 "manufacturer": "Vertiv",
 "manufacturer_slug": "vertiv",
 "model": "Liebert XDP refrigerant pumping unit",
 "model_slug": "xdp",
 "aliases": [
  "Liebert XDP",
  "XDP",
  "SL-28170"
 ],
 "equipment_type": "Refrigerant pumping unit for Liebert XD systems",
 "applies_to": "Liebert XDP pumping units of a Liebert XD pumped-refrigerant system (iCOM v4 controller).",
 "summary": "The Liebert XDP refrigerant pumping unit is part of a Liebert XD pumped-refrigerant cooling system and reports through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Binary Values carry events, Analog Values carry temperatures, capacities and settings, and Multi-state Values carry states, event control and event type settings. Objects are created when the card discovers the unit.",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Tables 5.81, 5.82, 5.83, pdf pages 1708-1721 of the 2024 guide (printed page numbers are 4 lower).",
  "Object names are Vertiv data IDs (e.g. 5331_1); the description holds the guide's data label. Labels repeated for different sensors or circuits get the group name in brackets.",
  "Most temperature objects come in pairs: a °C object and a °F object (name ending _deg_F), usually at instance + 10000."
 ],
 "source": {
  "title": "Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP)",
  "doc_number": "SL-28170",
  "revision_date": "2024-04 (Rev 29)",
  "url": "https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf"
 },
 "integration": {
  "summary": "Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the unit; the objects are then created automatically. Map the on/off and setpoint objects if the BMS controls the unit, and the status, main measurements and event objects for monitoring.",
  "minimum_points": [
   {
    "ref": "MV 841",
    "name": "5143_1",
    "why": "On/off command (1=off, 2=on)"
   },
   {
    "ref": "MV 876",
    "name": "4717_1",
    "why": "Acknowledge / reset events"
   },
   {
    "ref": "MV 838",
    "name": "4706_1",
    "why": "Run / standby / off state"
   },
   {
    "ref": "MV 837",
    "name": "4123_1",
    "why": "Normal, warning or alarm state"
   },
   {
    "ref": "AV 22",
    "name": "4624_1",
    "why": "Supply fluid temperature, °C"
   },
   {
    "ref": "AV 94",
    "name": "5490_1",
    "why": "Cooling output, %"
   },
   {
    "ref": "BV 458",
    "name": "5113_1_1",
    "why": "Unit shut down by an event"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "The card needs a unique Device Instance Number; the device object represents the card, not the unit.",
   "The cards have no BBMD; IS-UNITY-DP and IS-IPBML support foreign device registration (BBMD address and time-to-live).",
   "IS-UNITY-DP adds BACnet MS/TP; IS-WEBADPT and IS-IPBML are BACnet IP only. Check the compatibility table (guide section 1.1.3) for the card your unit supports."
  ],
  "gotchas": [
   "Vertiv asks for no more than about two writes and two reads per second on average; do not rewrite setpoints continuously.",
   "No segmented responses: large ReadPropertyMultiple requests can fail, so split them.",
   "Only data the managed unit actually has is created on the card, so object counts vary by model and options."
