Airflow measuring station (thermal dispersion) · BACnet points list

Air Monitor ELECTRA-flo/SD thermal airflow station (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The ELECTRA-flo/SD measures duct air velocity and temperature with thermistor sensors and sends them over BACnet MS/TP (or Modbus RTU, DIP-selectable). It has four Analog Inputs (velocity, velocity pressure, temperature, volumetric flow) and one writable Analog Value for the duct area. Airflow reads 0 until the duct area is written.

This page lists 5 BACnet objects for the Air Monitor ELECTRA-flo/SD thermal airflow station (BACnet MS/TP) — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Air Monitor’s own free documentation, linked below.

Manufacturer
Air Monitor
Model
ELECTRA-flo/SD thermal airflow station (BACnet MS/TP)
Equipment
Airflow measuring station (thermal dispersion)
Equipment type
Thermostats, sensors & meters
BACnet objects
5 (1 writable)
Transport
BACnet MS/TP
Firmware
0.8.3 (device object default)
Default device instance
Same as the DIP-switch MAC address
Also known as
ELECTRA-flo/SD, ElectraFlo/SD, Electra-flo SD, Air Monitor ELECTRA-flo
Source document
ELECTRA-flo/SD with BACnet MS/TP or MODBUS RTU Output · DOC-0005317 Rev. A
Download CSV 5 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Air Monitor’s current documentation and the live device before use. Not official Air Monitor information. Terms of use.

BMS integration notes: Air Monitor ELECTRA-flo/SD thermal airflow station (BACnet MS/TP)

Integration in brief

Set S1 SW5 down for BACnet, the MAC address and baud on the DIP switches, then write the duct area to AV 0 once. Read volumetric flow, velocity and temperature.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 0AV-0Duct area, ft2 (US) or m2 (SI); write onceWrite
AI 4Volumetric FlowAirflow, CFM or m3/minRead
AI 1VelocityAverage velocity, ft/min or m/minRead
AI 3TemperatureAir temperatureRead

Network setup

Watch out for

Air Monitor ELECTRA-flo/SD thermal airflow station (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

5 of 5 shown
Type
Access
Show
Air Monitor ELECTRA-flo/SD thermal airflow station (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1VelocityAverage air velocityft/min or m/minRead
AI2Velocity PressureEquivalent velocity pressureinH2O or cmH2ORead
AImin3TemperatureAir temperature°F or °CRead
AImin4Volumetric FlowAirflow = velocity x duct area (AV 0)CFM or m3/minRead
AVmin0AV-0Duct Area Scale Factor: duct area used to compute airflowft2 or m2Write
Object ID lookup: Air Monitor ELECTRA-flo/SD thermal airflow station point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ELECTRA-flo/SD thermal airflow station (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Air Monitor ELECTRA-flo/SD thermal airflow station (BACnet MS/TP)

How many BACnet points does the Air Monitor ELECTRA-flo/SD thermal airflow station (BACnet MS/TP) have?

This list has 5 BACnet objects: 4 analog inputs, 1 analog value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Air Monitor ELECTRA-flo/SD thermal airflow station (BACnet MS/TP) BACnet points are writable?

1 of the 5 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Air Monitor ELECTRA-flo/SD thermal airflow station (BACnet MS/TP) BACnet documentation?

The source is ELECTRA-flo/SD with BACnet MS/TP or MODBUS RTU Output (DOC-0005317 Rev. A), published free by Air Monitor at https://www.airmonitor.com/hvac/wp-content/uploads/sites/2/electra-flo-sd-bacnet-modbus-manual.pdf.

What are the minimum BACnet points to integrate the Air Monitor ELECTRA-flo/SD thermal airflow station (BACnet MS/TP)?

Start with AV 0 AV-0 (Duct area, ft2 (US) or m2 (SI); write once); AI 4 Volumetric Flow (Airflow, CFM or m3/min); AI 1 Velocity (Average velocity, ft/min or m/min); AI 3 Temperature (Air temperature).

How do I check these points on the real ELECTRA-flo/SD thermal airflow station (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: ELECTRA-flo/SD with BACnet MS/TP or MODBUS RTU Output · DOC-0005317 Rev. A. Object names, instances and units are reproduced as published; descriptions are our own.