Advantage Controls MegaTron Controller (BACnet H21 / H25) BACnet points list
Updated 4 November 2026
With the H21 or H25 option the MegaTron is a read-only BACnet IP device. It reports conductivity, pH, ORP, temperatures, water meter and flow meter values and up to sixteen 4-20 mA / 0-5 V inputs for up to four systems, plus alarm flags, setpoints, timer run times and relay states. Every object in this manual is marked Read Only, so the BMS can monitor but not adjust the controller.
This page lists 537 BACnet objects for the Advantage Controls MegaTron Controller (BACnet H21 / H25) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Advantage Controls’s own free documentation, linked below.
- Manufacturer
- Advantage Controls
- Model
- MegaTron Controller (BACnet H21 / H25)
- Equipment
- Water treatment controller
- Equipment type
- Other equipment
- BACnet objects
- 537 (0 writable)
- Transport
- BACnet IP
- Firmware
- JA.12.1 and higher
- Also known as
- MegaTron H21, MegaTron H25, BACnet H21, BACnet H25, M-BACnet, MegaTron MT BACnet, MegaTron XS BACnet
Reference only, provided as-is: verify against Advantage Controls’s current documentation and the live device before use. Not official Advantage Controls information. Terms of use.
BMS integration notes: Advantage Controls MegaTron Controller (BACnet H21 / H25)
Monitoring only. Read the chemistry inputs (conductivity, pH, ORP) and the flow switch for each system in use, and the per-system alarm BVs you need (there is no summary alarm object in this list). All objects are read-only, so setpoints and relays are changed at the controller, not from the BMS.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 0 | AI-000 | System 1 conductivity | Read |
| AI 8 | AI-008 | System 1 pH | Read |
| AI 12 | AI-012 | System 1 ORP | Read |
| BI 0 | BI-000 | System 1 flow switch | Read |
| AV 0 | AV-000 | System 1 conductivity setpoint 1 (read only) | Read |
Network setup
- BACnet IP only (Annex J), on the same Ethernet port used for the WebAdvantage service.
- Set the device instance and UDP port (47808 shown) in Setup/Run > Configure > Network > Settings > BAC, then reset the communications card and cycle power.
- On H25 (dual network card, MegaTron MT only) the dual network card must be enabled before the BAC options appear.
- 4194303 means unconfigured; the BMS must be on the same subnet as the MegaTron or BACnet traffic must be routed.
- Protocol revision 24, B-ASC; only DS-RP-B is listed for data sharing, so read one property per request.
Watch out for
- There is no All Alarms summary object (H22 has BV 301); map individual alarm BVs.
- No writable objects: setpoints, alarm limits and relays cannot be changed from the BMS on H21/H25.
- Points exist for four systems and sixteen mA inputs whether or not they are installed.
- AI 45-53 are flow meter contact values here, not totals as on H22.
Advantage Controls MegaTron Controller (BACnet H21 / H25) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 0 | BI-000 | System #1 – Flow Switch | Read | ||
| BI | 1 | BI-001 | System #2 – Flow Switch | Read | ||
| BI | 2 | BI-002 | System #3 – Flow Switch | Read | ||
| BI | 3 | BI-003 | System #4 – Flow Switch | Read | ||
| BV | 12 | BV-012 | System #1 – Conductivity High Alarm | Read | ||
| BV | 13 | BV-013 | System #1 – Conductivity Low Alarm | Read | ||
| BV | 14 | BV-014 | System #1 – Conductivity Limit Alarm | Read | ||
| BV | 15 | BV-015 | System #1 – pH High Alarm | Read | ||
| BV | 16 | BV-016 | System #1 – pH Low Alarm | Read | ||
| BV | 17 | BV-017 | System #1 – pH Limit Alarm | Read | ||
| BV | 18 | BV-018 | System #1 – ORP High Alarm | Read | ||
| BV | 19 | BV-019 | System #1 – ORP Low Alarm | Read | ||
| BV | 20 | BV-020 | System #1 – ORP Limit Alarm | Read | ||
| BV | 21 | BV-021 | System #1 – S. Temp High Alarm | Read | ||
| BV | 22 | BV-022 | System #1 – S. Temp Low Alarm | Read | ||
| BV | 23 | BV-023 | System #1 – M. Temp High Alarm | Read | ||
| BV | 24 | BV-024 | System #1 – M. Temp Low Alarm | Read | ||
| BV | 25 | BV-025 | System #1 – D. Temp High Alarm | Read | ||
| BV | 26 | BV-026 | System #1 – D. Temp Low Alarm | Read | ||
| BV | 27 | BV-027 | System #1 – No Flow Alarm | Read | ||
| BV | 28 | BV-028 | System #1 – Digital Input 1 Alarm | Read | ||
| BV | 29 | BV-029 | System #1 – Digital Input 2 Alarm | Read | ||
| BV | 30 | BV-030 | System #1 – Digital Input 3 Alarm | Read | ||
| BV | 31 | BV-031 | System #1 – Digital Input 4 Alarm | Read | ||
| BV | 32 | BV-032 | System #1 – Digital Input 5 Alarm | Read | ||
| BV | 34 | BV-034 | System #1 – M. Conductivity High Alarm | Read | ||
| BV | 35 | BV-035 | System #1 – M. Conductivity Low Alarm | Read | ||
| BV | 36 | BV-036 | System #1 – M. Conductivity Limit Alarm | Read | ||
| BV | 37 | BV-037 | System #1 – Notepad 1 High Alarm | Read | ||
| BV | 38 | BV-038 | System #1 – Notepad 2 High Alarm | Read | ||
| BV | 39 | BV-039 | System #1 – Notepad 3 High Alarm | Read | ||
| BV | 40 | BV-040 | System #1 – Notepad 4 High Alarm | Read | ||
| BV | 41 | BV-041 | System #1 – Notepad 5 High Alarm | Read | ||
| BV | 42 | BV-042 | System #1 – Notepad 6 High Alarm | Read | ||
| BV | 43 | BV-043 | System #1 – Notepad 7 High Alarm | Read | ||
| BV | 44 | BV-044 | System #1 – Notepad 8 High Alarm | Read | ||
| BV | 45 | BV-045 | System #1 – Notepad 9 High Alarm | Read | ||
| BV | 46 | BV-046 | System #1 – Notepad 10 High Alarm | Read | ||
| BV | 47 | BV-047 | System #1 – Notepad 1 Low Alarm | Read | ||
| BV | 48 | BV-048 | System #1 – Notepad 2 Low Alarm | Read | ||
| BV | 49 | BV-049 | System #1 – Notepad 3 Low Alarm | Read | ||
