Easy BACnet
  1. Home
  2. BACnet points lists
  3. Blue Ridge Technologies
  4. BR Series lighting controller (Lx5)

Other equipment (lighting relay panel controller) · BACnet points list

Blue Ridge Technologies BR Series lighting controller (Lx5) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The Lx5 is the controller in Blue Ridge Technologies lighting relay panels. Inputs (switches, occupancy sensors) control groups of relays, and BACnet MS/TP gives the BMS the same group-level control: each of the 60 groups has a command multistate value, binary and multistate status, a timer and a local schedule. The list adds six analog light-level inputs with their sensor ranges, the status of 60 relays and six common alarm flags.

This page lists 390 BACnet objects for the Blue Ridge Technologies BR Series lighting controller (Lx5) — 132 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Blue Ridge Technologies’s documentation hosted by Kele, not by Blue Ridge Technologies itself, so treat it as unofficial.

Manufacturer
Blue Ridge Technologies
Model
BR Series lighting controller (Lx5)
Equipment
Other equipment (lighting relay panel controller)
Equipment type
Other equipment
BACnet objects
390 (132 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
1320XX (XX = Lx5 network address)
Also known as
Lx5, Blue Ridge Lx5, BR Series Controller, BRT Relay Panel, Retrofit-Kit, Retrofit Interior, MAXIOM, Mezon, L2500, L2600, L3500, LP3500, Qwik-Kit Pro, BRT-Controller-ITG
Source document
BR Series Controller Integration Guide: Integration Information and Point List (BACnet MSTP and N2) · BRT-Controller-ITG-V10.01 · rev. 2012 (unofficial copy, hosted by Kele)
Download CSV 390 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Blue Ridge Technologies’s current documentation and the live device before use. Not official Blue Ridge Technologies information. Terms of use.

BMS integration notes: Blue Ridge Technologies BR Series lighting controller (Lx5)

Integration in brief

Command each lighting group with its MV n (4 = ON, 3 = OFF, 2 = OFF with flash warning, 1 = do nothing) and read back BV 100+n or MV 100+n. Use either the BMS command or the group's local schedule, not both. Relay status (BV 201-260) and light levels are read-only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1cmd_1Group 1 command: 4 = ON, 3 = OFF, 2 = OFF+flashWrite
BV 101b_groupstat_1Group 1 on/off statusRead
MV 101ms_groupstat_1Group 1 state and what switched itRead
AV 1timer_1Group 1 timer count-down, sRead
BV 201relay1stat_61Relay 1 statusRead
AV 101ai1_fc_61Light level input 1, fcRead
BV 4000000Module Halted AlarmController haltedRead

Enable & remote start

Each group is commanded by its MV (cmd_GG). Write 1 (Do Nothing / null) in manual-on sequences or sweeps that need repeated OFF commands.

Network setup

Watch out for

Blue Ridge Technologies BR Series lighting controller (Lx5) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

