Commercial gas water heater · BACnet points list

A. O. Smith Xi / MXi gas water heaters (ETH-1000 / Mirius gateway) BACnet points list

Updated 28 October 2026

Short answer

A. O. Smith's Xi and MXi gas water heater controls talk to BACnet through an ICC gateway: the Mirius gives BACnet MS/TP and the ETH-1000 gives BACnet IP. Each heater appears as a virtual BACnet device with tank temperatures, setpoint and differential, run-time and fault counters, safety-switch inputs, relay states and state/fault/alert codes. The BMS can write the setpoint and use an EMS control word to enable or disable heating.

This page lists 66 BACnet objects for the A. O. Smith Xi / MXi gas water heaters (ETH-1000 / Mirius gateway) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from A. O. Smith’s own free documentation, linked below.

Manufacturer
A. O. Smith
Model
Xi / MXi gas water heaters (ETH-1000 / Mirius gateway)
Equipment
Commercial gas water heater
Equipment type
Boilers & water heaters
BACnet objects
66 (5 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Mirius V3.300, ETH-1000 V4.002 (device object values in the manual)
Default device instance
520081
Also known as
Cyclone Xi, Xi 1.0, MXi, ETH-1000, Mirius, 100316044, 100316045, ICC gateway, iCOMM
Source document
Installation Manual: Inter-Appliance Communications, Communication Node for EMS/BMS Control (ETH-1000 / Mirius) · 100329879_2000571701 Rev. C · rev. 2020-02
Download CSV 66 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: A. O. Smith Xi / MXi gas water heaters (ETH-1000 / Mirius gateway)

Integration in brief

Install the ICC gateway (Mirius for BACnet MS/TP, ETH-1000 for BACnet IP) on the heater and set its address and device instance with ICC Configuration Studio. The BMS writes the tank setpoint (AV 201) and, if it should switch heating, takes EMS control through AV 263, which then has to be refreshed at least every 30 s. Read the tank temperature, CCB state and fault/alert codes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 263EMS Mode-StatusEMS control word: enable/disable heatingWrite
AV 201Temper SetpointTank setpoint, 32.2-82.2 °CWrite
AV 207Mxi Mod% CmdMXi firing-rate limit, 0-100 %Write
MV 801System StateCCB state: standby, purge, heating, faultRead
AI 5Tank TemperatureControlling tank temperature, °CRead
AI 3Upper TemperatureUpper tank probe temperature, °CRead
BV 504System In FaultHeater in faultRead
MV 802Fault CodeActive fault codeRead
MV 803Alert CodeActive alert codeRead

Enable & remote start

Heating on/off from the BMS goes through AV 263 EMS Mode-Status. Xi 1.0: write 3841 to enter EMS mode, then 1 to enable or 0 to disable heating; write 3840 to leave EMS mode. MXi: write 32769 to enter EMS mode with heating enabled, 32768 for EMS mode with heating disabled, 0 for no EMS control. Heating still also depends on tank temperature falling below setpoint minus differential and on the external thermostat if that option is on.

Heartbeat & communication loss

Xi 1.0: write 3584 (EMS Mode Refresh) within 30 s, 15 s or less recommended, or EMS mode ends and the heater resumes normal operation. MXi: the enable-heating command must be resent at least every 30 s or heating is disabled. On MXi software below 3.16 EMS mode cannot be cleared over BACnet; only a power cycle clears it.

