Water treatment controller · BACnet points list

Advantage Controls MegaTron Controller (BACnet H21 / H25) BACnet points list

Updated 4 November 2026

Short answer

With the H21 or H25 option the MegaTron is a read-only BACnet IP device. It reports conductivity, pH, ORP, temperatures, water meter and flow meter values and up to sixteen 4-20 mA / 0-5 V inputs for up to four systems, plus alarm flags, setpoints, timer run times and relay states. Every object in this manual is marked Read Only, so the BMS can monitor but not adjust the controller.

This page lists 537 BACnet objects for the Advantage Controls MegaTron Controller (BACnet H21 / H25) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Advantage Controls’s own free documentation, linked below.

Manufacturer
Advantage Controls
Model
MegaTron Controller (BACnet H21 / H25)
Equipment
Water treatment controller
Equipment type
Other equipment
BACnet objects
537 (0 writable)
Transport
BACnet IP
Firmware
JA.12.1 and higher
Also known as
MegaTron H21, MegaTron H25, BACnet H21, BACnet H25, M-BACnet, MegaTron MT BACnet, MegaTron XS BACnet
Source document
MegaTron Controller Supplemental BACnet H21 / H25 Communications Manual · M-BACnet · rev. 07/2026
Download CSV 537 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Advantage Controls’s current documentation and the live device before use. Not official Advantage Controls information. Terms of use.

BMS integration notes: Advantage Controls MegaTron Controller (BACnet H21 / H25)

Integration in brief

Monitoring only. Read the chemistry inputs (conductivity, pH, ORP) and the flow switch for each system in use, and the per-system alarm BVs you need (there is no summary alarm object in this list). All objects are read-only, so setpoints and relays are changed at the controller, not from the BMS.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 0AI-000System 1 conductivityRead
AI 8AI-008System 1 pHRead
AI 12AI-012System 1 ORPRead
BI 0BI-000System 1 flow switchRead
AV 0AV-000System 1 conductivity setpoint 1 (read only)Read

Network setup

Watch out for

Advantage Controls MegaTron Controller (BACnet H21 / H25) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