390 of 390 shown
Type
AnalogBinaryMulti-stateOther
Access
Show
Blue Ridge Technologies BR Series lighting controller (Lx5) BACnet Points List
DescriptionStates
SCH1schedule_schedule_1Local schedule for group 1Write
BVmin101b_groupstat_1Group 1 on/off statusRead0 = Group OFF, 1 = Group ON
MVmin1cmd_1Group 1 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MVmin101ms_groupstat_1Group 1 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AVmin1timer_1Group 1 timer count-down (0-64,800)sRead
SCH2schedule_schedule_2Local schedule for group 2Write
BV102b_groupstat_2Group 2 on/off statusRead0 = Group OFF, 1 = Group ON
MV2cmd_2Group 2 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV102ms_groupstat_2Group 2 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV2timer_2Group 2 timer count-down (0-64,800)sRead
SCH3schedule_schedule_3Local schedule for group 3Write
BV103b_groupstat_3Group 3 on/off statusRead0 = Group OFF, 1 = Group ON
MV3cmd_3Group 3 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV103ms_groupstat_3Group 3 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV3timer_3Group 3 timer count-down (0-64,800)sRead
SCH4schedule_schedule_4Local schedule for group 4Write
BV104b_groupstat_4Group 4 on/off statusRead0 = Group OFF, 1 = Group ON
MV4cmd_4Group 4 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV104ms_groupstat_4Group 4 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV4timer_4Group 4 timer count-down (0-64,800)sRead
SCH5schedule_schedule_5Local schedule for group 5Write
BV105b_groupstat_5Group 5 on/off statusRead0 = Group OFF, 1 = Group ON
MV5cmd_5Group 5 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV105ms_groupstat_5Group 5 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV5timer_5Group 5 timer count-down (0-64,800)sRead
SCH6schedule_schedule_6Local schedule for group 6Write
BV106b_groupstat_6Group 6 on/off statusRead0 = Group OFF, 1 = Group ON
MV6cmd_6Group 6 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV106ms_groupstat_6Group 6 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV6timer_6Group 6 timer count-down (0-64,800)sRead
SCH7schedule_schedule_7Local schedule for group 7Write
BV107b_groupstat_7Group 7 on/off statusRead0 = Group OFF, 1 = Group ON
MV7cmd_7Group 7 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV107ms_groupstat_7Group 7 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV7timer_7Group 7 timer count-down (0-64,800)sRead
SCH8schedule_schedule_8Local schedule for group 8Write
BV108b_groupstat_8Group 8 on/off statusRead0 = Group OFF, 1 = Group ON
MV8cmd_8Group 8 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV108ms_groupstat_8Group 8 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV8timer_8Group 8 timer count-down (0-64,800)sRead
SCH9schedule_schedule_9Local schedule for group 9Write
BV109b_groupstat_9Group 9 on/off statusRead0 = Group OFF, 1 = Group ON
MV9cmd_9Group 9 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV109ms_groupstat_9Group 9 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV9timer_9Group 9 timer count-down (0-64,800)sRead
SCH10schedule_schedule_10Local schedule for group 10Write
BV110b_groupstat_10Group 10 on/off statusRead0 = Group OFF, 1 = Group ON
MV10cmd_10Group 10 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV110ms_groupstat_10Group 10 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV10timer_10Group 10 timer count-down (0-64,800)sRead
SCH11schedule_schedule_11Local schedule for group 11Write
BV111b_groupstat_11Group 11 on/off statusRead0 = Group OFF, 1 = Group ON
MV11cmd_11Group 11 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV111ms_groupstat_11Group 11 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV11timer_11Group 11 timer count-down (0-64,800)sRead
SCH12schedule_schedule_12Local schedule for group 12Write
BV112b_groupstat_12Group 12 on/off statusRead0 = Group OFF, 1 = Group ON
MV12cmd_12Group 12 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV112ms_groupstat_12Group 12 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV12timer_12Group 12 timer count-down (0-64,800)sRead
SCH13schedule_schedule_13Local schedule for group 13Write
BV113b_groupstat_13Group 13 on/off statusRead0 = Group OFF, 1 = Group ON
MV13cmd_13Group 13 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV113ms_groupstat_13Group 13 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV13timer_13Group 13 timer count-down (0-64,800)sRead
