- Qalcosonic E3 / E4 heat meter BACnet MS/TP module
Heat / energy meter · BACnet points list
Axioma Metering Qalcosonic E3 / E4 heat meter BACnet MS/TP module BACnet points list
Updated 12 November 2026Unofficial source
A plug-in BACnet MS/TP module for the Qalcosonic E3/E4 heat meter. It polls the meter (default every 300 s) and serves 14 read-only Analog Inputs: heat and cooling energy, tariff registers, volume, two pulse inputs, power, flow, flow/return/differential temperature and the meter info code.
This page lists 14 BACnet objects for the Axioma Metering Qalcosonic E3 / E4 heat meter BACnet MS/TP module — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Axioma Metering’s documentation hosted by AxFlow, not by Axioma Metering itself, so treat it as unofficial.
- Manufacturer
- Axioma Metering
- Model
- Qalcosonic E3 / E4 heat meter BACnet MS/TP module
- Equipment
- Heat / energy meter
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 14 (0 writable)
- Transport
- BACnet MS/TP
- Firmware
- Firmware 0.8.3, application 2.1
- Also known as
- Qalcosonic E3, Qalcosonic E4, Axioma BACnet MS/TP base module, Axioma heat meter BACnet
- Source document
- BACnet MS/TP Module for Modular Heat Meter Qalcosonic E3/E4 · rev. 2022-01-03 (unofficial copy, hosted by AxFlow)
Reference only, provided as-is: verify against Axioma Metering’s current documentation and the live device before use. Not official Axioma Metering information. Terms of use.
BMS integration notes: Axioma Metering Qalcosonic E3 / E4 heat meter BACnet MS/TP module
Read-only meter: poll heat energy, power, flow and the two temperatures, and alarm on the info code.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 1 | Accumulated heat energy (E1) | Heat energy total | Read |
| AI 11 | Actual power | Thermal power | Read |
| AI 14 | Actual flow | Flow rate | Read |
| AI 19 | Flow temperature / Temperature 1 | Supply temperature | Read |
| AI 20 | Return temperature / Temperature 2 | Return temperature | Read |
| AI 30 | Info code (Error code) | Meter error / info code | Read |
Network setup
- MAC 1-127 follows the meter's M-Bus address; baud 9600-115200 (default 38400), 8E1.
- Data refresh interval defaults to 300 s (configurable).
- A RESET button restores module defaults after a bad configuration.
Watch out for
- Values update only at the module's polling interval, not continuously.
Axioma Metering Qalcosonic E3 / E4 heat meter BACnet MS/TP module BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | Meter serial number | Meter serial number | Read | ||
| AImin | 1 | Accumulated heat energy (E1) | Heat energy total | kWh / MWh | Read | |
| AI | 2 | Accumulated cooling energy (E2) / Energy 1 | Cooling energy total (or energy 1) | kWh / MWh | Read | |
| AI | 3 | Tariff 1 / Energy 2 | Tariff 1 register (or energy 2) | kWh / MWh | Read | |
| AI | 4 | Tariff 2 | Tariff 2 register | kWh / MWh | Read | |
| AI | 5 | Accumulated volume (V1) | Volume total | l / m³ | Read | |
| AI | 6 | Pulse input A accumulated / Accumulated volume (V2) | Pulse input A total | l / m³ / kWh / MWh | Read | |
| AI | 8 | Pulse input B accumulated / Accumulated volume (V3) | Pulse input B total | l / m³ / kWh / MWh | Read | |
| AImin | 11 | Actual power | Current thermal power | W / kW / MW | Read | |
| AImin | 14 | Actual flow | Current flow rate | l/h / m³/h | Read | |
| AImin | 19 | Flow temperature / Temperature 1 | Flow (supply) temperature | °C | Read | |
| AImin | 20 | Return temperature / Temperature 2 | Return temperature | °C | Read | |
| AI | 21 | Differential temperature | Flow minus return temperature | K | Read | |
| AImin | 30 | Info code (Error code) | Meter info / error code | Read |
No points match these filters.
Object ID lookup: Axioma Metering Qalcosonic E3 / E4 heat meter BACnet MS/TP module point IDs by name
AI0Meter serial numberAI1Accumulated heat energy (E1)AI2Accumulated cooling energy (E2) / Energy 1AI3Tariff 1 / Energy 2AI4Tariff 2AI5Accumulated volume (V1)AI6Pulse input A accumulated / Accumulated volume (V2)AI8Pulse input B accumulated / Accumulated volume (V3)AI11Actual powerAI14Actual flowAI19Flow temperature / Temperature 1AI20Return temperature / Temperature 2AI21Differential temperatureAI30Info code (Error code)
Integration notes
- Instances are sparse (AI 0-6, 8, 11, 14, 19-21, 30) as printed in the object table; the Object_List example on p4 numbers them differently, the table IDs are used here.
- Energy units follow the meter set-up (kWh or MWh); pulse inputs may be volume or energy.
- Vendor ID 1006. Device instance = last 5 digits of the meter serial number.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Qalcosonic E3 / E4 heat meter BACnet MS/TP module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Axioma Metering Qalcosonic E3 / E4 heat meter BACnet MS/TP module
How many BACnet points does the Axioma Metering Qalcosonic E3 / E4 heat meter BACnet MS/TP module have?
This list has 14 BACnet objects: 14 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Axioma Metering Qalcosonic E3 / E4 heat meter BACnet MS/TP module BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official Axioma Metering Qalcosonic E3 / E4 heat meter BACnet MS/TP module BACnet documentation?
Axioma Metering does not publish it on its own website. This list comes from BACnet MS/TP Module for Modular Heat Meter Qalcosonic E3/E4, revision 2022-01-03, a copy hosted by AxFlow at https://www.axflow.com/globalassets/catalog/ds/axioma-qalcosonic-e3-e4-bacnet-protocol.pdf. Ask Axioma Metering or its representative for the current revision.
What are the minimum BACnet points to integrate the Axioma Metering Qalcosonic E3 / E4 heat meter BACnet MS/TP module?
Start with AI 1 Accumulated heat energy (E1) (Heat energy total); AI 11 Actual power (Thermal power); AI 14 Actual flow (Flow rate); AI 19 Flow temperature / Temperature 1 (Supply temperature); AI 20 Return temperature / Temperature 2 (Return temperature); AI 30 Info code (Error code) (Meter error / info code).
How do I check these points on the real Qalcosonic E3 / E4 heat meter BACnet MS/TP module?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: BACnet MS/TP Module for Modular Heat Meter Qalcosonic E3/E4 · rev. 2022-01-03. Object names, instances and units are reproduced as published; descriptions are our own.