- Lincoln L70 BMS Interface (extension board) BACnet MS/TP
Air source heat pump (cascade BMS interface) · BACnet points list
Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP BACnet points list
Updated 12 November 2026
The Lincoln BMS Interface is an extension board that runs central heating (CH) and domestic hot water (DHW) control for a group of Adveco Lincoln L70 air source heat pumps and exposes it on BACnet MS/TP. The BMS can pick the CH and DHW control modes, send demand and flow or tank setpoints, run weather compensation and supplementary heating, and read the board's I/O plus inlet, outlet and ambient temperatures, compressor status, alarms and energy for each of up to 10 Lincolns.
This page lists 120 BACnet objects for the Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP — 36 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Adveco’s own free documentation, linked below.
- Manufacturer
- Adveco
- Model
- Lincoln L70 BMS Interface (extension board) BACnet MS/TP
- Equipment
- Air source heat pump (cascade BMS interface)
- Equipment type
- Heat pumps
- BACnet objects
- 120 (36 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 1
- Also known as
- Lincoln, L70, Lincoln L70, Lincoln extension board, Lincoln BMS Interface
Reference only, provided as-is: verify against Adveco’s current documentation and the live device before use. Not official Adveco information. Terms of use.
BMS integration notes: Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP
Set ch_mode_select (IV 49) to 4 (BMS Control), then switch heating with ch_bms_demand (BV 36) and set the flow temperature with ch_master_flow_SP (AV 15). For hot water set dhw_mode_select (IV 53) to 3 and use dhw_bms_demand (BV 44) with dhw_flow_SP (AV 18). Read ch_flow_SP and the fault flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| IV 49 | ch_mode_select | CH control mode; 4 = BMS Control | Write |
| BV 36 | ch_bms_demand | CH demand from the BMS (1 = active) | Write |
| IV 53 | dhw_mode_select | DHW control mode; 3 = BMS Control | Write |
| BV 44 | dhw_bms_demand | DHW demand from the BMS | Write |
| AV 15 | ch_master_flow_SP | CH flow setpoint in DI/BMS mode, °C | Write |
| AV 18 | dhw_flow_SP | DHW flow setpoint, °C | Write |
| AI 13 | ch_flow_SP | CH flow setpoint in use | Read |
| BI 37 | ch_demand | CH demand active | Read |
| BI 39 | ges_major_fault | Any major fault | Read |
| BI 40 | ges_minor_fault | Any minor fault | Read |
Enable & remote start
ch_mode_select (IV 49) = 4 puts central heating under BMS control, switched by ch_bms_demand (BV 36) to the ch_master_flow_SP setpoint; dhw_mode_select (IV 53) = 3 does the same for hot water with dhw_bms_demand (BV 44).
Sensors & values from the BMS
ambient_temp_select (IV 48) picks the ambient temperature for weather compensation and low-ambient logic: the average of all active Lincolns, Lincoln 1 only, or the probe wired to the extension board.
Network setup
- BACnet MS/TP on the BMS2 / Fieldbus 2 port; defaults device instance 1, 9600 baud (1200-375000 selectable).
- Device instance and baud rate are set with bacnet_device_instance (PIV 118) and bacnet_baudrate (PIV 119); write Reboot_UPC (BV 120) = 1 to apply.
Watch out for
- Weather compensation is ignored while CH runs in 4-20 mA or 0-10 V mode.
Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | AI_Input_0_10V | 0-10 V central heating control input | Read | ||
| AI | 2 | AI_Input_4_20mA | 4-20 mA central heating control input | Read | ||
| AI | 3 | AI_ambient_temp | Ambient temperature probe (extension board) | Read | ||
| AI | 4 | AI_ch_buffer_temp | CH buffer tank temperature | Read | ||
| AI | 5 | AI_dhw_tank_probe_1 | DHW tank probe 1 | Read | ||
| AI | 6 | AI_dhw_tank_probe_2 | DHW tank probe 2 | Read | ||
| AV | 7 | ch_0to10_lower_threshold | 0-10 V threshold: unit on / minimum flow | Write | ||
| AV | 8 | ch_0to10_upper_threshold | 0-10 V threshold: maximum flow | Write | ||
| AV | 9 | ch_4to20_lower_threshold | 4-20 mA threshold: unit on / minimum flow | Write | ||
| AV | 10 | ch_4to20_upper_threshold | 4-20 mA threshold: maximum flow | Write | ||
| AV | 11 | ch_buffer_supp_DIFF | CH supplementary heat off differential | Write | ||
| AV | 12 | ch_buffer_supp_SP | CH supplementary heat buffer tank setpoint | Write | ||
| AImin | 13 | ch_flow_SP | CH flow setpoint in use | Read | ||
| AV | 14 | ch_low_ambient_SP | CH supplementary heat low-ambient setpoint | Write | ||
| AVmin | 15 | ch_master_flow_SP | CH flow setpoint (DI or BMS mode) | Write | ||
| AV | 16 | ch_max_flow_temp | CH maximum flow temperature | Write | ||
| AV | 17 | ch_min_flow_temp | CH minimum flow temperature | Write | ||
| AVmin | 18 | dhw_flow_SP | DHW flow setpoint | Write | ||
| AV | 19 | dhw_low_ambient_SP | DHW supplementary heat low-ambient setpoint | Write | ||
| AI | 20 | dhw_master_tank_temp | DHW tank temperature used for control | Read | ||
| AV | 21 | dhw_supp_diff | DHW supplementary heat differential | Write | ||
| AV | 22 | dhw_tank_DIFF | DHW tank differential | Write | ||
| AV | 23 | dhw_tank_SP | DHW tank setpoint | Write | ||
| AV | 24 | min_air_temp_weather_comp | Weather compensation: air temp for max flow | Write | ||
| AV | 25 | max_air_temp_weather_comp | Weather compensation: air temp for min flow | Write | ||
| BI | 26 | DI_ch_ext_control | CH external control digital input | Read | ||
| BI | 27 | DI_dhw_ext_control | DHW external control digital input | Read | ||
| BI | 28 | DO_ch_dhw_valve_demand | CH/DHW valve output | Read | ||
| BI | 29 | DO_ch_pump_run | CH pump run output | Read | ||
| BI | 30 | DO_ch_supplementary | CH supplementary heat output | Read | ||
| BI | 31 | DO_dhw_supplementary | DHW supplementary heat output | Read | ||
| BI | 32 | DO_global_supplementary | Global supplementary heat output | Read | ||
| BI | 33 | DO_hx_pump_run | Heat exchanger pump run output | Read | ||
| BI | 34 | DO_output_major_faults | Major fault output | Read | ||
| BI | 35 | DO_output_minor_faults | Minor fault output | Read | ||
| BVmin | 36 | ch_bms_demand | CH demand from the BMS | Write | 0=CH demand inactive, 1=CH demand active | |
| BImin | 37 | ch_demand | CH demand active | Read | ||
| BI | 38 | dhw_demand | DHW demand active | Read | ||
| BImin | 39 | ges_major_fault | Any major fault | Read | ||
| BImin | 40 | ges_minor_fault | Any minor fault | Read | ||
| BV | 41 | ch_dhw_priority | CH / DHW priority | Write | 0=DHW priority, 1=CH priority | |
| BV | 42 | ch_manual_supp_force | Force CH supplementary heat on | Write | 0=Off, 1=On | |
