Air source heat pump (cascade BMS interface) · BACnet points list

Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP BACnet points list

Updated 12 November 2026

Short answer

The Lincoln BMS Interface is an extension board that runs central heating (CH) and domestic hot water (DHW) control for a group of Adveco Lincoln L70 air source heat pumps and exposes it on BACnet MS/TP. The BMS can pick the CH and DHW control modes, send demand and flow or tank setpoints, run weather compensation and supplementary heating, and read the board's I/O plus inlet, outlet and ambient temperatures, compressor status, alarms and energy for each of up to 10 Lincolns.

This page lists 120 BACnet objects for the Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP — 36 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Adveco’s own free documentation, linked below.

Manufacturer
Adveco
Model
Lincoln L70 BMS Interface (extension board) BACnet MS/TP
Equipment
Air source heat pump (cascade BMS interface)
Equipment type
Heat pumps
BACnet objects
120 (36 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
1
Also known as
Lincoln, L70, Lincoln L70, Lincoln extension board, Lincoln BMS Interface
Source document
Lincoln L70 BMS Interface BACnet Protocol · rev. Rev. 1 - 07062023
Download CSV 120 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Adveco’s current documentation and the live device before use. Not official Adveco information. Terms of use.

BMS integration notes: Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP

Integration in brief

Set ch_mode_select (IV 49) to 4 (BMS Control), then switch heating with ch_bms_demand (BV 36) and set the flow temperature with ch_master_flow_SP (AV 15). For hot water set dhw_mode_select (IV 53) to 3 and use dhw_bms_demand (BV 44) with dhw_flow_SP (AV 18). Read ch_flow_SP and the fault flags.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
IV 49ch_mode_selectCH control mode; 4 = BMS ControlWrite
BV 36ch_bms_demandCH demand from the BMS (1 = active)Write
IV 53dhw_mode_selectDHW control mode; 3 = BMS ControlWrite
BV 44dhw_bms_demandDHW demand from the BMSWrite
AV 15ch_master_flow_SPCH flow setpoint in DI/BMS mode, °CWrite
AV 18dhw_flow_SPDHW flow setpoint, °CWrite
AI 13ch_flow_SPCH flow setpoint in useRead
BI 37ch_demandCH demand activeRead
BI 39ges_major_faultAny major faultRead
BI 40ges_minor_faultAny minor faultRead

Enable & remote start

ch_mode_select (IV 49) = 4 puts central heating under BMS control, switched by ch_bms_demand (BV 36) to the ch_master_flow_SP setpoint; dhw_mode_select (IV 53) = 3 does the same for hot water with dhw_bms_demand (BV 44).

Sensors & values from the BMS

ambient_temp_select (IV 48) picks the ambient temperature for weather compensation and low-ambient logic: the average of all active Lincolns, Lincoln 1 only, or the probe wired to the extension board.