SCH14schedule_schedule_14Local schedule for group 14Write
BV114b_groupstat_14Group 14 on/off statusRead0 = Group OFF, 1 = Group ON
MV14cmd_14Group 14 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV114ms_groupstat_14Group 14 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV14timer_14Group 14 timer count-down (0-64,800)sRead
SCH15schedule_schedule_15Local schedule for group 15Write
BV115b_groupstat_15Group 15 on/off statusRead0 = Group OFF, 1 = Group ON
MV15cmd_15Group 15 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV115ms_groupstat_15Group 15 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV15timer_15Group 15 timer count-down (0-64,800)sRead
SCH16schedule_schedule_16Local schedule for group 16Write
BV116b_groupstat_16Group 16 on/off statusRead0 = Group OFF, 1 = Group ON
MV16cmd_16Group 16 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV116ms_groupstat_16Group 16 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV16timer_16Group 16 timer count-down (0-64,800)sRead
SCH17schedule_schedule_17Local schedule for group 17Write
BV117b_groupstat_17Group 17 on/off statusRead0 = Group OFF, 1 = Group ON
MV17cmd_17Group 17 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV117ms_groupstat_17Group 17 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV17timer_17Group 17 timer count-down (0-64,800)sRead
SCH18schedule_schedule_18Local schedule for group 18Write
BV118b_groupstat_18Group 18 on/off statusRead0 = Group OFF, 1 = Group ON
MV18cmd_18Group 18 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV118ms_groupstat_18Group 18 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV18timer_18Group 18 timer count-down (0-64,800)sRead
SCH19schedule_schedule_19Local schedule for group 19Write
BV119b_groupstat_19Group 19 on/off statusRead0 = Group OFF, 1 = Group ON
MV19cmd_19Group 19 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV119ms_groupstat_19Group 19 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV19timer_19Group 19 timer count-down (0-64,800)sRead
SCH20schedule_schedule_20Local schedule for group 20Write
BV120b_groupstat_20Group 20 on/off statusRead0 = Group OFF, 1 = Group ON
MV20cmd_20Group 20 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV120ms_groupstat_20Group 20 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV20timer_20Group 20 timer count-down (0-64,800)sRead
SCH21schedule_schedule_21Local schedule for group 21Write
BV121b_groupstat_21Group 21 on/off statusRead0 = Group OFF, 1 = Group ON
MV21cmd_21Group 21 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV121ms_groupstat_21Group 21 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV21timer_21Group 21 timer count-down (0-64,800)sRead
SCH22schedule_schedule_22Local schedule for group 22Write
BV122b_groupstat_22Group 22 on/off statusRead0 = Group OFF, 1 = Group ON
MV22cmd_22Group 22 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV122ms_groupstat_22Group 22 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV22timer_22Group 22 timer count-down (0-64,800)sRead
SCH23schedule_schedule_23Local schedule for group 23Write
BV123b_groupstat_23Group 23 on/off statusRead0 = Group OFF, 1 = Group ON
MV23cmd_23Group 23 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV123ms_groupstat_23Group 23 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV23timer_23Group 23 timer count-down (0-64,800)sRead
SCH24schedule_schedule_24Local schedule for group 24Write
BV124b_groupstat_24Group 24 on/off statusRead0 = Group OFF, 1 = Group ON
MV24cmd_24Group 24 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV124ms_groupstat_24Group 24 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV24timer_24Group 24 timer count-down (0-64,800)sRead
SCH25schedule_schedule_25Local schedule for group 25Write
BV125b_groupstat_25Group 25 on/off statusRead0 = Group OFF, 1 = Group ON
MV25cmd_25Group 25 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV125ms_groupstat_25Group 25 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV25timer_25Group 25 timer count-down (0-64,800)sRead
SCH26schedule_schedule_26Local schedule for group 26Write
BV126b_groupstat_26Group 26 on/off statusRead0 = Group OFF, 1 = Group ON
MV26cmd_26Group 26 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV126ms_groupstat_26Group 26 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV26timer_26Group 26 timer count-down (0-64,800)sRead