| BV | 50 | BV-050 | System #1 – Notepad 4 Low Alarm | Read | ||
| BV | 51 | BV-051 | System #1 – Notepad 5 Low Alarm | Read | ||
| BV | 52 | BV-052 | System #1 – Notepad 6 Low Alarm | Read | ||
| BV | 53 | BV-053 | System #1 – Notepad 7 Low Alarm | Read | ||
| BV | 54 | BV-054 | System #1 – Notepad 8 Low Alarm | Read | ||
| BV | 55 | BV-055 | System #1 – Notepad 9 Low Alarm | Read | ||
| BV | 56 | BV-056 | System #1 – Notepad 10 Low Alarm | Read | ||
| BV | 57 | BV-057 | System #1 – Notepad 1 Time Alarm | Read | ||
| BV | 58 | BV-058 | System #1 – Notepad 2 Time Alarm | Read | ||
| BV | 59 | BV-059 | System #1 – Notepad 3 Time Alarm | Read | ||
| BV | 60 | BV-060 | System #1 – Notepad 4 Time Alarm | Read | ||
| BV | 61 | BV-061 | System #1 – Notepad 5 Time Alarm | Read | ||
| BV | 62 | BV-062 | System #1 – Notepad 6 Time Alarm | Read | ||
| BV | 63 | BV-063 | System #1 – Notepad 7 Time Alarm | Read | ||
| BV | 64 | BV-064 | System #1 – Notepad 8 Time Alarm | Read | ||
| BV | 65 | BV-065 | System #1 – Notepad 9 Time Alarm | Read | ||
| BV | 66 | BV-066 | System #1 – Notepad 10 Time Alarm | Read | ||
| BV | 81 | BV-081 | System #2 – Conductivity High Alarm | Read | ||
| BV | 82 | BV-082 | System #2 – Conductivity Low Alarm | Read | ||
| BV | 83 | BV-083 | System #2 – Conductivity Limit Alarm | Read | ||
| BV | 84 | BV-084 | System #2 – pH High Alarm | Read | ||
| BV | 85 | BV-085 | System #2 – pH Low Alarm | Read | ||
| BV | 86 | BV-086 | System #2 – pH Limit Alarm | Read | ||
| BV | 87 | BV-087 | System #2 – ORP High Alarm | Read | ||
| BV | 88 | BV-088 | System #2 – ORP Low Alarm | Read | ||
| BV | 89 | BV-089 | System #2 – ORP Limit Alarm | Read | ||
| BV | 90 | BV-090 | System #2 – S. Temp High Alarm | Read | ||
| BV | 91 | BV-091 | System #2 – S. Temp Low Alarm | Read | ||
| BV | 92 | BV-092 | System #2 – M. Temp High Alarm | Read | ||
| BV | 93 | BV-093 | System #2 – M. Temp Low Alarm | Read | ||
| BV | 94 | BV-094 | System #2 – D. Temp High Alarm | Read | ||
| BV | 95 | BV-095 | System #2 – D. Temp Low Alarm | Read | ||
| BV | 96 | BV-096 | System #2 – No Flow Alarm | Read | ||
| BV | 97 | BV-097 | System #2 – Digital Input 1 Alarm | Read | ||
| BV | 98 | BV-098 | System #2 – Digital Input 2 Alarm | Read | ||
| BV | 99 | BV-099 | System #2 – Digital Input 3 Alarm | Read | ||
| BV | 100 | BV-100 | System #2 – Digital Input 4 Alarm | Read | ||
| BV | 101 | BV-101 | System #2 – Digital Input 5 Alarm | Read | ||
| BV | 103 | BV-103 | System #2 – M. Conductivity High Alarm | Read | ||
| BV | 104 | BV-104 | System #2 – M. Conductivity Low Alarm | Read | ||
| BV | 105 | BV-105 | System #2 – M. Conductivity Limit Alarm | Read | ||
| BV | 106 | BV-106 | System #2 – Notepad 1 High Alarm | Read | ||
| BV | 107 | BV-107 | System #2 – Notepad 2 High Alarm | Read | ||
| BV | 108 | BV-108 | System #2 – Notepad 3 High Alarm | Read | ||
| BV | 109 | BV-109 | System #2 – Notepad 4 High Alarm | Read | ||
| BV | 110 | BV-110 | System #2 – Notepad 5 High Alarm | Read | ||
| BV | 111 | BV-111 | System #2 – Notepad 6 High Alarm | Read | ||
| BV | 112 | BV-112 | System #2 – Notepad 7 High Alarm | Read | ||
| BV | 113 | BV-113 | System #2 – Notepad 8 High Alarm | Read | ||
| BV | 114 | BV-114 | System #2 – Notepad 9 High Alarm | Read | ||
| BV | 115 | BV-115 | System #2 – Notepad 10 High Alarm | Read | ||
| BV | 116 | BV-116 | System #2 – Notepad 1 Low Alarm | Read | ||
| BV | 117 | BV-117 | System #2 – Notepad 2 Low Alarm | Read | ||
| BV | 118 | BV-118 | System #2 – Notepad 3 Low Alarm | Read | ||
| BV | 119 | BV-119 | System #2 – Notepad 4 Low Alarm | Read | ||
| BV | 120 | BV-120 | System #2 – Notepad 5 Low Alarm | Read | ||
| BV | 121 | BV-121 | System #2 – Notepad 6 Low Alarm | Read | ||
| BV | 122 | BV-122 | System #2 – Notepad 7 Low Alarm | Read | ||
| BV | 123 | BV-123 | System #2 – Notepad 8 Low Alarm | Read | ||
| BV | 124 | BV-124 | System #2 – Notepad 9 Low Alarm | Read | ||
| BV | 125 | BV-125 | System #2 – Notepad 10 Low Alarm | Read | ||
| BV | 126 | BV-126 | System #2 – Notepad 1 Time Alarm | Read | ||
| BV | 127 | BV-127 | System #2 – Notepad 2 Time Alarm | Read | ||
| BV | 128 | BV-128 | System #2 – Notepad 3 Time Alarm | Read | ||
| BV | 129 | BV-129 | System #2 – Notepad 4 Time Alarm | Read | ||
| BV | 130 | BV-130 | System #2 – Notepad 5 Time Alarm | Read | ||
| BV | 131 | BV-131 | System #2 – Notepad 6 Time Alarm | Read | ||
| BV | 132 | BV-132 | System #2 – Notepad 7 Time Alarm | Read | ||
| BV | 133 | BV-133 | System #2 – Notepad 8 Time Alarm | Read | ||
| BV | 134 | BV-134 | System #2 – Notepad 9 Time Alarm | Read | ||
| BV | 135 | BV-135 | System #2 – Notepad 10 Time Alarm | Read | ||
| BV | 150 | BV-150 | System #3 – Conductivity High Alarm | Read | ||
| BV | 151 | BV-151 | System #3 – Conductivity Low Alarm | Read | ||
| BV | 152 | BV-152 | System #3 – Conductivity Limit Alarm | Read | ||
| BV | 153 | BV-153 | System #3 – pH High Alarm | Read | ||
| BV | 154 | BV-154 | System #3 – pH Low Alarm | Read | ||
| BV | 155 | BV-155 | System #3 – pH Limit Alarm | Read | ||
| BV | 156 | BV-156 | System #3 – ORP High Alarm | Read | ||
| BV | 157 | BV-157 | System #3 – ORP Low Alarm | Read | ||
| BV | 158 | BV-158 | System #3 – ORP Limit Alarm | Read | ||
| BV | 159 | BV-159 | System #3 – S. Temp High Alarm | Read | ||
| BV | 160 | BV-160 | System #3 – S. Temp Low Alarm | Read | ||
| BV | 161 | BV-161 | System #3 – M. Temp High Alarm | Read | ||
| BV | 162 | BV-162 | System #3 – M. Temp Low Alarm | Read | ||
| BV | 163 | BV-163 | System #3 – D. Temp High Alarm | Read | ||
| BV | 164 | BV-164 | System #3 – D. Temp Low Alarm | Read | ||