Network setup

Watch out for

Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

120 of 120 shown
Type
Access
Show
Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP BACnet Points List
DescriptionStates
AI1AI_Input_0_10V0-10 V central heating control inputRead
AI2AI_Input_4_20mA4-20 mA central heating control inputRead
AI3AI_ambient_tempAmbient temperature probe (extension board)Read
AI4AI_ch_buffer_tempCH buffer tank temperatureRead
AI5AI_dhw_tank_probe_1DHW tank probe 1Read
AI6AI_dhw_tank_probe_2DHW tank probe 2Read
AV7ch_0to10_lower_threshold0-10 V threshold: unit on / minimum flowWrite
AV8ch_0to10_upper_threshold0-10 V threshold: maximum flowWrite
AV9ch_4to20_lower_threshold4-20 mA threshold: unit on / minimum flowWrite
AV10ch_4to20_upper_threshold4-20 mA threshold: maximum flowWrite
AV11ch_buffer_supp_DIFFCH supplementary heat off differentialWrite
AV12ch_buffer_supp_SPCH supplementary heat buffer tank setpointWrite
AImin13ch_flow_SPCH flow setpoint in useRead
AV14ch_low_ambient_SPCH supplementary heat low-ambient setpointWrite
AVmin15ch_master_flow_SPCH flow setpoint (DI or BMS mode)Write
AV16ch_max_flow_tempCH maximum flow temperatureWrite
AV17ch_min_flow_tempCH minimum flow temperatureWrite
AVmin18dhw_flow_SPDHW flow setpointWrite
AV19dhw_low_ambient_SPDHW supplementary heat low-ambient setpointWrite
AI20dhw_master_tank_tempDHW tank temperature used for controlRead
AV21dhw_supp_diffDHW supplementary heat differentialWrite
AV22dhw_tank_DIFFDHW tank differentialWrite
AV23dhw_tank_SPDHW tank setpointWrite
AV24min_air_temp_weather_compWeather compensation: air temp for max flowWrite
AV25max_air_temp_weather_compWeather compensation: air temp for min flowWrite
BI26DI_ch_ext_controlCH external control digital inputRead
BI27DI_dhw_ext_controlDHW external control digital inputRead
BI28DO_ch_dhw_valve_demandCH/DHW valve outputRead
BI29DO_ch_pump_runCH pump run outputRead
BI30DO_ch_supplementaryCH supplementary heat outputRead
BI31DO_dhw_supplementaryDHW supplementary heat outputRead
BI32DO_global_supplementaryGlobal supplementary heat outputRead
BI33DO_hx_pump_runHeat exchanger pump run outputRead
BI34DO_output_major_faultsMajor fault outputRead
BI35DO_output_minor_faultsMinor fault outputRead
BVmin36ch_bms_demandCH demand from the BMSWrite0=CH demand inactive, 1=CH demand active
BImin37ch_demandCH demand activeRead
BI38dhw_demandDHW demand activeRead
BImin39ges_major_faultAny major faultRead
BImin40ges_minor_faultAny minor faultRead
BV41ch_dhw_priorityCH / DHW priorityWrite0=DHW priority, 1=CH priority
BV42ch_manual_supp_forceForce CH supplementary heat onWrite0=Off, 1=On
BV43ch_manual_supp_on_demandCH supplementary heat on every CH demandWrite0=Off, 1=On
BVmin44dhw_bms_demandDHW demand from the BMSWrite
BV45dhw_manual_supp_forceForce DHW supplementary heat onWrite
BV46dhw_manual_supp_on_demandDHW supplementary heat on every DHW demandWrite
BV47enable_weather_compensationEnable weather compensationWrite0=Off, 1=Enabled
IV48ambient_temp_selectAmbient temperature sourceWrite
IVmin49ch_mode_selectCentral heating control modeWrite0=None, 1=4-20mA, 2=0-10v, 3=Digital Input, 4=BMS Control
IV50ch_supp_modeCH buffer tank supplementary modeWrite0=Off, 1=Buffer tank temp supplementary on
IV51ch_supp_on_alarmCH supplementary heat on major alarmWrite0=Off, 1=On with major fault and CH demand, 2=On with major fault only
IV52dhw_master_tank_temp_selectionDHW tank temperature sourceWrite
IVmin53dhw_mode_selectDHW control modeWrite0=None, 1=Digital Input, 2=Tank Probe, 3=BMS Control
IV54dhw_supp_modeDHW supplementary heat modeWrite
IV55dhw_supp_on_alarmDHW supplementary heat on major alarmWrite
BI56lincoln_device_major_alarm[1]Lincoln 1: major alarmRead
BI57lincoln_device_minor_alarm[1]Lincoln 1: minor alarmRead
AI58lincoln_variables_OUT[1].T01_inlet_water_tempLincoln 1: inlet water temperatureRead
AI59lincoln_variables_OUT[1].T02_outlet_water_tempLincoln 1: outlet water temperatureRead
AI60lincoln_variables_OUT[1].T04_ambient_tempLincoln 1: ambient temperatureRead
BI61lincoln_variables_OUT[1].system1_compressor_statusLincoln 1: system 1 compressor statusRead
BI62lincoln_variables_OUT[1].system2_compressor_stausLincoln 1: system 2 compressor statusRead
AI63power_meter_variables_OUT_global[1].Direct_Positive_EnergyLincoln 1: energy meter, direct positive energyRead
AI64lincoln_variables_OUT[2].T01_inlet_water_tempLincoln 2: inlet water temperatureRead
AI65lincoln_variables_OUT[2].T02_outlet_water_tempLincoln 2: outlet water temperatureRead
AI66lincoln_variables_OUT[2].T04_ambient_tempLincoln 2: ambient temperatureRead
BI67lincoln_variables_OUT[2].system1_compressor_statusLincoln 2: system 1 compressor statusRead
BI68lincoln_variables_OUT[2].system2_compressor_stausLincoln 2: system 2 compressor statusRead
AI69power_meter_variables_OUT_global[2].Direct_Positive_EnergyLincoln 2: energy meter, direct positive energyRead