SCH27schedule_schedule_27Local schedule for group 27Write
BV127b_groupstat_27Group 27 on/off statusRead0 = Group OFF, 1 = Group ON
MV27cmd_27Group 27 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV127ms_groupstat_27Group 27 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV27timer_27Group 27 timer count-down (0-64,800)sRead
SCH28schedule_schedule_28Local schedule for group 28Write
BV128b_groupstat_28Group 28 on/off statusRead0 = Group OFF, 1 = Group ON
MV28cmd_28Group 28 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV128ms_groupstat_28Group 28 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV28timer_28Group 28 timer count-down (0-64,800)sRead
SCH29schedule_schedule_29Local schedule for group 29Write
BV129b_groupstat_29Group 29 on/off statusRead0 = Group OFF, 1 = Group ON
MV29cmd_29Group 29 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV129ms_groupstat_29Group 29 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV29timer_29Group 29 timer count-down (0-64,800)sRead
SCH30schedule_schedule_30Local schedule for group 30Write
BV130b_groupstat_30Group 30 on/off statusRead0 = Group OFF, 1 = Group ON
MV30cmd_30Group 30 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV130ms_groupstat_30Group 30 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV30timer_30Group 30 timer count-down (0-64,800)sRead
SCH31schedule_schedule_31Local schedule for group 31Write
BV131b_groupstat_31Group 31 on/off statusRead0 = Group OFF, 1 = Group ON
MV31cmd_31Group 31 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV131ms_groupstat_31Group 31 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV31timer_31Group 31 timer count-down (0-64,800)sRead
SCH32schedule_schedule_32Local schedule for group 32Write
BV132b_groupstat_32Group 32 on/off statusRead0 = Group OFF, 1 = Group ON
MV32cmd_32Group 32 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV132ms_groupstat_32Group 32 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV32timer_32Group 32 timer count-down (0-64,800)sRead
SCH33schedule_schedule_33Local schedule for group 33Write
BV133b_groupstat_33Group 33 on/off statusRead0 = Group OFF, 1 = Group ON
MV33cmd_33Group 33 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV133ms_groupstat_33Group 33 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV33timer_33Group 33 timer count-down (0-64,800)sRead
SCH34schedule_schedule_34Local schedule for group 34Write
BV134b_groupstat_34Group 34 on/off statusRead0 = Group OFF, 1 = Group ON
MV34cmd_34Group 34 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV134ms_groupstat_34Group 34 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV34timer_34Group 34 timer count-down (0-64,800)sRead
SCH35schedule_schedule_35Local schedule for group 35Write
BV135b_groupstat_35Group 35 on/off statusRead0 = Group OFF, 1 = Group ON
MV35cmd_35Group 35 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV135ms_groupstat_35Group 35 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV35timer_35Group 35 timer count-down (0-64,800)sRead
SCH36schedule_schedule_36Local schedule for group 36Write
BV136b_groupstat_36Group 36 on/off statusRead0 = Group OFF, 1 = Group ON
MV36cmd_36Group 36 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV136ms_groupstat_36Group 36 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV36timer_36Group 36 timer count-down (0-64,800)sRead
SCH37schedule_schedule_37Local schedule for group 37Write
BV137b_groupstat_37Group 37 on/off statusRead0 = Group OFF, 1 = Group ON
MV37cmd_37Group 37 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV137ms_groupstat_37Group 37 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV37timer_37Group 37 timer count-down (0-64,800)sRead
SCH38schedule_schedule_38Local schedule for group 38Write
BV138b_groupstat_38Group 38 on/off statusRead0 = Group OFF, 1 = Group ON
MV38cmd_38Group 38 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV138ms_groupstat_38Group 38 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV38timer_38Group 38 timer count-down (0-64,800)sRead
SCH39schedule_schedule_39Local schedule for group 39Write
BV139b_groupstat_39Group 39 on/off statusRead0 = Group OFF, 1 = Group ON
MV39cmd_39Group 39 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV139ms_groupstat_39Group 39 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV39timer_39Group 39 timer count-down (0-64,800)sRead
