a special LED pattern to find the meterWrite0=Inactive, 1=Active
MV0PhaseOffsetService type used for line-to-line voltages (default 4)Write1=Single-Phase, 2=3-Ph Grounded Delta, 3=3-Ph High-Leg Delta, 4=3-Ph Balanced, 5=1-Ph Center Neutral
MV1AveragingMeasurement averaging mode (default 2)Write1=Fastest, 2=Fast, 3=Medium, 4=Slow
MV2ZeroDemandRestart or reset demand measurementsWrite1=No Change, 2=Reset Min Max, 3=Start New Interval, 4=Reset and Start
FILE0FirmwareImageFile object for field firmware upgradesWrite
Object ID lookup: Continental Control Systems WattNode BACnet electric power meter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the WattNode BACnet electric power meter (WNC-...-BN) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Continental Control Systems WattNode BACnet electric power meter (WNC-...-BN)

How many BACnet points does the Continental Control Systems WattNode BACnet electric power meter (WNC-...-BN) have?

This list has 107 BACnet objects: 59 analog inputs, 38 analog values, 6 binary values, 1 file, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Continental Control Systems WattNode BACnet electric power meter (WNC-...-BN) BACnet points are writable?

50 of the 107 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Continental Control Systems WattNode BACnet electric power meter (WNC-...-BN) BACnet documentation?

The source is WattNode BACnet Electric Power Meter - Reference Manual (WNC-BN-1.20), revision 2017-08-25, published free by Continental Control Systems at https://ctlsys.com/wp-content/uploads/2017/09/WNC-BACnet-Manual-V1_20.pdf.

What are the minimum BACnet points to integrate the Continental Control Systems WattNode BACnet electric power meter (WNC-...-BN)?

Start with AI 3 PowerSum (Total real power, W); AI 0 EnergySumNR (Net energy total, kWh, never resets); AI 31 DemandSum (Real power demand, W); AI 15 VoltAvgLN (Average line-to-neutral voltage); AI 24 CurrentA (Phase A current, A); AI 27 PowerFactorAvg (Average power factor); AI 23 Freq (Line frequency, Hz); AV 0 ErrorStatus1 (Newest error code, 0 = no errors).

How do I check these points on the real WattNode BACnet electric power meter (WNC-...-BN)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: WattNode BACnet Electric Power Meter - Reference Manual · WNC-BN-1.20 · rev. 2017-08-25. Object names, instances and units are reproduced as published; descriptions are our own.