Airflow control valve (lab / fume hood) · BACnet points list

Accutrol AVC6000 AccuValve airflow control valve (fume hood and set point modes) BACnet points list

Updated 12 November 2026

Short answer

The AVC6000 is a valve-mounted airflow controller for lab supply, exhaust and fume hood valves, on BACnet MS/TP. It reports measured airflow, valve position and the active setpoint; in fume hood mode it adds face velocity, sash position, hood alarms and purge. The airflow setpoint can come from an analog input, dry contacts or a BACnet AV, and MSI 2 shows which mode is active.

This page lists 31 BACnet objects for the Accutrol AVC6000 AccuValve airflow control valve (fume hood and set point modes) — 14 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Accutrol’s own free documentation, linked below.

Manufacturer
Accutrol
Model
AVC6000 AccuValve airflow control valve (fume hood and set point modes)
Equipment
Airflow control valve (lab / fume hood)
Equipment type
Valves & actuators
BACnet objects
31 (14 writable)
Transport
BACnet MS/TP
Firmware
9.0 (PICS November 2018)
Also known as
AVC6000, AccuValve, AVC, AVC Product Family, Accutrol AccuValve
Source document
Installation & Operation Manual Model AVC6000 · rev. Rev M, 2026-10-01
Download CSV 31 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Accutrol’s current documentation and the live device before use. Not official Accutrol information. Terms of use.

BMS integration notes: Accutrol AVC6000 AccuValve airflow control valve (fume hood and set point modes)

Integration in brief

Check MSI 2 first: it shows whether the setpoint comes from the analog input, dry contacts, AV 1 or the fume hood logic. In BACnet setpoint mode write the airflow setpoint to AV 1 and read AI 1 and AI 8 back. In fume hood mode read face velocity, sash position and the hood alarms; BV 1 requests purge.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 1BACnet Airflow Volume SetpointAirflow setpoint when MSI 2 = 3 (BACnet mode)Write
BV 1Remote Purge RequestPurge request, fume hood modeWrite
AI 1Airflow VolumeMeasured airflowRead
AI 8Airflow Volume Setpoint to Control LoopActive airflow setpointRead
AI 3Valve Position FeedbackValve position, %Read
AI 4Face VelocityFace velocity, fume hood modeRead
AI 6Sash Position % OPENSash opening, %, fume hood modeRead
MI 2Mode SelectorControl mode; 3 = BACnet setpoint, 4 = fume hoodRead
BI 1AlarmGeneral alarmRead

Enable & remote start

The setpoint source is the controller's mode (MSI 2, read-only over BACnet); AV 1 only controls airflow in BACnet setpoint mode (MSI 2 = 3). The mode is configured with the Insight tool.

Network setup

Watch out for

Accutrol AVC6000 AccuValve airflow control valve (fume hood and set point modes) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

