Easy BACnet
  1. Home
  2. BACnet points lists
  3. BV-Control
  4. SLC24-16B SLC line 16-way BC24 master (fire / smoke damper controller)

Fire / smoke damper actuator controller (16-way line master) · BACnet points list

BV-Control SLC24-16B SLC line 16-way BC24 master (fire / smoke damper controller) BACnet points list

Updated 12 November 2026

Short answer

The SLC24-16B is a line master for up to 16 fire or smoke damper slave modules. Over BACnet it gives each slave a status, a damper position, a forced-control command, an active flag, a reset and eight live plus seven stored error flags. A heartbeat value must keep changing for BMS forced control to stay in effect.

This page lists 328 BACnet objects for the BV-Control SLC24-16B SLC line 16-way BC24 master (fire / smoke damper controller) — 49 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from BV-Control’s own free documentation, linked below.

Manufacturer
BV-Control
Model
SLC24-16B SLC line 16-way BC24 master (fire / smoke damper controller)
Equipment
Fire / smoke damper actuator controller (16-way line master)
Equipment type
Valves & actuators
BACnet objects
328 (49 writable)
Transport
—
Firmware
CDU software 2.0.0
Also known as
SLC24-16B, SLC24-16, SLC Linie 16-fach BC24 Master, BV-Control SLC
Source document
SLC24-16B - BACnet Objektauflistung · rev. November 2016
Download CSV 328 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against BV-Control’s current documentation and the live device before use. Not official BV-Control information. Terms of use.

BMS integration notes: BV-Control SLC24-16B SLC line 16-way BC24 master (fire / smoke damper controller)

Integration in brief

Read MV 0-15 for each slave's status and MV 16-31 for damper positions, and map the error BIs for alarms. To drive dampers from the BMS, write the BO forced-control commands and keep toggling BV 32 Control Heartbeat at least every 2 minutes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0Forced Control 1Forced control, slave 1 (BO 1-15 slaves 2-16)Command
BV 32Control HeartbeatHeartbeat; change at least every 2 minWrite
BV 16Reset 1Reset slave 1 after an error (BV 17-31 others)Write
MV 16Position 1Damper position, slave 1 (MV 17-31 others)Read
MV 0Status 1Slave 1 status (MV 1-15 others)Read
BI 242Relay All ClosedAll dampers closedRead
BI 243Relay All OpenAll dampers openRead
BI 240Relay OKMaster relay OKRead
BI 0Error BAE 1Slave 1 actuator error (BI 1-15 others)Read

Enable & remote start

BMS forced control (BO 0-15) stays active only while BV 32 Control Heartbeat keeps changing; otherwise local forced control applies.

Heartbeat & communication loss

BV 32 must change value at least once every two minutes or the master falls back to local forced control. The check can be turned off in the CDU software.

Network setup

Watch out for

BV-Control SLC24-16B SLC line 16-way BC24 master (fire / smoke damper controller) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

