Easy BACnet
  1. Home
  2. BACnet points lists
  3. Circutor
  4. CVM-B50 power analyzer (BACnet IP)

Power meter (power analyzer) · BACnet points list

Circutor CVM-B50 power analyzer (BACnet IP) BACnet points list

Updated 12 November 2026

Short answer

The CVM-B50 is a panel power analyzer with Ethernet that serves BACnet IP. Its PICS lists 50 Analog Inputs: per-phase and three-phase voltage, current, power, power factor, THD, consumed and generated energy, neutral current and maximum demands. Unlike the CVM-C10 family it has demand objects for inductive and capacitive reactive power and no average-current or three-phase current demand object.

This page lists 50 BACnet objects for the Circutor CVM-B50 power analyzer (BACnet IP) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Circutor’s own free documentation, linked below.

Manufacturer
Circutor
Model
CVM-B50 power analyzer (BACnet IP)
Equipment
Power meter (power analyzer)
Equipment type
Thermostats, sensors & meters
BACnet objects
50 (0 writable)
Transport
BACnet IP
Firmware
Application software 1.0.3 (PICS dated 20/02/2026)
Default device instance
1
Also known as
CVM-B50, Circutor CVM-B50
Source document
CVM-B50 Power analyzer Instruction manual (Annex A, PICS map) · M487B01-03-25A
Download CSV 50 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Circutor’s current documentation and the live device before use. Not official Circutor information. Terms of use.

BMS integration notes: Circutor CVM-B50 power analyzer (BACnet IP)

Integration in brief

Set the BACnet device ID and port on the meter screen or web page, then read the power, energy and demand AIs. Nothing needs to be written.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 15ActPwOn3PhThree-phase active power, kWRead
AI 30ActEnergyActive energy consumed, kWhRead
AI 0Ph2NU1Voltage L1-NRead
AI 1Ph1CurrentCurrent L1Read
AI 19PwFactOn3PhThree-phase power factorRead
AI 48MaxDemand_kWMaximum demand, kWRead

Network setup

Watch out for

Circutor CVM-B50 power analyzer (BACnet IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

50 of 50 shown
Type
Analog
Show
Circutor CVM-B50 power analyzer (BACnet IP) BACnet Points List
DescriptionStates
AImin0Ph2NU1Voltage L1-NVRead
AImin1Ph1CurrentCurrent L1ARead
AI2ActPwrPh1Active power L1kWRead
AI3ReactPwrPh1Reactive power L1kvarRead
AI4PwrFactPh1Power factor L1Read
AI5Ph2NU2Voltage L2-NVRead
AI6Ph2CurrentCurrent L2ARead
AI7ActPwrPh2Active power L2kWRead
AI8ReactPwrPh2Reactive power L2kvarRead
AI9PwrFactPh2Power factor L2Read
AI10Ph2NU3Voltage L3-NVRead
AI11Ph3CurrentCurrent L3ARead
AI12ActPwrPh3Active power L3kWRead
AI13ReactPwrPh3Reactive power L3kvarRead
AI14PwrFactPh3Power factor L3Read
AImin15ActPwOn3PhThree-phase active powerkWRead
AI16InductPwOn3PhThree-phase inductive reactive powerkvarLRead
AI17CapPwOn3PhThree-phase capacitive reactive powerkvarCRead
AI18CosphiThree-phase cos phiRead
AImin19PwFactOn3PhThree-phase power factorRead
AI20FrequencyFrequencyHzRead
AI21Ph2PhU12Voltage L1-L2VRead
AI22Ph2PhU23Voltage L2-L3VRead
AI23Ph2PhU31Voltage L3-L1VRead
AI24THDVal_U1Voltage THD L1%THDRead
AI25THDVal_U2Voltage THD L2%THDRead
AI26THDVal_U3Voltage THD L3%THDRead
AI27THDVal_I1Current THD L1%THDRead
AI28THDVal_I2Current THD L2%THDRead
AI29THDVal_I3Current THD L3%THDRead
AImin30ActEnergyThree-phase active energy, consumedkWhRead
AI31InductEnergyThree-phase inductive reactive energy, consumedkvarLhRead
AI32CapEnergyThree-phase capacitive reactive energy, consumedkvarChRead
AI33AppEnergyThree-phase apparent energy, consumedkVAhRead
AI34ActEnergy_expThree-phase active energy, generatedkWhRead
AI35IndEnergy_expThree-phase inductive reactive energy, generatedkvarLhRead
AI36CapEnergy_expThree-phase capacitive reactive energy, generatedkvarChRead
AI37AppEnergy_expThree-phase apparent energy, generatedkVAhRead
AI38NeutralCurrentNeutral currentARead
AI39AppPwrPh1Apparent power L1kVARead
AI40AppPwrPh2Apparent power L2kVARead
AI41AppPwrPh3Apparent power L3kVARead
AI42AppPw3PhThree-phase apparent powerkVARead
AI43MaxDemand_A1Maximum demand, current L1ARead
AI44MaxDemand_A2Maximum demand, current L2ARead
AI45MaxDemand_A3Maximum demand, current L3ARead
AI46MaxDemand_kvarLMaximum demand, inductive reactive powerkvarLRead
AI47MaxDemand_kvarCMaximum demand, capacitive reactive powerkvarCRead
AImin48MaxDemand_kWMaximum demand, active powerkWRead
AI49MaxDemand_kVAMaximum demand, apparent powerkVARead
Object ID lookup: Circutor CVM-B50 power analyzer point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CVM-B50 power analyzer (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Circutor CVM-B50 power analyzer (BACnet IP)

How many BACnet points does the Circutor CVM-B50 power analyzer (BACnet IP) have?

This list has 50 BACnet objects: 50 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Circutor CVM-B50 power analyzer (BACnet IP) BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Circutor CVM-B50 power analyzer (BACnet IP) BACnet documentation?

The source is CVM-B50 Power analyzer Instruction manual (Annex A, PICS map) (M487B01-03-25A), published free by Circutor at https://docs.circutor.com/docs/M487B01-03.pdf.

What are the minimum BACnet points to integrate the Circutor CVM-B50 power analyzer (BACnet IP)?

Start with AI 15 ActPwOn3Ph (Three-phase active power, kW); AI 30 ActEnergy (Active energy consumed, kWh); AI 0 Ph2NU1 (Voltage L1-N); AI 1 Ph1Current (Current L1); AI 19 PwFactOn3Ph (Three-phase power factor); AI 48 MaxDemand_kW (Maximum demand, kW).

How do I check these points on the real CVM-B50 power analyzer (BACnet IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Circutor BACnet points lists

Source: CVM-B50 Power analyzer Instruction manual (Annex A, PICS map) · M487B01-03-25A. Object names, instances and units are reproduced as published; descriptions are our own.