Easy BACnet
  1. Home
  2. BACnet points lists
  3. Bacharach
  4. MultiZone gas monitor (ProtoNode BACnet Protocol Converter Kit)

Refrigerant leak monitor (gas sensor) via BACnet gateway · BACnet points list

Bacharach MultiZone gas monitor (ProtoNode BACnet Protocol Converter Kit) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

A FieldServer ProtoNode reads the MultiZone monitor over Modbus and serves its data as 66 BACnet objects: the active zone, a fault value, and for each of 16 zones the gas reading in ppm, the refrigerant type and an alarm value. Each zone's refrigerant type appears twice, as a read-only AI and a writable AV.

This page lists 66 BACnet objects for the Bacharach MultiZone gas monitor (ProtoNode BACnet Protocol Converter Kit) — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Bacharach’s documentation hosted by Kele, not by Bacharach itself, so treat it as unofficial.

Manufacturer
Bacharach
Model
MultiZone gas monitor (ProtoNode BACnet Protocol Converter Kit)
Equipment
Refrigerant leak monitor (gas sensor) via BACnet gateway
Equipment type
Thermostats, sensors & meters
BACnet objects
66 (16 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
Bacharach MZ, MultiZone MZ, 3015-5609, 3015-5705, Bacharach BACnet Protocol Converter Kit
Source document
BACnet Protocol Converter Kit for Use with Bacharach MultiZone Gas Monitors - Installation Manual · 3015-5609 · rev. Revision 1, June 2012 (unofficial copy, hosted by Kele)
Download CSV 66 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Bacharach’s current documentation and the live device before use. Not official Bacharach information. Terms of use.

BMS integration notes: Bacharach MultiZone gas monitor (ProtoNode BACnet Protocol Converter Kit)

Integration in brief

Read the PPM and Alarm objects for each zone in use and the unit Fault value. The refrigerant type per zone is normally set once during commissioning.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1Active ZoneZone now being sampledRead
AI 3PPM [1]Zone 1 refrigerant concentration, ppmRead
AI 6Alarm [1]Zone 1 alarm statusRead
AI 2FaultMonitor faultRead

Network setup

Watch out for

Bacharach MultiZone gas monitor (ProtoNode BACnet Protocol Converter Kit) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

