Room pressure monitor · BACnet points list
Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP) BACnet points list
Updated 12 November 2026Unofficial source
The LUME is a wall-mounted touch-screen monitor for room differential pressure. On BACnet MS/TP it reports room pressure, pressure mode, alarm and caution status, and lets the BMS set the alarm limits and delays and switch or override the room mode. Its four universal inputs and three outputs appear as AI/BI/AO/BO objects named after their configured use.
This page lists 27 BACnet objects for the Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP) — 14 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Antec Controls’s documentation hosted by Holyoake (Price/Antec distributor), not by Antec Controls itself, so treat it as unofficial.
- Manufacturer
- Antec Controls
- Model
- LUME-1-X room pressure monitor (BACnet MS/TP)
- Equipment
- Room pressure monitor
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 27 (14 writable)
- Transport
- BACnet MS/TP
- Firmware
- Points list v1.0.0 or newer
- Also known as
- LUME, LUME-1-X, LUME11, LUME room pressure monitor, Antec LUME, Price LUME, 275288
- Source document
- LUME-1-X Room Pressure Monitor Product Submittal, BACnet Points List v1.0.0 or newer · 275288 Rev. B · rev. 2023-06-28 (unofficial copy, hosted by Holyoake (Price/Antec distributor))
Reference only, provided as-is: verify against Antec Controls’s current documentation and the live device before use. Not official Antec Controls information. Terms of use.
BMS integration notes: Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP)
Set the MS/TP address and baud on the device, then read AV 101 room pressure, MV 101 pressure mode and MV 102 alarm status. Write MV 3 or use the SCH 1 schedule to switch room modes, and adjust the pressure alarm limits on AV 102 and AV 104 if needed.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 3 | Room Mode Override | Room mode override from the BMS | Write |
| AV 101 | [Room Name] Pressure | Room differential pressure | Read |
| MV 2 | Room Mode | Current room mode | Write |
| MV 101 | [Room Name] Pressure Mode | Pressure mode: 1 positive, 2 negative | Read |
| MV 1 | Audible Alarm | Audible alarm: on, off or muted | Read |
| MV 103 | [Room Name] Caution Status | Room caution status | Read |
| MV 102 | [Room Name] Alarm Status | Room alarm status (low, high, input, door) | Read |
Enable & remote start
BACnet commands take priority over normal operation (control priority 1 = BACnet).
Network setup
- BACnet MS/TP (RS-485), 9600, 19200, 38400 or 76800 baud; B-AAC, BTL listed.
- Ethernet ports are for laptop configuration only.
- See the LUME manual for setup of inputs, outputs and room modes.
Watch out for
- Object names change with the configured room and I/O names, so rediscover after reconfiguring.
- Unused I/O objects and disabled alarm objects are hidden.
Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | AI1 – [AI1 Input Name] | Universal input 1 as analog; name, units and use set at configuration | Dynamic | Read | |
| AI | 2 | AI2 – [AI2 Input Name] | Universal input 2 as analog; name, units and use set at configuration | Dynamic | Read | |
| AI | 3 | AI3 – [AI3 Input Name] | Universal input 3 as analog; name, units and use set at configuration | Dynamic | Read | |
| AI | 4 | AI4 – [AI4 Input Name] | Universal input 4 as analog; name, units and use set at configuration | Dynamic | Read | |
| BI | 1 | BI1 – [BI1 Input Name] | Universal input 1 as binary (contact) | Read | Open/Closed | |
| BI | 2 | BI2 – [BI2 Input Name] | Universal input 2 as binary (contact) | Read | Open/Closed | |
| BI | 3 | BI3 – [BI3 Input Name] | Universal input 3 as binary (contact) | Read | Open/Closed | |
| BI | 4 | BI4 – [BI4 Input Name] | Universal input 4 as binary (contact) | Read | Open/Closed | |
| AO | 1 | AO1 – [AO1 Output Name] | Analog output, 0-10 V, configurable use | V | Write | |
| BO | 1 | BO1 – [BO1 Output Name] | Binary output 1, configurable use | Write | Active/Inactive | |
| BO | 2 | BO2 – [BO2 Output Name] | Binary output 2, configurable use | Write | Active/Inactive | |
| AVmin | 101 | [Room Name] Pressure | Room pressure, -5.0 to 5.0 in.w.c. | in.w.c. or Pa | Read | |
| AV | 102 | [Room Name] Low Pressure Alarm | Low pressure alarm setpoint (+/-) | in.w.c. or Pa | Write | |
| AV | 103 | [Room Name] Low Pressure Delay | Low pressure alarm delay, 0-600 | s | Write | |
| AV | 104 | [Room Name] High Pressure Alarm | High pressure alarm setpoint (+/-) | in.w.c. or Pa | Write | |
