Close control (precision) air conditioner · BACnet points list

Aermec P / G / R / TMC precision air conditioners with SURVEY3 controller (software 3.0) BACnet points list

Updated 12 November 2026

Short answer

The SURVEY3 controller runs Aermec precision air conditioners (DX, chilled water, two-source and free cooling variants). Its supervisor table maps each value to a Modbus register and a BACnet object: 530 objects covering digital inputs and alarms, outputs, return/supply temperature and humidity, remote probe modules, compressor and EEV data, fans, water circuit, humidifier, working hours, setpoints and regulation parameters, and alarm resets.

This page lists 530 BACnet objects for the Aermec P / G / R / TMC precision air conditioners with SURVEY3 controller (software 3.0) — 83 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Aermec’s own free documentation, linked below.

Manufacturer
Aermec
Model
P / G / R / TMC precision air conditioners with SURVEY3 controller (software 3.0)
Equipment
Close control (precision) air conditioner
Equipment type
Other equipment
BACnet objects
530 (83 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
SURVEY3 software 3.0
Default device instance
127
Also known as
SURVEY3, Aermec SURVEY3, Aermec P, Aermec G, Aermec R, Aermec TMC, Aermec close control, Aermec precision air conditioner BACnet, 5895970_01
Source document
Precision air conditioners P-G-R-TMC user manual · 5895970_01 · rev. 2020-11
Download CSV 530 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Aermec’s current documentation and the live device before use. Not official Aermec information. Terms of use.

BMS integration notes: Aermec P / G / R / TMC precision air conditioners with SURVEY3 controller (software 3.0)

Integration in brief

Fit the BACnet MS/TP (RS485) or BACnet IP (RJ45) option and set Device ID, baud rate, max master and MAC ID in User set-up > BACnet. Switch the unit with SupervOFF (BV 1), write temperature and humidity setpoints, and read unit status, temperatures, humidity, outputs and alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1SupervOFFOn/off command from the supervisorWrite
AV 108TemperatureSetpointTemperature setpoint, °CWrite
AV 109HumiditySetpointHumidity setpoint, %rHWrite
MV 19UnitStatusUnit statusRead
AI 1ReturnTemperatureReturn temperature, °CRead
AI 3SupplyTemperatureSupply temperature, °CRead
AI 6ReturnHumidityReturn humidity, %rHRead
BO 1FansDOFan control outputRead
BO 10Compressor1DOCompressor 1 outputRead
BI 2DirtyFilterDIDirty filter alarmRead

Enable & remote start

On/Off from supervisor is BV 1 (SupervOFF), writable.

Network setup

Watch out for

Aermec P / G / R / TMC precision air conditioners with SURVEY3 controller (software 3.0) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