537 of 537 shown
Type
Multi-state
Show
Advantage Controls MegaTron Controller (BACnet H21 / H25) BACnet Points List
DescriptionStates
BImin0BI-000System #1 – Flow SwitchRead
BI1BI-001System #2 – Flow SwitchRead
BI2BI-002System #3 – Flow SwitchRead
BI3BI-003System #4 – Flow SwitchRead
BV12BV-012System #1 – Conductivity High AlarmRead
BV13BV-013System #1 – Conductivity Low AlarmRead
BV14BV-014System #1 – Conductivity Limit AlarmRead
BV15BV-015System #1 – pH High AlarmRead
BV16BV-016System #1 – pH Low AlarmRead
BV17BV-017System #1 – pH Limit AlarmRead
BV18BV-018System #1 – ORP High AlarmRead
BV19BV-019System #1 – ORP Low AlarmRead
BV20BV-020System #1 – ORP Limit AlarmRead
BV21BV-021System #1 – S. Temp High AlarmRead
BV22BV-022System #1 – S. Temp Low AlarmRead
BV23BV-023System #1 – M. Temp High AlarmRead
BV24BV-024System #1 – M. Temp Low AlarmRead
BV25BV-025System #1 – D. Temp High AlarmRead
BV26BV-026System #1 – D. Temp Low AlarmRead
BV27BV-027System #1 – No Flow AlarmRead
BV28BV-028System #1 – Digital Input 1 AlarmRead
BV29BV-029System #1 – Digital Input 2 AlarmRead
BV30BV-030System #1 – Digital Input 3 AlarmRead
BV31BV-031System #1 – Digital Input 4 AlarmRead
BV32BV-032System #1 – Digital Input 5 AlarmRead
BV34BV-034System #1 – M. Conductivity High AlarmRead
BV35BV-035System #1 – M. Conductivity Low AlarmRead
BV36BV-036System #1 – M. Conductivity Limit AlarmRead
BV37BV-037System #1 – Notepad 1 High AlarmRead
BV38BV-038System #1 – Notepad 2 High AlarmRead
BV39BV-039System #1 – Notepad 3 High AlarmRead
BV40BV-040System #1 – Notepad 4 High AlarmRead
BV41BV-041System #1 – Notepad 5 High AlarmRead
BV42BV-042System #1 – Notepad 6 High AlarmRead
BV43BV-043System #1 – Notepad 7 High AlarmRead
BV44BV-044System #1 – Notepad 8 High AlarmRead
BV45BV-045System #1 – Notepad 9 High AlarmRead
BV46BV-046System #1 – Notepad 10 High AlarmRead
BV47BV-047System #1 – Notepad 1 Low AlarmRead
BV48BV-048System #1 – Notepad 2 Low AlarmRead
BV49BV-049System #1 – Notepad 3 Low AlarmRead
BV50BV-050System #1 – Notepad 4 Low AlarmRead
BV51BV-051System #1 – Notepad 5 Low AlarmRead
BV52BV-052System #1 – Notepad 6 Low AlarmRead
BV53BV-053System #1 – Notepad 7 Low AlarmRead
BV54BV-054System #1 – Notepad 8 Low AlarmRead
BV55BV-055System #1 – Notepad 9 Low AlarmRead
BV56BV-056System #1 – Notepad 10 Low AlarmRead
BV57BV-057System #1 – Notepad 1 Time AlarmRead
BV58BV-058System #1 – Notepad 2 Time AlarmRead
BV59BV-059System #1 – Notepad 3 Time AlarmRead
BV60BV-060System #1 – Notepad 4 Time AlarmRead
BV61BV-061System #1 – Notepad 5 Time AlarmRead
BV62BV-062System #1 – Notepad 6 Time AlarmRead
BV63BV-063System #1 – Notepad 7 Time AlarmRead
BV64BV-064System #1 – Notepad 8 Time AlarmRead
BV65BV-065System #1 – Notepad 9 Time AlarmRead
BV66BV-066System #1 – Notepad 10 Time AlarmRead
BV81BV-081System #2 – Conductivity High AlarmRead
BV82BV-082System #2 – Conductivity Low AlarmRead
BV83BV-083System #2 – Conductivity Limit AlarmRead
BV84BV-084System #2 – pH High AlarmRead
BV85BV-085System #2 – pH Low AlarmRead
BV86BV-086System #2 – pH Limit AlarmRead
BV87BV-087System #2 – ORP High AlarmRead
BV88BV-088System #2 – ORP Low AlarmRead
BV89BV-089System #2 – ORP Limit AlarmRead
BV90BV-090System #2 – S. Temp High AlarmRead
BV91BV-091System #2 – S. Temp Low AlarmRead
BV92BV-092System #2 – M. Temp High AlarmRead
BV93BV-093System #2 – M. Temp Low AlarmRead
BV94BV-094System #2 – D. Temp High AlarmRead
BV95BV-095System #2 – D. Temp Low AlarmRead
BV96BV-096System #2 – No Flow AlarmRead
BV97BV-097System #2 – Digital Input 1 AlarmRead
BV98BV-098System #2 – Digital Input 2 AlarmRead
BV99BV-099System #2 – Digital Input 3 AlarmRead
BV100BV-100System #2 – Digital Input 4 AlarmRead
BV101BV-101System #2 – Digital Input 5 AlarmRead
BV103BV-103System #2 – M. Conductivity High AlarmRead
BV104BV-104System #2 – M. Conductivity Low AlarmRead
BV105BV-105System #2 – M. Conductivity Limit AlarmRead
BV106BV-106System #2 – Notepad 1 High AlarmRead
BV107BV-107System #2 – Notepad 2 High AlarmRead
BV108BV-108System #2 – Notepad 3 High AlarmRead
