 "summary": "The Liebert EXL UPS reports to a BMS through a Liebert IntelliSlot card (BACnet IP or BACnet MS/TP). Analog Values carry input, bypass, output and battery measurements, Binary Values carry UPS events, and Multi-state Values carry system status, output source and settings. Objects are created when the card discovers the UPS.",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Tables 5.130, 5.131, 5.132, pdf pages 2008-2036 of the 2024 guide (printed page numbers are 4 lower).",
  "Object names are Vertiv data IDs (e.g. 5331_1); the description holds the guide's data label. Labels repeated for different sensors or circuits get the group name in brackets.",
  "Most temperature objects come in pairs: a °C object and a °F object (name ending _deg_F), usually at instance + 10000."
 ],
 "source": {
  "title": "Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP)",
  "doc_number": "SL-28170",
  "revision_date": "2024-04 (Rev 29)",
  "url": "https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf"
 },
 "integration": {
  "summary": "Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.",
  "minimum_points": [
   {
    "ref": "MV 117",
    "name": "4123_1",
    "why": "Normal, warning or alarm state"
   },
   {
    "ref": "MV 118",
    "name": "4872_1",
    "why": "Load on inverter, bypass or battery"
   },
   {
    "ref": "AV 58",
    "name": "4150_1",
    "why": "Estimated battery runtime, min"
   },
   {
    "ref": "AV 103",
    "name": "4208_1",
    "why": "Output power, kW"
   },
   {
    "ref": "AV 1",
    "name": "4097_1",
    "why": "Input voltage, V"
   },
   {
    "ref": "AV 96",
    "name": "4201_1",
    "why": "Output voltage, V"
   },
   {
    "ref": "AV 99",
    "name": "4204_1",
    "why": "Output current, A"
   },
   {
    "ref": "BV 40",
    "name": "4168_1",
    "why": "Load is on battery"
   },
   {
    "ref": "BV 155",
    "name": "4300_1",
    "why": "Internal communication lost"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "The card needs a unique Device Instance Number; the device object represents the card, not the unit.",
   "The cards have no BBMD; IS-UNITY-DP and IS-IPBML support foreign device registration (BBMD address and time-to-live).",
   "IS-UNITY-DP adds BACnet MS/TP; IS-WEBADPT and IS-IPBML are BACnet IP only. Check the compatibility table (guide section 1.1.3) for the card your unit supports."
  ],
  "gotchas": [
   "Vertiv asks for no more than about two writes and two reads per second on average; do not rewrite setpoints continuously.",
   "No segmented responses: large ReadPropertyMultiple requests can fail, so split them.",
   "Only data the managed unit actually has is created on the card, so object counts vary by model and options."
  ]
 },
 "points": [
  {
   "type": "BV",
   "instance": 1,
   "name": "4122_1",
   "description": "System Input Power Problem",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "4147_1",
   "description": "System Input Current Limit",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "5568_1",
   "description": "Input Undervoltage",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "4135_1",
   "description": "Bypass Not Available",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "4132_1",
   "description": "Bypass Overload Phase A",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "4133_1",
   "description": "Bypass Overload Phase B",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "4134_1",
   "description": "Bypass Overload Phase C",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "4137_1",
   "description": "Bypass Auto Retransfer Primed",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "4138_1",
   "description": "Bypass Auto Retransfer Failed",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "4139_1",
   "description": "Bypass - Excess Auto Retransfers",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "4142_1",
   "description": "Bypass Static Switch Overload",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "4143_1",
   "description": "Bypass Static Switch Unavailable",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 23,
   "name": "4144_1",
   "description": "Bypass Excessive Pulse Parallel",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "4145_1",
   "description": "Bypass Auto Transfer Failed",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 25,
   "name": "4218_1",
   "description": "Bypass - Manual Rexfr Inhibited",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 26,
   "name": "4217_1",
   "description": "Bypass - Manual Xfr Inhibited",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "5984_1",
   "description": "Bypass Undervoltage Warning",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 38,
   "name": "4740_1",
   "description": "Battery Test Inhibited",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 39,
   "name": "4166_1",
   "description": "Battery Capacity Low",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 40,
   "name": "4168_1",
   "description": "Battery Discharging",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 41,
   "name": "4169_1",
   "description": "Battery Temperature Imbalance",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 42,
   "name": "4170_1",
   "description": "Battery Equalize",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 43,
   "name": "4741_1",
   "description": "Battery Self Test",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 44,
   "name": "4323_1",
   "description": "Battery Test Failed",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 45,
   "name": "4173_1",
   "description": "Main Battery Disconnect Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 46,
   "name": "4162_1",
   "description": "Battery Low",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 47,
   "name": "4174_1",
   "description": "Battery Temperature Sensor Fault",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 48,
   "name": "4176_1",
   "description": "Battery Circuit Breaker 1 Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 49,
   "name": "4179_1",
   "description": "Battery Circuit Breaker 2 Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 50,
   "name": "4182_1",
   "description": "Battery Circuit Breaker 3 Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 51,
   "name": "4185_1",
   "description": "Battery Circuit Breaker 4 Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 52,
   "name": "4188_1",
   "description": "Battery Circuit Breaker 5 Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 53,
   "name": "4191_1",
   "description": "Battery Circuit Breaker 6 Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 54,
   "name": "4194_1",
   "description": "Battery Circuit Breaker 7 Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 55,
   "name": "4197_1",
   "description": "Battery Circuit Breaker 8 Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 56,
   "name": "5871_1",
   "description": "Battery Over Temperature Limit",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 57,
   "name": "4220_1",
   "description": "Battery - External Monitor 1",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 58,
   "name": "4221_1",
   "description": "Battery - External Monitor 2",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 59,
   "name": "4742_1",
   "description": "Battery Low Shutdown",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 70,
   "name": "4213_1",
   "description": "System Shutdown - EPO",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 71,
   "name": "4230_1",
   "description": "System Output Low Power Factor",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 72,
   "name": "4286_1",
   "description": "Output Amp Over User Limit-Phs A",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 73,
   "name": "4287_1",
   "description": "Output Amp Over User Limit-Phs B",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 74,
   "name": "4288_1",
   "description": "Output Amp Over User Limit-Phs C",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 75,
   "name": "4389_1",
   "description": "System Output Fault",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 76,
   "name": "5144_1",
   "description": "Output Of/Uf",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 77,
   "name": "5970_1",
   "description": "Ground Fault",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 87,
   "name": "4233_1",
   "description": "Inverter Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 88,
   "name": "4234_1",
   "description": "Inverter Overload Phase A",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 89,
   "name": "4235_1",
   "description": "Inverter Overload Phase B",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 90,
   "name": "4236_1",
   "description": "Inverter Overload Phase C",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 91,
   "name": "4290_1",
   "description": "Inverter Shutdown - Overload",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 102,
   "name": "4294_1",
   "description": "Inlet Air Over Temperature",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 103,
   "name": "6011_1",