31 of 31 shown
Type
Multi-state
Access
Show
Accutrol AVC6000 AccuValve airflow control valve (fume hood and set point modes) BACnet Points List
DescriptionStates
AImin1Airflow VolumeMeasured airflowCFM (or SI per MSI3)Read
AI2Analog Airflow Volume SetpointSetpoint from the hardware analog input AI-1; invalid in fume hood or BACnet setpoint modeCFM (or SI per MSI3)Read
AImin3Valve Position FeedbackValve position%Read
AImin4Face VelocityHood face velocity (fume hood mode only)FPM (or SI per MSI4)Read
AI5Face Velocity Set pointFace velocity setpoint (fume hood mode only)FPM (or SI per MSI4)Read
AImin6Sash Position % OPENSash opening (fume hood mode only)%Read
AI7Flash Writes RemainingFlash write cycles left (of 10,000)Read
AImin8Airflow Volume Setpoint to Control LoopActive airflow setpoint used by the loopCFM (or SI per MSI3)Read
AI9AccuNet Totalized Airflow VolumeTotal airflow of the AccuNet groupCFM (or SI per MSI3)Read
AVmin1BACnet Airflow Volume SetpointAirflow setpoint written by the BMS (BACnet setpoint mode)CFM (or SI per MSI3)Write
AV2Unsubscribed COV IntervalUnsubscribed COV broadcast interval, 0 = offsWrite
AV3Airflow Volume Setpoint OffsetOffset added to the airflow setpointCFM (or SI per MSI3)Write
AV4Airflow Volume Measurement AdjustAirflow measurement correction%Write
AV5Airflow Volume Range Minimum LimitMinimum airflow limitCFM (or SI per MSI3)Write
AV6Airflow Volume Range Maximum LimitMaximum airflow limitCFM (or SI per MSI3)Write
AO1Valve Actuator Command PositionActuator position; the internal loop writes at priority 10%Command
BImin1AlarmGeneral alarmRead0=normal, 1=alarm
BI2Low Face Velocity Alarm StatusLow face velocity alarm (fume hood mode only)Read0=normal, 1=alarm
BI3Low Volume Alarm StatusLow airflow alarm (fume hood mode only)Read0=normal, 1=alarm
BI4Sash Position Alarm StatusSash position alarm (fume hood mode only)Read0=normal, 1=alarm
BI5Emergency (Purge) StatusPurge active (fume hood mode only)Read0=normal, 1=purge
BVmin1Remote Purge RequestBMS purge command (fume hood mode only)Write0=normal, 1=purge
BV2Write to FlashWrite 1 to save the active configuration to flashWrite
BV3DI-1 BACnetNetwork value for digital input 1 (fume hood mode only)Write0=OPEN, 1=CLOSED
BV4DI-2 BACnetNetwork value for digital input 2 (fume hood mode only)Write0=OPEN, 1=CLOSED
BV5Enter HibernatePut the valve in hibernate (fume hood mode only)Write
MI1DI states 1..4Dry contact input state (setpoint select)Read1..4
MImin2Mode SelectorActive control modeRead1=AI2, 2=MSI1, 3=AV1, 4=Fume Hood, 5=Hibernate
MI3Airflow Volume UnitsAirflow units for all volume objectsWrite1=CFM, 2=CMS, 3=CMM, 4=CMH, 5=LPS, 6=LPM
MI4Face Velocity UnitsVelocity units (fume hood mode only)Write1=FPM, 2=MPM, 3=MPS
MI5AccuNet StatusAccuNet network role and healthRead1=Disabled, 2=StandardNode, 3=TotalizerNode Network Healthy, 4=TotalizerNode Network Unhealthy
Object ID lookup: Accutrol AVC6000 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AVC6000 AccuValve airflow control valve (fume hood and set point modes) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Accutrol AVC6000 AccuValve airflow control valve (fume hood and set point modes)

How many BACnet points does the Accutrol AVC6000 AccuValve airflow control valve (fume hood and set point modes) have?

This list has 31 BACnet objects: 9 analog inputs, 1 analog output, 6 analog values, 5 binary inputs, 5 binary values, 5 multi-state inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Accutrol AVC6000 AccuValve airflow control valve (fume hood and set point modes) BACnet points are writable?

14 of the 31 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Accutrol AVC6000 AccuValve airflow control valve (fume hood and set point modes) BACnet documentation?

The source is Installation & Operation Manual Model AVC6000, revision Rev M, 2026-10-01, published free by Accutrol at https://accutrolllc.com/wp-content/uploads/2026/10/AVC6000-Manual-RevM.pdf.

What are the minimum BACnet points to integrate the Accutrol AVC6000 AccuValve airflow control valve (fume hood and set point modes)?

Start with AV 1 BACnet Airflow Volume Setpoint (Airflow setpoint when MSI 2 = 3 (BACnet mode)); BV 1 Remote Purge Request (Purge request, fume hood mode); AI 1 Airflow Volume (Measured airflow); AI 8 Airflow Volume Setpoint to Control Loop (Active airflow setpoint); AI 3 Valve Position Feedback (Valve position, %); AI 4 Face Velocity (Face velocity, fume hood mode); AI 6 Sash Position % OPEN (Sash opening, %, fume hood mode); MI 2 Mode Selector (Control mode; 3 = BACnet setpoint, 4 = fume hood); BI 1 Alarm (General alarm).

How do I enable BMS control of the Accutrol AVC6000 AccuValve airflow control valve (fume hood and set point modes)?

The setpoint source is the controller's mode (MSI 2, read-only over BACnet); AV 1 only controls airflow in BACnet setpoint mode (MSI 2 = 3). The mode is configured with the Insight tool.

How do I check these points on the real AVC6000 AccuValve airflow control valve (fume hood and set point modes)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Accutrol BACnet points lists

Source: Installation & Operation Manual Model AVC6000 · rev. Rev M, 2026-10-01. Object names, instances and units are reproduced as published; descriptions are our own.