530 of 530 shown
Type
Multi-state
Access
Show
Aermec P / G / R / TMC precision air conditioners with SURVEY3 controller (software 3.0) BACnet Points List
DescriptionStates
BI1DamperStatusDIMotorised damper statusRead
BImin2DirtyFilterDIDirty filter alarmRead
BI3RemoteOffDIRemote OFFRead
BI4ElecHeaterAlarmDIGeneral Electric Coil AlarmRead
BI5CondPumpAlarmDICondensate discharge pump alarmRead
AV1ConfDI1ComboDescription of configurable input 1Read
BI6ConfigurableDI1Configurable input 1Read
AV2ConfDI2ComboDescription of configurable input 2Read
BI7ConfigurableDI2Configurable input 2Read
AV3ConfDI3ComboDescription of configurable input 3Read
BI8ConfigurableDI3Configurable input 3Read
AV4ConfDI4ComboDescription of configurable input 4Read
BI9ConfigurableDI4Configurable input 4Read
AV5ConfDI5ComboDescription of configurable input 5Read
BI10ConfigurableDI5Configurable input 5Read
BI11Comp1ThermAlarmDICompressor 1 breaker alarmRead
BI12Comp1HPAlarmDICompressor 1 high pressure alarmRead
BI13Comp1LPAlarmDICompressor 1 low pressure alarmRead
BI14Comp2ThermAlarmDICompressor 2 breaker alarmRead
BI15Comp2HPAlarmDICompressor 2 high pressure alarmRead
BI16Comp2LowPresAlarmDICompressor 2 low pressure alarmRead
BOmin1FansDOFan controlRead
BO2DamperDODamper controlRead
AV6ConfDO1ComboDescription of configurable digital output 1Read
BO3ConfigurableDO1Configurable digital output 1Read
AV7ConfDO2ComboDescription of configurable digital output 2Read
BO4ConfigurableDO2Configurable digital output 2Read
AV8ConfDO3ComboDescription of configurable digital output 3Read
BO5ConfigurableDO3Configurable digital output 3Read
AV9ConfDO4ComboDescription of configurable digital output 4Read
BO6ConfigurableDO4Configurable digital output 4Read
AV10ConfDO5ComboDescription of configurable digital output 5Read
BO7ConfigurableDO5Configurable digital output 5Read
BO8ElecHeaterStage1DOElectric heating coil stage 1Read
BO9ElecHeaterStage2DOElectric heating coil stage 2Read
BOmin10Compressor1DOCompressor 1 controlRead
BO11Compressor2DOCompressor 2 controlRead
AImin1ReturnTemperatureReturn temperature°CRead
AI2ReturnTempAvgReturn temperature (local network average)°CRead
AImin3SupplyTemperatureSupply temperature°CRead
AI4SupplyTempAvgSupply temperature (local network average)°CRead
AI5TemperatureDeltaTemperature Delta°CRead
AImin6ReturnHumidityReturn humidity%RhRead
AI7ReturnHumidityAvgReturn humidity (local network average)%RhRead
AI8SupplyHumiditySupply humidity%RhRead
AI9SupplyHumidityAvgSupply humidity (local network average)%RhRead
AV11AirFlowAir flow ratem3/hRead
AI10AirPressureAir pressurePaRead
AI11AirPressureAvgAir pressure (local network average)PaRead
MV1netMod1Combo1Probe 1 module 1 statusRead
AI12netMod1Probe1Probe 1 module 1 valueRead
MV2netMod1Combo2Probe 2 module 1 statusRead
AI13netMod1Probe2Probe 2 module 1 valueRead
MV3netMod1Combo3Probe 3 module 1 statusRead
AI14netMod1Probe3Probe 3 module 1 valueRead
MV4netMod1Combo4Probe 4 module 1 statusRead
AI15netMod1Probe4Probe 4 module 1 valueRead
MV5netMod1Combo5Probe 5 module 1 statusRead
AI16netMod1Probe5Probe 5 module 1 valueRead
MV6netMod1Combo6Probe 6 module 1 statusRead
AI17netMod1Probe6Probe 6 module 1 valueRead
MV7netMod2Combo1Probe 1 module 2 statusRead
AI18netMod2Probe1Probe 1 module 2 valueRead
MV8netMod2Combo2Probe 2 module 2 statusRead
AI19netMod2Probe2Probe 2 module 2 valueRead
MV9netMod2Combo3Probe 3 module 2 statusRead
AI20netMod2Probe3Probe 3 module 2 valueRead
MV10netMod2Combo4Probe 4 module 2 statusRead
AI21netMod2Probe4Probe 4 module 2 valueRead
MV11netMod2Combo5Probe 5 module 2 statusRead
AI22netMod2Probe5Probe 5 module 2 valueRead
MV12netMod2Combo6Probe 6 module 2 statusRead
AI23netMod2Probe6Probe 6 module 2 valueRead
MV13netMod3Combo1Probe 1 module 3 statusRead
AI24netMod3Probe1Probe 1 module 3 valueRead
MV14netMod3Combo2Probe 2 module 3 statusRead
AI25netMod3Probe2Probe 2 module 3 valueRead
MV15netMod3Combo3Probe 3 module 3 statusRead
AI26netMod3Probe3Probe 3 module 3 valueRead
MV16netMod3Combo4Probe 4 module 3 statusRead
AI27netMod3Probe4Probe 4 module 3 valueRead
MV17netMod3Combo5Probe 5 module 3 statusRead
AI28netMod3Probe5Probe 5 module 3 valueRead
MV18netMod3Combo6Probe 6 module 3 statusRead
AI29netMod3Probe6Probe 6 module 3 valueRead
AI30AvgModTempRemote module temperature probe average°CRead
AI31AvgModHumiRemote module humidity probe average%RhRead
AI32AvgModPressRemote module pressure probe averagePaRead
AO1UnitFansDryCoolerAOSupply Fan / Dry cooler modulation%Read