| BV | 43 | ch_manual_supp_on_demand | CH supplementary heat on every CH demand | Write | 0=Off, 1=On | |
| BVmin | 44 | dhw_bms_demand | DHW demand from the BMS | Write | ||
| BV | 45 | dhw_manual_supp_force | Force DHW supplementary heat on | Write | ||
| BV | 46 | dhw_manual_supp_on_demand | DHW supplementary heat on every DHW demand | Write | ||
| BV | 47 | enable_weather_compensation | Enable weather compensation | Write | 0=Off, 1=Enabled | |
| IV | 48 | ambient_temp_select | Ambient temperature source | Write | ||
| IVmin | 49 | ch_mode_select | Central heating control mode | Write | 0=None, 1=4-20mA, 2=0-10v, 3=Digital Input, 4=BMS Control | |
| IV | 50 | ch_supp_mode | CH buffer tank supplementary mode | Write | 0=Off, 1=Buffer tank temp supplementary on | |
| IV | 51 | ch_supp_on_alarm | CH supplementary heat on major alarm | Write | 0=Off, 1=On with major fault and CH demand, 2=On with major fault only | |
| IV | 52 | dhw_master_tank_temp_selection | DHW tank temperature source | Write | ||
| IVmin | 53 | dhw_mode_select | DHW control mode | Write | 0=None, 1=Digital Input, 2=Tank Probe, 3=BMS Control | |
| IV | 54 | dhw_supp_mode | DHW supplementary heat mode | Write | ||
| IV | 55 | dhw_supp_on_alarm | DHW supplementary heat on major alarm | Write | ||
| BI | 56 | lincoln_device_major_alarm[1] | Lincoln 1: major alarm | Read | ||
| BI | 57 | lincoln_device_minor_alarm[1] | Lincoln 1: minor alarm | Read | ||
| AI | 58 | lincoln_variables_OUT[1].T01_inlet_water_temp | Lincoln 1: inlet water temperature | Read | ||
| AI | 59 | lincoln_variables_OUT[1].T02_outlet_water_temp | Lincoln 1: outlet water temperature | Read | ||
| AI | 60 | lincoln_variables_OUT[1].T04_ambient_temp | Lincoln 1: ambient temperature | Read | ||
| BI | 61 | lincoln_variables_OUT[1].system1_compressor_status | Lincoln 1: system 1 compressor status | Read | ||
| BI | 62 | lincoln_variables_OUT[1].system2_compressor_staus | Lincoln 1: system 2 compressor status | Read | ||
| AI | 63 | power_meter_variables_OUT_global[1].Direct_Positive_Energy | Lincoln 1: energy meter, direct positive energy | Read | ||
| AI | 64 | lincoln_variables_OUT[2].T01_inlet_water_temp | Lincoln 2: inlet water temperature | Read | ||
| AI | 65 | lincoln_variables_OUT[2].T02_outlet_water_temp | Lincoln 2: outlet water temperature | Read | ||
| AI | 66 | lincoln_variables_OUT[2].T04_ambient_temp | Lincoln 2: ambient temperature | Read | ||
| BI | 67 | lincoln_variables_OUT[2].system1_compressor_status | Lincoln 2: system 1 compressor status | Read | ||
| BI | 68 | lincoln_variables_OUT[2].system2_compressor_staus | Lincoln 2: system 2 compressor status | Read | ||
| AI | 69 | power_meter_variables_OUT_global[2].Direct_Positive_Energy | Lincoln 2: energy meter, direct positive energy | Read | ||
| AI | 70 | lincoln_variables_OUT[3].T01_inlet_water_temp | Lincoln 3: inlet water temperature | Read | ||
| AI | 71 | lincoln_variables_OUT[3].T02_outlet_water_temp | Lincoln 3: outlet water temperature | Read | ||
| AI | 72 | lincoln_variables_OUT[3].T04_ambient_temp | Lincoln 3: ambient temperature | Read | ||
| BI | 73 | lincoln_variables_OUT[3].system1_compressor_status | Lincoln 3: system 1 compressor status | Read | ||
| BI | 74 | lincoln_variables_OUT[3].system2_compressor_staus | Lincoln 3: system 2 compressor status | Read | ||