| BV | 165 | BV-165 | System #3 – No Flow Alarm | Read | ||
| BV | 166 | BV-166 | System #3 – Digital Input 1 Alarm | Read | ||
| BV | 167 | BV-167 | System #3 – Digital Input 2 Alarm | Read | ||
| BV | 168 | BV-168 | System #3 – Digital Input 3 Alarm | Read | ||
| BV | 169 | BV-169 | System #3 – Digital Input 4 Alarm | Read | ||
| BV | 170 | BV-170 | System #3 – Digital Input 5 Alarm | Read | ||
| BV | 172 | BV-172 | System #3 – M. Conductivity High Alarm | Read | ||
| BV | 173 | BV-173 | System #3 – M. Conductivity Low Alarm | Read | ||
| BV | 174 | BV-174 | System #3 – M. Conductivity Limit Alarm | Read | ||
| BV | 175 | BV-175 | System #3 – Notepad 1 High Alarm | Read | ||
| BV | 176 | BV-176 | System #3 – Notepad 2 High Alarm | Read | ||
| BV | 177 | BV-177 | System #3 – Notepad 3 High Alarm | Read | ||
| BV | 178 | BV-178 | System #3 – Notepad 4 High Alarm | Read | ||
| BV | 179 | BV-179 | System #3 – Notepad 5 High Alarm | Read | ||
| BV | 180 | BV-180 | System #3 – Notepad 6 High Alarm | Read | ||
| BV | 181 | BV-181 | System #3 – Notepad 7 High Alarm | Read | ||
| BV | 182 | BV-182 | System #3 – Notepad 8 High Alarm | Read | ||
| BV | 183 | BV-183 | System #3 – Notepad 9 High Alarm | Read | ||
| BV | 184 | BV-184 | System #3 – Notepad 10 High Alarm | Read | ||
| BV | 185 | BV-185 | System #3 – Notepad 1 Low Alarm | Read | ||
| BV | 186 | BV-186 | System #3 – Notepad 2 Low Alarm | Read | ||
| BV | 187 | BV-187 | System #3 – Notepad 3 Low Alarm | Read | ||
| BV | 188 | BV-188 | System #3 – Notepad 4 Low Alarm | Read | ||
| BV | 189 | BV-189 | System #3 – Notepad 5 Low Alarm | Read | ||
| BV | 190 | BV-190 | System #3 – Notepad 6 Low Alarm | Read | ||
| BV | 191 | BV-191 | System #3 – Notepad 7 Low Alarm | Read | ||
| BV | 192 | BV-192 | System #3 – Notepad 8 Low Alarm | Read | ||
| BV | 193 | BV-193 | System #3 – Notepad 9 Low Alarm | Read | ||
| BV | 194 | BV-194 | System #3 – Notepad 10 Low Alarm | Read | ||
| BV | 195 | BV-195 | System #3 – Notepad 1 Time Alarm | Read | ||
| BV | 196 | BV-196 | System #3 – Notepad 2 Time Alarm | Read | ||
| BV | 197 | BV-197 | System #3 – Notepad 3 Time Alarm | Read | ||
| BV | 198 | BV-198 | System #3 – Notepad 4 Time Alarm | Read | ||
| BV | 199 | BV-199 | System #3 – Notepad 5 Time Alarm | Read | ||
| BV | 200 | BV-200 | System #3 – Notepad 6 Time Alarm | Read | ||
| BV | 201 | BV-201 | System #3 – Notepad 7 Time Alarm | Read | ||
| BV | 202 | BV-202 | System #3 – Notepad 8 Time Alarm | Read | ||
| BV | 203 | BV-203 | System #3 – Notepad 9 Time Alarm | Read | ||
| BV | 204 | BV-204 | System #3 – Notepad 10 Time Alarm | Read | ||
| BV | 219 | BV-219 | System #4 – Conductivity High Alarm | Read | ||
| BV | 220 | BV-220 | System #4 – Conductivity Low Alarm | Read | ||
| BV | 221 | BV-221 | System #4 – Conductivity Limit Alarm | Read | ||
| BV | 222 | BV-222 | System #4 – pH High Alarm | Read | ||
| BV | 223 | BV-223 | System #4 – pH Low Alarm | Read | ||
| BV | 224 | BV-224 | System #4 – pH Limit Alarm | Read | ||
| BV | 225 | BV-225 | System #4 – ORP High Alarm | Read | ||
| BV | 226 | BV-226 | System #4 – ORP Low Alarm | Read | ||
| BV | 227 | BV-227 | System #4 – ORP Limit Alarm | Read | ||
| BV | 228 | BV-228 | System #4 – S. Temp High Alarm | Read | ||
| BV | 229 | BV-229 | System #4 – S. Temp Low Alarm | Read | ||
| BV | 230 | BV-230 | System #4 – M. Temp High Alarm | Read | ||
| BV | 231 | BV-231 | System #4 – M. Temp Low Alarm | Read | ||
| BV | 232 | BV-232 | System #4 – D. Temp High Alarm | Read | ||
| BV | 233 | BV-233 | System #4 – D. Temp Low Alarm | Read | ||
| BV | 234 | BV-234 | System #4 – No Flow Alarm | Read | ||
| BV | 235 | BV-235 | System #4 – Digital Input 1 Alarm | Read | ||
| BV | 236 | BV-236 | System #4 – Digital Input 2 Alarm | Read | ||
| BV | 237 | BV-237 | System #4 – Digital Input 3 Alarm | Read | ||
| BV | 238 | BV-238 | System #4 – Digital Input 4 Alarm | Read | ||
| BV | 239 | BV-239 | System #4 – Digital Input 5 Alarm | Read | ||
| BV | 241 | BV-241 | System #4 – M. Conductivity High Alarm | Read | ||
| BV | 242 | BV-242 | System #4 – M. Conductivity Low Alarm | Read | ||
| BV | 243 | BV-243 | System #4 – M. Conductivity Limit Alarm | Read | ||
| BV | 244 | BV-244 | System #4 – Notepad 1 High Alarm | Read | ||
| BV | 245 | BV-245 | System #4 – Notepad 2 High Alarm | Read | ||
| BV | 246 | BV-246 | System #4 – Notepad 3 High Alarm | Read | ||
| BV | 247 | BV-247 | System #4 – Notepad 4 High Alarm | Read | ||
| BV | 248 | BV-248 | System #4 – Notepad 5 High Alarm | Read | ||
| BV | 249 | BV-249 | System #4 – Notepad 6 High Alarm | Read | ||
| BV | 250 | BV-250 | System #4 – Notepad 7 High Alarm | Read | ||
| BV | 251 | BV-251 | System #4 – Notepad 8 High Alarm | Read | ||
| BV | 252 | BV-252 | System #4 – Notepad 9 High Alarm | Read | ||
| BV | 253 | BV-253 | System #4 – Notepad 10 High Alarm | Read | ||
| BV | 254 | BV-254 | System #4 – Notepad 1 Low Alarm | Read | ||
| BV | 255 | BV-255 | System #4 – Notepad 2 Low Alarm | Read | ||
| BV | 256 | BV-256 | System #4 – Notepad 3 Low Alarm | Read | ||
| BV | 257 | BV-257 | System #4 – Notepad 4 Low Alarm | Read | ||
| BV | 258 | BV-258 | System #4 – Notepad 5 Low Alarm | Read | ||
| BV | 259 | BV-259 | System #4 – Notepad 6 Low Alarm | Read | ||
| BV | 260 | BV-260 | System #4 – Notepad 7 Low Alarm | Read | ||
| BV | 261 | BV-261 | System #4 – Notepad 8 Low Alarm | Read | ||
| BV | 262 | BV-262 | System #4 – Notepad 9 Low Alarm | Read | ||
| BV | 263 | BV-263 | System #4 – Notepad 10 Low Alarm | Read | ||
| BV | 264 | BV-264 | System #4 – Notepad 1 Time Alarm | Read | ||