BV109BV-109System #2 – Notepad 4 High AlarmRead
BV110BV-110System #2 – Notepad 5 High AlarmRead
BV111BV-111System #2 – Notepad 6 High AlarmRead
BV112BV-112System #2 – Notepad 7 High AlarmRead
BV113BV-113System #2 – Notepad 8 High AlarmRead
BV114BV-114System #2 – Notepad 9 High AlarmRead
BV115BV-115System #2 – Notepad 10 High AlarmRead
BV116BV-116System #2 – Notepad 1 Low AlarmRead
BV117BV-117System #2 – Notepad 2 Low AlarmRead
BV118BV-118System #2 – Notepad 3 Low AlarmRead
BV119BV-119System #2 – Notepad 4 Low AlarmRead
BV120BV-120System #2 – Notepad 5 Low AlarmRead
BV121BV-121System #2 – Notepad 6 Low AlarmRead
BV122BV-122System #2 – Notepad 7 Low AlarmRead
BV123BV-123System #2 – Notepad 8 Low AlarmRead
BV124BV-124System #2 – Notepad 9 Low AlarmRead
BV125BV-125System #2 – Notepad 10 Low AlarmRead
BV126BV-126System #2 – Notepad 1 Time AlarmRead
BV127BV-127System #2 – Notepad 2 Time AlarmRead
BV128BV-128System #2 – Notepad 3 Time AlarmRead
BV129BV-129System #2 – Notepad 4 Time AlarmRead
BV130BV-130System #2 – Notepad 5 Time AlarmRead
BV131BV-131System #2 – Notepad 6 Time AlarmRead
BV132BV-132System #2 – Notepad 7 Time AlarmRead
BV133BV-133System #2 – Notepad 8 Time AlarmRead
BV134BV-134System #2 – Notepad 9 Time AlarmRead
BV135BV-135System #2 – Notepad 10 Time AlarmRead
BV150BV-150System #3 – Conductivity High AlarmRead
BV151BV-151System #3 – Conductivity Low AlarmRead
BV152BV-152System #3 – Conductivity Limit AlarmRead
BV153BV-153System #3 – pH High AlarmRead
BV154BV-154System #3 – pH Low AlarmRead
BV155BV-155System #3 – pH Limit AlarmRead
BV156BV-156System #3 – ORP High AlarmRead
BV157BV-157System #3 – ORP Low AlarmRead
BV158BV-158System #3 – ORP Limit AlarmRead
BV159BV-159System #3 – S. Temp High AlarmRead
BV160BV-160System #3 – S. Temp Low AlarmRead
BV161BV-161System #3 – M. Temp High AlarmRead
BV162BV-162System #3 – M. Temp Low AlarmRead
BV163BV-163System #3 – D. Temp High AlarmRead
BV164BV-164System #3 – D. Temp Low AlarmRead
BV165BV-165System #3 – No Flow AlarmRead
BV166BV-166System #3 – Digital Input 1 AlarmRead
BV167BV-167System #3 – Digital Input 2 AlarmRead
BV168BV-168System #3 – Digital Input 3 AlarmRead
BV169BV-169System #3 – Digital Input 4 AlarmRead
BV170BV-170System #3 – Digital Input 5 AlarmRead
BV172BV-172System #3 – M. Conductivity High AlarmRead
BV173BV-173System #3 – M. Conductivity Low AlarmRead
BV174BV-174System #3 – M. Conductivity Limit AlarmRead
BV175BV-175System #3 – Notepad 1 High AlarmRead
BV176BV-176System #3 – Notepad 2 High AlarmRead
BV177BV-177System #3 – Notepad 3 High AlarmRead
BV178BV-178System #3 – Notepad 4 High AlarmRead
BV179BV-179System #3 – Notepad 5 High AlarmRead
BV180BV-180System #3 – Notepad 6 High AlarmRead
BV181BV-181System #3 – Notepad 7 High AlarmRead
BV182BV-182System #3 – Notepad 8 High AlarmRead
BV183BV-183System #3 – Notepad 9 High AlarmRead
BV184BV-184System #3 – Notepad 10 High AlarmRead
BV185BV-185System #3 – Notepad 1 Low AlarmRead
BV186BV-186System #3 – Notepad 2 Low AlarmRead
BV187BV-187System #3 – Notepad 3 Low AlarmRead
BV188BV-188System #3 – Notepad 4 Low AlarmRead
BV189BV-189System #3 – Notepad 5 Low AlarmRead
BV190BV-190System #3 – Notepad 6 Low AlarmRead
BV191BV-191System #3 – Notepad 7 Low AlarmRead
BV192BV-192System #3 – Notepad 8 Low AlarmRead
BV193BV-193System #3 – Notepad 9 Low AlarmRead
BV194BV-194System #3 – Notepad 10 Low AlarmRead
BV195BV-195System #3 – Notepad 1 Time AlarmRead
BV196BV-196System #3 – Notepad 2 Time AlarmRead
BV197BV-197System #3 – Notepad 3 Time AlarmRead
BV198BV-198System #3 – Notepad 4 Time AlarmRead
BV199BV-199System #3 – Notepad 5 Time AlarmRead
BV200BV-200System #3 – Notepad 6 Time AlarmRead
BV201BV-201System #3 – Notepad 7 Time AlarmRead
BV202BV-202System #3 – Notepad 8 Time AlarmRead
BV203BV-203System #3 – Notepad 9 Time AlarmRead
BV204BV-204System #3 – Notepad 10 Time AlarmRead
BV219BV-219System #4 – Conductivity High AlarmRead
BV220BV-220System #4 – Conductivity Low AlarmRead
BV221BV-221System #4 – Conductivity Limit AlarmRead
BV222BV-222System #4 – pH High AlarmRead