AO2CoolingAOCold valve / Free cooling / Condensing unit%Read
AO3HeatingAOHeating valve / Modulating electric coil%Read
AO4TwoSources2AOTwo sources water valve 2%Read
AO5Condenser1AOCondenser 1%Read
AO6Condenser2HumidifAOCondenser 2 / External humidifier%Read
MVmin19UnitStatusUnit statusRead
AV12FanSpeedFan speed%Read
AV12fan1ActspeedFan 1 speed%Read
AV14fan1ActRPMFan 1 speedRPMRead
AV15fan1CurFan 1 absorbed currentARead
AV16fan1PowerFan 1 absorbed electrical powerWRead
AV17fan2ActspeedFan 2 speed%Read
AV18fan2ActRPMFan 2 speedRPMRead
AV19fan2CurFan 2 absorbed currentARead
AV20fan2PowerFan 2 absorbed electrical powerWRead
AV21fan3ActspeedFan 3 speed%Read
AV22fan3ActRPMFan 3 speedRPMRead
AV13fan3CurFan 3 absorbed currentARead
AV24fan3PowerFan 3 absorbed electrical powerWRead
AV25fan4ActspeedFan 4 speed%Read
AV26fan4ActRPMFan 4 speedRPMRead
AV27fan4CurFan 4 absorbed currentARead
AV28fan4PowerFan 4 absorbed electrical powerWRead
AV29fan5ActspeedFan 5 speed%Read
AV30fan5ActRPMFan 5 speedRPMRead
AV31fan5CurFan 5 absorbed currentARead
AV32fan5PowerFan 5 absorbed electrical powerWRead
AV33fan6ActspeedFan 6 speed%Read
AV34fan6ActRPMFan 6 speedRPMRead
AV35fan6CurFan 6 absorbed currentARead
AV36fan6PowerFan 6 absorbed electrical powerWRead
AV37fan7ActspeedFan 7 speed%Read
AV38fan7ActRPMFan 7 speedRPMRead
AV39fan7CurFan 7 absorbed currentARead
AV40fan7PowerFan 7 absorbed electrical powerWRead
AV41fan8ActspeedFan 8 speed%Read
AV42fan8ActRPMFan 8 speedRPMRead
AV43fan8CurFan 8 absorbed currentARead
AV44fan8PowerFan 8 absorbed electrical powerWRead
AV45fan9ActspeedFan 9 speed%Read
AV46fan9ActRPMFan 9 speedRPMRead
AV47fan9CurFan 9 absorbed currentARead
AV48fan9PowerFan 9 absorbed electrical powerWRead
AV49fan10ActspeedFan 10 speed%Read
AV50fan10ActRPMFan 10 speedRPMRead
AV51fan10CurFan 10 absorbed currentARead
AV52fan10PowerFan 10 absorbed electrical powerWRead
AI33DiffFilterPressureDirty filter differential pressurePaRead
AV53CoolingRequestCurrent cooling request%Read
AV54HeatingRequestCurrent heating request%Read
AV55DehumidRequestCurrent dehumidification request%Read
AV56HumidifRequestCurrent humidification request%Read
AI34TempFcTsFree cooling/Two Sources temperature°CRead
MV20FCTSStatusFree cooling/Two Sources statusRead
AV57FCRequestCurrent Free Cooling request%Read
AV58ActiveCompCompressors activeRead
MV21Comp1StsCompressor 1 statusRead
MV22Comp2StsCompressor 2 statusRead
AV59InvComprReqInverter compressor request%Read
AV60InverterCompHzCurrent compressor speedHzRead
AV61InverterCompPowerCurrent compressor electrical powerkWRead
AV62InverterCompCurrentCurrent compressor input currentARead
AI35Comp1EvapPresCompressor 1 evaporation pressureBarGRead
AI36Comp1EvapTempCompressor 1 evaporation temperature°CRead
AI37Comp1SuctionTempCompressor 1 suction temperature°CRead
AV63Comp1SuperheatCompressor 1 superheatingKRead
AV64Comp1CompRatioCompressor 1 compression ratioRead
AI38Comp1DischTempCompressor 1 discharge temperature°CRead
AI39Comp1CondPressCompressor 1 condensation pressureBarGRead
AI40Compr1CondTempCompressor 1 condensation temperature°CRead
AV65Comp1DesuperheatCurrent compressor 1 de-superheatingKRead
AI41Comp1LiquidTempCompressor 1 liquid temperature°CRead
AV66Comp1SubcoolingCompressor 1 subcoolingKRead
AV67EEV1SuperheatSetEEV1 superheating set-pointKRead
AV68EEV1PositionEEV1 Position%Read
MV23EEV1StatusEEV1 regulation statusRead
AV69Cond1ActualSetCurrent condenser 1 set-point°CRead
AV70Cond1ReqCondenser 1 request%Read
AI42Comp2EvapPresCompressor 2 evaporation pressureBarGRead
AI43Comp2EvapTempCompressor 2 evaporation temperature°CRead
AI44Comp2SuctionTempCompressor 2 suction temperature°CRead
AV71EEV2SuperheatCompressor 2 superheatingKRead
AV72CompRatio2Compressor 2 compression ratioRead
AI45Comp2DischTempCompressor 2 discharge temperature°CRead
AI46Compr2CondPressCompressor 2 condensation pressureBarGRead
AI47Comp2CondTempCompressor 2 condensation temperature°CRead
AV73EEV2DesuperheatCompressor 2 de-superheatingKRead
AI48Compr2LiquidTempCompressor 2 liquid temperature°CRead
AV74EEV2SubcoolingCompressor 2 subcoolingKRead
AV75EEV2SuperheatSetEEV2 superheating set-pointKRead
AV76EEV2PositionEEV2 Position%Read
MV24EEV2StatusEEV2 regulation statusRead
AV77Cond2ActualSetCurrent condenser 2 set-point°CRead
AV78Cond2ReqCondenser 2 request%Read
AI49WaterINTemp1Water inlet temperature 1°CRead
AI50WaterOUTTemp1Water outlet temperature 1°CRead
AI51WaterDT1Water temperature Delta 1°CRead
AI52WaterFlow1Water flow rate 1l/hRead