AI70lincoln_variables_OUT[3].T01_inlet_water_tempLincoln 3: inlet water temperatureRead
AI71lincoln_variables_OUT[3].T02_outlet_water_tempLincoln 3: outlet water temperatureRead
AI72lincoln_variables_OUT[3].T04_ambient_tempLincoln 3: ambient temperatureRead
BI73lincoln_variables_OUT[3].system1_compressor_statusLincoln 3: system 1 compressor statusRead
BI74lincoln_variables_OUT[3].system2_compressor_stausLincoln 3: system 2 compressor statusRead
AI75power_meter_variables_OUT_global[3].Direct_Positive_EnergyLincoln 3: energy meter, direct positive energyRead
AI76lincoln_variables_OUT[4].T01_inlet_water_tempLincoln 4: inlet water temperatureRead
AI77lincoln_variables_OUT[4].T02_outlet_water_tempLincoln 4: outlet water temperatureRead
AI78lincoln_variables_OUT[4].T04_ambient_tempLincoln 4: ambient temperatureRead
BI79lincoln_variables_OUT[4].system1_compressor_statusLincoln 4: system 1 compressor statusRead
BI80lincoln_variables_OUT[4].system2_compressor_stausLincoln 4: system 2 compressor statusRead
AI81power_meter_variables_OUT_global[4].Direct_Positive_EnergyLincoln 4: energy meter, direct positive energyRead
AI82lincoln_variables_OUT[5].T01_inlet_water_tempLincoln 5: inlet water temperatureRead
AI83lincoln_variables_OUT[5].T02_outlet_water_tempLincoln 5: outlet water temperatureRead
AI84lincoln_variables_OUT[5].T04_ambient_tempLincoln 5: ambient temperatureRead
BI85lincoln_variables_OUT[5].system1_compressor_statusLincoln 5: system 1 compressor statusRead
BI86lincoln_variables_OUT[5].system2_compressor_stausLincoln 5: system 2 compressor statusRead
AI87power_meter_variables_OUT_global[5].Direct_Positive_EnergyLincoln 5: energy meter, direct positive energyRead
AI88lincoln_variables_OUT[6].T01_inlet_water_tempLincoln 6: inlet water temperatureRead
AI89lincoln_variables_OUT[6].T02_outlet_water_tempLincoln 6: outlet water temperatureRead
AI90lincoln_variables_OUT[6].T04_ambient_tempLincoln 6: ambient temperatureRead
BI91lincoln_variables_OUT[6].system1_compressor_statusLincoln 6: system 1 compressor statusRead
BI92lincoln_variables_OUT[6].system2_compressor_stausLincoln 6: system 2 compressor statusRead
AI93power_meter_variables_OUT_global[6].Direct_Positive_EnergyLincoln 6: energy meter, direct positive energyRead
AI94lincoln_variables_OUT[7].T01_inlet_water_tempLincoln 7: inlet water temperatureRead
AI95lincoln_variables_OUT[7].T02_outlet_water_tempLincoln 7: outlet water temperatureRead
AI96lincoln_variables_OUT[7].T04_ambient_tempLincoln 7: ambient temperatureRead
BI97lincoln_variables_OUT[7].system1_compressor_statusLincoln 7: system 1 compressor statusRead
BI98lincoln_variables_OUT[7].system2_compressor_stausLincoln 7: system 2 compressor statusRead
AI99power_meter_variables_OUT_global[7].Direct_Positive_EnergyLincoln 7: energy meter, direct positive energyRead
AI100lincoln_variables_OUT[8].T01_inlet_water_tempLincoln 8: inlet water temperatureRead
AI101lincoln_variables_OUT[8].T02_outlet_water_tempLincoln 8: outlet water temperatureRead
AI102lincoln_variables_OUT[8].T04_ambient_tempLincoln 8: ambient temperatureRead
BI103lincoln_variables_OUT[8].system1_compressor_statusLincoln 8: system 1 compressor statusRead
BI104lincoln_variables_OUT[8].system2_compressor_stausLincoln 8: system 2 compressor statusRead
AI105power_meter_variables_OUT_global[8].Direct_Positive_EnergyLincoln 8: energy meter, direct positive energyRead
AI106lincoln_variables_OUT[9].T01_inlet_water_tempLincoln 9: inlet water temperatureRead
AI107lincoln_variables_OUT[9].T02_outlet_water_tempLincoln 9: outlet water temperatureRead
AI108lincoln_variables_OUT[9].T04_ambient_tempLincoln 9: ambient temperatureRead
BI109lincoln_variables_OUT[9].system1_compressor_statusLincoln 9: system 1 compressor statusRead
BI110lincoln_variables_OUT[9].system2_compressor_stausLincoln 9: system 2 compressor statusRead
AI111power_meter_variables_OUT_global[9].Direct_Positive_EnergyLincoln 9: energy meter, direct positive energyRead
AI112lincoln_variables_OUT[10].T01_inlet_water_tempLincoln 10: inlet water temperatureRead
AI113lincoln_variables_OUT[10].T02_outlet_water_tempLincoln 10: outlet water temperatureRead
AI114lincoln_variables_OUT[10].T04_ambient_tempLincoln 10: ambient temperatureRead
BI115lincoln_variables_OUT[10].system1_compressor_statusLincoln 10: system 1 compressor statusRead
BI116lincoln_variables_OUT[10].system2_compressor_stausLincoln 10: system 2 compressor statusRead
AI117power_meter_variables_OUT_global[10].Direct_Positive_EnergyLincoln 10: energy meter, direct positive energyRead
PIV118bacnet_device_instanceBACnet device instanceWrite
PIV119bacnet_baudrateBACnet MS/TP baud rateWrite
BV120Reboot_UPCReboot the interface (1 = reboot)Write
Object ID lookup: Adveco Lincoln L70 BMS Interface BACnet MS/TP point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Lincoln L70 BMS Interface (extension board) BACnet MS/TP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP

How many BACnet points does the Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP have?

This list has 120 BACnet objects: 48 analog inputs, 17 analog values, 36 binary inputs, 9 binary values, 8 integer values, 2 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP BACnet points are writable?

36 of the 120 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP BACnet documentation?

The source is Lincoln L70 BMS Interface BACnet Protocol, revision Rev. 1 - 07062023, published free by Adveco at https://adveco.co/wp-content/uploads/2023/06/L70-Lincoln-Extension-BACnet-Protocol-Rev.1.pdf.

What are the minimum BACnet points to integrate the Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP?

Start with IV 49 ch_mode_select (CH control mode; 4 = BMS Control); BV 36 ch_bms_demand (CH demand from the BMS (1 = active)); IV 53 dhw_mode_select (DHW control mode; 3 = BMS Control); BV 44 dhw_bms_demand (DHW demand from the BMS); AV 15 ch_master_flow_SP (CH flow setpoint in DI/BMS mode, °C); AV 18 dhw_flow_SP (DHW flow setpoint, °C); AI 13 ch_flow_SP (CH flow setpoint in use); BI 37 ch_demand (CH demand active); BI 39 ges_major_fault (Any major fault); BI 40 ges_minor_fault (Any minor fault).

How do I enable BMS control of the Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP?

ch_mode_select (IV 49) = 4 puts central heating under BMS control, switched by ch_bms_demand (BV 36) to the ch_master_flow_SP setpoint; dhw_mode_select (IV 53) = 3 does the same for hot water with dhw_bms_demand (BV 44).

Can the BMS supply sensor values to the Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP?

ambient_temp_select (IV 48) picks the ambient temperature for weather compensation and low-ambient logic: the average of all active Lincolns, Lincoln 1 only, or the probe wired to the extension board.

How do I check these points on the real Lincoln L70 BMS Interface (extension board) BACnet MS/TP?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Lincoln L70 BMS Interface BACnet Protocol · rev. Rev. 1 - 07062023. Object names, instances and units are reproduced as published; descriptions are our own.