 "manufacturer": "York",
 "manufacturer_slug": "york",
 "model": "YMAE Four-Pipe Modular Heat Pump",
 "model_slug": "ymae",
 "aliases": [
  "YORK YMAE",
  "YMAE-130",
  "YMAE four pipe",
  "air-to-water heat pump"
 ],
 "equipment_type": "Air-to-water modular heat pump (four-pipe)",
 "applies_to": "YORK YMAE air-to-water modular heat pumps with inverter compressors in the four-pipe (simultaneous heating and cooling) version.",
 "summary": "The YMAE is the YORK by Johnson Controls modular air-to-water heat pump with inverter compressors; the four-pipe version heats and cools at the same time. Its BAS points list gives BACnet objects next to N2 and Modbus addresses: on/off and mode commands, entering and leaving water setpoints for cooling and heating, chiller-level status and temperatures, and module-level circuit values and bit-coded fault words. Module data is read one module at a time through AV 8.",
 "bacnet_transport": [],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Access comes from the Modbus function code column: points written with function 06 are marked writable, function 03 points read-only.",
  "The sheet does not name the BACnet interface or transport; its notes describe the unit's Modbus RTU link (9600 baud, 8-N-1) with the BAS as leader.",
  "Writable setpoint ranges (IP units) are in the descriptions; SI ranges are in the sheet.",
  "All MV enums are printed in the points table and the sheet has no add-1 note. Multistate states with their own enum in the points table are shown as printed, from 0. BACnet multistate values start at 1, so the device may report the printed number + 1; confirm by discovery (read the state text).",
  "The Fault point in the sheet has no BACnet object and is left out."
 ],
 "source": {
  "title": "YMAE Four Pipe Points List",
  "doc_number": null,
  "revision_date": "Rev 1.1, 2023-08-24",
  "url": "https://docs.johnsoncontrols.com/chillers/api/khub/documents/DAKAK2ryzuHrZbBA1Ny6_A/content"
 },
 "integration": {
  "summary": "Enable BAS start/stop and mode at the HMI (MV 4 and MV 3 show the selection), then switch the unit with MV 1 and pick the mode with MV 2. Write the leaving (or entering) water setpoints for cooling and heating, and read BV 100 for actual on/off, chiller loading, the chiller leaving water temperatures and the unit fault words.",
  "minimum_points": [
   {
    "ref": "MV 1",
    "name": "CHILLER ON|OFF (CMD)",
    "why": "On/off command (1 = on, 2 = off, as printed)"
   },
   {
    "ref": "MV 2",
    "name": "RUNNING MODE",
    "why": "Mode: cooling, heating, pump only, both"
   },
   {
    "ref": "AV 3",
    "name": "COOL LWT SETPOINT",
    "why": "Cooling leaving water setpoint"
   },
   {
    "ref": "AV 4",
    "name": "HEAT LWT SETPOINT",
    "why": "Heating leaving water setpoint"
   },
   {
    "ref": "MV 4",
    "name": "CHILLER ON|OFF CONTROL SELECTION",
    "why": "On/off source; must include BAS (set at HMI)"
   },
   {
    "ref": "BV 100",
    "name": "CHILLER ON|OFF (STATUS)",
    "why": "Actual on/off status"
   },
   {
    "ref": "AV 114",
    "name": "CHILLER LOADING",
    "why": "Chiller loading, %"
   },
   {
    "ref": "AV 111",
    "name": "CHILLER COOL LWT",
    "why": "Chiller cooling leaving water temperature"
   },
   {
    "ref": "AV 119",
    "name": "CHILLER HEAT LWT",
    "why": "Chiller heating leaving water temperature"
   },
   {
    "ref": "AV 109",
    "name": "UNIT FAULT STATUS (1-16)",
    "why": "Fault flags for modules 1-16, bit-coded"
   }
  ],
  "enable": "BAS start/stop and operating-mode control are enabled at the HMI. MV 4 (on/off source: HMI, Remote, HMI+BAS) and MV 3 (mode source: HMI, Remote, HMI+BAS, BAS) show the selection and are read-only over the network.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "The sheet's notes describe the microboard's Modbus RTU link: 9600 baud, 8 data bits, no parity, 1 stop bit; the BAS is the leader and module 1's microboard the follower. BAS addresses are set at the HMI.",
   "BV 5 and BV 6 show whether cooling and heating control on entering or leaving water temperature; write the matching setpoints (AV 1/AV 2 or AV 3/AV 4)."
  ],
  "gotchas": [
   "MV 1 only commands on/off; read the real state from BV 100.",
   "A BAS setpoint can be outside the unit's default range; read the setpoints back from the unit after writing.",
   "Data defaults to the leader module (No. 1). Write AV 8 to view another module's values; per-module AVs then show that module."