AV79ActWaterFlowSet1Current water flow rate 1 set-pointl/hRead
AV80WaterCoolCap1Chilled water 1 cooling capacitykWRead
AV81EER1EER 1Read
AV82Valve1PositionWater 1 Valve position%Read
AI53WaterINTemp2Water inlet temperature 2°CRead
AI54WaterOUTTemp2Water outlet temperature 2°CRead
AI55WaterDT2Water temperature Delta 2°CRead
AI56WaterFlow2Water flow rate 2l/hRead
AV83ActWaterFlowSet2Current water flow rate 1 set-pointl/hRead
AV84WaterCoolCap2Chilled water 2 cooling capacitykWRead
AV85EER1EER 2Read
AV86Valve2PositionWater 2 Valve position%Read
AV87HumidifSteamProdCurrent humidifier productionkg/hRead
AV88HumidifWaterConductSupply water conductivityμS/ cmRead
AV89HumidifierCurrentAbsorbed humidifier currentARead
MV25HumidifWorkingModeHumidifier operating modeRead
MV26HumidifWorkStatusHumidifier operating mode statusRead
BO12HumidifierPowerDOHumidifier controlRead
BO13HumidifDrainValveDODischarge valveRead
BO14HumidifFillValveDOCharging valveRead
BI17HumidifWaterLevelHigh water levelRead
AV90HeaterReqEelectric coil request%Read
AV91HeaterActiveStagesNumber of active stagesRead
AV92ElecHeaterPowerElectrical power requirementkWRead
AV93HeatValveReqWater heating valve request%Read
AV94DryCoolerActualSetCurrent dry cooler set-point°CRead
AV95DryCoolerReqDry cooler request%Read
AV96UnitWorkingHoursUnithRead
AV97Comp1WorkingHoursCompressor 1hRead
AV98Comp1StartupCompressor 1 startuphRead
AV99Compr2WorkingHoursCompressor 2hRead
AV100Comp2StartupCompressor 2 startuphRead
AV101CoolValveWorkHoursCooling valvehRead
AV102HeatingWorkingHoursHeatinghRead
AV103HumidifWorkingHoursHumidifierhRead
AV104FreeCoolWorkHoursFree CoolinghRead
AV105DryCoolerWorkHoursDry coolerhRead
AV106Cond1WorkingHoursCondenser 1hRead
AV107Cond2WorkingHoursCondenser 2hRead
BVmin1SupervOFFOn/Off from supervisorWrite
AVmin108TemperatureSetpointTemperature set-point°CWrite
AVmin109HumiditySetpointHumidity set-point%RhWrite
AV110AirFlowSetpointAir flow rate set-pointm3/hWrite
AV111AirPressureSetpointAir pressure set-pointPaWrite
AV112AirDTSetpointAir temperature delta set-point°CWrite
MV27TempControlSelRegulation sensorWrite
MV28TempControlTypeRegulation typeWrite
AV113TProportionalBandProportional Band°CWrite
AV114TIntagrativeTimeIntegration TimesWrite
AV115TDerivativeTimeDerivative timesWrite
AV116HighTempAlarmOffsetHigh temperature alarm offset°CWrite
AV117LowTempAlarmOffsetLow temperature alarm offset°CWrite
AV118HighLimitTempThrUpper limit temperature limit°CWrite
MV29HighLimitTempMngHigh limit temperature managementWrite
AV119LowLimitTempThrLower limit temperature limit°CWrite
MV30LowLimitTempMngLow limit temperature managementWrite
AV120DehumidifPropBandDehumidification proportional band%RHWrite
AV121HumidifPropBandHumidification proportional band%RHWrite
AV122HighRetHumAlOffsetHigh return humidity alarm offset%RHWrite
AV123LowRetHumAlOffsetLow return humidity alarm offset%RHWrite
AV124HighSupHumThrUpper supply humidity limit%RHWrite
AV125LowSupHumThrLower supply humidity limit%RHWrite
BV2EnableHumidifierHumidification enablingWrite
BV3HumidifManualDrainManual dischargeWrite
BV4HumidifCylWashingCylinder pre-washWrite
AV126FreeCoolingDeltaFree cooling delta°CWrite
AV127TSWaterSetpointTwo sources water set-point°CWrite
AV128TSWaterPropBandTwo sources water band°CWrite
BV5TSManExchangeTwo sources source exchangeWrite
BV6TSTempExchEnabSwitch due to high ambient temperatureWrite
AV129TSAirTempSetTwo sources high temperature set-point°CWrite
AV130CondSetpointCondensation set-point°CWrite
AV131CondPropoBandCondensation proportional band°CWrite
AV132CondSetIncreaseCondensation set-point increase°CWrite
AV133MaxCondSetpointMaximum condensation set-point°CWrite
AV134DryCoolerSetpointDry cooler set-point°CWrite
AV135DryCoolerPropBandDry Cooler proportional band°CWrite
AV136DryCoolerSetIncrDry Cooler set-point increase°CWrite
AV137MaxDryCoolerSetMaximum dry Cooler set-point°CWrite
AV138DirtyFiltersSetDirty filter set-pointPaWrite
AV139DirtyFiltersDiffDirty filter differentialPaWrite
BI18GeneralAlarmsGeneral AlarmRead
BI19NotCriticalAlarmsNon-critical alarmRead
BI20CriticalAlarmsCritical alarmRead
BI21FansAlarmsVentilation alarmRead
BI22CompAlarmsCompressor alarmRead
BI23TemperatureAlarmsTemperature alarmRead
BI24HumidityAlarmsHumidity alarmRead
BI25DamperAlDamper status alarmRead
BI26FireSmokeAlFire/Smoke presence alarmRead
BI27GenericSeriousAlCritical generic alarmRead
BI28FansGenAlGeneral supply fan alarm (Digital)Read
BI29Fan1GeneralAlGeneral fan 1 alarmRead
BI30Fan1PowerAlFan 1 no phase/power supply alarmRead
