Gas detection controller (sensor monitor) · BACnet points list

Armstrong Monitoring AMC-1DBx digital gas monitor (BACnet IP) BACnet points list

Updated 12 November 2026

Short answer

The AMC-1DBx is a gas detection controller for large sensor networks. Over BACnet IP it exposes 4,119 fixed objects: a system state, then for each possible sensor a raw value, a cause state and a status string, and the same kind of blocks for relays, zones and analog outputs, plus file objects for logs, database and firmware. Configuration is not available over BACnet.

This page lists 25 BACnet objects for the Armstrong Monitoring AMC-1DBx digital gas monitor (BACnet IP) — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Armstrong Monitoring’s own free documentation, linked below.

Manufacturer
Armstrong Monitoring
Model
AMC-1DBx digital gas monitor (BACnet IP)
Equipment
Gas detection controller (sensor monitor)
Equipment type
Thermostats, sensors & meters
BACnet objects
25 (6 writable)
Transport
BACnet IP
Firmware
Not stated
Default device instance
677003
Also known as
AMC-1DBx, AMC-1DB, 1DBx, AMC 1DBX, Armstrong 1DBx, Digital Gas Monitor 1DBx
Source document
Digital Monitor 1DBx Series BAS Interface Manual · rev. 2015-06-25
Download CSV 25 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Armstrong Monitoring’s current documentation and the live device before use. Not official Armstrong Monitoring information. Terms of use.

BMS integration notes: Armstrong Monitoring AMC-1DBx digital gas monitor (BACnet IP)

Integration in brief

Watch MSI 0 for the overall state (32 = All Clear; the Relay bit means an alarm event). Then read only the sensors, relays and zones actually installed, using the device counts in OS 0, rather than discovering all 4,119 objects. COV on the cause-state objects avoids heavy polling.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MI 0System Status StateMonitor state; 32 = All ClearRead
AI 0Sensors Raw InputSensor 1 gas level, mV (800-4000 = 0-100 %)Read
MI 1Sensor Cause StateSensor 1 alarm/fail state; 32 = All ClearRead
BI 0Relay Current ConditionRelay 1 state; check PolarityRead
MI 1245Zone Cause StateZone 1 alarm/fail state; 32 = All ClearRead

Network setup

Watch out for

Armstrong Monitoring AMC-1DBx digital gas monitor (BACnet IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

25 of 25 shown
Type
AnalogBinaryMulti-state
Access
Show
Armstrong Monitoring AMC-1DBx digital gas monitor (BACnet IP) BACnet Points List
DescriptionStates
MImin0System Status StateMonitor state, 6-bit mask: Failed, HourGlass, Relay, Acknowledge, PowerUpRead32 = All Clear; values 1-31 = bit mask [Failed, HourGlass, Relay, Acknowledge, PowerUp]
OSV0System Status Info.9-byte system info: state, DIP disables, delays, device countsRead
AImin0Sensors Raw InputSensor 001 raw value (AI 0-987 = sensors 1-988); 800-4000 mV = 0-100 % FSmVRead
MImin1Sensor Cause StateSensor 001 cause (MSI 1-988 = sensors 1-988)Read32 = All Clear; values 1-31 = bit mask [Delay Timer, Fail, Alarm3, Alarm2, Alarm1]
OSV1Sensor Status Info.Sensor 001 info (OS 1-988): availability, state, assigned relaysRead
BImin0Relay Current ConditionRelay 001 condition (BI 0-255 = relays 1-256); read with PolarityRead0=Off/Inactive, 1=On/Active (Polarity Normal); inverted when Polarity Reverse
MI989Relay Cause StateRelay 001 cause (MSI 989-1244 = relays 1-256)Read32 = All Clear; values 1-31 = bit mask [Run Timer, Dew, Schedule, Zone, Sensor]
OSV989Relay Status Info.Relay 001 info (OS 989-1244): availability, state, alarm counts, run timersRead
MImin1245Zone Cause StateZone 001 cause (MSI 1245-1372 = zones 1-128)Read32 = All Clear; values 1-31 = bit mask [Schedule, Fail, Alarm3, Alarm2, Alarm1]
OSV1245Zone Status Info.Zone 001 info (OS 1245-1372): availability, state, relays, analog outputRead
AI988Analog Output Raw OutputAnalog output 001 level (AI 988-1115 = outputs 1-128); 0-4000 mVmVRead
FILE0RAM1:\push.fwCommand file: write to start a firmware upgradeWrite
FILE1RAM1:\pull.dbCommand file: write to export the databaseWrite
FILE2RAM1:\push.dbCommand file: write to load a databaseWrite
FILE3RAM1:\10aquila.elf.csumFirmware image checksumWrite
FILE4RAM1:\10aquila.elf.rbinFirmware imageWrite
FILE5RAM1:\amc-1db.adfConfiguration databaseWrite
FILE6C:\system.logSystem logRead
FILE7C:\sensor.logSensor logRead
FILE8C:\relay.logRelay logRead
FILE9C:\alarm.logAlarm logRead
FILE10C:\admin.logAdmin logRead
FILE11C:\security.logSecurity logRead
FILE12C:\comm.logCommunication logRead
FILE13C:\print.logPrint logRead
Object ID lookup: Armstrong Monitoring AMC-1DBx point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AMC-1DBx digital gas monitor (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Armstrong Monitoring AMC-1DBx digital gas monitor (BACnet IP)

How many BACnet points does the Armstrong Monitoring AMC-1DBx digital gas monitor (BACnet IP) have?

This list has 25 BACnet objects: 2 analog inputs, 1 binary input, 14 files, 4 multi-state inputs, 4 octetstring values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Armstrong Monitoring AMC-1DBx digital gas monitor (BACnet IP) BACnet points are writable?

6 of the 25 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Armstrong Monitoring AMC-1DBx digital gas monitor (BACnet IP) BACnet documentation?

The source is Digital Monitor 1DBx Series BAS Interface Manual, revision 2015-06-25, published free by Armstrong Monitoring at https://armstrongmonitoring.com/wp-content/uploads/2022/01/AMC-1DBx-BAS-Interface-Manual.pdf.

What are the minimum BACnet points to integrate the Armstrong Monitoring AMC-1DBx digital gas monitor (BACnet IP)?

Start with MI 0 System Status State (Monitor state; 32 = All Clear); AI 0 Sensors Raw Input (Sensor 1 gas level, mV (800-4000 = 0-100 %)); MI 1 Sensor Cause State (Sensor 1 alarm/fail state; 32 = All Clear); BI 0 Relay Current Condition (Relay 1 state; check Polarity); MI 1245 Zone Cause State (Zone 1 alarm/fail state; 32 = All Clear).

How do I check these points on the real AMC-1DBx digital gas monitor (BACnet IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Digital Monitor 1DBx Series BAS Interface Manual · rev. 2015-06-25. Object names, instances and units are reproduced as published; descriptions are our own.