SCH40schedule_schedule_40Local schedule for group 40Write
BV140b_groupstat_40Group 40 on/off statusRead0 = Group OFF, 1 = Group ON
MV40cmd_40Group 40 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV140ms_groupstat_40Group 40 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV40timer_40Group 40 timer count-down (0-64,800)sRead
SCH41schedule_schedule_41Local schedule for group 41Write
BV141b_groupstat_41Group 41 on/off statusRead0 = Group OFF, 1 = Group ON
MV41cmd_41Group 41 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV141ms_groupstat_41Group 41 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV41timer_41Group 41 timer count-down (0-64,800)sRead
SCH42schedule_schedule_42Local schedule for group 42Write
BV142b_groupstat_42Group 42 on/off statusRead0 = Group OFF, 1 = Group ON
MV42cmd_42Group 42 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV142ms_groupstat_42Group 42 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV42timer_42Group 42 timer count-down (0-64,800)sRead
SCH43schedule_schedule_43Local schedule for group 43Write
BV143b_groupstat_43Group 43 on/off statusRead0 = Group OFF, 1 = Group ON
MV43cmd_43Group 43 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV143ms_groupstat_43Group 43 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV43timer_43Group 43 timer count-down (0-64,800)sRead
SCH44schedule_schedule_44Local schedule for group 44Write
BV144b_groupstat_44Group 44 on/off statusRead0 = Group OFF, 1 = Group ON
MV44cmd_44Group 44 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV144ms_groupstat_44Group 44 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV44timer_44Group 44 timer count-down (0-64,800)sRead
SCH45schedule_schedule_45Local schedule for group 45Write
BV145b_groupstat_45Group 45 on/off statusRead0 = Group OFF, 1 = Group ON
MV45cmd_45Group 45 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV145ms_groupstat_45Group 45 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV45timer_45Group 45 timer count-down (0-64,800)sRead
SCH46schedule_schedule_46Local schedule for group 46Write
BV146b_groupstat_46Group 46 on/off statusRead0 = Group OFF, 1 = Group ON
MV46cmd_46Group 46 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV146ms_groupstat_46Group 46 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV46timer_46Group 46 timer count-down (0-64,800)sRead
SCH47schedule_schedule_47Local schedule for group 47Write
BV147b_groupstat_47Group 47 on/off statusRead0 = Group OFF, 1 = Group ON
MV47cmd_47Group 47 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV147ms_groupstat_47Group 47 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV47timer_47Group 47 timer count-down (0-64,800)sRead
SCH48schedule_schedule_48Local schedule for group 48Write
BV148b_groupstat_48Group 48 on/off statusRead0 = Group OFF, 1 = Group ON
MV48cmd_48Group 48 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV148ms_groupstat_48Group 48 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV48timer_48Group 48 timer count-down (0-64,800)sRead
SCH49schedule_schedule_49Local schedule for group 49Write
BV149b_groupstat_49Group 49 on/off statusRead0 = Group OFF, 1 = Group ON
MV49cmd_49Group 49 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV149ms_groupstat_49Group 49 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV49timer_49Group 49 timer count-down (0-64,800)sRead
SCH50schedule_schedule_50Local schedule for group 50Write
BV150b_groupstat_50Group 50 on/off statusRead0 = Group OFF, 1 = Group ON
MV50cmd_50Group 50 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV150ms_groupstat_50Group 50 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV50timer_50Group 50 timer count-down (0-64,800)sRead
SCH51schedule_schedule_51Local schedule for group 51Write
BV151b_groupstat_51Group 51 on/off statusRead0 = Group OFF, 1 = Group ON
MV51cmd_51Group 51 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV151ms_groupstat_51Group 51 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV51timer_51Group 51 timer count-down (0-64,800)sRead
SCH52schedule_schedule_52Local schedule for group 52Write
BV152b_groupstat_52Group 52 on/off statusRead0 = Group OFF, 1 = Group ON
MV52cmd_52Group 52 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV152ms_groupstat_52Group 52 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV52timer_52Group 52 timer count-down (0-64,800)sRead
SCH53schedule_schedule_53Local schedule for group 53Write