| AI | 75 | power_meter_variables_OUT_global[3].Direct_Positive_Energy | Lincoln 3: energy meter, direct positive energy | Read | ||
| AI | 76 | lincoln_variables_OUT[4].T01_inlet_water_temp | Lincoln 4: inlet water temperature | Read | ||
| AI | 77 | lincoln_variables_OUT[4].T02_outlet_water_temp | Lincoln 4: outlet water temperature | Read | ||
| AI | 78 | lincoln_variables_OUT[4].T04_ambient_temp | Lincoln 4: ambient temperature | Read | ||
| BI | 79 | lincoln_variables_OUT[4].system1_compressor_status | Lincoln 4: system 1 compressor status | Read | ||
| BI | 80 | lincoln_variables_OUT[4].system2_compressor_staus | Lincoln 4: system 2 compressor status | Read | ||
| AI | 81 | power_meter_variables_OUT_global[4].Direct_Positive_Energy | Lincoln 4: energy meter, direct positive energy | Read | ||
| AI | 82 | lincoln_variables_OUT[5].T01_inlet_water_temp | Lincoln 5: inlet water temperature | Read | ||
| AI | 83 | lincoln_variables_OUT[5].T02_outlet_water_temp | Lincoln 5: outlet water temperature | Read | ||
| AI | 84 | lincoln_variables_OUT[5].T04_ambient_temp | Lincoln 5: ambient temperature | Read | ||
| BI | 85 | lincoln_variables_OUT[5].system1_compressor_status | Lincoln 5: system 1 compressor status | Read | ||
| BI | 86 | lincoln_variables_OUT[5].system2_compressor_staus | Lincoln 5: system 2 compressor status | Read | ||
| AI | 87 | power_meter_variables_OUT_global[5].Direct_Positive_Energy | Lincoln 5: energy meter, direct positive energy | Read | ||
| AI | 88 | lincoln_variables_OUT[6].T01_inlet_water_temp | Lincoln 6: inlet water temperature | Read | ||
| AI | 89 | lincoln_variables_OUT[6].T02_outlet_water_temp | Lincoln 6: outlet water temperature | Read | ||
| AI | 90 | lincoln_variables_OUT[6].T04_ambient_temp | Lincoln 6: ambient temperature | Read | ||
| BI | 91 | lincoln_variables_OUT[6].system1_compressor_status | Lincoln 6: system 1 compressor status | Read | ||
| BI | 92 | lincoln_variables_OUT[6].system2_compressor_staus | Lincoln 6: system 2 compressor status | Read | ||
| AI | 93 | power_meter_variables_OUT_global[6].Direct_Positive_Energy | Lincoln 6: energy meter, direct positive energy | Read | ||
| AI | 94 | lincoln_variables_OUT[7].T01_inlet_water_temp | Lincoln 7: inlet water temperature | Read | ||
| AI | 95 | lincoln_variables_OUT[7].T02_outlet_water_temp | Lincoln 7: outlet water temperature | Read | ||
| AI | 96 | lincoln_variables_OUT[7].T04_ambient_temp | Lincoln 7: ambient temperature | Read | ||
| BI | 97 | lincoln_variables_OUT[7].system1_compressor_status | Lincoln 7: system 1 compressor status | Read | ||
| BI | 98 | lincoln_variables_OUT[7].system2_compressor_staus | Lincoln 7: system 2 compressor status | Read | ||
| AI | 99 | power_meter_variables_OUT_global[7].Direct_Positive_Energy | Lincoln 7: energy meter, direct positive energy | Read | ||
| AI | 100 | lincoln_variables_OUT[8].T01_inlet_water_temp | Lincoln 8: inlet water temperature | Read | ||
| AI | 101 | lincoln_variables_OUT[8].T02_outlet_water_temp | Lincoln 8: outlet water temperature | Read | ||
| AI | 102 | lincoln_variables_OUT[8].T04_ambient_temp | Lincoln 8: ambient temperature | Read | ||
| BI | 103 | lincoln_variables_OUT[8].system1_compressor_status | Lincoln 8: system 1 compressor status | Read | ||