| BV | 265 | BV-265 | System #4 – Notepad 2 Time Alarm | Read | ||
| BV | 266 | BV-266 | System #4 – Notepad 3 Time Alarm | Read | ||
| BV | 267 | BV-267 | System #4 – Notepad 4 Time Alarm | Read | ||
| BV | 268 | BV-268 | System #4 – Notepad 5 Time Alarm | Read | ||
| BV | 269 | BV-269 | System #4 – Notepad 6 Time Alarm | Read | ||
| BV | 270 | BV-270 | System #4 – Notepad 7 Time Alarm | Read | ||
| BV | 271 | BV-271 | System #4 – Notepad 8 Time Alarm | Read | ||
| BV | 272 | BV-272 | System #4 – Notepad 9 Time Alarm | Read | ||
| BV | 273 | BV-273 | System #4 – Notepad 10 Time Alarm | Read | ||
| BV | 277 | BV-277 | ma Input 1 High Alarm | Read | ||
| BV | 278 | BV-278 | ma Input 1 Low Alarm | Read | ||
| BV | 280 | BV-280 | ma Input 2 High Alarm | Read | ||
| BV | 281 | BV-281 | ma Input 2 Low Alarm | Read | ||
| BV | 283 | BV-283 | ma Input 3 High Alarm | Read | ||
| BV | 284 | BV-284 | ma Input 3 Low Alarm | Read | ||
| BV | 286 | BV-286 | ma Input 4 High Alarm | Read | ||
| BV | 287 | BV-287 | ma Input 4 Low Alarm | Read | ||
| BV | 289 | BV-289 | ma Input 5 High Alarm | Read | ||
| BV | 290 | BV-290 | ma Input 5 Low Alarm | Read | ||
| BV | 292 | BV-292 | ma Input 6 High Alarm | Read | ||
| BV | 293 | BV-293 | ma Input 6 Low Alarm | Read | ||
| BV | 295 | BV-295 | ma Input 7 High Alarm | Read | ||
| BV | 296 | BV-296 | ma Input 7 Low Alarm | Read | ||
| BV | 298 | BV-298 | ma Input 8 High Alarm | Read | ||
| BV | 299 | BV-299 | ma Input 8 Low Alarm | Read | ||
| BV | 302 | BV-302 | Flow Meter 1 Flow Alarm | Read | ||
| BV | 303 | BV-303 | Flow Meter 1 Flow Verify Alarm | Read | ||
| BV | 304 | BV-304 | Flow Meter 1 Volume Alarm | Read | ||
| BV | 305 | BV-305 | Flow Meter 2 Flow Alarm | Read | ||
| BV | 306 | BV-306 | Flow Meter 2 Flow Verify Alarm | Read | ||
| BV | 307 | BV-307 | Flow Meter 2 Volume Alarm | Read | ||
| BV | 308 | BV-308 | Flow Meter 3 Flow Alarm | Read | ||
| BV | 309 | BV-309 | Flow Meter 3 Flow Verify Alarm | Read | ||
| BV | 310 | BV-310 | Flow Meter 3 Volume Alarm | Read | ||
| BV | 311 | BV-311 | Flow Meter 4 Flow Alarm | Read | ||
| BV | 312 | BV-312 | Flow Meter 4 Flow Verify Alarm | Read | ||
| BV | 313 | BV-313 | Flow Meter 4 Volume Alarm | Read | ||
| BV | 314 | BV-314 | Flow Meter 5 Flow Alarm | Read | ||
| BV | 315 | BV-315 | Flow Meter 5 Flow Verify Alarm | Read | ||
| BV | 316 | BV-216 | Flow Meter 5 Volume Alarm | Read | ||
| BV | 317 | BV-317 | Flow Meter 6 Flow Alarm | Read | ||
| BV | 318 | BV-318 | Flow Meter 6 Flow Verify Alarm | Read | ||
| BV | 319 | BV-319 | Flow Meter 6 Volume Alarm | Read | ||
| BV | 320 | BV-320 | Flow Meter 7 Flow Alarm | Read | ||
| BV | 321 | BV-321 | Flow Meter 7 Flow Verify Alarm | Read | ||
| BV | 322 | BV-322 | Flow Meter 7 Volume Alarm | Read | ||
| BV | 323 | BV-323 | Flow Meter 8 Flow Alarm | Read | ||
| BV | 324 | BV-324 | Flow Meter 8 Flow Verify Alarm | Read | ||
| BV | 325 | BV-325 | Flow Meter 8 Volume Alarm | Read | ||
| BV | 326 | BV-326 | Flow Meter 9 Flow Alarm | Read | ||
| BV | 327 | BV-327 | Flow Meter 9 Flow Verify Alarm | Read | ||
| BV | 328 | BV-328 | Flow Meter 9 Volume Alarm | Read | ||
| BV | 329 | BV-329 | Flow Meter 10 Flow Alarm | Read | ||
| BV | 330 | BV-330 | Flow Meter 10 Flow Verify Alarm | Read | ||
| BV | 331 | BV-331 | Flow Meter 10 Volume Alarm | Read | ||
| BV | 332 | BV-332 | Relay 1 Max Hours | Read | ||
| BV | 333 | BV-333 | Relay 2 Max Hours | Read | ||
| BV | 334 | BV-334 | Relay 3 Max Hours | Read | ||
| BV | 335 | BV-335 | Relay 4 Max Hours | Read | ||
| BV | 336 | BV-336 | Relay 5 Max Hours | Read | ||
| BV | 337 | BV-337 | Relay 6 Max Hours | Read | ||
| BV | 338 | BV-338 | Relay 7 Max Hours | Read | ||
| BV | 339 | BV-339 | Relay 8 Max Hours | Read | ||
| BV | 340 | BV-340 | Relay 9 Max Hours | Read | ||
| BV | 341 | BV-341 | Relay 10 Max Hours | Read | ||
| BV | 342 | BV-342 | Relay 11 Max Hours | Read | ||
| BV | 343 | BV-343 | Relay 12 Max Hours | Read | ||
| BV | 344 | BV-344 | Relay 13 Max Hours | Read | ||
| BV | 345 | BV-345 | Relay 14 Max Hours | Read | ||
| BV | 346 | BV-346 | Relay 15 Max Hours | Read | ||
| BV | 347 | BV-347 | Relay 16 Max Hours | Read | ||
| BV | 348 | Bv-348 | Relay 17 Max Hours | Read | ||
| BV | 349 | BV-349 | Relay 18 Max Hours | Read | ||
| BV | 350 | BV-350 | Relay 19 Max Hours | Read | ||
| BV | 351 | BV-351 | Relay 20 Max Hours | Read | ||
| BV | 352 | BV-352 | mA Input 1 Limit | Read | ||
| BV | 353 | BV-353 | mA Input 2 Limit | Read | ||
| BV | 354 | BV-354 | mA Input 3 Limit | Read | ||
| BV | 355 | BV-355 | mA Input 4 Limit | Read | ||
| BV | 356 | BV-356 | mA Input 5 Limit | Read | ||
| BV | 357 | BV-357 | mA Input 6 Limit | Read | ||
| BV | 358 | BV-358 | mA Input 7 Limit | Read | ||
| BV | 359 | BV-359 | mA Input 8 Limit | Read | ||
| BV | 360 | BV-360 | mA Input 9 Limit Alarm | Read | ||
| BV | 361 | BV-361 | mA Input 10 Limit Alarm | Read | ||
| BV | 362 | BV-362 | mA Input 11 Limit Alarm | Read | ||
| BV | 363 | BV-363 | mA Input 12 Limit Alarm | Read | ||
| BV | 364 | BV-364 | mA Input 13 Limit Alarm | Read | ||
| BV | 365 | BV-365 | mA Input 14 Limit Alarm | Read | ||
| BV | 366 | BV-366 | mA Input 15 Limit Alarm | Read | ||
| BV | 367 | BV-367 | mA Input 16 Limit Alarm | Read | ||
| BV | 369 | BV-369 | ma Input 9 High Alarm | Read | ||
| BV | 370 | BV-370 | ma Input 9 Low Alarm | Read | ||
| BV | 372 | BV-372 | ma Input 10 High Alarm | Read | ||
| BV | 373 | BV-373 | ma Input 10 Low Alarm | Read | ||
| BV | 375 | BV-375 | ma Input 11 High Alarm | Read | ||
| BV | 376 | BV-376 | ma Input 11 Low Alarm | Read | ||
| BV | 378 | BV-378 | ma Input 12 High Alarm | Read | ||