  ]
 },
 "points": [
  {
   "type": "BV",
   "instance": 1,
   "name": "4601_1",
   "description": "Ext Air Sensor A Over Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "4604_1",
   "description": "Ext Air Sensor B Over Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "4608_1",
   "description": "Ext Air Sensor A Under Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "4611_1",
   "description": "Ext Air Sensor B Under Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "4615_1",
   "description": "Ext Dew Point Over Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "4618_1",
   "description": "Ext Air Sensor A Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "4621_1",
   "description": "Ext Air Sensor B Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "4626_1",
   "description": "Supply Chilled Water Over Temp",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "4629_1",
   "description": "Supply Chilled Water Temp Sensor Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "4703_1",
   "description": "Chilled Water Control Valve Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "4634_1",
   "description": "Supply Refrigerant Over Temp",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "4637_1",
   "description": "Supply Refrigerant Under Temp",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "4640_1",
   "description": "Supply Refrigerant Temp Sensor Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 57,
   "name": "4656_1",
   "description": "Pump 1 Loss of Flow",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 58,
   "name": "4659_1",
   "description": "Pump 2 Loss of Flow",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 59,
   "name": "4662_1",
   "description": "Pump Short Cycle",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 70,
   "name": "5300_1_1",
   "description": "Pump Hours Exceeded (PumpHours)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 81,
   "name": "5300_1_2",
   "description": "Pump Hours Exceeded (PumpHours)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 112,
   "name": "5492_1",
   "description": "Ext System Condensation Detected (XDSystem)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 113,
   "name": "5495_1",
   "description": "Ext Fan Issue (XDSystem)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 114,
   "name": "5060_1",
   "description": "Sensor Issue (XDSystem)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 115,
   "name": "5500_1",
   "description": "Ext Remote Shutdown (XDSystem)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 116,
   "name": "5505_1",
   "description": "Hot Aisle Temp Out of Range (XDSystem)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 117,
   "name": "5508_1",
   "description": "Cold Aisle Temp Out of Range (XDSystem)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 118,
   "name": "6535_1",
   "description": "XD Module Communication Lost (XDSystem)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 128,
   "name": "5492_2",
   "description": "Ext System Condensation Detected (XDSystem 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 129,
   "name": "5495_2",
   "description": "Ext Fan Issue (XDSystem 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 130,
   "name": "5060_2",
   "description": "Sensor Issue (XDSystem 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 131,
   "name": "5500_2",
   "description": "Ext Remote Shutdown (XDSystem 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 132,
   "name": "5505_2",
   "description": "Hot Aisle Temp Out of Range (XDSystem 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 133,
   "name": "5508_2",
   "description": "Cold Aisle Temp Out of Range (XDSystem 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 134,
   "name": "6535_2",
   "description": "XD Module Communication Lost (XDSystem 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 432,
   "name": "4270_1",
   "description": "Customer Input 1",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 433,
   "name": "4711_1",
   "description": "System Condensation Detected",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 434,
   "name": "4714_1",
   "description": "Shutdown - Loss Of Power",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 435,
   "name": "4720_1",
   "description": "Smoke Detected",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 436,
   "name": "4723_1",
   "description": "Water Under Floor",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 437,
   "name": "4726_1",
   "description": "Service Required",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 438,
   "name": "4729_1",
   "description": "Fan Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 439,
   "name": "5419_1",
   "description": "Unit Communication Lost",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 440,
   "name": "5119_1",
   "description": "RAM Battery Issue",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 441,
   "name": "5120_1",
   "description": "Master Unit Communication Lost",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 442,
   "name": "5512_1",
   "description": "Remote Shutdown",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 443,
   "name": "5418_1",
   "description": "Unit Code Missing",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 454,