BV153b_groupstat_53Group 53 on/off statusRead0 = Group OFF, 1 = Group ON
MV53cmd_53Group 53 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV153ms_groupstat_53Group 53 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV53timer_53Group 53 timer count-down (0-64,800)sRead
SCH54schedule_schedule_54Local schedule for group 54Write
BV154b_groupstat_54Group 54 on/off statusRead0 = Group OFF, 1 = Group ON
MV54cmd_54Group 54 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV154ms_groupstat_54Group 54 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV54timer_54Group 54 timer count-down (0-64,800)sRead
SCH55schedule_schedule_55Local schedule for group 55Write
BV155b_groupstat_55Group 55 on/off statusRead0 = Group OFF, 1 = Group ON
MV55cmd_55Group 55 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV155ms_groupstat_55Group 55 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV55timer_55Group 55 timer count-down (0-64,800)sRead
SCH56schedule_schedule_56Local schedule for group 56Write
BV156b_groupstat_56Group 56 on/off statusRead0 = Group OFF, 1 = Group ON
MV56cmd_56Group 56 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV156ms_groupstat_56Group 56 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV56timer_56Group 56 timer count-down (0-64,800)sRead
SCH57schedule_schedule_57Local schedule for group 57Write
BV157b_groupstat_57Group 57 on/off statusRead0 = Group OFF, 1 = Group ON
MV57cmd_57Group 57 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV157ms_groupstat_57Group 57 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV57timer_57Group 57 timer count-down (0-64,800)sRead
SCH58schedule_schedule_58Local schedule for group 58Write
BV158b_groupstat_58Group 58 on/off statusRead0 = Group OFF, 1 = Group ON
MV58cmd_58Group 58 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV158ms_groupstat_58Group 58 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV58timer_58Group 58 timer count-down (0-64,800)sRead
SCH59schedule_schedule_59Local schedule for group 59Write
BV159b_groupstat_59Group 59 on/off statusRead0 = Group OFF, 1 = Group ON
MV59cmd_59Group 59 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV159ms_groupstat_59Group 59 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV59timer_59Group 59 timer count-down (0-64,800)sRead
SCH60schedule_schedule_60Local schedule for group 60Write
BV160b_groupstat_60Group 60 on/off statusRead0 = Group OFF, 1 = Group ON
MV60cmd_60Group 60 commandWrite1 = Do Nothing, 2 = Command Group OFF with Flash Warning, 3 = Command Group OFF, 4 = Command Group ON
MV160ms_groupstat_60Group 60 state and sourceRead1 = OFF by serial command or local schedule, 2 = ON by serial command or local schedule, 3 = OFF by override switch, 4 = ON by override switch, 5 = ON by override switch with timer count, 6 = ON by manual override on Lx5, 7 = OFF by manual override on Lx5
AV60timer_60Group 60 timer count-down (0-64,800)sRead
AVmin101ai1_fc_61Analog Input 1 light levelfcRead
AV111ai1_lux_61Analog Input 1 light levellxRead
AV121ai1_minAnalog Input 1 sensor minimum (0-1000)Write
AV131ai1_maxAnalog Input 1 sensor maximum (0-1000)Write
AV102ai2_fc_61Analog Input 2 light levelfcRead
AV112ai2_lux_61Analog Input 2 light levellxRead
AV122ai2_minAnalog Input 2 sensor minimum (0-1000)Write
AV132ai2_maxAnalog Input 2 sensor maximum (0-1000)Write
AV103ai3_fc_61Analog Input 3 light levelfcRead
AV113ai3_lux_61Analog Input 3 light levellxRead
AV123ai3_minAnalog Input 3 sensor minimum (0-1000)Write
AV133ai3_maxAnalog Input 3 sensor maximum (0-1000)Write
AV104ai4_fc_61Analog Input 4 light levelfcRead
AV114ai4_lux_61Analog Input 4 light levellxRead
AV124ai4_minAnalog Input 4 sensor minimum (0-1000)Write
AV134ai4_maxAnalog Input 4 sensor maximum (0-1000)Write
AV105ai5_fc_61Analog Input 5 light levelfcRead
AV115ai5_lux_61Analog Input 5 light levellxRead
AV125ai5_minAnalog Input 5 sensor minimum (0-1000)Write
AV135ai5_maxAnalog Input 5 sensor maximum (0-1000)Write
AV106ai6_fc_61Analog Input 6 light levelfcRead
AV116ai6_lux_61Analog Input 6 light levellxRead
AV126ai6_minAnalog Input 6 sensor minimum (0-1000)Write
AV136ai6_maxAnalog Input 6 sensor maximum (0-1000)Write
BVmin201relay1stat_61Relay 1 StatusRead0 = Relay OFF, 1 = Relay ON
BV202relay2stat_61Relay 2 StatusRead0 = Relay OFF, 1 = Relay ON
BV203relay3stat_61Relay 3 StatusRead0 = Relay OFF, 1 = Relay ON