   "description": "Equipment Over Temp Warning",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 104,
   "name": "5768_1",
   "description": "Outlet Air Overtemperature Limit",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 105,
   "name": "4747_1",
   "description": "Equipment Temperature Sensor Fail",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 106,
   "name": "6217_1",
   "description": "Memory Card Removed",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 107,
   "name": "6218_1",
   "description": "Auto Calibration Active",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 108,
   "name": "6219_1",
   "description": "Auto Calibration Failed",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 116,
   "name": "4270_1",
   "description": "Input Contact 01",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 117,
   "name": "4271_1",
   "description": "Input Contact 02",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 118,
   "name": "4272_1",
   "description": "Input Contact 03",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 119,
   "name": "4273_1",
   "description": "Input Contact 04",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 120,
   "name": "4274_1",
   "description": "Input Contact 05",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 121,
   "name": "4275_1",
   "description": "Input Contact 06",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 122,
   "name": "4276_1",
   "description": "Input Contact 07",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 123,
   "name": "4277_1",
   "description": "Input Contact 08",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 124,
   "name": "4278_1",
   "description": "Input Contact 09",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 125,
   "name": "4279_1",
   "description": "Input Contact 10",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 126,
   "name": "4280_1",
   "description": "Input Contact 11",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 127,
   "name": "4281_1",
   "description": "Input Contact 12",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 128,
   "name": "4282_1",
   "description": "Input Contact 13",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 129,
   "name": "4283_1",
   "description": "Input Contact 14",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 130,
   "name": "4284_1",
   "description": "Input Contact 15",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 131,
   "name": "4285_1",
   "description": "Input Contact 16",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 142,
   "name": "4295_1",
   "description": "Rectifier Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 153,
   "name": "4749_1",
   "description": "Fan Redundancy Warning",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 154,
   "name": "4750_1",
   "description": "Slave Fan Warning",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 155,
   "name": "4300_1",
   "description": "Internal Communications Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 156,
   "name": "4298_1",
   "description": "UPS Output on Bypass",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 157,
   "name": "4299_1",
   "description": "Output Load on Maint. Bypass",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 158,
   "name": "4325_1",
   "description": "Backfeed Breaker Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 159,
   "name": "4316_1",
   "description": "Auto Restart In Progress",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 160,
   "name": "4314_1",
   "description": "Power Supply Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 161,
   "name": "4315_1",
   "description": "On Generator",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 162,
   "name": "4317_1",
   "description": "Auto Restart Inhibited - Ext",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 163,
   "name": "4439_1",
   "description": "Automatic Restart Failed",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 164,
   "name": "4753_1",
   "description": "Main Controller Fault",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 165,
   "name": "4440_1",
   "description": "Fuse Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 166,
   "name": "4441_1",
   "description": "System Controller Error",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 167,
   "name": "4442_1",
   "description": "System Breaker(s) Open Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 168,
   "name": "4754_1",
   "description": "System Breaker(s) Close Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 169,
   "name": "5769_1",
   "description": "EMO Shutdown",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 170,
   "name": "4756_1",
   "description": "Service Code Active",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 171,
   "name": "4758_1",
   "description": "LBS Inhibited",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 172,
   "name": "5881_1",
   "description": "Regeneration Active",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 173,
   "name": "5882_1",
   "description": "Regeneration Operation Terminated",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 174,
   "name": "5883_1",
   "description": "Regeneration Operation Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 175,
   "name": "4760_1",
   "description": "Controls Reset Required",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 176,
   "name": "5561_1",
   "description": "LBS Active - Master",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 177,
   "name": "5562_1",
   "description": "LBS Active - Slave",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 178,
   "name": "5788_1",
   "description": "Cont Tie Active",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 179,
   "name": "6080_1",
   "description": "UPSC Communication Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 180,
   "name": "6066_1",
   "description": "Parallel Cable Failure",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 181,
   "name": "7467_1",
   "description": "Thermal Margin Warning",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 191,
   "name": "4823_1",
   "description": "Parallel Comm Warning",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 192,
   "name": "4825_1",
   "description": "Loss of Redundancy",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 193,
   "name": "4827_1",
   "description": "MMS Transfer Inhibit",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 194,
   "name": "4828_1",
   "description": "MMS Retransfer Inhibit",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 195,
   "name": "4831_1",
   "description": "MMS Overload",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 196,
   "name": "4834_1",
   "description": "MMS On Battery",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 197,
   "name": "4835_1",
   "description": "MMS Low Battery Warning",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 198,
   "name": "5145_1",
   "description": "MMS Module Alarm Active",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 199,
   "name": "6220_1",
   "description": "Module Output Breaker Open",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 209,
   "name": "5453_1",
   "description": "Module In Standby - Intelligent Paralleling",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 220,
   "name": "5456_1",
   "description": "ECO Mode Active",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 221,
   "name": "5457_1",
   "description": "ECO Mode Suspended",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 222,
   "name": "5458_1",
   "description": "Excess ECO Suspends",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 233,
   "name": "4726_1",
   "description": "Service Required",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 251,
   "name": "6216_1",
   "description": "Precharge Circuit Failed",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "4097_1",
   "description": "System Input RMS A-B",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "4099_1",
   "description": "System Input RMS B-C",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "4101_1",
   "description": "System Input RMS C-A",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "4113_1",
   "description": "System Input RMS Current Phase A",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "4114_1",
   "description": "System Input RMS Current Phase B",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "4115_1",
   "description": "System Input RMS Current Phase C",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "4105_1",
   "description": "System Input Frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "4125_1",
   "description": "Bypass Input Voltage RMS A-B",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "4126_1",
   "description": "Bypass Input Voltage RMS B-C",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "4127_1",
   "description": "Bypass Input Voltage RMS C-A",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "4131_1",
   "description": "Bypass Input Frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "4136_1",