| BV | 379 | BV-379 | ma Input 12 Low Alarm | Read | ||
| BV | 381 | BV-381 | ma Input 13 High Alarm | Read | ||
| BV | 382 | BV-382 | ma Input 13 Low Alarm | Read | ||
| BV | 384 | BV-384 | ma Input 14 High Alarm | Read | ||
| BV | 385 | BV-385 | ma Input 14 Low Alarm | Read | ||
| BV | 387 | BV-387 | ma Input 15 High Alarm | Read | ||
| BV | 388 | BV-388 | ma Input 15 Low Alarm | Read | ||
| BV | 390 | BV-390 | ma Input 16 High Alarm | Read | ||
| BV | 391 | BV-391 | ma Input 16 Low Alarm | Read | ||
| AImin | 0 | AI-000 | System #1 – Conductivity | Read | ||
| AI | 1 | AI-001 | System #2 – Conductivity | Read | ||
| AI | 2 | AI-002 | System #3 – Conductivity | Read | ||
| AI | 3 | AI-003 | System #4 – Conductivity | Read | ||
| AI | 4 | AI-004 | System #1 – M. Conductivity | Read | ||
| AI | 5 | AI-005 | System #2 – M. Conductivity | Read | ||
| AI | 6 | AI-006 | System #3 – M. Conductivity | Read | ||
| AI | 7 | AI-007 | System #4 – M. Conductivity | Read | ||
| AImin | 8 | AI-008 | System #1 – pH | Read | ||
| AI | 9 | AI-009 | System #2 – pH | Read | ||
| AI | 10 | AI-010 | System #3 – pH | Read | ||
| AI | 11 | AI-011 | System #4 – pH | Read | ||
| AImin | 12 | AI-012 | System #1 – ORP | Read | ||
| AI | 13 | AI-013 | System #2 – ORP | Read | ||
| AI | 14 | AI-014 | System #3 – ORP | Read | ||
| AI | 15 | AI-015 | System #4 – ORP | Read | ||
| AI | 16 | AI-016 | System #1 – S. Temp | Read | ||
| AI | 17 | AI-017 | System #2 – S. Temp | Read | ||
| AI | 18 | AI-018 | System #3 – S. Temp | Read | ||
| AI | 19 | AI-019 | System #4 – S. Temp | Read | ||
| AI | 20 | AI-020 | System #1 – M. Temp | Read | ||
| AI | 21 | AI-021 | System #2 – M. Temp | Read | ||
| AI | 22 | AI-022 | System #3 – M. Temp | Read | ||
| AI | 23 | AI-023 | System #4 – M. Temp | Read | ||
| AI | 24 | AI-024 | Sys #1 – Water Meter #1 - Total Value | Read | ||
| AI | 25 | AI-025 | Sys #2 – Water Meter #1 - Total Value | Read | ||
| AI | 26 | AI-026 | Sys #3 – Water Meter #1 - Total Value | Read | ||
| AI | 27 | AI-027 | Sys #4 – Water Meter #1 - Total Value | Read | ||
| AI | 28 | AI-028 | Sys #1 – Water Meter #2 - Total Value | Read | ||
| AI | 29 | AI-029 | Sys #2 – Water Meter #2 - Total Value | Read | ||
| AI | 30 | AI-030 | Sys #3 – Water Meter #2 - Total Value | Read | ||
| AI | 31 | AI-031 | Sys #4 – Water Meter #2 - Total Value | Read | ||
| AI | 32 | AI-032 | System #1 – M.Cycles | Read | ||
| AI | 33 | AI-033 | System #2 – M.Cycles | Read | ||
| AI | 34 | AI-034 | System #3 – M.Cycles | Read | ||
| AI | 35 | AI-035 | System #4 – M.Cycles | Read | ||
| AI | 36 | AI-036 | 4-20 mA / 0-5V Input #1 - Value | Read | ||
| AI | 37 | AI-037 | 4-20 mA / 0-5V Input #2 - Value | Read | ||
| AI | 38 | AI-038 | 4-20 mA / 0-5V Input #3 - Value | Read | ||
| AI | 39 | AI-039 | 4-20 mA / 0-5V Input #4 - Value | Read | ||
| AI | 40 | AI-040 | 4-20 mA / 0-5V Input #5 - Value | Read | ||
| AI | 41 | AI-041 | 4-20 mA / 0-5V Input #6 - Value | Read | ||
| AI | 42 | AI-042 | 4-20 mA / 0-5V Input #7 - Value | Read | ||
| AI | 43 | AI-043 | 4-20 mA / 0-5V Input #8 - Value | Read | ||
| AI | 44 | AI-044 | Flow Meter #1 – Total Value | Read | ||
| AI | 45 | AI-045 | Flow Meter #2 – Contact Value | Read | ||
| AI | 46 | AI-046 | Flow Meter #3 – Contact Value | Read | ||
| AI | 47 | AI-047 | Flow Meter #4 – Contact Value | Read | ||
| AI | 48 | AI-048 | Flow Meter #5 – Contact Value | Read | ||
| AI | 49 | AI-049 | Flow Meter #6 – Contact Value | Read | ||
| AI | 50 | AI-050 | Flow Meter #7 – Contact Value | Read | ||
| AI | 51 | AI-051 | Flow Meter #8 – Contact Value | Read | ||
| AI | 52 | AI-052 | Flow Meter #9 – Contact Value | Read | ||
| AI | 53 | AI-053 | Flow Meter #10 – Contact Value | Read | ||
| AI | 54 | AI-054 | Flow Meter #1 – Flow Rate (per MIN) | Read | ||
| AI | 55 | AI-055 | Flow Meter #2 – Flow Rate (per MIN) | Read | ||
| AI | 56 | AI-056 | Flow Meter #3 – Flow Rate (per MIN) | Read | ||
| AI | 57 | AI-057 | Flow Meter #4 – Flow Rate (per MIN) | Read | ||
| AI | 58 | AI-058 | Flow Meter #5 – Flow Rate (per MIN) | Read | ||
| AI | 59 | AI-059 | Flow Meter #6 – Flow Rate (per MIN) | Read | ||
| AI | 60 | AI-060 | Flow Meter #7 – Flow Rate (per MIN) | Read | ||
| AI | 61 | AI-061 | Flow Meter #8 – Flow Rate (per MIN) | Read | ||
| AI | 62 | AI-062 | Flow Meter #9 – Flow Rate (per MIN) | Read | ||
| AI | 63 | AI-063 | Flow Meter #10 – Flow Rate (per MIN) | Read | ||
| AI | 64 | AI-064 | 4-20 mA / 0-5V Input #9 - Value | Read | ||
| AI | 65 | AI-065 | 4-20 mA / 0-5V Input #10 - Value | Read | ||
| AI | 66 | AI-066 | 4-20 mA / 0-5V Input #11 - Value | Read | ||
| AI | 67 | AI-067 | 4-20 mA / 0-5V Input #12 - Value | Read | ||
| AI | 68 | AI-068 | 4-20 mA / 0-5V Input #13 - Value | Read | ||
| AI | 69 | AI-069 | 4-20 mA / 0-5V Input #14 - Value | Read | ||
| AI | 70 | AI-070 | 4-20 mA / 0-5V Input #15 - Value | Read | ||
| AI | 71 | AI-071 | 4-20 mA / 0-5V Input #16 - Value | Read | ||
| AVmin | 0 | AV-000 | System #1 – Conductivity Setpoint #1 | Read | ||
| AV | 1 | AV-001 | System #2 – Conductivity Setpoint #1 | Read | ||
| AV | 2 | AV-002 | System #3 – Conductivity Setpoint #1 | Read | ||
| AV | 3 | AV-003 | System #4 – Conductivity Setpoint #1 | Read | ||
| AV | 4 | AV-004 | System #1 – Conductivity Setpoint #2 | Read | ||
| AV | 5 | AV-005 | System #2 – Conductivity Setpoint #2 | Read | ||
| AV | 6 | AV-006 | System #3 – Conductivity Setpoint #2 | Read | ||
| AV | 7 | AV-007 | System #4 – Conductivity Setpoint #2 | Read | ||
| AV | 8 | AV-008 | System #1 – Conductivity High Alarm | Read | ||
| AV | 9 | AV-009 | System #2 – Conductivity High Alarm | Read | ||