328 of 328 shown
Type
Multi-state
Access
Show
BV-Control SLC24-16B SLC line 16-way BC24 master (fire / smoke damper controller) BACnet Points List
DescriptionStates
MVmin0Status 1Slave 1 statusReadinit, init error, test, normal operation, warning, error
MV1Status 2Slave 2 statusReadinit, init error, test, normal operation, warning, error
MV2Status 3Slave 3 statusReadinit, init error, test, normal operation, warning, error
MV3Status 4Slave 4 statusReadinit, init error, test, normal operation, warning, error
MV4Status 5Slave 5 statusReadinit, init error, test, normal operation, warning, error
MV5Status 6Slave 6 statusReadinit, init error, test, normal operation, warning, error
MV6Status 7Slave 7 statusReadinit, init error, test, normal operation, warning, error
MV7Status 8Slave 8 statusReadinit, init error, test, normal operation, warning, error
MV8Status 9Slave 9 statusReadinit, init error, test, normal operation, warning, error
MV9Status 10Slave 10 statusReadinit, init error, test, normal operation, warning, error
MV10Status 11Slave 11 statusReadinit, init error, test, normal operation, warning, error
MV11Status 12Slave 12 statusReadinit, init error, test, normal operation, warning, error
MV12Status 13Slave 13 statusReadinit, init error, test, normal operation, warning, error
MV13Status 14Slave 14 statusReadinit, init error, test, normal operation, warning, error
MV14Status 15Slave 15 statusReadinit, init error, test, normal operation, warning, error
MV15Status 16Slave 16 statusReadinit, init error, test, normal operation, warning, error
MVmin16Position 1Slave 1 damper positionReadunknown, closed, open, closing, opening
MV17Position 2Slave 2 damper positionReadunknown, closed, open, closing, opening
MV18Position 3Slave 3 damper positionReadunknown, closed, open, closing, opening
MV19Position 4Slave 4 damper positionReadunknown, closed, open, closing, opening
MV20Position 5Slave 5 damper positionReadunknown, closed, open, closing, opening
MV21Position 6Slave 6 damper positionReadunknown, closed, open, closing, opening
MV22Position 7Slave 7 damper positionReadunknown, closed, open, closing, opening
MV23Position 8Slave 8 damper positionReadunknown, closed, open, closing, opening
MV24Position 9Slave 9 damper positionReadunknown, closed, open, closing, opening
MV25Position 10Slave 10 damper positionReadunknown, closed, open, closing, opening
MV26Position 11Slave 11 damper positionReadunknown, closed, open, closing, opening
MV27Position 12Slave 12 damper positionReadunknown, closed, open, closing, opening
MV28Position 13Slave 13 damper positionReadunknown, closed, open, closing, opening
MV29Position 14Slave 14 damper positionReadunknown, closed, open, closing, opening
MV30Position 15Slave 15 damper positionReadunknown, closed, open, closing, opening
MV31Position 16Slave 16 damper positionReadunknown, closed, open, closing, opening
BOmin0Forced Control 1Forced control command, slave 1Command
BO1Forced Control 2Forced control command, slave 2Command
BO2Forced Control 3Forced control command, slave 3Command
BO3Forced Control 4Forced control command, slave 4Command
BO4Forced Control 5Forced control command, slave 5Command
BO5Forced Control 6Forced control command, slave 6Command
BO6Forced Control 7Forced control command, slave 7Command
BO7Forced Control 8Forced control command, slave 8Command
BO8Forced Control 9Forced control command, slave 9Command
BO9Forced Control 10Forced control command, slave 10Command
BO10Forced Control 11Forced control command, slave 11Command
BO11Forced Control 12Forced control command, slave 12Command
BO12Forced Control 13Forced control command, slave 13Command
BO13Forced Control 14Forced control command, slave 14Command
BO14Forced Control 15Forced control command, slave 15Command
BO15Forced Control 16Forced control command, slave 16Command
BV0Slave Active 1Slave 1 configured as activeWrite
BV1Slave Active 2Slave 2 configured as activeWrite