| AV | 105 | [Room Name] High Pressure Delay | High pressure alarm delay, 0-600 | s | Write | |
| MVmin | 1 | Audible Alarm | Room audible alarm state | Read | 1=On, 2=Off, 3=Muted | |
| MVmin | 2 | Room Mode | Current room mode | Write | 1=[Room Mode 1 Name], 2=[Room Mode 2 Name] | |
| MVmin | 3 | Room Mode Override | Room mode override | Write | 1=[Room Mode 1 Name], 2=[Room Mode 2 Name] | |
| MV | 99 | Firmware Update Status | Firmware update state | Write | 1=Idle, 2=Start Firmware Update, 3=Updating Firmware, 4=Firmware Update Failed | |
| MVmin | 101 | [Room Name] Pressure Mode | Room pressure mode | Read | 1=Positive, 2=Negative | |
| MVmin | 102 | [Room Name] Alarm Status | Room alarm status | Read | 1=Low Pressure Alarm, 2=High Pressure Alarm, 3=Binary Input Alarm, 4=Door Open Alarm, 5=No Alarm | |
| MVmin | 103 | [Room Name] Caution Status | Room caution status | Read | 1=Low Pressure Caution, 2=High Pressure Caution, 3=Binary Input Caution, 4=Door Open Caution, 5=No Caution | |
| FILE | 1 | Firmware | File object for firmware upgrades (if the BAS supports it) | Write | ||
| CAL | 1 | Calendar Object | Calendar for scheduling | Write | ||
| NC | 1 | Notification Class object | Notification class for alarms | Write | ||
| SCH | 1 | Room Mode Override Schedule | Schedule for room mode changes | Write |
No points match these filters.
Object ID lookup: Antec Controls LUME-1-X room pressure monitor point IDs by name
AI1AI1 – [AI1 Input Name]AI2AI2 – [AI2 Input Name]AI3AI3 – [AI3 Input Name]AI4AI4 – [AI4 Input Name]BI1BI1 – [BI1 Input Name]BI2BI2 – [BI2 Input Name]BI3BI3 – [BI3 Input Name]BI4BI4 – [BI4 Input Name]AO1AO1 – [AO1 Output Name]BO1BO1 – [BO1 Output Name]BO2BO2 – [BO2 Output Name]AV101[Room Name] PressureAV102[Room Name] Low Pressure AlarmAV103[Room Name] Low Pressure DelayAV104[Room Name] High Pressure AlarmAV105[Room Name] High Pressure DelayMV1Audible AlarmMV2Room ModeMV3Room Mode OverrideMV99Firmware Update StatusMV101[Room Name] Pressure ModeMV102[Room Name] Alarm StatusMV103[Room Name] Caution StatusFILE1FirmwareCAL1Calendar ObjectNC1Notification Class objectSCH1Room Mode Override Schedule
Integration notes
- Names in square brackets are filled in from the configuration (room name, input/output names, room mode names).
- AI, BI, AO and BO objects are hidden when that input or output isn't configured.
- AV 102-105 alarm objects are hidden unless the alarm is enabled.
- Pressure units are in.w.c. or Pa; the range is -5.0 to 5.0 in.w.c. (-1245 to 1245 Pa).
- The notification class object is printed with the identifier 'EVC1'.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the LUME-1-X room pressure monitor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP)
How many BACnet points does the Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP) have?
This list has 27 BACnet objects: 4 analog inputs, 1 analog output, 5 analog values, 4 binary inputs, 2 binary outputs, 1 calendar, 1 file, 1 notification class, 1 schedule, 7 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP) BACnet points are writable?
14 of the 27 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP) BACnet documentation?
Antec Controls does not publish it on its own website. This list comes from LUME-1-X Room Pressure Monitor Product Submittal, BACnet Points List v1.0.0 or newer (275288 Rev. B), revision 2023-06-28, a copy hosted by Holyoake (Price/Antec distributor) at https://holyoake.com/wp-content/uploads/2023/08/Submittal_LUME-1-X-275288-B.pdf. Ask Antec Controls or its representative for the current revision.
What are the minimum BACnet points to integrate the Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP)?
Start with MV 3 Room Mode Override (Room mode override from the BMS); AV 101 [Room Name] Pressure (Room differential pressure); MV 2 Room Mode (Current room mode); MV 101 [Room Name] Pressure Mode (Pressure mode: 1 positive, 2 negative); MV 1 Audible Alarm (Audible alarm: on, off or muted); MV 103 [Room Name] Caution Status (Room caution status); MV 102 [Room Name] Alarm Status (Room alarm status (low, high, input, door)).
How do I enable BMS control of the Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP)?
BACnet commands take priority over normal operation (control priority 1 = BACnet).
How do I check these points on the real LUME-1-X room pressure monitor (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: LUME-1-X Room Pressure Monitor Product Submittal, BACnet Points List v1.0.0 or newer · 275288 Rev. B · rev. 2023-06-28. Object names, instances and units are reproduced as published; descriptions are our own.