BV223BV-223System #4 – pH Low AlarmRead
BV224BV-224System #4 – pH Limit AlarmRead
BV225BV-225System #4 – ORP High AlarmRead
BV226BV-226System #4 – ORP Low AlarmRead
BV227BV-227System #4 – ORP Limit AlarmRead
BV228BV-228System #4 – S. Temp High AlarmRead
BV229BV-229System #4 – S. Temp Low AlarmRead
BV230BV-230System #4 – M. Temp High AlarmRead
BV231BV-231System #4 – M. Temp Low AlarmRead
BV232BV-232System #4 – D. Temp High AlarmRead
BV233BV-233System #4 – D. Temp Low AlarmRead
BV234BV-234System #4 – No Flow AlarmRead
BV235BV-235System #4 – Digital Input 1 AlarmRead
BV236BV-236System #4 – Digital Input 2 AlarmRead
BV237BV-237System #4 – Digital Input 3 AlarmRead
BV238BV-238System #4 – Digital Input 4 AlarmRead
BV239BV-239System #4 – Digital Input 5 AlarmRead
BV241BV-241System #4 – M. Conductivity High AlarmRead
BV242BV-242System #4 – M. Conductivity Low AlarmRead
BV243BV-243System #4 – M. Conductivity Limit AlarmRead
BV244BV-244System #4 – Notepad 1 High AlarmRead
BV245BV-245System #4 – Notepad 2 High AlarmRead
BV246BV-246System #4 – Notepad 3 High AlarmRead
BV247BV-247System #4 – Notepad 4 High AlarmRead
BV248BV-248System #4 – Notepad 5 High AlarmRead
BV249BV-249System #4 – Notepad 6 High AlarmRead
BV250BV-250System #4 – Notepad 7 High AlarmRead
BV251BV-251System #4 – Notepad 8 High AlarmRead
BV252BV-252System #4 – Notepad 9 High AlarmRead
BV253BV-253System #4 – Notepad 10 High AlarmRead
BV254BV-254System #4 – Notepad 1 Low AlarmRead
BV255BV-255System #4 – Notepad 2 Low AlarmRead
BV256BV-256System #4 – Notepad 3 Low AlarmRead
BV257BV-257System #4 – Notepad 4 Low AlarmRead
BV258BV-258System #4 – Notepad 5 Low AlarmRead
BV259BV-259System #4 – Notepad 6 Low AlarmRead
BV260BV-260System #4 – Notepad 7 Low AlarmRead
BV261BV-261System #4 – Notepad 8 Low AlarmRead
BV262BV-262System #4 – Notepad 9 Low AlarmRead
BV263BV-263System #4 – Notepad 10 Low AlarmRead
BV264BV-264System #4 – Notepad 1 Time AlarmRead
BV265BV-265System #4 – Notepad 2 Time AlarmRead
BV266BV-266System #4 – Notepad 3 Time AlarmRead
BV267BV-267System #4 – Notepad 4 Time AlarmRead
BV268BV-268System #4 – Notepad 5 Time AlarmRead
BV269BV-269System #4 – Notepad 6 Time AlarmRead
BV270BV-270System #4 – Notepad 7 Time AlarmRead
BV271BV-271System #4 – Notepad 8 Time AlarmRead
BV272BV-272System #4 – Notepad 9 Time AlarmRead
BV273BV-273System #4 – Notepad 10 Time AlarmRead
BV277BV-277ma Input 1 High AlarmRead
BV278BV-278ma Input 1 Low AlarmRead
BV280BV-280ma Input 2 High AlarmRead
BV281BV-281ma Input 2 Low AlarmRead
BV283BV-283ma Input 3 High AlarmRead
BV284BV-284ma Input 3 Low AlarmRead
BV286BV-286ma Input 4 High AlarmRead
BV287BV-287ma Input 4 Low AlarmRead
BV289BV-289ma Input 5 High AlarmRead
BV290BV-290ma Input 5 Low AlarmRead
BV292BV-292ma Input 6 High AlarmRead
BV293BV-293ma Input 6 Low AlarmRead
BV295BV-295ma Input 7 High AlarmRead
BV296BV-296ma Input 7 Low AlarmRead
BV298BV-298ma Input 8 High AlarmRead
BV299BV-299ma Input 8 Low AlarmRead
BV302BV-302Flow Meter 1 Flow AlarmRead
BV303BV-303Flow Meter 1 Flow Verify AlarmRead
BV304BV-304Flow Meter 1 Volume AlarmRead
BV305BV-305Flow Meter 2 Flow AlarmRead
BV306BV-306Flow Meter 2 Flow Verify AlarmRead
BV307BV-307Flow Meter 2 Volume AlarmRead
BV308BV-308Flow Meter 3 Flow AlarmRead
BV309BV-309Flow Meter 3 Flow Verify AlarmRead
BV310BV-310Flow Meter 3 Volume AlarmRead
BV311BV-311Flow Meter 4 Flow AlarmRead
BV312BV-312Flow Meter 4 Flow Verify AlarmRead
BV313BV-313Flow Meter 4 Volume AlarmRead
BV314BV-314Flow Meter 5 Flow AlarmRead
BV315BV-315Flow Meter 5 Flow Verify AlarmRead
BV316BV-216Flow Meter 5 Volume AlarmRead
BV317BV-317Flow Meter 6 Flow AlarmRead
BV318BV-318Flow Meter 6 Flow Verify AlarmRead
BV319BV-319Flow Meter 6 Volume AlarmRead
BV320BV-320Flow Meter 7 Flow AlarmRead
BV321BV-321Flow Meter 7 Flow Verify AlarmRead
BV322BV-322Flow Meter 7 Volume AlarmRead
BV323BV-323Flow Meter 8 Flow AlarmRead
BV324BV-324Flow Meter 8 Flow Verify AlarmRead
BV325BV-325Flow Meter 8 Volume AlarmRead
BV326BV-326Flow Meter 9 Flow AlarmRead
BV327BV-327Flow Meter 9 Flow Verify AlarmRead
BV328BV-328Flow Meter 9 Volume AlarmRead