BV2Slave Active 3Slave 3 configured as activeWrite
BV3Slave Active 4Slave 4 configured as activeWrite
BV4Slave Active 5Slave 5 configured as activeWrite
BV5Slave Active 6Slave 6 configured as activeWrite
BV6Slave Active 7Slave 7 configured as activeWrite
BV7Slave Active 8Slave 8 configured as activeWrite
BV8Slave Active 9Slave 9 configured as activeWrite
BV9Slave Active 10Slave 10 configured as activeWrite
BV10Slave Active 11Slave 11 configured as activeWrite
BV11Slave Active 12Slave 12 configured as activeWrite
BV12Slave Active 13Slave 13 configured as activeWrite
BV13Slave Active 14Slave 14 configured as activeWrite
BV14Slave Active 15Slave 15 configured as activeWrite
BV15Slave Active 16Slave 16 configured as activeWrite
BVmin16Reset 1Reset slave 1 (only with an active or stored error)Write
BV17Reset 2Reset slave 2 (only with an active or stored error)Write
BV18Reset 3Reset slave 3 (only with an active or stored error)Write
BV19Reset 4Reset slave 4 (only with an active or stored error)Write
BV20Reset 5Reset slave 5 (only with an active or stored error)Write
BV21Reset 6Reset slave 6 (only with an active or stored error)Write
BV22Reset 7Reset slave 7 (only with an active or stored error)Write
BV23Reset 8Reset slave 8 (only with an active or stored error)Write
BV24Reset 9Reset slave 9 (only with an active or stored error)Write
BV25Reset 10Reset slave 10 (only with an active or stored error)Write
BV26Reset 11Reset slave 11 (only with an active or stored error)Write
BV27Reset 12Reset slave 12 (only with an active or stored error)Write
BV28Reset 13Reset slave 13 (only with an active or stored error)Write
BV29Reset 14Reset slave 14 (only with an active or stored error)Write
BV30Reset 15Reset slave 15 (only with an active or stored error)Write
BV31Reset 16Reset slave 16 (only with an active or stored error)Write
BVmin32Control HeartbeatChange at least every 2 min to keep BMS forced controlWrite
BImin240Relay OKMaster relay OKRead
BI241Relay > 72 DegreesMaster relay above 72 degreesRead
BImin242Relay All ClosedAll dampers closedRead
BImin243Relay All OpenAll dampers openRead
BI244Local Forced ControlLocal forced control inputRead
BI245Local ResetLocal reset inputRead
BI246DI3Digital input 3Read
BImin0Error BAE 1Slave 1 actuator errorRead
BI1Error BAE 2Slave 2 actuator errorRead
BI2Error BAE 3Slave 3 actuator errorRead
BI3Error BAE 4Slave 4 actuator errorRead
BI4Error BAE 5Slave 5 actuator errorRead
BI5Error BAE 6Slave 6 actuator errorRead
BI6Error BAE 7Slave 7 actuator errorRead
BI7Error BAE 8Slave 8 actuator errorRead
BI8Error BAE 9Slave 9 actuator errorRead
BI9Error BAE 10Slave 10 actuator errorRead
BI10Error BAE 11Slave 11 actuator errorRead
BI11Error BAE 12Slave 12 actuator errorRead
BI12Error BAE 13Slave 13 actuator errorRead
BI13Error BAE 14Slave 14 actuator errorRead
BI14Error BAE 15Slave 15 actuator errorRead
BI15Error BAE 16Slave 16 actuator errorRead
BI16Error ORM 1Slave 1 smoke detector (ORM) errorRead
BI17Error ORM 2Slave 2 smoke detector (ORM) errorRead
BI18Error ORM 3Slave 3 smoke detector (ORM) errorRead
BI19Error ORM 4Slave 4 smoke detector (ORM) errorRead
BI20Error ORM 5Slave 5 smoke detector (ORM) errorRead
BI21Error ORM 6Slave 6 smoke detector (ORM) errorRead
BI22Error ORM 7Slave 7 smoke detector (ORM) errorRead
BI23Error ORM 8Slave 8 smoke detector (ORM) errorRead
BI24Error ORM 9Slave 9 smoke detector (ORM) errorRead
BI25Error ORM 10Slave 10 smoke detector (ORM) errorRead
BI26Error ORM 11Slave 11 smoke detector (ORM) errorRead
BI27Error ORM 12Slave 12 smoke detector (ORM) errorRead
BI28Error ORM 13Slave 13 smoke detector (ORM) errorRead
BI29Error ORM 14Slave 14 smoke detector (ORM) errorRead
BI30Error ORM 15Slave 15 smoke detector (ORM) errorRead
BI31Error ORM 16Slave 16 smoke detector (ORM) errorRead
BI32Error No Load 1Slave 1 no loadRead
BI33Error No Load 2Slave 2 no loadRead
BI34Error No Load 3Slave 3 no loadRead
