Room pressure monitor · BACnet points list

Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The LUME is a wall-mounted touch-screen monitor for room differential pressure. On BACnet MS/TP it reports room pressure, pressure mode, alarm and caution status, and lets the BMS set the alarm limits and delays and switch or override the room mode. Its four universal inputs and three outputs appear as AI/BI/AO/BO objects named after their configured use.

This page lists 27 BACnet objects for the Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP) — 14 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Antec Controls’s documentation hosted by Holyoake (Price/Antec distributor), not by Antec Controls itself, so treat it as unofficial.

Manufacturer
Antec Controls
Model
LUME-1-X room pressure monitor (BACnet MS/TP)
Equipment
Room pressure monitor
Equipment type
Thermostats, sensors & meters
BACnet objects
27 (14 writable)
Transport
BACnet MS/TP
Firmware
Points list v1.0.0 or newer
Also known as
LUME, LUME-1-X, LUME11, LUME room pressure monitor, Antec LUME, Price LUME, 275288
Source document
LUME-1-X Room Pressure Monitor Product Submittal, BACnet Points List v1.0.0 or newer · 275288 Rev. B · rev. 2023-06-28 (unofficial copy, hosted by Holyoake (Price/Antec distributor))
Download CSV 27 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Antec Controls’s current documentation and the live device before use. Not official Antec Controls information. Terms of use.

BMS integration notes: Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP)

Integration in brief

Set the MS/TP address and baud on the device, then read AV 101 room pressure, MV 101 pressure mode and MV 102 alarm status. Write MV 3 or use the SCH 1 schedule to switch room modes, and adjust the pressure alarm limits on AV 102 and AV 104 if needed.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 3Room Mode OverrideRoom mode override from the BMSWrite
AV 101[Room Name] PressureRoom differential pressureRead
MV 2Room ModeCurrent room modeWrite
MV 101[Room Name] Pressure ModePressure mode: 1 positive, 2 negativeRead
MV 1Audible AlarmAudible alarm: on, off or mutedRead
MV 103[Room Name] Caution StatusRoom caution statusRead
MV 102[Room Name] Alarm StatusRoom alarm status (low, high, input, door)Read

Enable & remote start

BACnet commands take priority over normal operation (control priority 1 = BACnet).

Network setup

Watch out for

Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

27 of 27 shown
Type
Multi-state
Access
Show
Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP) BACnet Points List
DescriptionStates
AI1AI1 – [AI1 Input Name]Universal input 1 as analog; name, units and use set at configurationDynamicRead
AI2AI2 – [AI2 Input Name]Universal input 2 as analog; name, units and use set at configurationDynamicRead
AI3AI3 – [AI3 Input Name]Universal input 3 as analog; name, units and use set at configurationDynamicRead
AI4AI4 – [AI4 Input Name]Universal input 4 as analog; name, units and use set at configurationDynamicRead
BI1BI1 – [BI1 Input Name]Universal input 1 as binary (contact)ReadOpen/Closed
BI2BI2 – [BI2 Input Name]Universal input 2 as binary (contact)ReadOpen/Closed
BI3BI3 – [BI3 Input Name]Universal input 3 as binary (contact)ReadOpen/Closed
BI4BI4 – [BI4 Input Name]Universal input 4 as binary (contact)ReadOpen/Closed
AO1AO1 – [AO1 Output Name]Analog output, 0-10 V, configurable useVWrite
BO1BO1 – [BO1 Output Name]Binary output 1, configurable useWriteActive/Inactive
BO2BO2 – [BO2 Output Name]Binary output 2, configurable useWriteActive/Inactive
AVmin101[Room Name] PressureRoom pressure, -5.0 to 5.0 in.w.c.in.w.c. or PaRead
AV102[Room Name] Low Pressure AlarmLow pressure alarm setpoint (+/-)in.w.c. or PaWrite
AV103[Room Name] Low Pressure DelayLow pressure alarm delay, 0-600sWrite
AV104[Room Name] High Pressure AlarmHigh pressure alarm setpoint (+/-)in.w.c. or PaWrite
AV105[Room Name] High Pressure DelayHigh pressure alarm delay, 0-600sWrite
MVmin1Audible AlarmRoom audible alarm stateRead1=On, 2=Off, 3=Muted
MVmin2Room ModeCurrent room modeWrite1=[Room Mode 1 Name], 2=[Room Mode 2 Name]
MVmin3Room Mode OverrideRoom mode overrideWrite1=[Room Mode 1 Name], 2=[Room Mode 2 Name]
MV99Firmware Update StatusFirmware update stateWrite1=Idle, 2=Start Firmware Update, 3=Updating Firmware, 4=Firmware Update Failed
MVmin101[Room Name] Pressure ModeRoom pressure modeRead1=Positive, 2=Negative
MVmin102[Room Name] Alarm StatusRoom alarm statusRead1=Low Pressure Alarm, 2=High Pressure Alarm, 3=Binary Input Alarm, 4=Door Open Alarm, 5=No Alarm
MVmin103[Room Name] Caution StatusRoom caution statusRead1=Low Pressure Caution, 2=High Pressure Caution, 3=Binary Input Caution, 4=Door Open Caution, 5=No Caution
FILE1FirmwareFile object for firmware upgrades (if the BAS supports it)Write
CAL1Calendar ObjectCalendar for schedulingWrite
NC1Notification Class objectNotification class for alarmsWrite
SCH1Room Mode Override ScheduleSchedule for room mode changesWrite
Object ID lookup: Antec Controls LUME-1-X room pressure monitor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the LUME-1-X room pressure monitor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP)

How many BACnet points does the Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP) have?

This list has 27 BACnet objects: 4 analog inputs, 1 analog output, 5 analog values, 4 binary inputs, 2 binary outputs, 1 calendar, 1 file, 1 notification class, 1 schedule, 7 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP) BACnet points are writable?

14 of the 27 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP) BACnet documentation?

Antec Controls does not publish it on its own website. This list comes from LUME-1-X Room Pressure Monitor Product Submittal, BACnet Points List v1.0.0 or newer (275288 Rev. B), revision 2023-06-28, a copy hosted by Holyoake (Price/Antec distributor) at https://holyoake.com/wp-content/uploads/2023/08/Submittal_LUME-1-X-275288-B.pdf. Ask Antec Controls or its representative for the current revision.

What are the minimum BACnet points to integrate the Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP)?

Start with MV 3 Room Mode Override (Room mode override from the BMS); AV 101 [Room Name] Pressure (Room differential pressure); MV 2 Room Mode (Current room mode); MV 101 [Room Name] Pressure Mode (Pressure mode: 1 positive, 2 negative); MV 1 Audible Alarm (Audible alarm: on, off or muted); MV 103 [Room Name] Caution Status (Room caution status); MV 102 [Room Name] Alarm Status (Room alarm status (low, high, input, door)).

How do I enable BMS control of the Antec Controls LUME-1-X room pressure monitor (BACnet MS/TP)?

BACnet commands take priority over normal operation (control priority 1 = BACnet).

How do I check these points on the real LUME-1-X room pressure monitor (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: LUME-1-X Room Pressure Monitor Product Submittal, BACnet Points List v1.0.0 or newer · 275288 Rev. B · rev. 2023-06-28. Object names, instances and units are reproduced as published; descriptions are our own.