   "description": "Bypass Sync Phase Difference",
   "units": "deg",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "4157_1",
   "description": "Bypass SS Overload Time Remain",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "5980_1",
   "description": "Manual Transfer Bypass Voltage High Limit",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "5981_1",
   "description": "Manual Transfer Bypass Voltage Low Limit",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "4738_1",
   "description": "Auto Retransfer Time Remaining",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "4152_1",
   "description": "Battery Total Discharge Time",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "4153_1",
   "description": "Battery Percentage Charge",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "4155_1_1",
   "description": "Battery Volts for Cabinet 1",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "4155_1_2",
   "description": "Battery Volts for Cabinet 2",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "4155_1_3",
   "description": "Battery Volts for Cabinet 3",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "4155_1_4",
   "description": "Battery Volts for Cabinet 4",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "4155_1_5",
   "description": "Battery Volts for Cabinet 5",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "4155_1_6",
   "description": "Battery Volts for Cabinet 6",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "4155_1_7",
   "description": "Battery Volts for Cabinet 7",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "4155_1_8",
   "description": "Battery Volts for Cabinet 8",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "4156_1_1",
   "description": "Battery Temperature for Cabinet 1",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10047,
   "name": "4156_1_1_deg_F",
   "description": "Battery Temperature for Cabinet 1",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "4156_1_2",
   "description": "Battery Temperature for Cabinet 2",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10048,
   "name": "4156_1_2_deg_F",
   "description": "Battery Temperature for Cabinet 2",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "4156_1_3",
   "description": "Battery Temperature for Cabinet 3",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10049,
   "name": "4156_1_3_deg_F",
   "description": "Battery Temperature for Cabinet 3",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "4156_1_4",
   "description": "Battery Temperature for Cabinet 4",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10050,
   "name": "4156_1_4_deg_F",
   "description": "Battery Temperature for Cabinet 4",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "4156_1_5",
   "description": "Battery Temperature for Cabinet 5",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10051,
   "name": "4156_1_5_deg_F",
   "description": "Battery Temperature for Cabinet 5",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "4156_1_6",
   "description": "Battery Temperature for Cabinet 6",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10052,
   "name": "4156_1_6_deg_F",
   "description": "Battery Temperature for Cabinet 6",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "4156_1_7",
   "description": "Battery Temperature for Cabinet 7",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10053,
   "name": "4156_1_7_deg_F",
   "description": "Battery Temperature for Cabinet 7",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "4156_1_8",
   "description": "Battery Temperature for Cabinet 8",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10054,
   "name": "4156_1_8_deg_F",
   "description": "Battery Temperature for Cabinet 8",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "5987_1",
   "description": "Battery Recharge Voltage",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "5988_1",
   "description": "Battery Float Voltage",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "4739_1",
   "description": "Battery Amp-Hours Consumed This Discharge",
   "units": "AH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "4150_1",
   "description": "Battery Time Remaining",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "4151_1",
   "description": "Battery Discharge Time",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "4159_1",
   "description": "Battery Discharge Power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "4160_1",
   "description": "Battery Commission Date",
   "units": "Secs since Epoch(UTC)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "5989_1",
   "description": "Battery Equalize Voltage",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "5990_1",
   "description": "Battery Equalize Time",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "5991_1",
   "description": "Battery Self Test Cycle Time",
   "units": "week(s)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "5992_1",
   "description": "Battery Self Test Time of Test",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "5993_1",
   "description": "Battery Self Test Start Date",
   "units": "Secs since Epoch(UTC)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "5994_1",
   "description": "Battery Self Test Duration",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "5995_1",
   "description": "Battery Self Test Minimum Voltage",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "5802_1",
   "description": "Low Battery Warning Time",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "5996_1",
   "description": "Battery Over Temp Warn Setting",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10070,
   "name": "5996_1_deg_F",
   "description": "Battery Over Temp Warn Setting",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "5997_1",
   "description": "Battery Over Temp Limit Setting",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10071,
   "name": "5997_1_deg_F",
   "description": "Battery Over Temp Limit Setting",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "6000_1",
   "description": "Battery Cell Count Adjust",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "6001_1",
   "description": "Battery Cell Count",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "4148_1",
   "description": "DC Bus Voltage",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "4149_1",
   "description": "DC Bus Current",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 96,
   "name": "4201_1",
   "description": "System Output Voltage RMS A-B",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 97,
   "name": "4202_1",
   "description": "System Output Voltage RMS B-C",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 98,
   "name": "4203_1",
   "description": "System Output Voltage RMS C-A",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 99,
   "name": "4204_1",
   "description": "System Output RMS Current Phs A",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 100,
   "name": "4205_1",
   "description": "System Output RMS Current Phs B",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 101,
   "name": "4206_1",
   "description": "System Output RMS Current Phs C",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 102,
   "name": "4207_1",
   "description": "System Output Frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "4208_1",
   "description": "System Output Power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 104,
   "name": "4209_1",
   "description": "System Output Apparent Power",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 105,
   "name": "4210_1",
   "description": "System Output Power Factor Phs A",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 106,
   "name": "4211_1",
   "description": "System Output Power Factor Phs B",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 107,
   "name": "4212_1",
   "description": "System Output Power Factor Phs C",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 108,
   "name": "4223_1",
   "description": "System Output Pct Power Phase A",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 109,
   "name": "4224_1",
   "description": "System Output Pct Power Phase B",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 110,
   "name": "4225_1",
   "description": "System Output Pct Power Phase C",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 111,
   "name": "4226_1",
   "description": "System Output Pct Pwr (VA) Phs A",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 112,
   "name": "4227_1",
   "description": "System Output Pct Pwr (VA) Phs B",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 113,
   "name": "4228_1",
   "description": "System Output Pct Pwr (VA) Phs C",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 124,
   "name": "4232_1",
   "description": "Inverter Overload Time Remaining",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 125,
   "name": "6005_1",
   "description": "Maximum Load Exceeded Phase A",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 126,
   "name": "6006_1",
   "description": "Maximum Load Exceeded Phase B",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 127,