   "name": "5109_1_1",
   "description": "Unit On",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 455,
   "name": "5110_1_1",
   "description": "Unit Off",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 456,
   "name": "5111_1_1",
   "description": "Unit Standby",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 457,
   "name": "5112_1_1",
   "description": "Unit Partial Shutdown",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 458,
   "name": "5113_1_1",
   "description": "Unit Shutdown",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 459,
   "name": "5116_1_1",
   "description": "Maintenance Due",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 460,
   "name": "5117_1_1",
   "description": "Maintenance Completed",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18000,
   "name": "5642_1",
   "description": "SFA Reserved Event 1",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18001,
   "name": "5643_1",
   "description": "SFA Reserved Event 2",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18002,
   "name": "5644_1",
   "description": "SFA Reserved Event 3",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18003,
   "name": "5645_1",
   "description": "SFA Reserved Event 4",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18004,
   "name": "5646_1",
   "description": "SFA Reserved Event 5",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18005,
   "name": "5647_1",
   "description": "SFA Reserved Event 6",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18006,
   "name": "5648_1",
   "description": "SFA Reserved Event 7",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18007,
   "name": "5649_1",
   "description": "SFA Reserved Event 8",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18008,
   "name": "5650_1",
   "description": "SFA Reserved Event 9",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18009,
   "name": "5651_1",
   "description": "SFA Reserved Event 10",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18010,
   "name": "5652_1",
   "description": "SFA Reserved Event 11",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18011,
   "name": "5653_1",
   "description": "SFA Reserved Event 12",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18012,
   "name": "5654_1",
   "description": "SFA Reserved Event 13",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18013,
   "name": "5655_1",
   "description": "SFA Reserved Event 14",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18014,
   "name": "5656_1",
   "description": "SFA Reserved Event 15",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18015,
   "name": "5657_1",
   "description": "SFA Reserved Event 16",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18016,
   "name": "5658_1",
   "description": "SFA Reserved Event 17",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18017,
   "name": "5659_1",
   "description": "SFA Reserved Event 18",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18018,
   "name": "5660_1",
   "description": "SFA Reserved Event 19",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18019,
   "name": "5661_1",
   "description": "SFA Reserved Event 20",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18020,
   "name": "5662_1",
   "description": "SFA Reserved Event 21",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18021,
   "name": "5663_1",
   "description": "SFA Reserved Event 22",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18022,
   "name": "5664_1",
   "description": "SFA Reserved Event 23",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18023,
   "name": "5665_1",
   "description": "SFA Reserved Event 24",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18024,
   "name": "5666_1",
   "description": "SFA Reserved Event 25",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 71,
   "name": "6534_1_1",
   "description": "Pump Thermal Overload (Pumps – Pump 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 82,
   "name": "6534_1_2",
   "description": "Pump Thermal Overload (Pumps – Pumps 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "4867_1",
   "description": "Dew Point Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10001,
   "name": "4867_1_deg_F",
   "description": "Dew Point Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "4709_1",
   "description": "Minimum Room Temperature Set Point",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10002,
   "name": "4709_1_deg_F",
   "description": "Minimum Room Temperature Set Point",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "4594_1",
   "description": "Ext Air Sensor A Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10003,
   "name": "4594_1_deg_F",
   "description": "Ext Air Sensor A Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "4595_1",
   "description": "Ext Air Sensor A Humidity",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "4596_1",
   "description": "Ext Air Sensor A Dew Point Temp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10005,
   "name": "4596_1_deg_F",
   "description": "Ext Air Sensor A Dew Point Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "4597_1",
   "description": "Ext Air Sensor B Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10006,
   "name": "4597_1_deg_F",