| BI | 104 | lincoln_variables_OUT[8].system2_compressor_staus | Lincoln 8: system 2 compressor status | Read | ||
| AI | 105 | power_meter_variables_OUT_global[8].Direct_Positive_Energy | Lincoln 8: energy meter, direct positive energy | Read | ||
| AI | 106 | lincoln_variables_OUT[9].T01_inlet_water_temp | Lincoln 9: inlet water temperature | Read | ||
| AI | 107 | lincoln_variables_OUT[9].T02_outlet_water_temp | Lincoln 9: outlet water temperature | Read | ||
| AI | 108 | lincoln_variables_OUT[9].T04_ambient_temp | Lincoln 9: ambient temperature | Read | ||
| BI | 109 | lincoln_variables_OUT[9].system1_compressor_status | Lincoln 9: system 1 compressor status | Read | ||
| BI | 110 | lincoln_variables_OUT[9].system2_compressor_staus | Lincoln 9: system 2 compressor status | Read | ||
| AI | 111 | power_meter_variables_OUT_global[9].Direct_Positive_Energy | Lincoln 9: energy meter, direct positive energy | Read | ||
| AI | 112 | lincoln_variables_OUT[10].T01_inlet_water_temp | Lincoln 10: inlet water temperature | Read | ||
| AI | 113 | lincoln_variables_OUT[10].T02_outlet_water_temp | Lincoln 10: outlet water temperature | Read | ||
| AI | 114 | lincoln_variables_OUT[10].T04_ambient_temp | Lincoln 10: ambient temperature | Read | ||
| BI | 115 | lincoln_variables_OUT[10].system1_compressor_status | Lincoln 10: system 1 compressor status | Read | ||
| BI | 116 | lincoln_variables_OUT[10].system2_compressor_staus | Lincoln 10: system 2 compressor status | Read | ||
| AI | 117 | power_meter_variables_OUT_global[10].Direct_Positive_Energy | Lincoln 10: energy meter, direct positive energy | Read | ||
| PIV | 118 | bacnet_device_instance | BACnet device instance | Write | ||
| PIV | 119 | bacnet_baudrate | BACnet MS/TP baud rate | Write | ||
| BV | 120 | Reboot_UPC | Reboot the interface (1 = reboot) | Write |
No points match these filters.
Object ID lookup: Adveco Lincoln L70 BMS Interface BACnet MS/TP point IDs by name
AI1AI_Input_0_10VAI2AI_Input_4_20mAAI3AI_ambient_tempAI4AI_ch_buffer_tempAI5AI_dhw_tank_probe_1AI6AI_dhw_tank_probe_2AV7ch_0to10_lower_thresholdAV8ch_0to10_upper_thresholdAV9ch_4to20_lower_thresholdAV10ch_4to20_upper_thresholdAV11ch_buffer_supp_DIFFAV12ch_buffer_supp_SPAI13ch_flow_SPAV14ch_low_ambient_SPAV15ch_master_flow_SPAV16ch_max_flow_tempAV17ch_min_flow_tempAV18dhw_flow_SPAV19dhw_low_ambient_SPAI20dhw_master_tank_tempAV21dhw_supp_diffAV22dhw_tank_DIFFAV23dhw_tank_SPAV24min_air_temp_weather_compAV25max_air_temp_weather_compBI26DI_ch_ext_controlBI27DI_dhw_ext_controlBI28DO_ch_dhw_valve_demandBI29DO_ch_pump_runBI30DO_ch_supplementaryBI31DO_dhw_supplementaryBI32DO_global_supplementaryBI33DO_hx_pump_runBI34DO_output_major_faultsBI35DO_output_minor_faultsBV36ch_bms_demandBI37ch_demandBI38dhw_demandBI39ges_major_faultBI40ges_minor_faultBV41ch_dhw_priorityBV42ch_manual_supp_forceBV43ch_manual_supp_on_demandBV44dhw_bms_demandBV45dhw_manual_supp_forceBV46dhw_manual_supp_on_demandBV47enable_weather_compensationIV48ambient_temp_selectIV49ch_mode_selectIV50ch_supp_modeIV51ch_supp_on_alarmIV52dhw_master_tank_temp_selectionIV53dhw_mode_selectIV54dhw_supp_modeIV55dhw_supp_on_alarmBI56lincoln_device_major_alarm[1]BI57lincoln_device_minor_alarm[1]AI58lincoln_variables_OUT[1].T01_inlet_water_tempAI59lincoln_variables_OUT[1].T02_outlet_water_tempAI60lincoln_variables_OUT[1].T04_ambient_tempBI61lincoln_variables_OUT[1].system1_compressor_statusBI62lincoln_variables_OUT[1].system2_compressor_stausAI63power_meter_variables_OUT_global[1].Direct_Positive_EnergyAI64lincoln_variables_OUT[2].T01_inlet_water_tempAI65lincoln_variables_OUT[2].T02_outlet_water_tempAI66lincoln_variables_OUT[2].T04_ambient_tempBI67lincoln_variables_OUT[2].system1_compressor_statusBI68lincoln_variables_OUT[2].system2_compressor_stausAI69power_meter_variables_OUT_global[2].Direct_Positive_EnergyAI70lincoln_variables_OUT[3].T01_inlet_water_tempAI71lincoln_variables_OUT[3].T02_outlet_water_tempAI72lincoln_variables_OUT[3].T04_ambient_tempBI73lincoln_variables_OUT[3].system1_compressor_statusBI74lincoln_variables_OUT[3].system2_compressor_stausAI75power_meter_variables_OUT_global[3].Direct_Positive_EnergyAI76lincoln_variables_OUT[4].T01_inlet_water_tempAI77lincoln_variables_OUT[4].T02_outlet_water_tempAI78lincoln_variables_OUT[4].T04_ambient_tempBI79lincoln_variables_OUT[4].system1_compressor_statusBI80lincoln_variables_OUT[4].system2_compressor_stausAI81power_meter_variables_OUT_global[4].Direct_Positive_EnergyAI82lincoln_variables_OUT[5].T01_inlet_water_tempAI83lincoln_variables_OUT[5].T02_outlet_water_tempAI84lincoln_variables_OUT[5].T04_ambient_tempBI85lincoln_variables_OUT[5].system1_compressor_statusBI86lincoln_variables_OUT[5].system2_compressor_stausAI87power_meter_variables_OUT_global[5].Direct_Positive_EnergyAI88lincoln_variables_OUT[6].T01_inlet_water_tempAI89lincoln_variables_OUT[6].T02_outlet_water_tempAI90lincoln_variables_OUT[6].T04_ambient_tempBI91lincoln_variables_OUT[6].system1_compressor_statusBI92lincoln_variables_OUT[6].system2_compressor_stausAI93power_meter_variables_OUT_global[6].Direct_Positive_EnergyAI94lincoln_variables_OUT[7].T01_inlet_water_tempAI95lincoln_variables_OUT[7].T02_outlet_water_tempAI96lincoln_variables_OUT[7].T04_ambient_tempBI97lincoln_variables_OUT[7].system1_compressor_statusBI98lincoln_variables_OUT[7].system2_compressor_stausAI99power_meter_variables_OUT_global[7].Direct_Positive_EnergyAI100lincoln_variables_OUT[8].T01_inlet_water_tempAI101lincoln_variables_OUT[8].T02_outlet_water_tempAI102lincoln_variables_OUT[8].T04_ambient_tempBI103lincoln_variables_OUT[8].system1_compressor_statusBI104lincoln_variables_OUT[8].system2_compressor_stausAI105power_meter_variables_OUT_global[8].Direct_Positive_EnergyAI106lincoln_variables_OUT[9].T01_inlet_water_tempAI107lincoln_variables_OUT[9].T02_outlet_water_tempAI108lincoln_variables_OUT[9].T04_ambient_tempBI109lincoln_variables_OUT[9].system1_compressor_statusBI110lincoln_variables_OUT[9].system2_compressor_stausAI111power_meter_variables_OUT_global[9].Direct_Positive_EnergyAI112lincoln_variables_OUT[10].T01_inlet_water_tempAI113lincoln_variables_OUT[10].T02_outlet_water_tempAI114lincoln_variables_OUT[10].T04_ambient_tempBI115lincoln_variables_OUT[10].system1_compressor_statusBI116lincoln_variables_OUT[10].system2_compressor_stausAI117power_meter_variables_OUT_global[10].Direct_Positive_EnergyPIV118bacnet_device_instancePIV119bacnet_baudrateBV120Reboot_UPC
Integration notes
- The guide gives no units; temperatures are in °C going by the prose (for example ch_master_flow_SP default 35 °C).