BI31Fan1CommAlFan 1 communication down alarmRead
BI32Fan1HighTempAlHigh fan 1 regulation module temperatureRead
BI33Fan1NetComAlNo fan 1 master-slave communicationRead
BI34Fan1InvRegAlFan 1 regulation module malfunctionRead
BI35Fan1HighMotTempAlFan 1 high motor temperatureRead
BI36Fan1HallSensAlFan 1 Hall sensor errorRead
BI37Fan1OverloadAlFan 1 motor overloadRead
BI38Fan1LowDCAlFan 1 low DC power supplyRead
BI39Fan2GeneralAlGeneral fan 2 alarmRead
BI40Fan2PowerAlFan 2 no phase/power supply alarmRead
BI41Fan2CommAlFan 2 communication down alarmRead
BI42Fan2HighTempAlHigh fan 2 regulation module temperatureRead
BI43Fan2NetComAlNo fan 2 master-slave communicationRead
BI44Fan2InvRegAlFan 2 regulation module malfunctionRead
BI45Fan2HighMotTempAlFan 2 high motor temperatureRead
BI46Fan2HallSensAlFan 2 Hall sensor errorRead
BI47Fan2OverloadAlFan 2 motor overloadRead
BI48Fan2LowDCAlFan 2 low DC power supplyRead
BI49Fan3GeneralAlGeneral fan 3 alarmRead
BI50Fan3PowerAlFan 3 no phase/power supply alarmRead
BI51Fan3CommAlFan 3 communication down alarmRead
BI52Fan3HighTempAlHigh fan 3 regulation module temperatureRead
BI53Fan3NetComAlNo fan 3 master-slave communicationRead
BI54Fan3InvRegAlFan 3 regulation module malfunctionRead
BI55Fan3HighMotTempAlFan 3 high motor temperatureRead
BI56Fan3HallSensAlFan 3 Hall sensor errorRead
BI57Fan3OverloadAlFan 3 motor overloadRead
BI58Fan3LowDCAlFan 3 low DC power supplyRead
BI59Fan4GeneralAlGeneral fan 4 alarmRead
BI60Fan4PowerAlFan 4 no phase/power supply alarmRead
BI61Fan4CommAlFan 4 communication down alarmRead
BI62Fan4HighTempAlHigh fan 4 regulation module temperatureRead
BI63Fan4NetComAlNo fan 4 master-slave communicationRead
BI64Fan4InvRegAlFan 4 regulation module malfunctionRead
BI65Fan4HighMotTempAlFan 4 high motor temperatureRead
BI66Fan4HallSensAlFan 4 Hall sensor errorRead
BI67Fan4OverloadAlFan 4 motor overloadRead
BI68Fan4LowDCAlFan 4 low DC power supplyRead
BI69Fan5GeneralAlGeneral fan 5 alarmRead
BI70Fan5PowerAlFan 5 no phase/power supply alarmRead
BI71Fan5CommAlFan 5 communication down alarmRead
BI72Fan5HighTempAlHigh fan 5 regulation module temperatureRead
BI73Fan5NetComAlNo fan 5 master-slave communicationRead
BI74Fan5InvRegAlFan 5 regulation module malfunctionRead
BI75Fan5HighMotTempAlFan 5 high motor temperatureRead
BI76Fan5HallSensAlFan 5 Hall sensor errorRead
BI77Fan5OverloadAlFan 5 motor overloadRead
BI78Fan5LowDCAlFan 5 low DC power supplyRead
BI79Fan6GeneralAlGeneral fan 6 alarmRead
BI80Fan6PowerAlFan 6 no phase/power supply alarmRead
BI81Fan6CommAlFan 6 communication down alarmRead
BI82Fan6HighTempAlHigh fan 6 regulation module temperatureRead
BI83Fan6NetComAlNo fan 6 master-slave communicationRead
BI84Fan6InvRegAlFan 6 regulation module malfunctionRead
BI85Fan6HighMotTempAlFan 6 high motor temperatureRead
BI86Fan6HallSensAlFan 6 Hall sensor errorRead
BI87Fan6OverloadAlFan 6 motor overloadRead
BI88Fan6LowDCAlFan 6 low DC power supplyRead
BI89Fan7GeneralAlGeneral fan 7 alarmRead
BI90Fan7PowerAlFan 7 no phase/power supply alarmRead
BI91Fan7CommAlFan 7 communication down alarmRead
BI92Fan7HighTempAlHigh fan 7 regulation module temperatureRead
BI93Fan7NetComAlNo fan 7 master-slave communicationRead
BI94Fan7InvRegAlFan 7 regulation module malfunctionRead
BI95Fan7HighMotTempAlFan 7 high motor temperatureRead
BI96Fan7HallSensAlFan 7 Hall sensor errorRead
BI97Fan7OverloadAlFan 7 motor overloadRead
BI98Fan7LowDCAlFan 7 low DC power supplyRead
BI99Fan8GeneralAlGeneral fan 8 alarmRead
BI100Fan8PowerAlFan 8 no phase/power supply alarmRead
BI101Fan8CommAlFan 8 communication down alarmRead
BI102Fan8HighTempAlHigh fan 8 regulation module temperatureRead
BI103Fan8NetComAlNo fan 8 master-slave communicationRead
BI104Fan8InvRegAlFan 8 regulation module malfunctionRead
BI105Fan8HighMotTempAlFan 8 high motor temperatureRead
BI106Fan8HallSensAlFan 8 Hall sensor errorRead
BI107Fan8OverloadAlFan 8 motor overloadRead
BI108Fan8LowDCAlFan 8 low DC power supplyRead
BI109Fan9InverterAlGeneral fan 9 alarmRead
BI110Fan9PowerAlFan 9 no phase/power supply alarmRead
BI111Fan9CommAlFan 9 communication down alarmRead
BI112Fan9HighTempAlHigh fan 9 regulation module temperatureRead
BI113Fan9NetComAlNo fan 9 master-slave communicationRead
BI114Fan9InvRegAlFan 9 regulation module malfunctionRead
BI115Fan9HighMotTempAlFan 9 high motor temperatureRead
BI116Fan9HallSensAlFan 9 Hall sensor errorRead
BI117Fan9OverloadAlFan 9 motor overloadRead
BI118Fan9LowDCAlFan 9 low DC power supplyRead