BI35Error No Load 4Slave 4 no loadRead
BI36Error No Load 5Slave 5 no loadRead
BI37Error No Load 6Slave 6 no loadRead
BI38Error No Load 7Slave 7 no loadRead
BI39Error No Load 8Slave 8 no loadRead
BI40Error No Load 9Slave 9 no loadRead
BI41Error No Load 10Slave 10 no loadRead
BI42Error No Load 11Slave 11 no loadRead
BI43Error No Load 12Slave 12 no loadRead
BI44Error No Load 13Slave 13 no loadRead
BI45Error No Load 14Slave 14 no loadRead
BI46Error No Load 15Slave 15 no loadRead
BI47Error No Load 16Slave 16 no loadRead
BI48Error Mech 1Slave 1 mechanical faultRead
BI49Error Mech 2Slave 2 mechanical faultRead
BI50Error Mech 3Slave 3 mechanical faultRead
BI51Error Mech 4Slave 4 mechanical faultRead
BI52Error Mech 5Slave 5 mechanical faultRead
BI53Error Mech 6Slave 6 mechanical faultRead
BI54Error Mech 7Slave 7 mechanical faultRead
BI55Error Mech 8Slave 8 mechanical faultRead
BI56Error Mech 9Slave 9 mechanical faultRead
BI57Error Mech 10Slave 10 mechanical faultRead
BI58Error Mech 11Slave 11 mechanical faultRead
BI59Error Mech 12Slave 12 mechanical faultRead
BI60Error Mech 13Slave 13 mechanical faultRead
BI61Error Mech 14Slave 14 mechanical faultRead
BI62Error Mech 15Slave 15 mechanical faultRead
BI63Error Mech 16Slave 16 mechanical faultRead
BI64Error Overcurrent 1Slave 1 overcurrentRead
BI65Error Overcurrent 2Slave 2 overcurrentRead
BI66Error Overcurrent 3Slave 3 overcurrentRead
BI67Error Overcurrent 4Slave 4 overcurrentRead
BI68Error Overcurrent 5Slave 5 overcurrentRead
BI69Error Overcurrent 6Slave 6 overcurrentRead
BI70Error Overcurrent 7Slave 7 overcurrentRead
BI71Error Overcurrent 8Slave 8 overcurrentRead
BI72Error Overcurrent 9Slave 9 overcurrentRead
BI73Error Overcurrent 10Slave 10 overcurrentRead
BI74Error Overcurrent 11Slave 11 overcurrentRead
BI75Error Overcurrent 12Slave 12 overcurrentRead
BI76Error Overcurrent 13Slave 13 overcurrentRead
BI77Error Overcurrent 14Slave 14 overcurrentRead
BI78Error Overcurrent 15Slave 15 overcurrentRead
BI79Error Overcurrent 16Slave 16 overcurrentRead
BI80Error Comm Timeout 1Slave 1 communication timeoutRead
BI81Error Comm Timeout 2Slave 2 communication timeoutRead
BI82Error Comm Timeout 3Slave 3 communication timeoutRead
BI83Error Comm Timeout 4Slave 4 communication timeoutRead
BI84Error Comm Timeout 5Slave 5 communication timeoutRead
BI85Error Comm Timeout 6Slave 6 communication timeoutRead
BI86Error Comm Timeout 7Slave 7 communication timeoutRead
BI87Error Comm Timeout 8Slave 8 communication timeoutRead
BI88Error Comm Timeout 9Slave 9 communication timeoutRead
BI89Error Comm Timeout 10Slave 10 communication timeoutRead
BI90Error Comm Timeout 11Slave 11 communication timeoutRead
BI91Error Comm Timeout 12Slave 12 communication timeoutRead
BI92Error Comm Timeout 13Slave 13 communication timeoutRead
BI93Error Comm Timeout 14Slave 14 communication timeoutRead
BI94Error Comm Timeout 15Slave 15 communication timeoutRead
BI95Error Comm Timeout 16Slave 16 communication timeoutRead
BI96Error Not Connected 1Slave 1 not connectedRead
BI97Error Not Connected 2Slave 2 not connectedRead
BI98Error Not Connected 3Slave 3 not connectedRead
BI99Error Not Connected 4Slave 4 not connectedRead
BI100Error Not Connected 5Slave 5 not connectedRead
BI101Error Not Connected 6Slave 6 not connectedRead
BI102Error Not Connected 7Slave 7 not connectedRead
BI103Error Not Connected 8Slave 8 not connectedRead
BI104Error Not Connected 9Slave 9 not connectedRead
BI105Error Not Connected 10Slave 10 not connectedRead
BI106Error Not Connected 11Slave 11 not connectedRead
BI107Error Not Connected 12Slave 12 not connectedRead
BI108Error Not Connected 13Slave 13 not connectedRead
BI109Error Not Connected 14Slave 14 not connectedRead
BI110Error Not Connected 15Slave 15 not connectedRead
BI111Error Not Connected 16Slave 16 not connectedRead
BI112Error Init 1Slave 1 initialisation errorRead
BI113Error Init 2Slave 2 initialisation errorRead