- Per-heat-pump objects (instances 56-117) carry the Lincoln number as the index in the name. Temperatures, compressor status and energy are printed for Lincolns 1 to 10; the minor and major alarm objects are printed for Lincoln 1 only.
- Access comes from the guide's Read/Write Mode column: Writeable / Read_Write = W, NoWrite = R.
- ch_bms_demand prose says 1 = ON, 2 = OFF in one place and 0 / 1 in another; the BinaryValue object is 0 = inactive, 1 = active.
- BACnet type IntegerValue is listed as IV and PositiveIntegerValue as PIV.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Lincoln L70 BMS Interface (extension board) BACnet MS/TP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP
How many BACnet points does the Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP have?
This list has 120 BACnet objects: 48 analog inputs, 17 analog values, 36 binary inputs, 9 binary values, 8 integer values, 2 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP BACnet points are writable?
36 of the 120 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP BACnet documentation?
The source is Lincoln L70 BMS Interface BACnet Protocol, revision Rev. 1 - 07062023, published free by Adveco at https://adveco.co/wp-content/uploads/2023/06/L70-Lincoln-Extension-BACnet-Protocol-Rev.1.pdf.
What are the minimum BACnet points to integrate the Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP?
Start with IV 49 ch_mode_select (CH control mode; 4 = BMS Control); BV 36 ch_bms_demand (CH demand from the BMS (1 = active)); IV 53 dhw_mode_select (DHW control mode; 3 = BMS Control); BV 44 dhw_bms_demand (DHW demand from the BMS); AV 15 ch_master_flow_SP (CH flow setpoint in DI/BMS mode, °C); AV 18 dhw_flow_SP (DHW flow setpoint, °C); AI 13 ch_flow_SP (CH flow setpoint in use); BI 37 ch_demand (CH demand active); BI 39 ges_major_fault (Any major fault); BI 40 ges_minor_fault (Any minor fault).
How do I enable BMS control of the Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP?
ch_mode_select (IV 49) = 4 puts central heating under BMS control, switched by ch_bms_demand (BV 36) to the ch_master_flow_SP setpoint; dhw_mode_select (IV 53) = 3 does the same for hot water with dhw_bms_demand (BV 44).
Can the BMS supply sensor values to the Adveco Lincoln L70 BMS Interface (extension board) BACnet MS/TP?
ambient_temp_select (IV 48) picks the ambient temperature for weather compensation and low-ambient logic: the average of all active Lincolns, Lincoln 1 only, or the probe wired to the extension board.
How do I check these points on the real Lincoln L70 BMS Interface (extension board) BACnet MS/TP?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: Lincoln L70 BMS Interface BACnet Protocol · rev. Rev. 1 - 07062023. Object names, instances and units are reproduced as published; descriptions are our own.