BI119Fan10GeneralAlGeneral fan 10 alarmRead
BI120Fan10PowerAlFan 10 no phase/power supply alarmRead
BI121Fan10CommAlFan 10 communication down alarmRead
BI122Fan10HighTempAlHigh fan 10 regulation module temperatureRead
BI123Fan10NetComAlNo fan 10 master-slave communicationRead
BI124Fan10InvRegAlFan 10 regulation module malfunctionRead
BI125Fan10HighMotTempAlFan 10 high motor temperatureRead
BI126Fan10HallSensAlFan 10 Hall sensor errorRead
BI127Fan10OverloadAlFan 10 motor overloadRead
BI128Fan10LowDCAlFan 10 low DC power supplyRead
BI129RetTempProbAlReturn temperature probe alarmRead
BI130SupTempProbAlSupply temperature probe alarmRead
BI131RetHumProbAlReturn humidity probe alarmRead
BI132SupHumProbAlSupply humidity probe alarmRead
BI133AirPrSensorAlDifferential air pressure sensor alarmRead
BI134WatIN1ProbAlIN 1/Free cooling water temperature probe alarmRead
BI135WatOUT1ProbAlOUT 1 water temperature probe alarmRead
BI136WatIN2ProbAlIN 2 water temperature probe alarmRead
BI137WatOUT2ProbAlOUT 2 water temperature probe alarmRead
BI138WatFlw1ProbAlWater flow rate/liquid temperature 1 sensor alarmRead
BI139WatFlw2ProbAlWater flow rate/liquid temperature 2 sensor alarmRead
BI140DFPSGenAlDirty filter pressure sensor general alarmRead
BI141DFPSBrokenAlBroken dirty filter pressure sensor alarmRead
BI142DFPSCablingAlDirty filter pressure sensor wiring alarmRead
BI143DFPSRangeAlDirty filter pressure sensor pressure range alarmRead
BI144DFPSADCAlDirty filter pressure sensor overload ADC alarmRead
BI145DFPSSettingAlDirty filter pressure sensor calibration alarmRead
BI146DFPSDCOAlDirty filter pressure sensor DCO alarmRead
BI147DFPSWatchdogAlDirty filter pressure sensor watchdog alarmRead
BI148DFPSCommAlDirty filter pressure sensor communication alarmRead
BI149InverterCompGenAlDC compressor inverter general alarmRead
BI150InvCompCommAlarmDC compressor inverter communication alarmRead
MV31InvCompAlCode1DC compressor 1 inverter alarm codeRead
MV32InvCompAlCode2DC compressor 2 inverter alarm codeRead
MV33InvCompAlCode3DC compressor 3 inverter alarm codeRead
MV34InvCompAlCode4DC compressor 4 inverter alarm codeRead
MV35InvCompAlCode5DC compressor 5 inverter alarm codeRead
BI151C1ThermAlCompressor 1 thermal magnetic protection alarmRead
BI152C1HighPresAlCompressor 1 high pressure alarmRead
BI153C1LowPresAlCompressor 1 low pressure alarmRead
BI154C1HighDischAlCompressor 1 discharge high temperature alarmRead
BI155C1LowComprRatioAlCompressor 1 low compression alarmRead
BI156Condenser1AlCondenser 1 general alarmRead
BI157C1WatFlowAlCondenser 1 water flow alarmRead
BI158EEV1GenAlGeneral EEV 1 alarmRead
BI159EEV1CommAlEEV1 communication down alarmRead
BI160EEV1SuctProbAlEEV1 suction temperature probe alarmRead
BI161EEV1EvapProbAlEEV1 evaporation pressure probe alarmRead
BI162EEV1CondProbAlEEV1 condensation pressure probe alarmRead
BI163EEV1DischProbAlEEV1 discharge temperature probe alarmRead
BI164C2ThermAlCompressor 2 thermal magnetic protection alarmRead
BI165C2HighPresAlCompressor 2 high pressure alarmRead
BI166C2LowPresAlCompressor 2 low pressure alarmRead
BI167C2HighDischAlCompressor 2 discharge high temperature alarmRead
BI168C2LowComprRatioAlCompressor 2 low compression alarmRead
BI169Condenser2AlCondenser 2 general alarmRead
BI170C2WatFlowAlCondenser 2 water flow alarmRead
BI171EEV2GenAlGeneral EEV 2 alarmRead
BI172EEV2CommAlEEV2 communication down alarmRead
BI173EEV2SuctProbAlEEV2 suction temperature probe alarmRead
BI174EEV2EvapProbAlEEV2 evaporation pressure probe alarmRead
BI175EEV2CondProbAlEEV2 condensation pressure probe alarmRead
BI176EEV2DischProbAlEEV2 discharge temperature probe alarmRead
BI177InternalHumidGenAlInternal humidifier general alarmRead
BI178CPYCommAlCPY communication down alarmRead
BI179CPYMemoryAlInternal memory errorRead
BI180CPYParameterAlParameter errorRead
BI181CPYHighCurrentAlHigh electrode currentRead
BI182CPYLowSteamAlLow steam flow rateRead
BI183CPYDrainAlFailed dischargeRead
BI184CPYMaintAlMaintenance time expiredRead
BI185CPYNoWaterAlNo waterRead
BI186CPYCylMaintAlCylinder maintenanceRead
BI187CPYDirtyCylAlCylinder burnt outRead
BI188CPYFoamAlFoam presenceRead
BI189CPYLifeTimeAlLife timer expiredRead
BI190CPYHighWatLevAlHigh water levelRead
BI91CPYHighWatConductAlHigh water conductivityRead
BI192CPYConnectionAlConnection errorRead
BI193WatPresAlWater presence sensor alarmRead
BI194DrainPumpAlCondensate discharge pump alarmRead
BI195ElHeatAlElectric coil safety thermostatRead
BI196FilterAlClogged air filter alarmRead