  ]
 },
 "points": [
  {
   "type": "MV",
   "instance": 1,
   "name": "CHILLER ON|OFF (CMD)",
   "description": "Chiller on/off command",
   "units": "",
   "access": "W",
   "states": "0=Invalid, 1=On, 2=Off"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "RUNNING MODE",
   "description": "Running Mode",
   "units": "",
   "access": "W",
   "states": "0=Cooling, 1=Heating, 8=Pump Only, 9=Cooling+Heating"
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "COOL EWT SETPOINT",
   "description": "Cool Entering Water Temperature Setpoint, 19.4-86.0 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "HEAT EWT SETPOINT",
   "description": "Heat Entering Water Temperature Setpoint, 59.0-131.0 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "COOL LWT SETPOINT",
   "description": "Cool Leaving Water Temperature Setpoint, 14.0-68.0 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "HEAT LWT SETPOINT",
   "description": "Heat Leaving Water Temperature Setpoint, 77.0-140.0 °F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "NOISE REDUCTION",
   "description": "Noise Reduction",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "COOLING CONTROL SELECT",
   "description": "Cooling Control Select",
   "units": "",
   "access": "W",
   "states": "0=Manual EWT control, 1=Manual LWT control"
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "HEATING CONTROL SELECT",
   "description": "Heating Control Select",
   "units": "",
   "access": "W",
   "states": "0=Manual EWT control, 1=Manual LWT control"
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "TEMP CONTROL CYCLE",
   "description": "Temperature Control Cycle, 10-120 Sec",
   "units": "Sec",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "WATER TEMP CONTROL DIFF",
   "description": "Water Temperature Control Differential, 1.8-5.4 °F (diff)",
   "units": "°F (diff)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "EWT PULLDOWN RATE SELECT",
   "description": "Entering Water Temperature Pulldown Rate Select, 0-6",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "MODULE NUMBER",
   "description": "Module number to read (1-32)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "CHILLER MODE CONTROL SELECTION",
   "description": "Chiller Mode Control Selection",
   "units": "",
   "access": "R",
   "states": "0=HMI, 1=Remote, 2=HMI+BAS, 3=BAS"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "CHILLER ON|OFF CONTROL SELECTION",
   "description": "Chiller ON/OFF Control Selection",
   "units": "",
   "access": "R",
   "states": "0=HMI, 1=Remote, 2=HMI+BAS"
  },
  {
   "type": "BV",
   "instance": 100,
   "name": "CHILLER ON|OFF (STATUS)",
   "description": "Chiller on/off status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "MV",
   "instance": 101,
   "name": "SYSTEM STATUS",
   "description": "System Status",
   "units": "",
   "access": "R",
   "states": "0=Cooling, 1=Heating, 8=Pump Only, 9=Cooling+Heating"
  },
  {
   "type": "AV",
   "instance": 102,
   "name": "OTHER STATUS",
   "description": "Other Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 103,
   "name": "HMI COMMUNICATION STATUS",
   "description": "Human Machine Interface Communication Status",
   "units": "",
   "access": "R",
   "states": "0=Offline, 1=Online"
  },
  {
   "type": "AV",
   "instance": 104,
   "name": "UNIT NETWORK STATUS (1-16)",
   "description": "Network status of units 1-16, bit-coded",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 109,
   "name": "UNIT FAULT STATUS (1-16)",
   "description": "Fault status of units 1-16, bit-coded",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 110,
   "name": "CHILLER COOL EWT",
   "description": "Chiller Cool Entering Water Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 111,
   "name": "CHILLER COOL LWT",
   "description": "Chiller Cool Leaving Water Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 113,
   "name": "AMBIENT TEMP",
   "description": "Ambient Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 114,
   "name": "CHILLER LOADING",
   "description": "Chiller Loading",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 117,
   "name": "TOTAL RUN HOURS",
   "description": "Total Run Hours",
   "units": "Hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 118,
   "name": "CHILLER HEAT EWT",
   "description": "Chiller Heat Entering Water Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 119,
   "name": "CHILLER HEAT LWT",
   "description": "Chiller Heat Leaving Water Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 121,
   "name": "UNIT NETWORK STATUS (17-32)",
   "description": "Network status of units 17-32, bit-coded",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 122,
   "name": "UNIT FAULT STATUS (17-32)",
   "description": "Fault status of units 17-32, bit-coded",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 123,
   "name": "UNIT QUANTITY",