   "description": "Ext Air Sensor B Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "4598_1",
   "description": "Ext Air Sensor B Humidity",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "4599_1",
   "description": "Ext Air Sensor B Dew Point Temp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10008,
   "name": "4599_1_deg_F",
   "description": "Ext Air Sensor B Dew Point Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "4600_1",
   "description": "Ext Air Over Temp Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10009,
   "name": "4600_1_deg_F",
   "description": "Ext Air Over Temp Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "4607_1",
   "description": "Ext Air Under Temp Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10010,
   "name": "4607_1_deg_F",
   "description": "Ext Air Under Temp Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "4614_1",
   "description": "Ext Dew Point Over Temp Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10011,
   "name": "4614_1_deg_F",
   "description": "Ext Dew Point Over Temp Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "4624_1",
   "description": "Supply Fluid Temperature (Chilled Water)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10022,
   "name": "4624_1_deg_F",
   "description": "Supply Fluid Temperature (Chilled Water)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "4625_1",
   "description": "High Supply Fluid Temperature Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10023,
   "name": "4625_1_deg_F",
   "description": "High Supply Fluid Temperature Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "5640_1",
   "description": "Chilled Water Valve Open Position",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "4632_1",
   "description": "Supply Refrigerant Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10034,
   "name": "4632_1_deg_F",
   "description": "Supply Refrigerant Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "4633_1",
   "description": "Supply Refrig Over Temp Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10035,
   "name": "4633_1_deg_F",
   "description": "Supply Refrig Over Temp Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "4643_1",
   "description": "Supply Fluid Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10046,
   "name": "4643_1_deg_F",
   "description": "Supply Fluid Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "4644_1",
   "description": "Supply Fluid Over Temp Threshold",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10047,
   "name": "4644_1_deg_F",
   "description": "Supply Fluid Over Temp Threshold",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "5298_1_1",
   "description": "Pump Hours (PumpHours)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "5299_1_1",
   "description": "Pump Hours Threshold (PumpHours)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "5298_1_2",
   "description": "Pump Hours (PumpHours)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "5299_1_2",
   "description": "Pump Hours Threshold (PumpHours)",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 94,
   "name": "5490_1",
   "description": "Cooling Capacity (XDSystem)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 95,
   "name": "5491_1",
   "description": "Cooling Capacity (XDSystem)",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 96,
   "name": "5503_1",
   "description": "Hot Aisle Over Temp Threshold (XDSystem)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10096,
   "name": "5503_1_deg_F",
   "description": "Hot Aisle Over Temp Threshold (XDSystem)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 97,
   "name": "5504_1",
   "description": "Hot Aisle Under Temp Threshold (XDSystem)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10097,
   "name": "5504_1_deg_F",
   "description": "Hot Aisle Under Temp Threshold (XDSystem)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 98,
   "name": "5506_1",
   "description": "Cold Aisle Over Temp Threshold (XDSystem)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10098,
   "name": "5506_1_deg_F",
   "description": "Cold Aisle Over Temp Threshold (XDSystem)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 99,
   "name": "5507_1",
   "description": "Cold Aisle Under Temp Threshold (XDSystem)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10099,
   "name": "5507_1_deg_F",
   "description": "Cold Aisle Under Temp Threshold (XDSystem)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 110,
   "name": "5059_1_1",
   "description": "Sensor Temperature (XDSystem – Temperature Sensor 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10110,
   "name": "5059_1_1_deg_F",
   "description": "Sensor Temperature (XDSystem – Temperature Sensor 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 121,
   "name": "5059_1_2",
   "description": "Sensor Temperature (XDSystem – Temperature Sensor 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10121,
   "name": "5059_1_2_deg_F",
   "description": "Sensor Temperature (XDSystem – Temperature Sensor 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 143,
   "name": "5059_1_4",
   "description": "Sensor Temperature (XDSystem – Temperature Sensor 4)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10143,
   "name": "5059_1_4_deg_F",