   "name": "6007_1",
   "description": "Maximum Load Exceeded Phase C",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 128,
   "name": "6008_1",
   "description": "Maximum Load Exceeded Delay",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 139,
   "name": "6010_1",
   "description": "Inlet Air Warning Setting",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10139,
   "name": "6010_1_deg_F",
   "description": "Inlet Air Warning Setting",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 140,
   "name": "4291_1",
   "description": "Inlet Air Temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10140,
   "name": "4291_1_deg_F",
   "description": "Inlet Air Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 141,
   "name": "4292_1",
   "description": "Total System Operating Time",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 142,
   "name": "4293_1",
   "description": "System Date and Time",
   "units": "Secs since Epoch(UTC)",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 143,
   "name": "5446_1",
   "description": "Total kW Hours Saved",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 154,
   "name": "6013_1",
   "description": "Delay for Input Contact 01",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 155,
   "name": "6014_1",
   "description": "Delay for Input Contact 02",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 156,
   "name": "6015_1",
   "description": "Delay for Input Contact 03",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 157,
   "name": "6016_1",
   "description": "Delay for Input Contact 04",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 158,
   "name": "6017_1",
   "description": "Delay for Input Contact 05",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 159,
   "name": "6018_1",
   "description": "Delay for Input Contact 06",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 160,
   "name": "6019_1",
   "description": "Delay for Input Contact 07",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 161,
   "name": "6020_1",
   "description": "Delay for Input Contact 08",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 162,
   "name": "6021_1",
   "description": "Delay for Input Contact 09",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 163,
   "name": "6022_1",
   "description": "Delay for Input Contact 10",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 164,
   "name": "6023_1",
   "description": "Delay for Input Contact 11",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 165,
   "name": "6024_1",
   "description": "Delay for Input Contact 12",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 166,
   "name": "6025_1",
   "description": "Delay for Input Contact 13",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 167,
   "name": "6026_1",
   "description": "Delay for Input Contact 14",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 168,
   "name": "6027_1",
   "description": "Delay for Input Contact 15",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 169,
   "name": "6028_1",
   "description": "Delay for Input Contact 16",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 180,
   "name": "6075_1",
   "description": "PRB Relay Trigger Event # 1 (External Output Signals 1)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 181,
   "name": "6076_1",
   "description": "PRB Relay Trigger Event # 2 (External Output Signals 1)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 182,
   "name": "6077_1",
   "description": "PRB Relay Trigger Event # 3 (External Output Signals 1)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 183,
   "name": "6078_1",
   "description": "PRB Relay Trigger Event # 4 (External Output Signals 1)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 184,
   "name": "6079_1",
   "description": "PRB Delay (External Output Signals 1)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 195,
   "name": "6075_2",
   "description": "PRB Relay Trigger Event # 1 (External Output Signals 2)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 196,
   "name": "6076_2",
   "description": "PRB Relay Trigger Event # 2 (External Output Signals 2)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 197,
   "name": "6077_2",
   "description": "PRB Relay Trigger Event # 3 (External Output Signals 2)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 198,
   "name": "6078_2",
   "description": "PRB Relay Trigger Event # 4 (External Output Signals 2)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 199,
   "name": "6079_2",
   "description": "PRB Delay (External Output Signals 2)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 210,
   "name": "6075_3",
   "description": "PRB Relay Trigger Event # 1 (External Output Signals 3)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 211,
   "name": "6076_3",
   "description": "PRB Relay Trigger Event # 2 (External Output Signals 3)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 212,
   "name": "6077_3",
   "description": "PRB Relay Trigger Event # 3 (External Output Signals 3)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 213,
   "name": "6078_3",
   "description": "PRB Relay Trigger Event # 4 (External Output Signals 3)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 214,
   "name": "6079_3",
   "description": "PRB Delay (External Output Signals 3)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 225,
   "name": "6075_4",
   "description": "PRB Relay Trigger Event # 1 (External Output Signals 4)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 226,
   "name": "6076_4",
   "description": "PRB Relay Trigger Event # 2 (External Output Signals 4)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 227,
   "name": "6077_4",
   "description": "PRB Relay Trigger Event # 3 (External Output Signals 4)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 228,
   "name": "6078_4",
   "description": "PRB Relay Trigger Event # 4 (External Output Signals 4)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 229,
   "name": "6079_4",
   "description": "PRB Delay (External Output Signals 4)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 240,
   "name": "6075_5",
   "description": "PRB Relay Trigger Event # 1 (External Output Signals 5)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 241,
   "name": "6076_5",
   "description": "PRB Relay Trigger Event # 2 (External Output Signals 5)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 242,
   "name": "6077_5",
   "description": "PRB Relay Trigger Event # 3 (External Output Signals 5)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 243,
   "name": "6078_5",
   "description": "PRB Relay Trigger Event # 4 (External Output Signals 5)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 244,
   "name": "6079_5",
   "description": "PRB Delay (External Output Signals 5)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 255,
   "name": "6075_6",
   "description": "PRB Relay Trigger Event # 1 (External Output Signals 6)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 256,
   "name": "6076_6",
   "description": "PRB Relay Trigger Event # 2 (External Output Signals 6)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 257,
   "name": "6077_6",
   "description": "PRB Relay Trigger Event # 3 (External Output Signals 6)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 258,
   "name": "6078_6",
   "description": "PRB Relay Trigger Event # 4 (External Output Signals 6)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 259,
   "name": "6079_6",
   "description": "PRB Delay (External Output Signals 6)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 270,
   "name": "6075_7",
   "description": "PRB Relay Trigger Event # 1 (External Output Signals 7)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 271,
   "name": "6076_7",
   "description": "PRB Relay Trigger Event # 2 (External Output Signals 7)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 272,
   "name": "6077_7",
   "description": "PRB Relay Trigger Event # 3 (External Output Signals 7)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 273,
   "name": "6078_7",
   "description": "PRB Relay Trigger Event # 4 (External Output Signals 7)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 274,
   "name": "6079_7",
   "description": "PRB Delay (External Output Signals 7)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 285,
   "name": "6075_8",
   "description": "PRB Relay Trigger Event # 1 (External Output Signals 8)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 286,
   "name": "6076_8",
   "description": "PRB Relay Trigger Event # 2 (External Output Signals 8)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 287,
   "name": "6077_8",
   "description": "PRB Relay Trigger Event # 3 (External Output Signals 8)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 288,
   "name": "6078_8",
   "description": "PRB Relay Trigger Event # 4 (External Output Signals 8)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 289,
   "name": "6079_8",
   "description": "PRB Delay (External Output Signals 8)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 300,