   "description": "Unit Quantity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1021,
   "name": "UNIT COOL EWT",
   "description": "Unit Cool Entering Water Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1023,
   "name": "CKT1 COIL TEMP",
   "description": "Circuit 1 Coil Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1024,
   "name": "CKT2 COIL TEMP",
   "description": "Circuit 2 Coil Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1025,
   "name": "UNIT COOL LWT",
   "description": "Unit Cool Leaving Water Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1027,
   "name": "CKT1 SUCT TEMP",
   "description": "Circuit 1 Suction Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1028,
   "name": "CKT2 SUCT TEMP",
   "description": "Circuit 2 Suction Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1029,
   "name": "SYS 1 DISCHARGE TEMP",
   "description": "System 1 Discharge Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1033,
   "name": "CKT1 ECO ENTERING TEMP",
   "description": "Circuit 1 Economizer Entering Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1031,
   "name": "SYS 2 DISCHARGE TEMP",
   "description": "System 2 Discharge Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1035,
   "name": "CKT2 ECO ENTERING TEMP",
   "description": "Circuit 2 Economizer Entering Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1034,
   "name": "CKT1 ECO LEAVING TEMP",
   "description": "Circuit 1 Economizer Leaving Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1036,
   "name": "CKT2 ECO LEAVING TEMP",
   "description": "Circuit 2 Economizer Leaving Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1200,
   "name": "R454B RELATIVE LFL",
   "description": "R454B leak sensor, % of lower flammable limit",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1037,
   "name": "UNIT HEAT LWT",
   "description": "Unit Heat Leaving Water Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1039,
   "name": "UNIT HEAT EWT",
   "description": "Unit Heat Entering Water Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1040,
   "name": "CKT1 SUCT PRS",
   "description": "Circuit 1 Suction Pressure",
   "units": "PSIG",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1041,
   "name": "CKT2 SUCT PRS",
   "description": "Circuit 2 Suction Pressure",
   "units": "PSIG",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1042,
   "name": "CKT1 DISCH PRS",
   "description": "Circuit 1 Discharge Pressure",
   "units": "PSIG",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1043,
   "name": "CKT2 DISCH PRS",
   "description": "Circuit 2 Discharge Pressure",
   "units": "PSIG",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1053,
   "name": "DI17-32",
   "description": "Digital inputs 17-32, bit-coded",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1054,
   "name": "DI1-16",
   "description": "Digital inputs 1-16, bit-coded",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1055,
   "name": "DO17-33",
   "description": "Digital outputs 17-32, bit-coded",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1056,
   "name": "DO1-16",
   "description": "Digital outputs 1-16, bit-coded",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1057,
   "name": "CKT1 EEV",
   "description": "Circuit 1 electronic expansion valve opening, steps",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1058,
   "name": "CKT2 EEV",
   "description": "Circuit 2 electronic expansion valve opening, steps",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1059,
   "name": "CKT1 ECO EEV",
   "description": "Circuit 1 economizer EEV opening, steps",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1060,
   "name": "CKT2 ECO EEV",
   "description": "Circuit 2 economizer EEV opening, steps",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1065,
   "name": "CKT1 FAN SPEED",
   "description": "Circuit 1 Fan Speed",
   "units": "RPM",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1066,
   "name": "CKT2 FAN SPEED",
   "description": "Circuit 2 Fan Speed",
   "units": "RPM",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1073,
   "name": "DIAL SWITCH STATUS",
   "description": "Dial Switch Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1080,
   "name": "CKT1 INV COMP FREQ",
   "description": "Circuit 1 Inverter Compressor Frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1096,
   "name": "CKT2 INV COMP FREQ",
   "description": "Circuit 2 Inverter Compressor Frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1155,
   "name": "FAULT STATUS 1",
   "description": "Fault status word 1, bit-coded",
   "units": "",
   "access": "R",