Network setup

Watch out for

A. O. Smith Xi / MXi gas water heaters (ETH-1000 / Mirius gateway) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

66 of 66 shown
Type
Multi-state
Access
Show
A. O. Smith Xi / MXi gas water heaters (ETH-1000 / Mirius gateway) BACnet Points List
DescriptionStates
AI1Firmware Ver-Rev1Firmware version; major in upper byte, minor in lowerRead
AI2ConfigurationConfiguration wordRead
AImin3Upper TemperatureUpper or Primary Temperature°CRead
AI4Lower TemperatureLower or Secondary Temperature°CRead
AImin5Tank TemperatureControlling tank temperature, calculated°CRead
AVmin201Temper SetpointTank temperature setpoint; 32.2-82.2 °C (90-180 °F)°CWrite
AV202SetPoint DifferSetpoint differential; 1.1-11.1 °C (2-20 °F)°CWrite
AVmin207Mxi Mod% CmdMXi modulation limit, 0 = minimum to 100 = rated input%Write
AV208MxiLowTempAlrmSP2MXi low tank temperature alarm setpoint; 32.2-82.2 °C°CWrite
AV209Number of CyclesNumber of heating cyclesRead
AV210Elapsed TimePowered-up time, hours with two decimalshRead
AV211Elapsed DaysPowered-up time, days partdaysRead
AV212Elapsed HoursPowered-up time, hours part (use with Elapsed Days)hRead
AV213Heating TimeTime spent heating, hours with two decimalshRead
AV214Heating DaysTime spent heating, days partdaysRead
AV215Heating HoursTime spent heating, hours part (use with Heating Days)hRead
AV216IgniterCurrentHot Surface Igniter current in ampsARead
AV217#CCB HW FaultsCCB Hardware Fault CounterRead
AV218#Model FaultsModel Fault CounterRead
AV219#Upper Temp FaultsUpper Temperature Probe Fault CounterRead
AV220#Lower Temp FaultsLower Temperature Probe Fault CounterRead
AV221#Flame Probe FltFlame Probe Fault CounterRead
AV222#Flame Status FltFlame status fault counterRead
AV223#CCB Comm FaultsCommunication Fault CounterRead
AV224#ECO FaultsHigh-temperature ECO trip counterRead
AV225#LowGasPress FltLow Gas Pressure switch Fault CounterRead
AV226#Blocked In FltsBlocked Inlet pressure switch Fault CounterRead
AV227#Blocked Exhst FltBlocked exhaust / condensate switch fault counterRead
AV228#Ext Vent FaultsExternal Vent Fault CounterRead
AV229#Blower Prv FltsBlower Prove Pressure Switch Fault CounterRead
AV230#Igniter FaultsIgniter Fault CounterRead
AV231#Ignition FailureIgnition Failure Fault CounterRead
AV232#Powr Supply FltPower Supply Fault CounterRead
AV233#Powr Anode FltsPowered Anode Alert CounterRead
AVmin263EMS Mode-StatusEMS control word (BMS enable/disable of heating); see notesWrite
BI301Upper Temp OpenUpper temperature Probe open statusRead0=Okay, 1=Open
BI302Upper Temp ShortUpper temperature Probe shorted statusRead0=Okay, 1=Shorted
BI303MXi Call For HeatMXi call for heatRead0=No, 1=Yes
BI304Lower Temp OpenLower temperature probe openRead0=Okay, 1=Open
BI305Lower Temp ShortLower temperature probe shortedRead0=Okay, 1=Shorted
BI306Igntr Current OKIgniter Current SensedRead0=No Current, 1=Current Sensed
BI307Flame SensedFlame sensedRead0=No Flame, 1=Flame Sensed
BI308Blower Prove PSBlower Prove pressure switchRead0=Open Switch, 1=Closed Switch
BI309Ext Vent PSExternal vent pressure switch (if enabled by DIP switch)Read0=Open Switch, 1=Closed Switch
BI310Blocked Exhaust PSBlocked exhaust pressure switchRead0=Open Switch, 1=Closed Switch
BI311Blocked Inlet PSBlocked air intake pressure switchRead0=Open Switch, 1=Closed Switch
BI312Low Gas PSLow Gas supply pressure switchRead0=Open Switch, 1=Closed Switch
BI313Upper Temp ECOUpper probe high-temperature energy cut-out (ECO) statusRead0=Open Switch, 1=Closed Switch
BI314External T’statExternal thermostat input (if enabled by DIP switch)Read0=No, 1=Yes
BI315Xi 1.0 Call For HeatXi 1.0 conditions allow heatingRead0=Okay, 1=Alarm
BI316MXi LowTemp AlrmMXi tank below low-temperature alarm setpointRead0=Okay, 1=Alarm
BI317MXi LeakDetectedOptional leak detector trippedRead0=No Leak, 1=Leak Detected
BI318Mxi HeaterEnab’dMXi front heater-enable switchRead0=Disabled, 1=Enabled
BI319MXi External EnabMXi optional external enable inputRead0=Disabled, 1=Enabled
BI320Xi 1.0 Ign TriesXi 1.0 ignition tries set by DIP switchRead0=3 tries, 1=1 try
BO401Ext Vent RelayExternal Vent Relay output commanded statusRead0=Off, 1=On
BO402Blower RelayBlower Relay output commanded statusRead0=Off, 1=On
BO403Ignition RelayIgnition Relay output commanded statusRead0=Off, 1=On
BO404Gas Valve RelayGas valve Relay output commanded statusRead0=Off, 1=On
BV501MXi Ign TriesMXi ignition tries (set at the UIM)Read0=3 tries, 1=1 try
BV502MXi Use Ext EnabMXi use the optional external enable inputRead0=No, 1=Yes
BV503MXi ModulationMXi modulation enable (CCB software 3.15+)Read0=Disabled, 1=Enabled
BVmin504System In FaultHeater in faultRead0=Okay, 1=Alarm
MVmin801System StateCCB control stateReadXi 1.0: 1=Off (Standby), 2=Pre-Purge, 3=Igniter Warmup, 4=Ignition Activation, 5=Ignition Verification, 6=Inter-Purge, 7=Heating, 8=Post-Purge, 9=Fault; MXi: 1=Off (Standby), 2=Pre-Purge, 3=Igniting, 4=Gas Valve On, 5=Inter-Purge, 6=Heating, 7=Post-Purge, 8=In Fault
MVmin802Fault CodeActive fault codeReadNumeric code; see the fault codes and warnings table in the manual
MVmin803Alert CodeActive alert codeReadNumeric code; see the fault codes and warnings table in the manual