   "name": "6075_9",
   "description": "PRB Relay Trigger Event # 1 (External Output Signals 9)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 301,
   "name": "6076_9",
   "description": "PRB Relay Trigger Event # 2 (External Output Signals 9)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 302,
   "name": "6077_9",
   "description": "PRB Relay Trigger Event # 3 (External Output Signals 9)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 303,
   "name": "6078_9",
   "description": "PRB Relay Trigger Event # 4 (External Output Signals 9)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 304,
   "name": "6079_9",
   "description": "PRB Delay (External Output Signals 9)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 315,
   "name": "6075_10",
   "description": "PRB Relay Trigger Event # 1 (External Output Signals 10)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 316,
   "name": "6076_10",
   "description": "PRB Relay Trigger Event # 2 (External Output Signals 10)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 317,
   "name": "6077_10",
   "description": "PRB Relay Trigger Event # 3 (External Output Signals 10)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 318,
   "name": "6078_10",
   "description": "PRB Relay Trigger Event # 4 (External Output Signals 10)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 319,
   "name": "6079_10",
   "description": "PRB Delay (External Output Signals 10)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 330,
   "name": "6075_11",
   "description": "PRB Relay Trigger Event # 1 (External Output Signals 11)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 331,
   "name": "6076_11",
   "description": "PRB Relay Trigger Event # 2 (External Output Signals 11)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 332,
   "name": "6077_11",
   "description": "PRB Relay Trigger Event # 3 (External Output Signals 11)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 333,
   "name": "6078_11",
   "description": "PRB Relay Trigger Event # 4 (External Output Signals 11)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 334,
   "name": "6079_11",
   "description": "PRB Delay (External Output Signals 11)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 345,
   "name": "6075_12",
   "description": "PRB Relay Trigger Event # 1 (External Output Signals 12)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 346,
   "name": "6076_12",
   "description": "PRB Relay Trigger Event # 2 (External Output Signals 12)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 347,
   "name": "6077_12",
   "description": "PRB Relay Trigger Event # 3 (External Output Signals 12)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 348,
   "name": "6078_12",
   "description": "PRB Relay Trigger Event # 4 (External Output Signals 12)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 349,
   "name": "6079_12",
   "description": "PRB Delay (External Output Signals 12)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 360,
   "name": "6075_13",
   "description": "PRB Relay Trigger Event # 1 (External Output Signals 13)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 361,
   "name": "6076_13",
   "description": "PRB Relay Trigger Event # 2 (External Output Signals 13)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 362,
   "name": "6077_13",
   "description": "PRB Relay Trigger Event # 3 (External Output Signals 13)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 363,
   "name": "6078_13",
   "description": "PRB Relay Trigger Event # 4 (External Output Signals 13)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 364,
   "name": "6079_13",
   "description": "PRB Delay (External Output Signals 13)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 375,
   "name": "6075_14",
   "description": "PRB Relay Trigger Event # 1 (External Output Signals 14)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 376,
   "name": "6076_14",
   "description": "PRB Relay Trigger Event # 2 (External Output Signals 14)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 377,
   "name": "6077_14",
   "description": "PRB Relay Trigger Event # 3 (External Output Signals 14)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 378,
   "name": "6078_14",
   "description": "PRB Relay Trigger Event # 4 (External Output Signals 14)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 379,
   "name": "6079_14",
   "description": "PRB Delay (External Output Signals 14)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 390,
   "name": "6075_15",
   "description": "PRB Relay Trigger Event # 1 (External Output Signals 15)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 391,
   "name": "6076_15",
   "description": "PRB Relay Trigger Event # 2 (External Output Signals 15)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 392,
   "name": "6077_15",
   "description": "PRB Relay Trigger Event # 3 (External Output Signals 15)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 393,
   "name": "6078_15",
   "description": "PRB Relay Trigger Event # 4 (External Output Signals 15)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 394,
   "name": "6079_15",
   "description": "PRB Delay (External Output Signals 15)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 405,
   "name": "6075_16",
   "description": "PRB Relay Trigger Event # 1 (External Output Signals 16)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 406,
   "name": "6076_16",
   "description": "PRB Relay Trigger Event # 2 (External Output Signals 16)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 407,
   "name": "6077_16",
   "description": "PRB Relay Trigger Event # 3 (External Output Signals 16)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 408,
   "name": "6078_16",
   "description": "PRB Relay Trigger Event # 4 (External Output Signals 16)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 409,
   "name": "6079_16",
   "description": "PRB Delay (External Output Signals 16)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 420,
   "name": "5789_1",
   "description": "System Accumulated Energy",
   "units": "kWh",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 421,
   "name": "5790_1",
   "description": "Module Accumulated Energy",
   "units": "kWh",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 422,
   "name": "5791_1",
   "description": "Output kWh Reset Timestamp",
   "units": "Secs since Epoch(UTC)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 423,
   "name": "5793_1",
   "description": "Output Peak kW Demand",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 424,
   "name": "5794_1",
   "description": "Output Peak kW Demand Hist",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 425,
   "name": "5797_1",
   "description": "Peak kW Demand Timestamp",
   "units": "Secs since Epoch(UTC)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 426,
   "name": "6048_1",
   "description": "Regeneration Time Remaining",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 437,
   "name": "4259_1",
   "description": "Bypass Nominal Voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 438,
   "name": "4102_1",
   "description": "System Input Nominal Voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 439,
   "name": "4103_1",
   "description": "System Input Nominal Frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 440,
   "name": "4260_1",
   "description": "System Output Nominal Voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 441,
   "name": "4261_1",
   "description": "System Output Nominal Frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 442,
   "name": "4262_1",
   "description": "Battery Cell Count - Lead Acid",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 443,
   "name": "4264_1",
   "description": "Output Apparent Power Rating",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 444,
   "name": "4265_1",
   "description": "Output Real Power Rating",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 445,
   "name": "4800_1",
   "description": "System UPS Module Count",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 446,
   "name": "4267_1",
   "description": "System Output Maximum Amp Rating",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 457,
   "name": "4801_1",
   "description": "Multi-module System Output Voltage RMS A-B",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 458,
   "name": "4802_1",
   "description": "Multi-module System Output Voltage RMS B-C",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 459,
   "name": "4803_1",
   "description": "Multi-module System Output Voltage RMS C-A",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 460,
   "name": "4804_1",
   "description": "Multi-module System Output Voltage RMS A-N",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 461,
   "name": "4805_1",
   "description": "Multi-module System Output Voltage RMS B-N",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 462,
   "name": "4806_1",
   "description": "Multi-module System Output Voltage RMS C-N",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 463,
   "name": "4807_1",