| AV | 10 | AV-010 | System #3 – Conductivity High Alarm | Read | ||
| AV | 11 | AV-011 | System #4 – Conductivity High Alarm | Read | ||
| AV | 12 | AV-012 | System #1 – Conductivity Low Alarm | Read | ||
| AV | 13 | AV-013 | System #2 – Conductivity Low Alarm | Read | ||
| AV | 14 | AV-014 | System #3 – Conductivity Low Alarm | Read | ||
| AV | 15 | AV-015 | System #4 – Conductivity Low Alarm | Read | ||
| AV | 16 | AV-016 | System #1 – M. Conductivity Setpoint | Read | ||
| AV | 17 | AV-017 | System #2 – M. Conductivity Setpoint | Read | ||
| AV | 18 | AV-018 | System #3 – M. Conductivity Setpoint | Read | ||
| AV | 19 | AV-019 | System #4 – M. Conductivity Setpoint | Read | ||
| AV | 20 | AV-020 | System #1 – M. Conductivity High Alarm | Read | ||
| AV | 21 | AV-021 | System #2 – M. Conductivity High Alarm | Read | ||
| AV | 22 | AV-022 | System #3 – M. Conductivity High Alarm | Read | ||
| AV | 23 | AV-023 | System #4 – M. Conductivity High Alarm | Read | ||
| AV | 24 | AV-024 | System #1 – M. Conductivity Low Alarm | Read | ||
| AV | 25 | AV-025 | System #2 – M. Conductivity Low Alarm | Read | ||
| AV | 26 | AV-026 | System #3 – M. Conductivity Low Alarm | Read | ||
| AV | 27 | AV-027 | System #4 – M. Conductivity Low Alarm | Read | ||
| AV | 28 | AV-028 | System #1 – pH Setpoint #1 | Read | ||
| AV | 29 | AV-029 | System #2 – pH Setpoint #1 | Read | ||
| AV | 30 | AV-030 | System #3 – pH Setpoint #1 | Read | ||
| AV | 31 | AV-031 | System #4 – pH Setpoint #1 | Read | ||
| AV | 32 | AV-032 | System #1 – pH Setpoint #2 | Read | ||
| AV | 33 | AV-033 | System #2 – pH Setpoint #2 | Read | ||
| AV | 34 | AV-034 | System #3 – pH Setpoint #2 | Read | ||
| AV | 35 | AV-035 | System #4 – pH Setpoint #2 | Read | ||
| AV | 36 | AV-036 | System #1 – pH High Alarm | Read | ||
| AV | 37 | AV-037 | System #2 – pH High Alarm | Read | ||
| AV | 38 | AV-038 | System #3 – pH High Alarm | Read | ||
| AV | 39 | AV-039 | System #4 – pH High Alarm | Read | ||
| AV | 40 | AV-040 | System #1 – pH Low Alarm | Read | ||
| AV | 41 | AV-041 | System #2 – pH Low Alarm | Read | ||
| AV | 42 | AV-042 | System #3 – pH Low Alarm | Read | ||
| AV | 43 | AV-043 | System #4 – pH Low Alarm | Read | ||
| AV | 44 | AV-044 | System #1 – ORP Setpoint #1 | Read | ||
| AV | 45 | AV-045 | System #2 – ORP Setpoint #1 | Read | ||
| AV | 46 | AV-046 | System #3 – ORP Setpoint #1 | Read | ||
| AV | 47 | AV-047 | System #4 – ORP Setpoint #1 | Read | ||
| AV | 48 | AV-048 | System #1 – ORP Setpoint #2 | Read | ||
| AV | 49 | AV-049 | System #2 – ORP Setpoint #2 | Read | ||
| AV | 50 | AV-050 | System #3 – ORP Setpoint #2 | Read | ||
| AV | 51 | AV-051 | System #4 – ORP Setpoint #2 | Read | ||
| AV | 52 | AV-052 | System #1 – ORP High Alarm | Read | ||
| AV | 53 | AV-053 | System #2 – ORP High Alarm | Read | ||
| AV | 54 | AV-054 | System #3 – ORP High Alarm | Read | ||
| AV | 55 | AV-055 | System #4 – ORP High Alarm | Read | ||
| AV | 56 | AV-056 | System #1 – ORP Low Alarm | Read | ||
| AV | 57 | AV-057 | System #2 – ORP Low Alarm | Read | ||
| AV | 58 | AV-058 | System #3 – ORP Low Alarm | Read | ||
| AV | 59 | AV-059 | System #4 – ORP Low Alarm | Read | ||
| AV | 60 | AV-060 | System #1 – S. Temp Setpoint | Read | ||
| AV | 61 | AV-061 | System #2 – S. Temp Setpoint | Read | ||
| AV | 62 | AV-062 | System #3 – S. Temp Setpoint | Read | ||
| AV | 63 | AV-063 | System #4 – S. Temp Setpoint | Read | ||
| AV | 64 | AV-064 | System #1 – S. Temp High Alarm | Read | ||
| AV | 65 | AV-065 | System #2 – S. Temp High Alarm | Read | ||
| AV | 66 | AV-066 | System #3 – S. Temp High Alarm | Read | ||
| AV | 67 | AV-067 | System #4 – S. Temp High Alarm | Read | ||
| AV | 68 | AV-068 | System #1 – S. Temp Low Alarm | Read | ||
| AV | 69 | AV-069 | System #2 – S. Temp Low Alarm | Read | ||
| AV | 70 | AV-070 | System #3 – S. Temp Low Alarm | Read | ||
| AV | 71 | AV-071 | System #4 – S. Temp Low Alarm | Read | ||
| AV | 72 | AV-072 | System #1 – M. Temp Setpoint | Read | ||
| AV | 73 | AV-073 | System #2 – M. Temp Setpoint | Read | ||
| AV | 74 | AV-074 | System #3 – M. Temp Setpoint | Read | ||
| AV | 75 | AV-075 | System #4 – M. Temp Setpoint | Read | ||
| AV | 76 | AV-076 | System #1 – M. Temp High Alarm | Read | ||
| AV | 77 | AV-077 | System #2 – M. Temp High Alarm | Read | ||
| AV | 78 | AV-078 | System #3 – M. Temp High Alarm | Read | ||
| AV | 79 | AV-079 | System #4 – M. Temp High Alarm | Read | ||
| AV | 80 | AV-080 | System #1 – M. Temp Low Alarm | Read | ||
| AV | 81 | AV-081 | System #2 – M. Temp Low Alarm | Read | ||
| AV | 82 | AV-082 | System #3 – M. Temp Low Alarm | Read | ||
| AV | 83 | AV-083 | System #4 – M. Temp Low Alarm | Read | ||
| AV | 84 | AV-084 | System #1 – D. Temp Setpoint | Read | ||
| AV | 85 | AV-085 | System #2 – D. Temp Setpoint | Read | ||
| AV | 86 | AV-086 | System #3 – D. Temp Setpoint | Read | ||
| AV | 87 | AV-087 | System #4 – D. Temp Setpoint | Read | ||
| AV | 88 | AV-088 | System #1 – D. Temp High Alarm | Read | ||
| AV | 89 | AV-089 | System #2 – D. Temp High Alarm | Read | ||
| AV | 90 | AV-090 | System #3 – D. Temp High Alarm | Read | ||
| AV | 91 | AV-091 | System #4 – D. Temp High Alarm | Read | ||
| AV | 92 | AV-092 | System #1 – D. Temp Low Alarm | Read | ||
| AV | 93 | AV-093 | System #2 – D. Temp Low Alarm | Read | ||
| AV | 94 | AV-094 | System #3 – D. Temp Low Alarm | Read | ||
| AV | 95 | AV-095 | System #4 – D. Temp Low Alarm | Read | ||
| AV | 96 | AV-096 | System #1 – Flow Switch Conf. | Read | ||
| AV | 97 | AV-097 | System #2 – Flow Switch Conf. | Read | ||
| AV | 98 | AV-098 | System #3 – Flow Switch Conf. | Read | ||