BI114Error Init 3Slave 3 initialisation errorRead
BI115Error Init 4Slave 4 initialisation errorRead
BI116Error Init 5Slave 5 initialisation errorRead
BI117Error Init 6Slave 6 initialisation errorRead
BI118Error Init 7Slave 7 initialisation errorRead
BI119Error Init 8Slave 8 initialisation errorRead
BI120Error Init 9Slave 9 initialisation errorRead
BI121Error Init 10Slave 10 initialisation errorRead
BI122Error Init 11Slave 11 initialisation errorRead
BI123Error Init 12Slave 12 initialisation errorRead
BI124Error Init 13Slave 13 initialisation errorRead
BI125Error Init 14Slave 14 initialisation errorRead
BI126Error Init 15Slave 15 initialisation errorRead
BI127Error Init 16Slave 16 initialisation errorRead
BI128Mem Error BAE 1Slave 1 stored actuator errorRead
BI129Mem Error BAE 2Slave 2 stored actuator errorRead
BI130Mem Error BAE 3Slave 3 stored actuator errorRead
BI131Mem Error BAE 4Slave 4 stored actuator errorRead
BI132Mem Error BAE 5Slave 5 stored actuator errorRead
BI133Mem Error BAE 6Slave 6 stored actuator errorRead
BI134Mem Error BAE 7Slave 7 stored actuator errorRead
BI135Mem Error BAE 8Slave 8 stored actuator errorRead
BI136Mem Error BAE 9Slave 9 stored actuator errorRead
BI137Mem Error BAE 10Slave 10 stored actuator errorRead
BI138Mem Error BAE 11Slave 11 stored actuator errorRead
BI139Mem Error BAE 12Slave 12 stored actuator errorRead
BI140Mem Error BAE 13Slave 13 stored actuator errorRead
BI141Mem Error BAE 14Slave 14 stored actuator errorRead
BI142Mem Error BAE 15Slave 15 stored actuator errorRead
BI143Mem Error BAE 16Slave 16 stored actuator errorRead
BI144Mem Error ORM 1Slave 1 stored smoke detector (ORM) errorRead
BI145Mem Error ORM 2Slave 2 stored smoke detector (ORM) errorRead
BI146Mem Error ORM 3Slave 3 stored smoke detector (ORM) errorRead
BI147Mem Error ORM 4Slave 4 stored smoke detector (ORM) errorRead
BI148Mem Error ORM 5Slave 5 stored smoke detector (ORM) errorRead
BI149Mem Error ORM 6Slave 6 stored smoke detector (ORM) errorRead
BI150Mem Error ORM 7Slave 7 stored smoke detector (ORM) errorRead
BI151Mem Error ORM 8Slave 8 stored smoke detector (ORM) errorRead
BI152Mem Error ORM 9Slave 9 stored smoke detector (ORM) errorRead
BI153Mem Error ORM 10Slave 10 stored smoke detector (ORM) errorRead
BI154Mem Error ORM 11Slave 11 stored smoke detector (ORM) errorRead
BI155Mem Error ORM 12Slave 12 stored smoke detector (ORM) errorRead
BI156Mem Error ORM 13Slave 13 stored smoke detector (ORM) errorRead
BI157Mem Error ORM 14Slave 14 stored smoke detector (ORM) errorRead
BI158Mem Error ORM 15Slave 15 stored smoke detector (ORM) errorRead
BI159Mem Error ORM 16Slave 16 stored smoke detector (ORM) errorRead
BI160Mem Error No Load 1Slave 1 stored no loadRead
BI161Mem Error No Load 2Slave 2 stored no loadRead
BI162Mem Error No Load 3Slave 3 stored no loadRead
BI163Mem Error No Load 4Slave 4 stored no loadRead
BI164Mem Error No Load 5Slave 5 stored no loadRead
BI165Mem Error No Load 6Slave 6 stored no loadRead
BI166Mem Error No Load 7Slave 7 stored no loadRead
BI167Mem Error No Load 8Slave 8 stored no loadRead
BI168Mem Error No Load 9Slave 9 stored no loadRead
BI169Mem Error No Load 10Slave 10 stored no loadRead
BI170Mem Error No Load 11Slave 11 stored no loadRead
BI171Mem Error No Load 12Slave 12 stored no loadRead
BI172Mem Error No Load 13Slave 13 stored no loadRead
BI173Mem Error No Load 14Slave 14 stored no loadRead
BI174Mem Error No Load 15Slave 15 stored no loadRead
BI175Mem Error No Load 16Slave 16 stored no loadRead
BI176Mem Error Mech 1Slave 1 stored mechanical faultRead
BI177Mem Error Mech 2Slave 2 stored mechanical faultRead
BI178Mem Error Mech 3Slave 3 stored mechanical faultRead
BI179Mem Error Mech 4Slave 4 stored mechanical faultRead
BI180Mem Error Mech 5Slave 5 stored mechanical faultRead
BI181Mem Error Mech 6Slave 6 stored mechanical faultRead
BI182Mem Error Mech 7Slave 7 stored mechanical faultRead
BI183Mem Error Mech 8Slave 8 stored mechanical faultRead