BV204relay4stat_61Relay 4 StatusRead0 = Relay OFF, 1 = Relay ON
BV205relay5stat_61Relay 5 StatusRead0 = Relay OFF, 1 = Relay ON
BV206relay6stat_61Relay 6 StatusRead0 = Relay OFF, 1 = Relay ON
BV207relay7stat_61Relay 7 StatusRead0 = Relay OFF, 1 = Relay ON
BV208relay8stat_61Relay 8 StatusRead0 = Relay OFF, 1 = Relay ON
BV209relay9stat_61Relay 9 StatusRead0 = Relay OFF, 1 = Relay ON
BV210relay10stat_61Relay 10 StatusRead0 = Relay OFF, 1 = Relay ON
BV211relay11stat_61Relay 11 StatusRead0 = Relay OFF, 1 = Relay ON
BV212relay12stat_61Relay 12 StatusRead0 = Relay OFF, 1 = Relay ON
BV213relay13stat_61Relay 13 StatusRead0 = Relay OFF, 1 = Relay ON
BV214relay14stat_61Relay 14 StatusRead0 = Relay OFF, 1 = Relay ON
BV215relay15stat_61Relay 15 StatusRead0 = Relay OFF, 1 = Relay ON
BV216relay16stat_61Relay 16 StatusRead0 = Relay OFF, 1 = Relay ON
BV217relay17stat_61Relay 17 StatusRead0 = Relay OFF, 1 = Relay ON
BV218relay18stat_61Relay 18 StatusRead0 = Relay OFF, 1 = Relay ON
BV219relay19stat_61Relay 19 StatusRead0 = Relay OFF, 1 = Relay ON
BV220relay20stat_61Relay 20 StatusRead0 = Relay OFF, 1 = Relay ON
BV221relay21stat_61Relay 21 StatusRead0 = Relay OFF, 1 = Relay ON
BV222relay22stat_61Relay 22 StatusRead0 = Relay OFF, 1 = Relay ON
BV223relay23stat_61Relay 23 StatusRead0 = Relay OFF, 1 = Relay ON
BV224relay24stat_61Relay 24 StatusRead0 = Relay OFF, 1 = Relay ON
BV225relay25stat_61Relay 25 StatusRead0 = Relay OFF, 1 = Relay ON
BV226relay26stat_61Relay 26 StatusRead0 = Relay OFF, 1 = Relay ON
BV227relay27stat_61Relay 27 StatusRead0 = Relay OFF, 1 = Relay ON
BV228relay28stat_61Relay 28 StatusRead0 = Relay OFF, 1 = Relay ON
BV229relay29stat_61Relay 29 StatusRead0 = Relay OFF, 1 = Relay ON
BV230relay30stat_61Relay 30 StatusRead0 = Relay OFF, 1 = Relay ON
BV231relay31stat_61Relay 31 StatusRead0 = Relay OFF, 1 = Relay ON
BV232relay32stat_61Relay 32 StatusRead0 = Relay OFF, 1 = Relay ON
BV233relay33stat_61Relay 33 StatusRead0 = Relay OFF, 1 = Relay ON
BV234relay34stat_61Relay 34 StatusRead0 = Relay OFF, 1 = Relay ON
BV235relay35stat_61Relay 35 StatusRead0 = Relay OFF, 1 = Relay ON
BV236relay36stat_61Relay 36 StatusRead0 = Relay OFF, 1 = Relay ON
BV237relay37stat_61Relay 37 StatusRead0 = Relay OFF, 1 = Relay ON
BV238relay38stat_61Relay 38 StatusRead0 = Relay OFF, 1 = Relay ON
BV239relay39stat_61Relay 39 StatusRead0 = Relay OFF, 1 = Relay ON
BV240relay40stat_61Relay 40 StatusRead0 = Relay OFF, 1 = Relay ON
BV241relay41stat_61Relay 41 StatusRead0 = Relay OFF, 1 = Relay ON
BV242relay42stat_61Relay 42 StatusRead0 = Relay OFF, 1 = Relay ON
BV243relay43stat_61Relay 43 StatusRead0 = Relay OFF, 1 = Relay ON
BV244relay44stat_61Relay 44 StatusRead0 = Relay OFF, 1 = Relay ON
BV245relay45stat_61Relay 45 StatusRead0 = Relay OFF, 1 = Relay ON
BV246relay46stat_61Relay 46 StatusRead0 = Relay OFF, 1 = Relay ON
BV247relay47stat_61Relay 47 StatusRead0 = Relay OFF, 1 = Relay ON
BV248relay48stat_61Relay 48 StatusRead0 = Relay OFF, 1 = Relay ON
BV249relay49stat_61Relay 49 StatusRead0 = Relay OFF, 1 = Relay ON
BV250relay50stat_61Relay 50 StatusRead0 = Relay OFF, 1 = Relay ON
BV251relay51stat_61Relay 51 StatusRead0 = Relay OFF, 1 = Relay ON
BV252relay52stat_61Relay 52 StatusRead0 = Relay OFF, 1 = Relay ON
BV253relay53stat_61Relay 53 StatusRead0 = Relay OFF, 1 = Relay ON
BV254relay54stat_61Relay 54 StatusRead0 = Relay OFF, 1 = Relay ON
BV255relay55stat_61Relay 55 StatusRead0 = Relay OFF, 1 = Relay ON
BV256relay56stat_61Relay 56 StatusRead0 = Relay OFF, 1 = Relay ON
BV257relay57stat_61Relay 57 StatusRead0 = Relay OFF, 1 = Relay ON
BV258relay58stat_61Relay 58 StatusRead0 = Relay OFF, 1 = Relay ON
BV259relay59stat_61Relay 59 StatusRead0 = Relay OFF, 1 = Relay ON
BV260relay60stat_61Relay 60 StatusRead0 = Relay OFF, 1 = Relay ON
BVmin4000000Module Halted AlarmCommon alarm: Module haltedRead
BV4000001All Programs Stopped AlarmCommon alarm: All programs stoppedRead
BV4000002Duplicate Address AlarmCommon alarm: Duplicate network addressRead
BV4000003Locked I/O AlarmCommon alarm: Locked I/ORead
BV4000004Control Program AlarmCommon alarm: Control program alarmRead
BV4000005Program Stopped AlarmCommon alarm: Program stoppedRead
Object ID lookup: Blue Ridge Technologies BR Series lighting controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BR Series lighting controller (Lx5) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Blue Ridge Technologies BR Series lighting controller (Lx5)