BV329BV-329Flow Meter 10 Flow AlarmRead
BV330BV-330Flow Meter 10 Flow Verify AlarmRead
BV331BV-331Flow Meter 10 Volume AlarmRead
BV332BV-332Relay 1 Max HoursRead
BV333BV-333Relay 2 Max HoursRead
BV334BV-334Relay 3 Max HoursRead
BV335BV-335Relay 4 Max HoursRead
BV336BV-336Relay 5 Max HoursRead
BV337BV-337Relay 6 Max HoursRead
BV338BV-338Relay 7 Max HoursRead
BV339BV-339Relay 8 Max HoursRead
BV340BV-340Relay 9 Max HoursRead
BV341BV-341Relay 10 Max HoursRead
BV342BV-342Relay 11 Max HoursRead
BV343BV-343Relay 12 Max HoursRead
BV344BV-344Relay 13 Max HoursRead
BV345BV-345Relay 14 Max HoursRead
BV346BV-346Relay 15 Max HoursRead
BV347BV-347Relay 16 Max HoursRead
BV348Bv-348Relay 17 Max HoursRead
BV349BV-349Relay 18 Max HoursRead
BV350BV-350Relay 19 Max HoursRead
BV351BV-351Relay 20 Max HoursRead
BV352BV-352mA Input 1 LimitRead
BV353BV-353mA Input 2 LimitRead
BV354BV-354mA Input 3 LimitRead
BV355BV-355mA Input 4 LimitRead
BV356BV-356mA Input 5 LimitRead
BV357BV-357mA Input 6 LimitRead
BV358BV-358mA Input 7 LimitRead
BV359BV-359mA Input 8 LimitRead
BV360BV-360mA Input 9 Limit AlarmRead
BV361BV-361mA Input 10 Limit AlarmRead
BV362BV-362mA Input 11 Limit AlarmRead
BV363BV-363mA Input 12 Limit AlarmRead
BV364BV-364mA Input 13 Limit AlarmRead
BV365BV-365mA Input 14 Limit AlarmRead
BV366BV-366mA Input 15 Limit AlarmRead
BV367BV-367mA Input 16 Limit AlarmRead
BV369BV-369ma Input 9 High AlarmRead
BV370BV-370ma Input 9 Low AlarmRead
BV372BV-372ma Input 10 High AlarmRead
BV373BV-373ma Input 10 Low AlarmRead
BV375BV-375ma Input 11 High AlarmRead
BV376BV-376ma Input 11 Low AlarmRead
BV378BV-378ma Input 12 High AlarmRead
BV379BV-379ma Input 12 Low AlarmRead
BV381BV-381ma Input 13 High AlarmRead
BV382BV-382ma Input 13 Low AlarmRead
BV384BV-384ma Input 14 High AlarmRead
BV385BV-385ma Input 14 Low AlarmRead
BV387BV-387ma Input 15 High AlarmRead
BV388BV-388ma Input 15 Low AlarmRead
BV390BV-390ma Input 16 High AlarmRead
BV391BV-391ma Input 16 Low AlarmRead
AImin0AI-000System #1 – ConductivityRead
AI1AI-001System #2 – ConductivityRead
AI2AI-002System #3 – ConductivityRead
AI3AI-003System #4 – ConductivityRead
AI4AI-004System #1 – M. ConductivityRead
AI5AI-005System #2 – M. ConductivityRead
AI6AI-006System #3 – M. ConductivityRead
AI7AI-007System #4 – M. ConductivityRead
AImin8AI-008System #1 – pHRead
AI9AI-009System #2 – pHRead
AI10AI-010System #3 – pHRead
AI11AI-011System #4 – pHRead
AImin12AI-012System #1 – ORPRead
AI13AI-013System #2 – ORPRead
AI14AI-014System #3 – ORPRead
AI15AI-015System #4 – ORPRead
AI16AI-016System #1 – S. TempRead
AI17AI-017System #2 – S. TempRead
AI18AI-018System #3 – S. TempRead
AI19AI-019System #4 – S. TempRead
AI20AI-020System #1 – M. TempRead
AI21AI-021System #2 – M. TempRead
AI22AI-022System #3 – M. TempRead
AI23AI-023System #4 – M. TempRead
AI24AI-024Sys #1 – Water Meter #1 - Total ValueRead
AI25AI-025Sys #2 – Water Meter #1 - Total ValueRead
AI26AI-026Sys #3 – Water Meter #1 - Total ValueRead
AI27AI-027Sys #4 – Water Meter #1 - Total ValueRead
AI28AI-028Sys #1 – Water Meter #2 - Total ValueRead
AI29AI-029Sys #2 – Water Meter #2 - Total ValueRead
AI30AI-030Sys #3 – Water Meter #2 - Total ValueRead
AI31AI-031Sys #4 – Water Meter #2 - Total ValueRead
AI32AI-032System #1 – M.CyclesRead
AI33AI-033System #2 – M.CyclesRead
AI34AI-034System #3 – M.CyclesRead
AI35AI-035System #4 – M.CyclesRead
AI36AI-0364-20 mA / 0-5V Input #1 - ValueRead
AI37AI-0374-20 mA / 0-5V Input #2 - ValueRead
AI38AI-0384-20 mA / 0-5V Input #3 - ValueRead
AI39AI-0394-20 mA / 0-5V Input #4 - ValueRead
AI40AI-0404-20 mA / 0-5V Input #5 - ValueRead
AI41AI-0414-20 mA / 0-5V Input #6 - ValueRead
AI42AI-0424-20 mA / 0-5V Input #7 - ValueRead
AI43AI-0434-20 mA / 0-5V Input #8 - ValueRead
AI44AI-044Flow Meter #1 – Total ValueRead
AI45AI-045Flow Meter #2 – Contact ValueRead
AI46AI-046Flow Meter #3 – Contact ValueRead
AI47AI-047Flow Meter #4 – Contact ValueRead
AI48AI-048Flow Meter #5 – Contact ValueRead
AI49AI-049Flow Meter #6 – Contact ValueRead
AI50AI-050Flow Meter #7 – Contact ValueRead