   "states": "Bit 0=Unit cooling entering water temperature sensor fault, Bit 1=Ambient temperature sensor fault, Bit 2=Circuit 1 coil temperature sensor fault, Bit 3=Circuit 2 coil temperature sensor fault, Bit 4=Unit cooling leaving water temperature sensor fault, Bit 5=Chiller cooling leaving water temperature sensor fault, Bit 6=Circuit 1 accumulator inlet temperature sensor fault, Bit 7=Circuit 2 accumulator inlet temperature sensor fault, Bit 8=Circuit 1 compressor 1 discharge port temperature sensor fault, Bit 10=Circuit 2 compressor 1 discharge port temperature sensor fault, Bit 12=Circuit 1 economizer entering temperature sensor fault, Bit 13=Circuit 1 economizer leaving temperature sensor fault, Bit 14=Circuit 2 economizer entering temperature sensor fault, Bit 15=Circuit 2 economizer leaving temperature sensor fault (1=fault)"
  },
  {
   "type": "AV",
   "instance": 1156,
   "name": "FAULT STATUS 2",
   "description": "Fault status word 2, bit-coded",
   "units": "",
   "access": "R",
   "states": "Bit 0=Unit heating leaving water temperature sensor fault, Bit 1=Chiller heating leaving water temperature sensor fault, Bit 2=Unit heating entering water temperature sensor fault, Bit 3=Circuit 1 low pressure transducer fault, Bit 4=Circuit 2 low pressure transducer fault, Bit 5=Circuit 1 high pressure transducer fault, Bit 6=Circuit 2 high pressure transducer fault (1=fault)"
  },
  {
   "type": "AV",
   "instance": 1157,
   "name": "FAULT STATUS 3",
   "description": "Fault status word 3, bit-coded",
   "units": "",
   "access": "R",
   "states": "Bit 0=Circuit 1 fan motor fault, Bit 1=Circuit 2 fan motor fault, Bit 2=Circuit 1 high pressure switch fault, Bit 3=Circuit 1 low pressure switch fault, Bit 4=Chiller cooling Water flow fault, Bit 7=External interlock fault, Bit 8=Power fault, Bit 9=Circuit 2 high pressure switch fault, Bit 10=Circuit 2 low pressure switch fault, Bit 11=Unit cooling Water flow fault, Bit 12=Unit heating Water flow fault, Bit 13=Chiller heating Water flow fault (1=fault)"
  },
  {
   "type": "AV",
   "instance": 1158,
   "name": "FAULT STATUS 4",
   "description": "Fault status word 4, bit-coded",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1159,
   "name": "FAULT STATUS 5",
   "description": "Fault status word 5, bit-coded",
   "units": "",
   "access": "R",
   "states": "Bit 0=Communication failure (Follower unit with leader), Bit 1=Chiller Dial Switch setting error, Bit 2=Time limit protection, Bit 3=Low ambient temperature in cooling, Bit 4=High ambient temperature in heating, Bit 5=Chiller low leaving temperature in cooling, Bit 6=Chiller high leaving temperature in heating, Bit 7=Chiller locking, Bit 8=Communication failure (FCU with leader), Bit 10=Unit low leaving temperature in cooling, Bit 12=Unit high leaving temperature in heating, Bit 14=Unit low leaving temperature in heatinging (1=fault)"
  },
  {
   "type": "AV",
   "instance": 1160,
   "name": "FAULT STATUS 6",
   "description": "Fault status word 6, bit-coded",
   "units": "",
   "access": "R",
   "states": "Bit 0=Circuit 1 compressor 1 high discharge port temperature, Bit 2=Circuit 2 compressor 1 high discharge port temperature, Bit 8=Circuit 1 cooling brazed plate heat exchanger anti-freeze protect, Bit 9=Circuit 2 Cooling brazed plate heat exchanger anti-freeze protect, Bit 10=Circuit 1 heating brazed plate heat exchanger anti-freeze protect, Bit 11=Circuit 2 heating brazed plate heat exchanger anti-freeze protect, Bit 14=Circuit 1 four way valve action failure, Bit 15=Circuit 2 four way valve action failure (1=fault)"
  },
  {
   "type": "AV",
   "instance": 1161,
   "name": "FAULT STATUS 7",
   "description": "Fault status word 7, bit-coded",
   "units": "",
   "access": "R",
   "states": "Bit 0=Unit Dial Switch setting error, Bit 1=Communication failure (unit with circuit 1 driver), Bit 2=Communication failure (unit with circuit 1 fan), Bit 3=Communication failure (unit with circuit 2 fan), Bit 4=Communication failure (unit with circuit 2 driver), Bit 5=Driver fault or inverter compressor fault, Bit 7=Circuit 1 fan motor overspeed, Bit 8=Circuit 2 fan motor overspeed, Bit 9=Circuit 1 fan motor underspeed, Bit 10=Circuit 2 fan motor underspeed, Bit 11=Circuit 1 VSD heat dissipation alarm, Bit 12=Circuit 2 VSD heat dissipation alarm, Bit 13=Communication failure (Mainboard with Expansion Board) (1=fault)"
  },
  {
   "type": "AV",
   "instance": 1162,
   "name": "FAULT STATUS 8",
   "description": "Fault status word 8, bit-coded",
   "units": "",
   "access": "R",
   "states": "Bit 2=Circuit 1 High pressure alarm, Bit 3=Circuit 2 High pressure alarm, Bit 4=Circuit 1 Low discharge pressure alarm, Bit 5=Circuit 2 Low discharge pressure alarm, Bit 6=Circuit 1 Low pressure alarm, Bit 7=Circuit 2 Low pressure alarm (1=fault)"
  },
  {
   "type": "AV",
   "instance": 1163,
   "name": "CHILLER MODEL NUMBER",
   "description": "Chiller Model Number",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/york/ymae",
 "note": "Re-typed from the manufacturer's public documentation (see source). Point availability varies by firmware and options; verify against the live device."
}