66 of 66 shown
Type
Access
Show
Bacharach MultiZone gas monitor (ProtoNode BACnet Protocol Converter Kit) BACnet Points List
DescriptionStates
AImin1Active ZoneZone currently being sampledRead
AImin2FaultMonitor fault statusRead
AImin3PPM [1]Zone 1 gas concentrationppmRead
AI4Refrig Type [1]Zone 1 refrigerant type (read)Read
AV5Refrig Type [1]Zone 1 refrigerant type (write)Write
AImin6Alarm [1]Zone 1 alarm statusRead
AI7PPM [2]Zone 2 gas concentrationppmRead
AI8Refrig Type [2]Zone 2 refrigerant type (read)Read
AV9Refrig Type [2]Zone 2 refrigerant type (write)Write
AI10Alarm [2]Zone 2 alarm statusRead
AI11PPM [3]Zone 3 gas concentrationppmRead
AI12Refrig Type [3]Zone 3 refrigerant type (read)Read
AV13Refrig Type [3]Zone 3 refrigerant type (write)Write
AI14Alarm [3]Zone 3 alarm statusRead
AI15PPM [4]Zone 4 gas concentrationppmRead
AI16Refrig Type [4]Zone 4 refrigerant type (read)Read
AV17Refrig Type [4]Zone 4 refrigerant type (write)Write
AI18Alarm [4]Zone 4 alarm statusRead
AI19PPM [5]Zone 5 gas concentrationppmRead
AI20Refrig Type [5]Zone 5 refrigerant type (read)Read
AV21Refrig Type [5]Zone 5 refrigerant type (write)Write
AI22Alarm [5]Zone 5 alarm statusRead
AI23PPM [6]Zone 6 gas concentrationppmRead
AI24Refrig Type [6]Zone 6 refrigerant type (read)Read
AV25Refrig Type [6]Zone 6 refrigerant type (write)Write
AI26Alarm [6]Zone 6 alarm statusRead
AI27PPM [7]Zone 7 gas concentrationppmRead
AI28Refrig Type [7]Zone 7 refrigerant type (read)Read
AV29Refrig Type [7]Zone 7 refrigerant type (write)Write
AI30Alarm [7]Zone 7 alarm statusRead
AI31PPM [8]Zone 8 gas concentrationppmRead
AI32Refrig Type [8]Zone 8 refrigerant type (read)Read
AV33Refrig Type [8]Zone 8 refrigerant type (write)Write
AI34Alarm [8]Zone 8 alarm statusRead
AI35PPM [9]Zone 9 gas concentrationppmRead
AI36Refrig Type [9]Zone 9 refrigerant type (read)Read
AV37Refrig Type [9]Zone 9 refrigerant type (write)Write
AI38Alarm [9]Zone 9 alarm statusRead
AI39PPM [10]Zone 10 gas concentrationppmRead
AI40Refrig Type [10]Zone 10 refrigerant type (read)Read
AV41Refrig Type [10]Zone 10 refrigerant type (write)Write
AI42Alarm [10]Zone 10 alarm statusRead
AI43PPM [11]Zone 11 gas concentrationppmRead
AI44Refrig Type [11]Zone 11 refrigerant type (read)Read
AV45Refrig Type [11]Zone 11 refrigerant type (write)Write
AI46Alarm [11]Zone 11 alarm statusRead
AI47PPM [12]Zone 12 gas concentrationppmRead
AI48Refrig Type [12]Zone 12 refrigerant type (read)Read
AV49Refrig Type [12]Zone 12 refrigerant type (write)Write
AI50Alarm [12]Zone 12 alarm statusRead
AI51PPM [13]Zone 13 gas concentrationppmRead
AI52Refrig Type [13]Zone 13 refrigerant type (read)Read
AV53Refrig Type [13]Zone 13 refrigerant type (write)Write
AI54Alarm [13]Zone 13 alarm statusRead
AI55PPM [14]Zone 14 gas concentrationppmRead
AI56Refrig Type [14]Zone 14 refrigerant type (read)Read
AV57Refrig Type [14]Zone 14 refrigerant type (write)Write
AI58Alarm [14]Zone 14 alarm statusRead
AI59PPM [15]Zone 15 gas concentrationppmRead
AI60Refrig Type [15]Zone 15 refrigerant type (read)Read
AV61Refrig Type [15]Zone 15 refrigerant type (write)Write
AI62Alarm [15]Zone 15 alarm statusRead
AI63PPM [16]Zone 16 gas concentrationppmRead
AI64Refrig Type [16]Zone 16 refrigerant type (read)Read
AV65Refrig Type [16]Zone 16 refrigerant type (write)Write
AI66Alarm [16]Zone 16 alarm statusRead
Object ID lookup: Bacharach MultiZone gas monitor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MultiZone gas monitor (ProtoNode BACnet Protocol Converter Kit) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Bacharach MultiZone gas monitor (ProtoNode BACnet Protocol Converter Kit)

How many BACnet points does the Bacharach MultiZone gas monitor (ProtoNode BACnet Protocol Converter Kit) have?

This list has 66 BACnet objects: 50 analog inputs, 16 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Bacharach MultiZone gas monitor (ProtoNode BACnet Protocol Converter Kit) BACnet points are writable?

16 of the 66 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Bacharach MultiZone gas monitor (ProtoNode BACnet Protocol Converter Kit) BACnet documentation?

Bacharach does not publish it on its own website. This list comes from BACnet Protocol Converter Kit for Use with Bacharach MultiZone Gas Monitors - Installation Manual (3015-5609), revision Revision 1, June 2012, a copy hosted by Kele at https://assets.kele.com/Catalog/08%20Gas_Specialty_Sensors/PDFs/3015-5705%20Bacnet%20Manual.pdf. Ask Bacharach or its representative for the current revision.

What are the minimum BACnet points to integrate the Bacharach MultiZone gas monitor (ProtoNode BACnet Protocol Converter Kit)?

Start with AI 1 Active Zone (Zone now being sampled); AI 3 PPM [1] (Zone 1 refrigerant concentration, ppm); AI 6 Alarm [1] (Zone 1 alarm status); AI 2 Fault (Monitor fault).

How do I check these points on the real MultiZone gas monitor (ProtoNode BACnet Protocol Converter Kit)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Bacharach BACnet points lists

Source: BACnet Protocol Converter Kit for Use with Bacharach MultiZone Gas Monitors - Installation Manual · 3015-5609 · rev. Revision 1, June 2012. Object names, instances and units are reproduced as published; descriptions are our own.