   "description": "Sum of MMS Output RMS Currents for Phase A",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 464,
   "name": "4808_1",
   "description": "Sum of MMS Output RMS Currents for Phase B",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 465,
   "name": "4809_1",
   "description": "Sum of MMS Output RMS Currents for Phase C",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 466,
   "name": "4810_1",
   "description": "MMS Output Frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 467,
   "name": "4811_1",
   "description": "MMS Output Power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 468,
   "name": "4812_1",
   "description": "MMS Output Apparent Power",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 469,
   "name": "4813_1",
   "description": "MMS Output Power Factor Phase A",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 470,
   "name": "4814_1",
   "description": "MMS Output Power Factor Phase B",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 471,
   "name": "4815_1",
   "description": "MMS Output Power Factor Phase C",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 472,
   "name": "4816_1",
   "description": "MMS Output Pct Power Phase A",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 473,
   "name": "4817_1",
   "description": "MMS Output Pct Power Phase B",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 474,
   "name": "4818_1",
   "description": "MMS Output Pct Power Phase C",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 475,
   "name": "4819_1",
   "description": "MMS Output Pct Apparent Pwr (kVA) Phase A",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 476,
   "name": "4820_1",
   "description": "MMS Output Pct Apparent Pwr (kVA) Phase B",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 477,
   "name": "4821_1",
   "description": "MMS Output Pct Apparent Pwr (kVA) Phase C",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 478,
   "name": "4822_1",
   "description": "Number of Redundant Modules",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 479,
   "name": "4829_1",
   "description": "MMS Module Number",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 480,
   "name": "4833_1",
   "description": "Number of Modules in a MMS",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 491,
   "name": "4861_1",
   "description": "MMS Module Total kW Output (ModuleList 1)",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 492,
   "name": "4862_1",
   "description": "MMS Module Total kVA Output (ModuleList 1)",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 493,
   "name": "4863_1",
   "description": "MMS Module DC Bus Voltage (ModuleList 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 494,
   "name": "4864_1",
   "description": "MMS Module Battery Current (ModuleList 1)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 495,
   "name": "4865_1",
   "description": "MMS Module Battery Time Remaining (ModuleList 1)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 506,
   "name": "4861_2",
   "description": "MMS Module Total kW Output (ModuleList 2)",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 507,
   "name": "4862_2",
   "description": "MMS Module Total kVA Output (ModuleList 2)",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 508,
   "name": "4863_2",
   "description": "MMS Module DC Bus Voltage (ModuleList 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 509,
   "name": "4864_2",
   "description": "MMS Module Battery Current (ModuleList 2)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 510,
   "name": "4865_2",
   "description": "MMS Module Battery Time Remaining (ModuleList 2)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 521,
   "name": "4861_3",
   "description": "MMS Module Total kW Output (ModuleList 3)",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 522,
   "name": "4862_3",
   "description": "MMS Module Total kVA Output (ModuleList 3)",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 523,
   "name": "4863_3",
   "description": "MMS Module DC Bus Voltage (ModuleList 3)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 524,
   "name": "4864_3",
   "description": "MMS Module Battery Current (ModuleList 3)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 525,
   "name": "4865_3",
   "description": "MMS Module Battery Time Remaining (ModuleList 3)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 536,
   "name": "4861_4",
   "description": "MMS Module Total kW Output (ModuleList 4)",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 537,
   "name": "4862_4",
   "description": "MMS Module Total kVA Output (ModuleList 4)",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 538,
   "name": "4863_4",
   "description": "MMS Module DC Bus Voltage (ModuleList 4)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 539,
   "name": "4864_4",
   "description": "MMS Module Battery Current (ModuleList 4)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 540,
   "name": "4865_4",
   "description": "MMS Module Battery Time Remaining (ModuleList 4)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 551,
   "name": "4861_5",
   "description": "MMS Module Total kW Output (ModuleList 5)",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 552,
   "name": "4862_5",
   "description": "MMS Module Total kVA Output (ModuleList 5)",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 553,
   "name": "4863_5",
   "description": "MMS Module DC Bus Voltage (ModuleList 5)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 554,
   "name": "4864_5",
   "description": "MMS Module Battery Current (ModuleList 5)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 555,
   "name": "4865_5",
   "description": "MMS Module Battery Time Remaining (ModuleList 5)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 566,
   "name": "4861_6",
   "description": "MMS Module Total kW Output (ModuleList 6)",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 567,
   "name": "4862_6",
   "description": "MMS Module Total kVA Output (ModuleList 6)",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 568,
   "name": "4863_6",
   "description": "MMS Module DC Bus Voltage (ModuleList 6)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 569,
   "name": "4864_6",
   "description": "MMS Module Battery Current (ModuleList 6)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 570,
   "name": "4865_6",
   "description": "MMS Module Battery Time Remaining (ModuleList 6)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 581,
   "name": "4861_7",
   "description": "MMS Module Total kW Output (ModuleList 7)",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 582,
   "name": "4862_7",
   "description": "MMS Module Total kVA Output (ModuleList 7)",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 583,
   "name": "4863_7",
   "description": "MMS Module DC Bus Voltage (ModuleList 7)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 584,
   "name": "4864_7",
   "description": "MMS Module Battery Current (ModuleList 7)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 585,
   "name": "4865_7",
   "description": "MMS Module Battery Time Remaining (ModuleList 7)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 596,
   "name": "4861_8",
   "description": "MMS Module Total kW Output (ModuleList 8)",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 597,
   "name": "4862_8",
   "description": "MMS Module Total kVA Output (ModuleList 8)",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 598,
   "name": "4863_8",
   "description": "MMS Module DC Bus Voltage (ModuleList 8)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 599,
   "name": "4864_8",
   "description": "MMS Module Battery Current (ModuleList 8)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 600,
   "name": "4865_8",
   "description": "MMS Module Battery Time Remaining (ModuleList 8)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 611,
   "name": "5450_1",
   "description": "Intelligent Paralleling Shutdown Delay",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 612,
   "name": "5451_1",
   "description": "Intelligent Parallel Minimum Redundancy",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 613,
   "name": "5452_1",
   "description": "Intelligent Parallel Maximum Time in Standby",
   "units": "day",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 624,
   "name": "5459_1",
   "description": "Maximum Auto Suspensions - ECO Mode",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 625,
   "name": "5460_1",
   "description": "Restart Delay - ECO Mode",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 626,
   "name": "5466_1",
   "description": "Time Remaining - ECO Mode",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 637,
   "name": "5464_1_1",
   "description": "Schedule Hour - ECO Mode (EcoModeSchedule 1)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 638,
   "name": "5465_1_1",
   "description": "Schedule Minute - ECO Mode (EcoModeSchedule 1)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 649,
   "name": "5464_1_2",