   "description": "Sensor Temperature (XDSystem – Temperature Sensor 4)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 154,
   "name": "5490_2",
   "description": "Cooling Capacity (XDSystem 2)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 155,
   "name": "5491_2",
   "description": "Cooling Capacity (XDSystem 2)",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 156,
   "name": "5503_2",
   "description": "Hot Aisle Over Temp Threshold (XDSystem 2)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10156,
   "name": "5503_2_deg_F",
   "description": "Hot Aisle Over Temp Threshold (XDSystem 2)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 157,
   "name": "5504_2",
   "description": "Hot Aisle Under Temp Threshold (XDSystem 2)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10157,
   "name": "5504_2_deg_F",
   "description": "Hot Aisle Under Temp Threshold (XDSystem 2)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 158,
   "name": "5506_2",
   "description": "Cold Aisle Over Temp Threshold (XDSystem 2)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10158,
   "name": "5506_2_deg_F",
   "description": "Cold Aisle Over Temp Threshold (XDSystem 2)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 159,
   "name": "5507_2",
   "description": "Cold Aisle Under Temp Threshold (XDSystem 2)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10159,
   "name": "5507_2_deg_F",
   "description": "Cold Aisle Under Temp Threshold (XDSystem 2)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 170,
   "name": "5059_2_1",
   "description": "Sensor Temperature (XDSystem – Temperature Sensor 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10170,
   "name": "5059_2_1_deg_F",
   "description": "Sensor Temperature (XDSystem – Temperature Sensor 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10181,
   "name": "5059_2_2_deg_F",
   "description": "Sensor Temperature (XDSystem – Temperature Sensor 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 203,
   "name": "5059_2_4",
   "description": "Sensor Temperature (XDSystem – Temperature Sensor 4)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10203,
   "name": "5059_2_4_deg_F",
   "description": "Sensor Temperature (XDSystem – Temperature Sensor 4)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1294,
   "name": "4710_1",
   "description": "Auto Restart Delay",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1295,
   "name": "4870_1",
   "description": "Maintenance Ramp",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1296,
   "name": "4868_1",
   "description": "Calculated Next Maintenance Month",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1297,
   "name": "4869_1",
   "description": "Calculated Next Maintenance Year",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1308,
   "name": "4293_1",
   "description": "System Date and Time",
   "units": "Secs since Epoch(UTC)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18000,
   "name": "5641_1",
   "description": "SFA ID Number",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18001,
   "name": "5667_1",
   "description": "SFA 16bit Read Only Value 1",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18002,
   "name": "5668_1",
   "description": "SFA 16bit Read Only Value 2",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18003,
   "name": "5669_1",
   "description": "SFA 16bit Read Only Value 3",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18004,
   "name": "5670_1",
   "description": "SFA 16bit Read Only Value 4",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18005,
   "name": "5671_1",
   "description": "SFA 16bit Read Only Value 5",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18006,
   "name": "5672_1",
   "description": "SFA 16bit Read Only Value 6",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18007,
   "name": "5673_1",
   "description": "SFA 16bit Read Only Value 7",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18008,
   "name": "5674_1",
   "description": "SFA 16bit Read Only Value 8",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18009,
   "name": "5675_1",
   "description": "SFA 16bit Read Only Value 9",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18010,
   "name": "5676_1",
   "description": "SFA 16bit Read Only Value 10",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18011,
   "name": "5692_1",
   "description": "SFA 32bit Read Only Value 1",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18012,
   "name": "5693_1",
   "description": "SFA 32bit Read Only Value 2",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18013,
   "name": "5694_1",
   "description": "SFA 32bit Read Only Value 3",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18014,
   "name": "5695_1",
   "description": "SFA 32bit Read Only Value 4",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18015,
   "name": "5696_1",
   "description": "SFA 32bit Read Only Value 5",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18016,
   "name": "5697_1",
   "description": "SFA 32bit Read Only Value 6",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18017,
   "name": "5698_1",
   "description": "SFA 32bit Read Only Value 7",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18018,
   "name": "5699_1",
   "description": "SFA 32bit Read Only Value 8",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18019,