AI51AI-051Flow Meter #8 – Contact ValueRead
AI52AI-052Flow Meter #9 – Contact ValueRead
AI53AI-053Flow Meter #10 – Contact ValueRead
AI54AI-054Flow Meter #1 – Flow Rate (per MIN)Read
AI55AI-055Flow Meter #2 – Flow Rate (per MIN)Read
AI56AI-056Flow Meter #3 – Flow Rate (per MIN)Read
AI57AI-057Flow Meter #4 – Flow Rate (per MIN)Read
AI58AI-058Flow Meter #5 – Flow Rate (per MIN)Read
AI59AI-059Flow Meter #6 – Flow Rate (per MIN)Read
AI60AI-060Flow Meter #7 – Flow Rate (per MIN)Read
AI61AI-061Flow Meter #8 – Flow Rate (per MIN)Read
AI62AI-062Flow Meter #9 – Flow Rate (per MIN)Read
AI63AI-063Flow Meter #10 – Flow Rate (per MIN)Read
AI64AI-0644-20 mA / 0-5V Input #9 - ValueRead
AI65AI-0654-20 mA / 0-5V Input #10 - ValueRead
AI66AI-0664-20 mA / 0-5V Input #11 - ValueRead
AI67AI-0674-20 mA / 0-5V Input #12 - ValueRead
AI68AI-0684-20 mA / 0-5V Input #13 - ValueRead
AI69AI-0694-20 mA / 0-5V Input #14 - ValueRead
AI70AI-0704-20 mA / 0-5V Input #15 - ValueRead
AI71AI-0714-20 mA / 0-5V Input #16 - ValueRead
AVmin0AV-000System #1 – Conductivity Setpoint #1Read
AV1AV-001System #2 – Conductivity Setpoint #1Read
AV2AV-002System #3 – Conductivity Setpoint #1Read
AV3AV-003System #4 – Conductivity Setpoint #1Read
AV4AV-004System #1 – Conductivity Setpoint #2Read
AV5AV-005System #2 – Conductivity Setpoint #2Read
AV6AV-006System #3 – Conductivity Setpoint #2Read
AV7AV-007System #4 – Conductivity Setpoint #2Read
AV8AV-008System #1 – Conductivity High AlarmRead
AV9AV-009System #2 – Conductivity High AlarmRead
AV10AV-010System #3 – Conductivity High AlarmRead
AV11AV-011System #4 – Conductivity High AlarmRead
AV12AV-012System #1 – Conductivity Low AlarmRead
AV13AV-013System #2 – Conductivity Low AlarmRead
AV14AV-014System #3 – Conductivity Low AlarmRead
AV15AV-015System #4 – Conductivity Low AlarmRead
AV16AV-016System #1 – M. Conductivity SetpointRead
AV17AV-017System #2 – M. Conductivity SetpointRead
AV18AV-018System #3 – M. Conductivity SetpointRead
AV19AV-019System #4 – M. Conductivity SetpointRead
AV20AV-020System #1 – M. Conductivity High AlarmRead
AV21AV-021System #2 – M. Conductivity High AlarmRead
AV22AV-022System #3 – M. Conductivity High AlarmRead
AV23AV-023System #4 – M. Conductivity High AlarmRead
AV24AV-024System #1 – M. Conductivity Low AlarmRead
AV25AV-025System #2 – M. Conductivity Low AlarmRead
AV26AV-026System #3 – M. Conductivity Low AlarmRead
AV27AV-027System #4 – M. Conductivity Low AlarmRead
AV28AV-028System #1 – pH Setpoint #1Read
AV29AV-029System #2 – pH Setpoint #1Read
AV30AV-030System #3 – pH Setpoint #1Read
AV31AV-031System #4 – pH Setpoint #1Read
AV32AV-032System #1 – pH Setpoint #2Read
AV33AV-033System #2 – pH Setpoint #2Read
AV34AV-034System #3 – pH Setpoint #2Read
AV35AV-035System #4 – pH Setpoint #2Read
AV36AV-036System #1 – pH High AlarmRead
AV37AV-037System #2 – pH High AlarmRead
AV38AV-038System #3 – pH High AlarmRead
AV39AV-039System #4 – pH High AlarmRead
AV40AV-040System #1 – pH Low AlarmRead
AV41AV-041System #2 – pH Low AlarmRead
AV42AV-042System #3 – pH Low AlarmRead
AV43AV-043System #4 – pH Low AlarmRead
AV44AV-044System #1 – ORP Setpoint #1Read
AV45AV-045System #2 – ORP Setpoint #1Read
AV46AV-046System #3 – ORP Setpoint #1Read
AV47AV-047System #4 – ORP Setpoint #1Read
AV48AV-048System #1 – ORP Setpoint #2Read
AV49AV-049System #2 – ORP Setpoint #2Read
AV50AV-050System #3 – ORP Setpoint #2Read
AV51AV-051System #4 – ORP Setpoint #2Read
AV52AV-052System #1 – ORP High AlarmRead
AV53AV-053System #2 – ORP High AlarmRead
AV54AV-054System #3 – ORP High AlarmRead
AV55AV-055System #4 – ORP High AlarmRead
AV56AV-056System #1 – ORP Low AlarmRead
AV57AV-057System #2 – ORP Low AlarmRead
AV58AV-058System #3 – ORP Low AlarmRead
AV59AV-059System #4 – ORP Low AlarmRead
AV60AV-060System #1 – S. Temp SetpointRead
AV61AV-061System #2 – S. Temp SetpointRead
AV62AV-062System #3 – S. Temp SetpointRead
AV63AV-063System #4 – S. Temp SetpointRead
AV64AV-064System #1 – S. Temp High AlarmRead
AV65AV-065System #2 – S. Temp High AlarmRead
AV66AV-066System #3 – S. Temp High AlarmRead