BI184Mem Error Mech 9Slave 9 stored mechanical faultRead
BI185Mem Error Mech 10Slave 10 stored mechanical faultRead
BI186Mem Error Mech 11Slave 11 stored mechanical faultRead
BI187Mem Error Mech 12Slave 12 stored mechanical faultRead
BI188Mem Error Mech 13Slave 13 stored mechanical faultRead
BI189Mem Error Mech 14Slave 14 stored mechanical faultRead
BI190Mem Error Mech 15Slave 15 stored mechanical faultRead
BI191Mem Error Mech 16Slave 16 stored mechanical faultRead
BI192Mem Error Overcurrent 1Slave 1 stored overcurrentRead
BI193Mem Error Overcurrent 2Slave 2 stored overcurrentRead
BI194Mem Error Overcurrent 3Slave 3 stored overcurrentRead
BI195Mem Error Overcurrent 4Slave 4 stored overcurrentRead
BI196Mem Error Overcurrent 5Slave 5 stored overcurrentRead
BI197Mem Error Overcurrent 6Slave 6 stored overcurrentRead
BI198Mem Error Overcurrent 7Slave 7 stored overcurrentRead
BI199Mem Error Overcurrent 8Slave 8 stored overcurrentRead
BI200Mem Error Overcurrent 9Slave 9 stored overcurrentRead
BI201Mem Error Overcurrent 10Slave 10 stored overcurrentRead
BI202Mem Error Overcurrent 11Slave 11 stored overcurrentRead
BI203Mem Error Overcurrent 12Slave 12 stored overcurrentRead
BI204Mem Error Overcurrent 13Slave 13 stored overcurrentRead
BI205Mem Error Overcurrent 14Slave 14 stored overcurrentRead
BI206Mem Error Overcurrent 15Slave 15 stored overcurrentRead
BI207Mem Error Overcurrent 16Slave 16 stored overcurrentRead
BI208Mem Error Comm Timeout 1Slave 1 stored communication timeoutRead
BI209Mem Error Comm Timeout 2Slave 2 stored communication timeoutRead
BI210Mem Error Comm Timeout 3Slave 3 stored communication timeoutRead
BI211Mem Error Comm Timeout 4Slave 4 stored communication timeoutRead
BI212Mem Error Comm Timeout 5Slave 5 stored communication timeoutRead
BI213Mem Error Comm Timeout 6Slave 6 stored communication timeoutRead
BI214Mem Error Comm Timeout 7Slave 7 stored communication timeoutRead
BI215Mem Error Comm Timeout 8Slave 8 stored communication timeoutRead
BI216Mem Error Comm Timeout 9Slave 9 stored communication timeoutRead
BI217Mem Error Comm Timeout 10Slave 10 stored communication timeoutRead
BI218Mem Error Comm Timeout 11Slave 11 stored communication timeoutRead
BI219Mem Error Comm Timeout 12Slave 12 stored communication timeoutRead
BI220Mem Error Comm Timeout 13Slave 13 stored communication timeoutRead
BI221Mem Error Comm Timeout 14Slave 14 stored communication timeoutRead
BI222Mem Error Comm Timeout 15Slave 15 stored communication timeoutRead
BI223Mem Error Comm Timeout 16Slave 16 stored communication timeoutRead
BI224Mem Error Not Connected 1Slave 1 stored not connectedRead
BI225Mem Error Not Connected 2Slave 2 stored not connectedRead
BI226Mem Error Not Connected 3Slave 3 stored not connectedRead
BI227Mem Error Not Connected 4Slave 4 stored not connectedRead
BI228Mem Error Not Connected 5Slave 5 stored not connectedRead
BI229Mem Error Not Connected 6Slave 6 stored not connectedRead
BI230Mem Error Not Connected 7Slave 7 stored not connectedRead
BI231Mem Error Not Connected 8Slave 8 stored not connectedRead
BI232Mem Error Not Connected 9Slave 9 stored not connectedRead
BI233Mem Error Not Connected 10Slave 10 stored not connectedRead
BI234Mem Error Not Connected 11Slave 11 stored not connectedRead
BI235Mem Error Not Connected 12Slave 12 stored not connectedRead
BI236Mem Error Not Connected 13Slave 13 stored not connectedRead
BI237Mem Error Not Connected 14Slave 14 stored not connectedRead
BI238Mem Error Not Connected 15Slave 15 stored not connectedRead
BI239Mem Error Not Connected 16Slave 16 stored not connectedRead
Object ID lookup: BV-Control SLC24-16B point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SLC24-16B SLC line 16-way BC24 master (fire / smoke damper controller) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the BV-Control SLC24-16B SLC line 16-way BC24 master (fire / smoke damper controller)