BI197DryCoolerAlDry cooler general alarmRead
BI198ExternalHumidifAlExternal humidifier general alarmRead
BI199WaterPumpAlGeneral water pump alarmRead
BI200CondUnitGeneralAlCondensing unit general alarmRead
BI201GasLeakAlRefrigerant gas leak detector alarmRead
BI202PowerSupplyAlNo power supply alarmRead
BI203GenericSoftAlNon-critical generic alarmRead
BI204LocalNetworkAlLocal network communication alarmRead
BI205RegHighTempAlHigh temperature regulation alarmRead
BI206RegLowTempAlLow temperature regulation alarmRead
BI207HighLimTempAlHigh limit temperature alarmRead
BI208LowLimTempAlLow limit temperature alarmRead
BI209RetHighHumiAlHigh return humidity alarmRead
BI210RetLowHumiAlLow return humidity alarmRead
BI211SupHighHumiAlHigh supply humidity alarmRead
BI212SupLowHumiAlLow supply humidity alarmRead
BI213ProbeMod1COMModule 1 communication alarmRead
BI214ProbeMod1err1Probe 1 module 1 alarmRead
BI215ProbeMod1err2Probe 2 module 1 alarmRead
BI216ProbeMod1err3Probe 3 module 1 alarmRead
BI217ProbeMod1err4Probe 4 module 1 alarmRead
BI218ProbeMod1err5Probe 5 module 1 alarmRead
BI219ProbeMod1err6Probe 6 module 1 alarmRead
BI220ProbeMod2COMModule 2 communication alarmRead
BI221ProbeMod2err1Probe 1 module 2 alarmRead
BI222ProbeMod2err2Probe 2 module 2 alarmRead
BI223ProbeMod2err3Probe 3 module 2 alarmRead
BI224ProbeMod2err4Probe 4 module 2 alarmRead
BI225ProbeMod2err5Probe 5 module 2 alarmRead
BI226ProbeMod2err6Probe 6 module 2 alarmRead
BI227ProbeMod3COMModule 3 communication alarmRead
BI228ProbeMod3err1Probe 1 module 3 alarmRead
BI229ProbeMod3err2Probe 2 module 3 alarmRead
BI230ProbeMod3err3Probe 3 module 3 alarmRead
BI231ProbeMod3err4Probe 4 module 3 alarmRead
BI232ProbeMod3err5Probe 5 module 3 alarmRead
BI233ProbeMod3err6Probe 6 module 3 alarmRead
BV7DamperAlResDamper status alarm resetWrite
BV8FireSmokeAlResFire/Smoke presence alarm resetWrite
BV9GenericSeriousAlResCritical generic alarm resetWrite
BV10FansGenAlResGeneral supply fans alarm resetWrite
BV11Fan1InverterAlResFan 1 inverter alarm resetWrite
BV12Fan2InverterAlResFan 2 inverter alarm resetWrite
BV13Fan3InverterAlResFan 3 inverter alarm resetWrite
BV14Fan4InverterAlResFan 4 inverter alarm resetWrite
BV15Fan5InverterAlResFan 5 inverter alarm resetWrite
BV16Fan6InverterAlResFan 6 inverter alarm resetWrite
BV17Fan7InverterAlResFan 7 inverter alarm resetWrite
BV18Fan8InverterAlResFan 8 inverter alarm resetWrite
BV19Fan9InverterAlResFan 9 inverter alarm resetWrite
BV20Fan10InverterAlResFan 10 inverter alarm resetWrite
BV21InverterCompAlResCompressor 1 inverter alarm resetWrite
BV22C1ThermAlResCompressor 1 thermal magnetic protection alarm resetWrite
BV23C1HighPresAlResCompressor 1 high pressure alarm resetWrite
BV24C1LowPresAlResCompressor 1 low pressure alarm resetWrite
BV25C1HighDischAlResCompressor 1 discharge high temperature alarm resetWrite
BV26C1LoComprRatioAlResCompressor 1 low compression alarm resetWrite
BV27Condenser1AlResCondenser 1 general alarm resetWrite
BV28EEV1AlResCompressor 1 EEV alarm resetWrite
BV29C2ThermAlResCompressor 2 thermal magnetic protection alarm resetWrite
BV30C2HighPresAlResCompressor 2 high pressure alarm resetWrite
BV31C2LowPresAlResCompressor 2 low pressure alarm resetWrite
BV32C2HighDischAlResCompressor 2 discharge high temperature alarm resetWrite
BV33C2LoComprRatioAlResCompressor 2 low compression alarm resetWrite
BV34Condenser2AlResCondenser 2 general alarm resetWrite
BV35EEV2AlResCompressor 2 EEV alarm resetWrite
BV36IntHumidifAlResInternal humidifier alarm resetWrite
BV37WatPresAlResWater presence sensor alarm resetWrite
BV38DrainPumpAlResCondensate discharge pump alarm resetWrite
BV39ElHeatAlResElectr. coil safety thermostat alarm resetWrite
BV40FilterAlResClogged air filter alarm resetWrite
BV41DryCoolerAlResDry cooler general alarm resetWrite
BV42ExtHumidifAlResExternal humidifier general alarm resetWrite
BV43WaterPumpAlResGeneral water pump alarm resetWrite
BV44CondUnitGenAlResCondensing unit generic alarm resetWrite
BV45GasLeakAlResRefrigerant gas leak detector alarm resetWrite
BV46PowerSupplyAlResNo power supply alarm resetWrite
BV47GenericSoftAlResNon-critical generic alarm resetWrite
Object ID lookup: Aermec Aermec SURVEY3 close control point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the P / G / R / TMC precision air conditioners with SURVEY3 controller (software 3.0) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Aermec P / G / R / TMC precision air conditioners with SURVEY3 controller (software 3.0)