   "name": "5700_1",
   "description": "SFA 32bit Read Only Value 9",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18020,
   "name": "5701_1",
   "description": "SFA 32bit Read Only Value 10",
   "units": "Generic",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18021,
   "name": "5717_1",
   "description": "SFA 16bit Writable Value 1",
   "units": "Generic",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18022,
   "name": "5718_1",
   "description": "SFA 16bit Writable Value 2",
   "units": "Generic",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18023,
   "name": "5719_1",
   "description": "SFA 16bit Writable Value 3",
   "units": "Generic",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18024,
   "name": "5720_1",
   "description": "SFA 16bit Writable Value 4",
   "units": "Generic",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18025,
   "name": "5721_1",
   "description": "SFA 16bit Writable Value 5",
   "units": "Generic",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18026,
   "name": "5722_1",
   "description": "SFA 16bit Writable Value 6",
   "units": "Generic",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18027,
   "name": "5723_1",
   "description": "SFA 16bit Writable Value 7",
   "units": "Generic",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18028,
   "name": "5724_1",
   "description": "SFA 16bit Writable Value 8",
   "units": "Generic",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18029,
   "name": "5725_1",
   "description": "SFA 16bit Writable Value 9",
   "units": "Generic",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18030,
   "name": "5726_1",
   "description": "SFA 16bit Writable Value 10",
   "units": "Generic",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18031,
   "name": "5742_1",
   "description": "SFA 32bit Writable Value 1",
   "units": "Generic",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18032,
   "name": "5743_1",
   "description": "SFA 32bit Writable Value 2",
   "units": "Generic",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18033,
   "name": "5744_1",
   "description": "SFA 32bit Writable Value 3",
   "units": "Generic",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18034,
   "name": "5745_1",
   "description": "SFA 32bit Writable Value 4",
   "units": "Generic",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18035,
   "name": "5746_1",
   "description": "SFA 32bit Writable Value 5",
   "units": "Generic",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18036,
   "name": "5747_1",
   "description": "SFA 32bit Writable Value 6",
   "units": "Generic",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18037,
   "name": "5748_1",
   "description": "SFA 32bit Writable Value 7",
   "units": "Generic",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18038,
   "name": "5749_1",
   "description": "SFA 32bit Writable Value 8",
   "units": "Generic",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18039,
   "name": "5750_1",
   "description": "SFA 32bit Writable Value 9",
   "units": "Generic",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18040,
   "name": "5751_1",
   "description": "SFA 32bit Writable Value 10",
   "units": "Generic",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "4602_1",
   "description": "Ext Air Sensor A Over Temp - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "4603_1",
   "description": "Ext Air Sensor A Over Temp - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "4605_1",
   "description": "Ext Air Sensor B Over Temp - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "4606_1",
   "description": "Ext Air Sensor B Over Temp - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "4609_1",
   "description": "Ext Air Sensor A Under Temp - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 6,
   "name": "4610_1",
   "description": "Ext Air Sensor A Under Temp - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 7,
   "name": "4612_1",
   "description": "Ext Air Sensor B Under Temp - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 8,
   "name": "4613_1",
   "description": "Ext Air Sensor B Under Temp - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 9,
   "name": "4616_1",
   "description": "Ext Dew Point Over Temp - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 10,
   "name": "4617_1",
   "description": "Ext Dew Point Over Temp - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 11,
   "name": "4619_1",
   "description": "Ext Air Sensor A Issue - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 12,
   "name": "4620_1",
   "description": "Ext Air Sensor A Issue - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 13,
   "name": "4622_1",
   "description": "Ext Air Sensor B Issue - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 14,
   "name": "4623_1",
   "description": "Ext Air Sensor B Issue - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 25,
   "name": "4627_1",
   "description": "Supply CW Over Temp - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 26,
   "name": "4628_1",
   "description": "Supply CW Over Temp - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 27,
   "name": "4630_1",
   "description": "Supply CW Temp Sensor Issue - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 28,