How many BACnet points does the BV-Control SLC24-16B SLC line 16-way BC24 master (fire / smoke damper controller) have?

This list has 328 BACnet objects: 247 binary inputs, 16 binary outputs, 33 binary values, 32 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which BV-Control SLC24-16B SLC line 16-way BC24 master (fire / smoke damper controller) BACnet points are writable?

49 of the 328 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official BV-Control SLC24-16B SLC line 16-way BC24 master (fire / smoke damper controller) BACnet documentation?

The source is SLC24-16B - BACnet Objektauflistung, revision November 2016, published free by BV-Control at https://www.bv-control.ch/Base1/SLC/SLC24-16B/alt/BACnet%20SLC24-16.pdf.

What are the minimum BACnet points to integrate the BV-Control SLC24-16B SLC line 16-way BC24 master (fire / smoke damper controller)?

Start with BO 0 Forced Control 1 (Forced control, slave 1 (BO 1-15 slaves 2-16)); BV 32 Control Heartbeat (Heartbeat; change at least every 2 min); BV 16 Reset 1 (Reset slave 1 after an error (BV 17-31 others)); MV 16 Position 1 (Damper position, slave 1 (MV 17-31 others)); MV 0 Status 1 (Slave 1 status (MV 1-15 others)); BI 242 Relay All Closed (All dampers closed); BI 243 Relay All Open (All dampers open); BI 240 Relay OK (Master relay OK); BI 0 Error BAE 1 (Slave 1 actuator error (BI 1-15 others)).

How do I enable BMS control of the BV-Control SLC24-16B SLC line 16-way BC24 master (fire / smoke damper controller)?

BMS forced control (BO 0-15) stays active only while BV 32 Control Heartbeat keeps changing; otherwise local forced control applies.

Does the BV-Control SLC24-16B SLC line 16-way BC24 master (fire / smoke damper controller) need a BACnet heartbeat or have a communication timeout?

BV 32 must change value at least once every two minutes or the master falls back to local forced control. The check can be turned off in the CDU software.

How do I check these points on the real SLC24-16B SLC line 16-way BC24 master (fire / smoke damper controller)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: SLC24-16B - BACnet Objektauflistung · rev. November 2016. Object names, instances and units are reproduced as published; descriptions are our own.