How many BACnet points does the Aermec P / G / R / TMC precision air conditioners with SURVEY3 controller (software 3.0) have?

This list has 530 BACnet objects: 56 analog inputs, 6 analog outputs, 139 analog values, 233 binary inputs, 14 binary outputs, 47 binary values, 35 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Aermec P / G / R / TMC precision air conditioners with SURVEY3 controller (software 3.0) BACnet points are writable?

83 of the 530 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Aermec P / G / R / TMC precision air conditioners with SURVEY3 controller (software 3.0) BACnet documentation?

The source is Precision air conditioners P-G-R-TMC user manual (5895970_01), revision 2020-11, published free by Aermec at https://aermec.com/download?id=13846.

What are the minimum BACnet points to integrate the Aermec P / G / R / TMC precision air conditioners with SURVEY3 controller (software 3.0)?

Start with BV 1 SupervOFF (On/off command from the supervisor); AV 108 TemperatureSetpoint (Temperature setpoint, °C); AV 109 HumiditySetpoint (Humidity setpoint, %rH); MV 19 UnitStatus (Unit status); AI 1 ReturnTemperature (Return temperature, °C); AI 3 SupplyTemperature (Supply temperature, °C); AI 6 ReturnHumidity (Return humidity, %rH); BO 1 FansDO (Fan control output); BO 10 Compressor1DO (Compressor 1 output); BI 2 DirtyFilterDI (Dirty filter alarm).

How do I enable BMS control of the Aermec P / G / R / TMC precision air conditioners with SURVEY3 controller (software 3.0)?

On/Off from supervisor is BV 1 (SupervOFF), writable.

How do I check these points on the real P / G / R / TMC precision air conditioners with SURVEY3 controller (software 3.0)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Precision air conditioners P-G-R-TMC user manual · 5895970_01 · rev. 2020-11. Object names, instances and units are reproduced as published; descriptions are our own.