   "name": "4631_1",
   "description": "Supply CW Temp Sensor Issue - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 29,
   "name": "4704_1",
   "description": "Chilled Water Cntrl Valve Pos - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 30,
   "name": "4705_1",
   "description": "Chilled Water Cntrl Valve Pos - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 41,
   "name": "4635_1",
   "description": "Supply Refrig Over Temp - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 42,
   "name": "4636_1",
   "description": "Supply Refrig Over Temp - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 43,
   "name": "4638_1",
   "description": "Supply Refrig Under Temp - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 44,
   "name": "4639_1",
   "description": "Supply Refrig Under Temp - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 45,
   "name": "4641_1",
   "description": "Supply Refrig Temp Sensor Issue - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 46,
   "name": "4642_1",
   "description": "Supply Refrig Temp Sensor Issue - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 57,
   "name": "4646_1",
   "description": "Supply Fluid Over Temp - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 58,
   "name": "4647_1",
   "description": "Supply Fluid Over Temp - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 59,
   "name": "4649_1",
   "description": "Supply Fluid Under Temp - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 60,
   "name": "4650_1",
   "description": "Supply Fluid Under Temp - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 61,
   "name": "4652_1",
   "description": "Supply Fluid Temp Sensor Issue - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 62,
   "name": "4653_1",
   "description": "Supply Fluid Temp Sensor Issue - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 73,
   "name": "4654_1",
   "description": "Pump 1 State",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 74,
   "name": "4655_1",
   "description": "Pump 2 State",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 75,
   "name": "4657_1",
   "description": "Pump 1 Loss of Flow - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 76,
   "name": "4658_1",
   "description": "Pump 1 Loss of Flow - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 77,
   "name": "4660_1",
   "description": "Pump 2 Loss of Flow - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 78,
   "name": "4661_1",
   "description": "Pump 2 Loss of Flow - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 79,
   "name": "4663_1",
   "description": "Pump Short Cycle - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 80,
   "name": "4664_1",
   "description": "Pump Short Cycle - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 137,
   "name": "5486_1",
   "description": "Communication Status (XDSystem)",
   "units": "",
   "access": "R",
   "states": "1=Connected, 2=Not Connected"
  },
  {
   "type": "MV",
   "instance": 138,
   "name": "5487_1",
   "description": "Fan On/Off Control (XDSystem)",
   "units": "",
   "access": "W",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 139,
   "name": "5509_1",
   "description": "Master Fan Group State (XDSystem)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on, 3=economy"
  },
  {
   "type": "MV",
   "instance": 140,
   "name": "5488_1",
   "description": "Fan Button Control (XDSystem)",
   "units": "",
   "access": "W",
   "states": "1=enabled, 2=disabled"
  },
  {
   "type": "MV",
   "instance": 141,
   "name": "5489_1",
   "description": "Visual ID Control (XDSystem)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 142,
   "name": "5493_1",
   "description": "Ext System Condensation Detected - Event Control (XDSystem)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 143,
   "name": "5494_1",
   "description": "Ext System Condensation Detected - Event Type (XDSystem)",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 144,
   "name": "5496_1",
   "description": "Ext Fan Issue - Event Control (XDSystem)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 145,
   "name": "5497_1",
   "description": "Ext Fan Issue - Event Type (XDSystem)",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 146,
   "name": "5498_1",
   "description": "Sensor Issue - Event Control (XDSystem)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 147,
   "name": "5499_1",
   "description": "Sensor Issue - Event Type (XDSystem)",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 148,
   "name": "5501_1",
   "description": "Ext Remote Shutdown - Event Control (XDSystem)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 149,
   "name": "5502_1",
   "description": "Ext Remote Shutdown - Event Type (XDSystem)",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 160,
   "name": "5510_1_1",
   "description": "Fan State (XDSystem – Slave Fans 1)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on, 3=economy"
  },
  {
   "type": "MV",
   "instance": 161,
   "name": "5511_1_1",
   "description": "Fan Economy Mode (XDSystem – Slave Fans 1)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=automatic, 3=manual"
  },
  {
   "type": "MV",
   "instance": 172,
   "name": "5486_2",
   "description": "Communication Status (XDSystem 2)",