| AV | 99 | AV-099 | System #4 – Flow Switch Conf. | Read | ||
| AV | 100 | AV-100 | mA 1 - Output Value | Read | ||
| AV | 101 | AV-101 | mA 2 - Output Value | Read | ||
| AV | 102 | AV-102 | mA 3 - Output Value | Read | ||
| AV | 103 | AV-103 | mA 4 - Output Value | Read | ||
| AV | 104 | AV-104 | mA 5 - Output Value | Read | ||
| AV | 105 | AV-105 | mA 6 - Output Value | Read | ||
| AV | 106 | AV-106 | System #1 - Timer #1 - Run Time | Read | ||
| AV | 107 | AV-107 | System #1 - Timer #2 - Run Time | Read | ||
| AV | 108 | AV-108 | System #1 - Timer #3 - Run Time | Read | ||
| AV | 109 | AV-109 | System #1 - Timer #4 - Run Time | Read | ||
| AV | 110 | AV-110 | System #1 - Timer #5 - Run Time | Read | ||
| AV | 111 | AV-111 | System #2 - Timer #1 - Run Time | Read | ||
| AV | 112 | AV-112 | System #2 - Timer #2 - Run Time | Read | ||
| AV | 113 | AV-113 | System #2 - Timer #3 - Run Time | Read | ||
| AV | 114 | AV-114 | System #2 - Timer #4 - Run Time | Read | ||
| AV | 115 | AV-115 | System #2 - Timer #5 - Run Time | Read | ||
| AV | 116 | AV-116 | System #3 - Timer #1 - Run Time | Read | ||
| AV | 117 | AV-117 | System #3 - Timer #2 - Run Time | Read | ||
| AV | 118 | AV-118 | System #3 - Timer #3 - Run Time | Read | ||
| AV | 119 | AV-119 | System #3 - Timer #4 - Run Time | Read | ||
| AV | 120 | AV-120 | System #3 - Timer #5 - Run Time | Read | ||
| AV | 121 | AV-121 | System #4 - Timer #1 - Run Time | Read | ||
| AV | 122 | AV-122 | System #4 - Timer #2 - Run Time | Read | ||
| AV | 123 | AV-123 | System #4 - Timer #3 - Run Time | Read | ||
| AV | 124 | AV-124 | System #4 - Timer #4 - Run Time | Read | ||
| AV | 125 | AV-125 | System #4 - Timer #5 - Run Time | Read | ||
| AV | 126 | AV-126 | Read-Only | Read | ||
| MV | 0 | MSV-000 | Relay 1 – State | Read | 1=H-OFF, 2=H-ON, 3=OFF, 4=ON | |
| MV | 1 | MSV-001 | Relay 2 – State | Read | 1=H-OFF, 2=H-ON, 3=OFF, 4=ON | |
| MV | 2 | MSV-002 | Relay 3 – State | Read | 1=H-OFF, 2=H-ON, 3=OFF, 4=ON | |
| MV | 3 | MSV-003 | Relay 4 – State | Read | 1=H-OFF, 2=H-ON, 3=OFF, 4=ON | |
| MV | 4 | MSV-004 | Relay 5 – State | Read | 1=H-OFF, 2=H-ON, 3=OFF, 4=ON | |
| MV | 5 | MSV-005 | Relay 6 – State | Read | 1=H-OFF, 2=H-ON, 3=OFF, 4=ON | |
| MV | 6 | MSV-006 | Relay 7 – State | Read | 1=H-OFF, 2=H-ON, 3=OFF, 4=ON | |
| MV | 7 | MSV-007 | Relay 8 – State | Read | 1=H-OFF, 2=H-ON, 3=OFF, 4=ON | |
| MV | 8 | MSV-008 | Relay 9 – State | Read | 1=H-OFF, 2=H-ON, 3=OFF, 4=ON | |
| MV | 9 | MSV-009 | Relay 10 – State | Read | 1=H-OFF, 2=H-ON, 3=OFF, 4=ON | |
| MV | 10 | MSV-010 | Relay 11 – State | Read | 1=H-OFF, 2=H-ON, 3=OFF, 4=ON | |
| MV | 11 | MSV-011 | Relay 12 – State | Read | 1=H-OFF, 2=H-ON, 3=OFF, 4=ON | |
| MV | 12 | MSV-012 | Relay 13 – State | Read | 1=H-OFF, 2=H-ON, 3=OFF, 4=ON | |
| MV | 13 | MSV-013 | Relay 14 – State | Read | 1=H-OFF, 2=H-ON, 3=OFF, 4=ON | |
| MV | 14 | MSV-014 | Relay 15 – State | Read | 1=H-OFF, 2=H-ON, 3=OFF, 4=ON | |
| MV | 15 | MSV-015 | Relay 16 – State | Read | 1=H-OFF, 2=H-ON, 3=OFF, 4=ON | |
| MV | 16 | MSV-016 | Relay 17 – State | Read | 1=H-OFF, 2=H-ON, 3=OFF, 4=ON | |
| MV | 17 | MSV-017 | Relay 18 – State | Read | 1=H-OFF, 2=H-ON, 3=OFF, 4=ON | |
| MV | 18 | MSV-018 | Relay 19 – State | Read | 1=H-OFF, 2=H-ON, 3=OFF, 4=ON | |
| MV | 19 | MSV-019 | Relay 20 – State | Read | 1=H-OFF, 2=H-ON, 3=OFF, 4=ON |
No points match these filters.
Object ID lookup: Advantage Controls MegaTron Controller point IDs by name
BI0BI-000BI1BI-001BI2BI-002BI3BI-003BV12BV-012BV13BV-013BV14BV-014BV15BV-015BV16BV-016BV17BV-017BV18BV-018BV19BV-019BV20BV-020BV21BV-021BV22BV-022BV23BV-023BV24BV-024BV25BV-025BV26BV-026BV27BV-027BV28BV-028BV29BV-029BV30BV-030BV31BV-031BV32BV-032BV34BV-034BV35BV-035BV36BV-036BV37BV-037BV38BV-038BV39BV-039BV40BV-040BV41BV-041BV42BV-042BV43BV-043BV44BV-044BV45BV-045BV46BV-046BV47BV-047BV48BV-048BV49BV-049BV50BV-050BV51BV-051BV52BV-052BV53BV-053BV54BV-054BV55BV-055BV56BV-056BV57BV-057BV58BV-058BV59BV-059BV60BV-060BV61BV-061BV62BV-062BV63BV-063BV64BV-064BV65BV-065BV66BV-066BV81BV-081BV82BV-082BV83BV-083BV84BV-084BV85BV-085BV86BV-086BV87BV-087BV88BV-088BV89BV-089BV90BV-090BV91BV-091BV92BV-092BV93BV-093BV94BV-094BV95BV-095BV96BV-096BV97BV-097BV98BV-098BV99BV-099BV100BV-100BV101BV-101BV103BV-103BV104BV-104BV105BV-105BV106BV-106BV107BV-107BV108BV-108BV109BV-109BV110BV-110BV111BV-111BV112BV-112BV113BV-113BV114BV-114BV115BV-115BV116BV-116BV117BV-117BV118BV-118BV119BV-119BV120BV-120BV121BV-121BV122BV-122BV123BV-123BV124BV-124BV125BV-125BV126BV-126BV127BV-127BV128BV-128BV129BV-129BV130BV-130BV131BV-131BV132BV-132BV133BV-133BV134BV-134BV135BV-135BV150BV-150BV151BV-151BV152BV-152BV153BV-153BV154BV-154BV155BV-155BV156BV-156BV157BV-157BV158BV-158BV159BV-159BV160BV-160BV161BV-161BV162BV-162BV163BV-163BV164BV-164BV165BV-165BV166BV-166BV167BV-167BV168BV-168BV169BV-169BV170BV-170BV172BV-172BV173BV-173BV174BV-174BV175BV-175BV176BV-176BV177BV-177BV178BV-178BV179BV-179BV180BV-180BV181BV-181BV182BV-182BV183BV-183BV184BV-184BV185BV-185BV186BV-186BV187BV-187BV188BV-188BV189BV-189BV190BV-190BV191BV-191BV192BV-192BV193BV-193BV194BV-194BV195BV-195BV196BV-196BV197BV-197BV198BV-198BV199BV-199BV200BV-200BV201BV-201BV202BV-202BV203BV-203BV204BV-204BV219BV-219BV220BV-220BV221BV-221BV222BV-222BV223BV-223BV224BV-224BV225BV-225BV226BV-226BV227BV-227BV228BV-228BV229BV-229BV230BV-230BV231BV-231BV232BV-232BV233BV-233BV234BV-234BV235BV-235BV236BV-236BV237BV-237BV238BV-238BV239BV-239BV241BV-241BV242BV-242BV243BV-243BV244BV-244BV245BV-245BV246BV-246BV247BV-247BV248BV-248BV249BV-249BV250BV-250BV251BV-251BV252BV-252BV253BV-253BV254BV-254BV255BV-255BV256BV-256