AV67AV-067System #4 – S. Temp High AlarmRead
AV68AV-068System #1 – S. Temp Low AlarmRead
AV69AV-069System #2 – S. Temp Low AlarmRead
AV70AV-070System #3 – S. Temp Low AlarmRead
AV71AV-071System #4 – S. Temp Low AlarmRead
AV72AV-072System #1 – M. Temp SetpointRead
AV73AV-073System #2 – M. Temp SetpointRead
AV74AV-074System #3 – M. Temp SetpointRead
AV75AV-075System #4 – M. Temp SetpointRead
AV76AV-076System #1 – M. Temp High AlarmRead
AV77AV-077System #2 – M. Temp High AlarmRead
AV78AV-078System #3 – M. Temp High AlarmRead
AV79AV-079System #4 – M. Temp High AlarmRead
AV80AV-080System #1 – M. Temp Low AlarmRead
AV81AV-081System #2 – M. Temp Low AlarmRead
AV82AV-082System #3 – M. Temp Low AlarmRead
AV83AV-083System #4 – M. Temp Low AlarmRead
AV84AV-084System #1 – D. Temp SetpointRead
AV85AV-085System #2 – D. Temp SetpointRead
AV86AV-086System #3 – D. Temp SetpointRead
AV87AV-087System #4 – D. Temp SetpointRead
AV88AV-088System #1 – D. Temp High AlarmRead
AV89AV-089System #2 – D. Temp High AlarmRead
AV90AV-090System #3 – D. Temp High AlarmRead
AV91AV-091System #4 – D. Temp High AlarmRead
AV92AV-092System #1 – D. Temp Low AlarmRead
AV93AV-093System #2 – D. Temp Low AlarmRead
AV94AV-094System #3 – D. Temp Low AlarmRead
AV95AV-095System #4 – D. Temp Low AlarmRead
AV96AV-096System #1 – Flow Switch Conf.Read
AV97AV-097System #2 – Flow Switch Conf.Read
AV98AV-098System #3 – Flow Switch Conf.Read
AV99AV-099System #4 – Flow Switch Conf.Read
AV100AV-100mA 1 - Output ValueRead
AV101AV-101mA 2 - Output ValueRead
AV102AV-102mA 3 - Output ValueRead
AV103AV-103mA 4 - Output ValueRead
AV104AV-104mA 5 - Output ValueRead
AV105AV-105mA 6 - Output ValueRead
AV106AV-106System #1 - Timer #1 - Run TimeRead
AV107AV-107System #1 - Timer #2 - Run TimeRead
AV108AV-108System #1 - Timer #3 - Run TimeRead
AV109AV-109System #1 - Timer #4 - Run TimeRead
AV110AV-110System #1 - Timer #5 - Run TimeRead
AV111AV-111System #2 - Timer #1 - Run TimeRead
AV112AV-112System #2 - Timer #2 - Run TimeRead
AV113AV-113System #2 - Timer #3 - Run TimeRead
AV114AV-114System #2 - Timer #4 - Run TimeRead
AV115AV-115System #2 - Timer #5 - Run TimeRead
AV116AV-116System #3 - Timer #1 - Run TimeRead
AV117AV-117System #3 - Timer #2 - Run TimeRead
AV118AV-118System #3 - Timer #3 - Run TimeRead
AV119AV-119System #3 - Timer #4 - Run TimeRead
AV120AV-120System #3 - Timer #5 - Run TimeRead
AV121AV-121System #4 - Timer #1 - Run TimeRead
AV122AV-122System #4 - Timer #2 - Run TimeRead
AV123AV-123System #4 - Timer #3 - Run TimeRead
AV124AV-124System #4 - Timer #4 - Run TimeRead
AV125AV-125System #4 - Timer #5 - Run TimeRead
AV126AV-126Read-OnlyRead
MV0MSV-000Relay 1 – StateRead1=H-OFF, 2=H-ON, 3=OFF, 4=ON
MV1MSV-001Relay 2 – StateRead1=H-OFF, 2=H-ON, 3=OFF, 4=ON
MV2MSV-002Relay 3 – StateRead1=H-OFF, 2=H-ON, 3=OFF, 4=ON
MV3MSV-003Relay 4 – StateRead1=H-OFF, 2=H-ON, 3=OFF, 4=ON
MV4MSV-004Relay 5 – StateRead1=H-OFF, 2=H-ON, 3=OFF, 4=ON
MV5MSV-005Relay 6 – StateRead1=H-OFF, 2=H-ON, 3=OFF, 4=ON
MV6MSV-006Relay 7 – StateRead1=H-OFF, 2=H-ON, 3=OFF, 4=ON
MV7MSV-007Relay 8 – StateRead1=H-OFF, 2=H-ON, 3=OFF, 4=ON
MV8MSV-008Relay 9 – StateRead1=H-OFF, 2=H-ON, 3=OFF, 4=ON
MV9MSV-009Relay 10 – StateRead1=H-OFF, 2=H-ON, 3=OFF, 4=ON
MV10MSV-010Relay 11 – StateRead1=H-OFF, 2=H-ON, 3=OFF, 4=ON
MV11MSV-011Relay 12 – StateRead1=H-OFF, 2=H-ON, 3=OFF, 4=ON
MV12MSV-012Relay 13 – StateRead1=H-OFF, 2=H-ON, 3=OFF, 4=ON
MV13MSV-013Relay 14 – StateRead1=H-OFF, 2=H-ON, 3=OFF, 4=ON
MV14MSV-014Relay 15 – StateRead1=H-OFF, 2=H-ON, 3=OFF, 4=ON
MV15MSV-015Relay 16 – StateRead1=H-OFF, 2=H-ON, 3=OFF, 4=ON
MV16MSV-016Relay 17 – StateRead1=H-OFF, 2=H-ON, 3=OFF, 4=ON
MV17MSV-017Relay 18 – StateRead1=H-OFF, 2=H-ON, 3=OFF, 4=ON
MV18MSV-018Relay 19 – StateRead1=H-OFF, 2=H-ON, 3=OFF, 4=ON
MV19MSV-019Relay 20 – StateRead1=H-OFF, 2=H-ON, 3=OFF, 4=ON
Object ID lookup: Advantage Controls MegaTron Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MegaTron Controller (BACnet H21 / H25) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Advantage Controls MegaTron Controller (BACnet H21 / H25)