   "description": "Schedule Hour - ECO Mode (EcoModeSchedule 2)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 650,
   "name": "5465_1_2",
   "description": "Schedule Minute - ECO Mode (EcoModeSchedule 2)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 661,
   "name": "5464_1_3",
   "description": "Schedule Hour - ECO Mode (EcoModeSchedule 3)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 662,
   "name": "5465_1_3",
   "description": "Schedule Minute - ECO Mode (EcoModeSchedule 3)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 673,
   "name": "5464_1_4",
   "description": "Schedule Hour - ECO Mode (EcoModeSchedule 4)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 674,
   "name": "5465_1_4",
   "description": "Schedule Minute - ECO Mode (EcoModeSchedule 4)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 685,
   "name": "5464_1_5",
   "description": "Schedule Hour - ECO Mode (EcoModeSchedule 5)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 686,
   "name": "5465_1_5",
   "description": "Schedule Minute - ECO Mode (EcoModeSchedule 5)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 697,
   "name": "5464_1_6",
   "description": "Schedule Hour - ECO Mode (EcoModeSchedule 6)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 698,
   "name": "5465_1_6",
   "description": "Schedule Minute - ECO Mode (EcoModeSchedule 6)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 709,
   "name": "5464_1_7",
   "description": "Schedule Hour - ECO Mode (EcoModeSchedule 7)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 710,
   "name": "5465_1_7",
   "description": "Schedule Minute - ECO Mode (EcoModeSchedule 7)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 721,
   "name": "5464_1_8",
   "description": "Schedule Hour - ECO Mode (EcoModeSchedule 8)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 722,
   "name": "5465_1_8",
   "description": "Schedule Minute - ECO Mode (EcoModeSchedule 8)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 733,
   "name": "5464_1_9",
   "description": "Schedule Hour - ECO Mode (EcoModeSchedule 9)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 734,
   "name": "5465_1_9",
   "description": "Schedule Minute - ECO Mode (EcoModeSchedule 9)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 745,
   "name": "5464_1_10",
   "description": "Schedule Hour - ECO Mode (EcoModeSchedule 10)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 746,
   "name": "5465_1_10",
   "description": "Schedule Minute - ECO Mode (EcoModeSchedule 10)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 757,
   "name": "5464_1_11",
   "description": "Schedule Hour - ECO Mode (EcoModeSchedule 11)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 758,
   "name": "5465_1_11",
   "description": "Schedule Minute - ECO Mode (EcoModeSchedule 11)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 769,
   "name": "5464_1_12",
   "description": "Schedule Hour - ECO Mode (EcoModeSchedule 12)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 770,
   "name": "5465_1_12",
   "description": "Schedule Minute - ECO Mode (EcoModeSchedule 12)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 781,
   "name": "5464_1_13",
   "description": "Schedule Hour - ECO Mode (EcoModeSchedule 13)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 782,
   "name": "5465_1_13",
   "description": "Schedule Minute - ECO Mode (EcoModeSchedule 13)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 793,
   "name": "5464_1_14",
   "description": "Schedule Hour - ECO Mode (EcoModeSchedule 14)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 794,
   "name": "5465_1_14",
   "description": "Schedule Minute - ECO Mode (EcoModeSchedule 14)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 805,
   "name": "5464_1_15",
   "description": "Schedule Hour - ECO Mode (EcoModeSchedule 15)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 806,
   "name": "5465_1_15",
   "description": "Schedule Minute - ECO Mode (EcoModeSchedule 15)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 817,
   "name": "5464_1_16",
   "description": "Schedule Hour - ECO Mode (EcoModeSchedule 16)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 818,
   "name": "5465_1_16",
   "description": "Schedule Minute - ECO Mode (EcoModeSchedule 16)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "4735_1",
   "description": "Input Qualification Status",
   "units": "",
   "access": "R",
   "states": "1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "5979_1",
   "description": "Input Breaker Operation",
   "units": "",
   "access": "R",
   "states": "1=Manual, 2=Elec Op"
  },
  {
   "type": "MV",
   "instance": 13,
   "name": "4736_1",
   "description": "Static Bypass Switch",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 14,
   "name": "4737_1",
   "description": "Bypass Qualification Status",
   "units": "",
   "access": "R",
   "states": "1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High"
  },
  {
   "type": "MV",
   "instance": 25,
   "name": "5986_1",
   "description": "Battery Recharge Method",
   "units": "",
   "access": "R",
   "states": "1=Constant Voltage, 2=Two Step Constant Voltage"
  },
  {
   "type": "MV",
   "instance": 26,
   "name": "5803_1",
   "description": "Automatic Battery Test",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 27,
   "name": "5999_1",
   "description": "Battery Disconnect Setting",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 28,
   "name": "6002_1",
   "description": "Battery Breaker Operation",
   "units": "",
   "access": "R",
   "states": "1=Manual, 2=Elec Op"
  },
  {
   "type": "MV",
   "instance": 39,
   "name": "4743_1",
   "description": "DC Bus Qualification Status",
   "units": "",
   "access": "R",
   "states": "1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High"
  },
  {
   "type": "MV",
   "instance": 40,
   "name": "6003_1",
   "description": "DC Converter Status",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 51,
   "name": "4744_1",
   "description": "Output Qualification Status",
   "units": "",
   "access": "R",
   "states": "1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High"
  },
  {
   "type": "MV",
   "instance": 52,
   "name": "6004_1",
   "description": "Output Breaker Operation",
   "units": "",
   "access": "R",
   "states": "1=Manual, 2=Elec Op"
  },
  {
   "type": "MV",
   "instance": 63,
   "name": "4745_1",
   "description": "Inverter Output Qualification Status",
   "units": "",
   "access": "R",
   "states": "1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High"
  },
  {
   "type": "MV",
   "instance": 64,
   "name": "4746_1",
   "description": "Inverter On/Off State",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 91,
   "name": "6073_1",
   "description": "Include Input Contact Interface 1 Alarms In Summary",
   "units": "",
   "access": "R",
   "states": "1=Not Included, 2=Included"
  },
  {
   "type": "MV",
   "instance": 92,
   "name": "6074_1",
   "description": "Include Input Contact Interface 2 Alarms In Summary",
   "units": "",
   "access": "R",
   "states": "1=Not Included, 2=Included"
  },
  {
   "type": "MV",
   "instance": 103,
   "name": "4748_1",
   "description": "Rectifier Status",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 114,
   "name": "4303_1",
   "description": "UPS Module Type",
   "units": "",
   "access": "R",
   "states": "1=Single Module System, 2=Module (1 + 1), 3=Module (1 + N), 4=Module (N + 1), 5=System Control Cabinet, 6=Main Static Switch"
  },
  {
   "type": "MV",
   "instance": 115,
   "name": "4752_1",
   "description": "UPS System Output Source",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=Normal, 3=Bypass, 4=Maintenance Bypass"
  },
  {
   "type": "MV",
   "instance": 116,
   "name": "4318_1",
   "description": "System Input Power Source",
   "units": "",
   "access": "R",
   "states": "1=None, 2=Utility (mains), 3=Generator"
  },
  {
   "type": "MV",
   "instance": 117,
   "name": "4123_1",
   "description": "System Status",
   "units": "",
   "access": "R",
   "states": "1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation"
  },
  {
   "type": "MV",
   "instance": 118,
   "name": "4872_1",
   "description": "UPS Output Source",
   "units": "",
   "access": "R",
   "states": "1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer"
  },
  {
   "type": "MV",
   "instance": 119,
   "name": "5795_1",
   "description": "Peak kW Demand Period",
   "units": "",
   "access": "R",
   "states": "1=Hourly, 2=Daily, 3=Weekly, 4=Monthly, 5=Yearly"
  },
  {
   "type": "MV",
   "instance": 130,
   "name": "4764_1",
   "description": "Backfeed Breaker",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 131,
   "name": "4766_1",
   "description": "Input Breaker (CB1/RIB)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 132,
   "name": "4768_1",
   "description": "Output Breaker (CB2/IOB)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 133,
   "name": "4770_1",
   "description": "Bypass Isolation Breaker",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 134,
   "name": "4771_1",
   "description": "Rectifier Feed Breaker (RFB)",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 135,