BV257BV-257BV258BV-258BV259BV-259BV260BV-260BV261BV-261BV262BV-262BV263BV-263BV264BV-264BV265BV-265BV266BV-266BV267BV-267BV268BV-268BV269BV-269BV270BV-270BV271BV-271BV272BV-272BV273BV-273BV277BV-277BV278BV-278BV280BV-280BV281BV-281BV283BV-283BV284BV-284BV286BV-286BV287BV-287BV289BV-289BV290BV-290BV292BV-292BV293BV-293BV295BV-295BV296BV-296BV298BV-298BV299BV-299BV302BV-302BV303BV-303BV304BV-304BV305BV-305BV306BV-306BV307BV-307BV308BV-308BV309BV-309BV310BV-310BV311BV-311BV312BV-312BV313BV-313BV314BV-314BV315BV-315BV316BV-216BV317BV-317BV318BV-318BV319BV-319BV320BV-320BV321BV-321BV322BV-322BV323BV-323BV324BV-324BV325BV-325BV326BV-326BV327BV-327BV328BV-328BV329BV-329BV330BV-330BV331BV-331BV332BV-332BV333BV-333BV334BV-334BV335BV-335BV336BV-336BV337BV-337BV338BV-338BV339BV-339BV340BV-340BV341BV-341BV342BV-342BV343BV-343BV344BV-344BV345BV-345BV346BV-346BV347BV-347BV348Bv-348BV349BV-349BV350BV-350BV351BV-351BV352BV-352BV353BV-353BV354BV-354BV355BV-355BV356BV-356BV357BV-357BV358BV-358BV359BV-359BV360BV-360BV361BV-361BV362BV-362BV363BV-363BV364BV-364BV365BV-365BV366BV-366BV367BV-367BV369BV-369BV370BV-370BV372BV-372BV373BV-373BV375BV-375BV376BV-376BV378BV-378BV379BV-379BV381BV-381BV382BV-382BV384BV-384BV385BV-385BV387BV-387BV388BV-388BV390BV-390BV391BV-391AI0AI-000AI1AI-001AI2AI-002AI3AI-003AI4AI-004AI5AI-005AI6AI-006AI7AI-007AI8AI-008AI9AI-009AI10AI-010AI11AI-011AI12AI-012AI13AI-013AI14AI-014AI15AI-015AI16AI-016AI17AI-017AI18AI-018AI19AI-019AI20AI-020AI21AI-021AI22AI-022AI23AI-023AI24AI-024AI25AI-025AI26AI-026AI27AI-027AI28AI-028AI29AI-029AI30AI-030AI31AI-031AI32AI-032AI33AI-033AI34AI-034AI35AI-035AI36AI-036AI37AI-037AI38AI-038AI39AI-039AI40AI-040AI41AI-041AI42AI-042AI43AI-043AI44AI-044AI45AI-045AI46AI-046AI47AI-047AI48AI-048AI49AI-049AI50AI-050AI51AI-051AI52AI-052AI53AI-053AI54AI-054AI55AI-055AI56AI-056AI57AI-057AI58AI-058AI59AI-059AI60AI-060AI61AI-061AI62AI-062AI63AI-063AI64AI-064AI65AI-065AI66AI-066AI67AI-067AI68AI-068AI69AI-069AI70AI-070AI71AI-071AV0AV-000AV1AV-001AV2AV-002AV3AV-003AV4AV-004AV5AV-005AV6AV-006AV7AV-007AV8AV-008AV9AV-009AV10AV-010AV11AV-011AV12AV-012AV13AV-013AV14AV-014AV15AV-015AV16AV-016AV17AV-017AV18AV-018AV19AV-019AV20AV-020AV21AV-021AV22AV-022AV23AV-023AV24AV-024AV25AV-025AV26AV-026AV27AV-027AV28AV-028AV29AV-029AV30AV-030AV31AV-031AV32AV-032AV33AV-033AV34AV-034AV35AV-035AV36AV-036AV37AV-037AV38AV-038AV39AV-039AV40AV-040AV41AV-041AV42AV-042AV43AV-043AV44AV-044AV45AV-045AV46AV-046AV47AV-047AV48AV-048AV49AV-049AV50AV-050AV51AV-051AV52AV-052AV53AV-053AV54AV-054AV55AV-055AV56AV-056AV57AV-057AV58AV-058AV59AV-059AV60AV-060AV61AV-061AV62AV-062AV63AV-063AV64AV-064AV65AV-065AV66AV-066AV67AV-067AV68AV-068AV69AV-069AV70AV-070AV71AV-071AV72AV-072AV73AV-073AV74AV-074AV75AV-075AV76AV-076AV77AV-077AV78AV-078AV79AV-079AV80AV-080AV81AV-081AV82AV-082AV83AV-083AV84AV-084AV85AV-085AV86AV-086AV87AV-087AV88AV-088AV89AV-089AV90AV-090AV91AV-091AV92AV-092AV93AV-093AV94AV-094AV95AV-095AV96AV-096AV97AV-097AV98AV-098AV99AV-099AV100AV-100AV101AV-101AV102AV-102AV103AV-103AV104AV-104AV105AV-105AV106AV-106AV107AV-107AV108AV-108AV109AV-109AV110AV-110AV111AV-111AV112AV-112AV113AV-113AV114AV-114AV115AV-115AV116AV-116AV117AV-117AV118AV-118AV119AV-119AV120AV-120AV121AV-121AV122AV-122AV123AV-123AV124AV-124AV125AV-125AV126AV-126MV0MSV-000MV1MSV-001MV2MSV-002MV3MSV-003MV4MSV-004MV5MSV-005MV6MSV-006MV7MSV-007MV8MSV-008MV9MSV-009MV10MSV-010MV11MSV-011MV12MSV-012MV13MSV-013MV14MSV-014MV15MSV-015MV16MSV-016MV17MSV-017MV18MSV-018MV19MSV-019
Integration notes
- Object names in the manual are generic (BI-000, BV-011, AI-008 ...); the Purpose column is used as the description.
- Every object, including the setpoint AVs and relay state MSVs, is marked Read Only. The H22 manual marks the same AVs and MSVs Read / Write.
- Compared with H22, this list adds mA inputs 9-16 (AI 64-71) and their alarms (BV 360-391), drops the 'Future Use' BVs, BV 300 Utility, BV 301 All Alarms, the M. Conductivity alarms and the mA input 'Alarm' flags, and labels AI 45-53 as flow meter contact values instead of totals.
- Instances start at 0 and most points repeat for System #1 to #4. No engineering units are printed.
- BV 316 is printed with the object name BV-216 (kept as printed); BV 348 is printed as Bv-348.
- Relay state MSVs use the printed states 1=H-OFF, 2=H-ON, 3=OFF, 4=ON.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MegaTron Controller (BACnet H21 / H25) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Advantage Controls MegaTron Controller (BACnet H21 / H25)
How many BACnet points does the Advantage Controls MegaTron Controller (BACnet H21 / H25) have?
This list has 537 BACnet objects: 72 analog inputs, 127 analog values, 4 binary inputs, 314 binary values, 20 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Advantage Controls MegaTron Controller (BACnet H21 / H25) BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official Advantage Controls MegaTron Controller (BACnet H21 / H25) BACnet documentation?
The source is MegaTron Controller Supplemental BACnet H21 / H25 Communications Manual (M-BACnet), revision 07/2026, published free by Advantage Controls at https://www.advantagecontrols.com/downloads/pdf/M-BACnet.pdf.
What are the minimum BACnet points to integrate the Advantage Controls MegaTron Controller (BACnet H21 / H25)?
Start with AI 0 AI-000 (System 1 conductivity); AI 8 AI-008 (System 1 pH); AI 12 AI-012 (System 1 ORP); BI 0 BI-000 (System 1 flow switch); AV 0 AV-000 (System 1 conductivity setpoint 1 (read only)).
How do I check these points on the real MegaTron Controller (BACnet H21 / H25)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.