How many BACnet points does the Advantage Controls MegaTron Controller (BACnet H21 / H25) have?

This list has 537 BACnet objects: 72 analog inputs, 127 analog values, 4 binary inputs, 314 binary values, 20 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Advantage Controls MegaTron Controller (BACnet H21 / H25) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Advantage Controls MegaTron Controller (BACnet H21 / H25) BACnet documentation?

The source is MegaTron Controller Supplemental BACnet H21 / H25 Communications Manual (M-BACnet), revision 07/2026, published free by Advantage Controls at https://www.advantagecontrols.com/downloads/pdf/M-BACnet.pdf.

What are the minimum BACnet points to integrate the Advantage Controls MegaTron Controller (BACnet H21 / H25)?

Start with AI 0 AI-000 (System 1 conductivity); AI 8 AI-008 (System 1 pH); AI 12 AI-012 (System 1 ORP); BI 0 BI-000 (System 1 flow switch); AV 0 AV-000 (System 1 conductivity setpoint 1 (read only)).

How do I check these points on the real MegaTron Controller (BACnet H21 / H25)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Advantage Controls BACnet points lists

Source: MegaTron Controller Supplemental BACnet H21 / H25 Communications Manual · M-BACnet · rev. 07/2026. Object names, instances and units are reproduced as published; descriptions are our own.