How many BACnet points does the Blue Ridge Technologies BR Series lighting controller (Lx5) have?

This list has 390 BACnet objects: 84 analog values, 126 binary values, 60 schedules, 120 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Blue Ridge Technologies BR Series lighting controller (Lx5) BACnet points are writable?

132 of the 390 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Blue Ridge Technologies BR Series lighting controller (Lx5) BACnet documentation?

Blue Ridge Technologies does not publish it on its own website. This list comes from BR Series Controller Integration Guide: Integration Information and Point List (BACnet MSTP and N2) (BRT-Controller-ITG-V10.01), revision 2012, a copy hosted by Kele at https://assets.kele.com/Catalog/12%20Lighting%20Controls/PDFs/BRT_Controller_manual.pdf. Ask Blue Ridge Technologies or its representative for the current revision.

What are the minimum BACnet points to integrate the Blue Ridge Technologies BR Series lighting controller (Lx5)?

Start with MV 1 cmd_1 (Group 1 command: 4 = ON, 3 = OFF, 2 = OFF+flash); BV 101 b_groupstat_1 (Group 1 on/off status); MV 101 ms_groupstat_1 (Group 1 state and what switched it); AV 1 timer_1 (Group 1 timer count-down, s); BV 201 relay1stat_61 (Relay 1 status); AV 101 ai1_fc_61 (Light level input 1, fc); BV 4000000 Module Halted Alarm (Controller halted).

How do I enable BMS control of the Blue Ridge Technologies BR Series lighting controller (Lx5)?

Each group is commanded by its MV (cmd_GG). Write 1 (Do Nothing / null) in manual-on sequences or sweeps that need repeated OFF commands.

How do I check these points on the real BR Series lighting controller (Lx5)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: BR Series Controller Integration Guide: Integration Information and Point List (BACnet MSTP and N2) · BRT-Controller-ITG-V10.01 · rev. 2012. Object names, instances and units are reproduced as published; descriptions are our own.