   "units": "",
   "access": "R",
   "states": "1=Connected, 2=Not Connected"
  },
  {
   "type": "MV",
   "instance": 173,
   "name": "5487_2",
   "description": "Fan On/Off Control (XDSystem 2)",
   "units": "",
   "access": "W",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 174,
   "name": "5509_2",
   "description": "Master Fan Group State (XDSystem 2)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on, 3=economy"
  },
  {
   "type": "MV",
   "instance": 175,
   "name": "5488_2",
   "description": "Fan Button Control (XDSystem 2)",
   "units": "",
   "access": "W",
   "states": "1=enabled, 2=disabled"
  },
  {
   "type": "MV",
   "instance": 176,
   "name": "5489_2",
   "description": "Visual ID Control (XDSystem 2)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 177,
   "name": "5493_2",
   "description": "Ext System Condensation Detected - Event Control (XDSystem 2)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 178,
   "name": "5494_2",
   "description": "Ext System Condensation Detected - Event Type (XDSystem 2)",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 179,
   "name": "5496_2",
   "description": "Ext Fan Issue - Event Control (XDSystem 2)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 180,
   "name": "5497_2",
   "description": "Ext Fan Issue - Event Type (XDSystem 2)",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 181,
   "name": "5498_2",
   "description": "Sensor Issue - Event Control (XDSystem 2)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 182,
   "name": "5499_2",
   "description": "Sensor Issue - Event Type (XDSystem 2)",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 183,
   "name": "5501_2",
   "description": "Ext Remote Shutdown - Event Control (XDSystem 2)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 184,
   "name": "5502_2",
   "description": "Ext Remote Shutdown - Event Type (XDSystem 2)",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 195,
   "name": "5510_2_1",
   "description": "Fan State (XDSystem – Slave Fans 1)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on, 3=economy"
  },
  {
   "type": "MV",
   "instance": 196,
   "name": "5511_2_1",
   "description": "Fan Economy Mode (XDSystem – Slave Fans 1)",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=automatic, 3=manual"
  },
  {
   "type": "MV",
   "instance": 837,
   "name": "4123_1",
   "description": "System Status",
   "units": "",
   "access": "R",
   "states": "1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation"
  },
  {
   "type": "MV",
   "instance": 838,
   "name": "4706_1",
   "description": "Unit Operating State",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on, 3=standby"
  },
  {
   "type": "MV",
   "instance": 839,
   "name": "4707_1",
   "description": "Unit Control Mode",
   "units": "",
   "access": "R",
   "states": "1=Internal (Auto), 2=External (Manual)"
  },
  {
   "type": "MV",
   "instance": 840,
   "name": "5074_1",
   "description": "Unit Off Reason",
   "units": "",
   "access": "R",
   "states": "1=None, 2=User, 3=Alarm, 4=Timer, 5=Monitoring, 6=Remote Off7 = HCS12 Off"
  },
  {
   "type": "MV",
   "instance": 841,
   "name": "5143_1",
   "description": "System On/Off Control",
   "units": "",
   "access": "W",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 852,
   "name": "4718_1",
   "description": "Customer Input 1 - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 853,
   "name": "4719_1",
   "description": "Customer Input 1 - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 854,
   "name": "4712_1",
   "description": "System Condensation Detected - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 855,
   "name": "4713_1",
   "description": "System Condensation Detected - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 856,
   "name": "4715_1",
   "description": "Shutdown - Loss Of Power - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 857,
   "name": "4716_1",
   "description": "Shutdown - Loss Of Power - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 858,
   "name": "4721_1",
   "description": "Smoke Detected - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 859,
   "name": "4722_1",
   "description": "Smoke Detected - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 860,
   "name": "4724_1",
   "description": "Water Under Floor - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 861,
   "name": "4725_1",
   "description": "Water Under Floor - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 862,
   "name": "4727_1",
   "description": "Service Required - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 863,
   "name": "4728_1",
   "description": "Service Required - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 864,
   "name": "4730_1",
   "description": "Fan Issue - Event Control",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 865,
   "name": "4731_1",
   "description": "Fan Issue - Event Type",
   "units": "",
   "access": "W",
   "states": "1=Message, 2=Warning, 3=Alarm"
  },
  {
   "type": "MV",
   "instance": 876,
   "name": "4717_1",
   "description": "System Event Acknowledge/Reset",
   "units": "",
   "access": "W",
   "states": "1=Reset, 2=Acknowledge"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/vertiv/xdp",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}