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Xi / MXi gas water heaters (ETH-1000 / Mirius gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the A. O. Smith Xi / MXi gas water heaters (ETH-1000 / Mirius gateway)

How many BACnet points does the A. O. Smith Xi / MXi gas water heaters (ETH-1000 / Mirius gateway) have?

This list has 66 BACnet objects: 5 analog inputs, 30 analog values, 20 binary inputs, 4 binary outputs, 4 binary values, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which A. O. Smith Xi / MXi gas water heaters (ETH-1000 / Mirius gateway) BACnet points are writable?

5 of the 66 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official A. O. Smith Xi / MXi gas water heaters (ETH-1000 / Mirius gateway) BACnet documentation?

The source is Installation Manual: Inter-Appliance Communications, Communication Node for EMS/BMS Control (ETH-1000 / Mirius) (100329879_2000571701 Rev. C), revision 2020-02, published free by A. O. Smith at https://assets.hotwater.com/damroot/Original/10004/100329879.pdf.

What are the minimum BACnet points to integrate the A. O. Smith Xi / MXi gas water heaters (ETH-1000 / Mirius gateway)?

Start with AV 263 EMS Mode-Status (EMS control word: enable/disable heating); AV 201 Temper Setpoint (Tank setpoint, 32.2-82.2 °C); AV 207 Mxi Mod% Cmd (MXi firing-rate limit, 0-100 %); MV 801 System State (CCB state: standby, purge, heating, fault); AI 5 Tank Temperature (Controlling tank temperature, °C); AI 3 Upper Temperature (Upper tank probe temperature, °C); BV 504 System In Fault (Heater in fault); MV 802 Fault Code (Active fault code); MV 803 Alert Code (Active alert code).

How do I enable BMS control of the A. O. Smith Xi / MXi gas water heaters (ETH-1000 / Mirius gateway)?

Heating on/off from the BMS goes through AV 263 EMS Mode-Status. Xi 1.0: write 3841 to enter EMS mode, then 1 to enable or 0 to disable heating; write 3840 to leave EMS mode. MXi: write 32769 to enter EMS mode with heating enabled, 32768 for EMS mode with heating disabled, 0 for no EMS control. Heating still also depends on tank temperature falling below setpoint minus differential and on the external thermostat if that option is on.

Does the A. O. Smith Xi / MXi gas water heaters (ETH-1000 / Mirius gateway) need a BACnet heartbeat or have a communication timeout?

Xi 1.0: write 3584 (EMS Mode Refresh) within 30 s, 15 s or less recommended, or EMS mode ends and the heater resumes normal operation. MXi: the enable-heating command must be resent at least every 30 s or heating is disabled. On MXi software below 3.16 EMS mode cannot be cleared over BACnet; only a power cycle clears it.

How do I check these points on the real Xi / MXi gas water heaters (ETH-1000 / Mirius gateway)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More A. O. Smith BACnet points lists

Source: Installation Manual: Inter-Appliance Communications, Communication Node for EMS/BMS Control (ETH-1000 / Mirius) · 100329879_2000571701 Rev. C · rev. 2020-02. Object names, instances and units are reproduced as published; descriptions are our own.