   "name": "4772_1",
   "description": "Maintenance Bypass Breaker",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 136,
   "name": "4773_1",
   "description": "Maintenance Isolation Breaker",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 137,
   "name": "6051_1",
   "description": "Precharge Contactor",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 148,
   "name": "4836_1",
   "description": "Module Output Breaker for Module 1",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 149,
   "name": "4837_1",
   "description": "Module Output Breaker for Module 2",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 150,
   "name": "4838_1",
   "description": "Module Output Breaker for Module 3",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 151,
   "name": "4839_1",
   "description": "Module Output Breaker for Module 4",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 152,
   "name": "4840_1",
   "description": "Module Output Breaker for Module 5",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 153,
   "name": "4841_1",
   "description": "Module Output Breaker for Module 6",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 154,
   "name": "4842_1",
   "description": "Module Output Breaker for Module 7",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 155,
   "name": "4843_1",
   "description": "Module Output Breaker for Module 8",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 156,
   "name": "4844_1",
   "description": "Bypass Isolation Breaker for Module 1",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 157,
   "name": "4845_1",
   "description": "Bypass Isolation Breaker for Module 2",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 158,
   "name": "4846_1",
   "description": "Bypass Isolation Breaker for Module 3",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 159,
   "name": "4847_1",
   "description": "Bypass Isolation Breaker for Module 4",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 160,
   "name": "4848_1",
   "description": "Bypass Isolation Breaker for Module 5",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 161,
   "name": "4849_1",
   "description": "Bypass Isolation Breaker for Module 6",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 162,
   "name": "4850_1",
   "description": "Bypass Isolation Breaker for Module 7",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 163,
   "name": "4851_1",
   "description": "Bypass Isolation Breaker for Module 8",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 164,
   "name": "4852_1",
   "description": "System Output Breaker",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 165,
   "name": "4853_1",
   "description": "System Load Bank Breaker",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 166,
   "name": "4854_1",
   "description": "System Isolation Output Breaker",
   "units": "",
   "access": "R",
   "states": "1=Open, 2=Close, 3=Not Installed"
  },
  {
   "type": "MV",
   "instance": 167,
   "name": "4855_1",
   "description": "SCC Event Summary",
   "units": "",
   "access": "R",
   "states": "1=None, 2=Alarm, 3=Fault"
  },
  {
   "type": "MV",
   "instance": 168,
   "name": "4873_1",
   "description": "MMS UPS Battery Status",
   "units": "",
   "access": "R",
   "states": "1=Unknown, 2=Normal, 3=Low, 4=Depleted"
  },
  {
   "type": "MV",
   "instance": 169,
   "name": "4874_1",
   "description": "MMS UPS Output Source",
   "units": "",
   "access": "R",
   "states": "1=Other, 2=Off, 3=Normal, 4=Bypass, 5=Battery, 6=Booster, 7=Reducer"
  },
  {
   "type": "MV",
   "instance": 180,
   "name": "4856_1",
   "description": "MMS Inter-Module Comm Status (ModuleList 1)",
   "units": "",
   "access": "R",
   "states": "1=Failed, 2=Normal"
  },
  {
   "type": "MV",
   "instance": 181,
   "name": "4857_1",
   "description": "MMS Event Summary (ModuleList 1)",
   "units": "",
   "access": "R",
   "states": "1=None, 2=Alarm, 3=Fault"
  },
  {
   "type": "MV",
   "instance": 182,
   "name": "4858_1",
   "description": "MMS Module Inverter Status (ModuleList 1)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 183,
   "name": "4859_1",
   "description": "MMS Module Output Voltage Status (ModuleList 1)",
   "units": "",
   "access": "R",
   "states": "1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High"
  },
  {
   "type": "MV",
   "instance": 184,
   "name": "4860_1",
   "description": "MMS Module Output Source (ModuleList 1)",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=Normal, 3=Bypass, 4=Maintenance Bypass"
  },
  {
   "type": "MV",
   "instance": 195,
   "name": "4856_2",
   "description": "MMS Inter-Module Comm Status (ModuleList 2)",
   "units": "",
   "access": "R",
   "states": "1=Failed, 2=Normal"
  },
  {
   "type": "MV",
   "instance": 196,
   "name": "4857_2",
   "description": "MMS Event Summary (ModuleList 2)",
   "units": "",
   "access": "R",
   "states": "1=None, 2=Alarm, 3=Fault"
  },
  {
   "type": "MV",
   "instance": 197,
   "name": "4858_2",
   "description": "MMS Module Inverter Status (ModuleList 2)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 198,
   "name": "4859_2",
   "description": "MMS Module Output Voltage Status (ModuleList 2)",
   "units": "",
   "access": "R",
   "states": "1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High"
  },
  {
   "type": "MV",
   "instance": 199,
   "name": "4860_2",
   "description": "MMS Module Output Source (ModuleList 2)",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=Normal, 3=Bypass, 4=Maintenance Bypass"
  },
  {
   "type": "MV",
   "instance": 210,
   "name": "4856_3",
   "description": "MMS Inter-Module Comm Status (ModuleList 3)",
   "units": "",
   "access": "R",
   "states": "1=Failed, 2=Normal"
  },
  {
   "type": "MV",
   "instance": 211,
   "name": "4857_3",
   "description": "MMS Event Summary (ModuleList 3)",
   "units": "",
   "access": "R",
   "states": "1=None, 2=Alarm, 3=Fault"
  },
  {
   "type": "MV",
   "instance": 212,
   "name": "4858_3",
   "description": "MMS Module Inverter Status (ModuleList 3)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 213,
   "name": "4859_3",
   "description": "MMS Module Output Voltage Status (ModuleList 3)",
   "units": "",
   "access": "R",
   "states": "1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High"
  },
  {
   "type": "MV",
   "instance": 214,
   "name": "4860_3",
   "description": "MMS Module Output Source (ModuleList 3)",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=Normal, 3=Bypass, 4=Maintenance Bypass"
  },
  {
   "type": "MV",
   "instance": 225,
   "name": "4856_4",
   "description": "MMS Inter-Module Comm Status (ModuleList 4)",
   "units": "",
   "access": "R",
   "states": "1=Failed, 2=Normal"
  },
  {
   "type": "MV",
   "instance": 226,
   "name": "4857_4",
   "description": "MMS Event Summary (ModuleList 4)",
   "units": "",
   "access": "R",
   "states": "1=None, 2=Alarm, 3=Fault"
  },
  {
   "type": "MV",
   "instance": 227,
   "name": "4858_4",
   "description": "MMS Module Inverter Status (ModuleList 4)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 228,
   "name": "4859_4",
   "description": "MMS Module Output Voltage Status (ModuleList 4)",
   "units": "",
   "access": "R",
   "states": "1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High"
  },
  {
   "type": "MV",
   "instance": 229,
   "name": "4860_4",
   "description": "MMS Module Output Source (ModuleList 4)",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=Normal, 3=Bypass, 4=Maintenance Bypass"
  },
  {
   "type": "MV",
   "instance": 240,
   "name": "4856_5",
   "description": "MMS Inter-Module Comm Status (ModuleList 5)",
   "units": "",
   "access": "R",
   "states": "1=Failed, 2=Normal"
  },
  {
   "type": "MV",
   "instance": 241,
   "name": "4857_5",
   "description": "MMS Event Summary (ModuleList 5)",
   "units": "",
   "access": "R",
   "states": "1=None, 2=Alarm, 3=Fault"
  },
  {
   "type": "MV",
   "instance": 242,
   "name": "4858_5",
   "description": "MMS Module Inverter Status (ModuleList 5)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 243,
   "name": "4859_5",
   "description": "MMS Module Output Voltage Status (ModuleList 5)",
   "units": "",
   "access": "R",
   "states": "1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High"
  },
  {
   "type": "MV",
   "instance": 244,
   "name": "4860_5",
   "description": "MMS Module Output Source (ModuleList 5)",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=Normal, 3=Bypass, 4=Maintenance Bypass"
  },
  {
   "type": "MV",
   "instance": 255,
   "name": "4856_6",
   "description": "MMS Inter-Module Comm Status (ModuleList 6)",
   "units": "",
   "access": "R",
   "states": "1=Failed, 2=Normal"
  },
  {
   "type": "MV",
   "instance": 256,
   "name": "4857_6",
   "description": "MMS Event Summary (ModuleList 6)",
   "units": "",
   "access": "R",
   "states": "1=None, 2=Alarm, 3=Fault"
  },
  {
   "type": "MV",
   "instance": 257,
   "name": "4858_6",
   "description": "MMS Module Inverter Status (ModuleList 6)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 258,
   "name": "4859_6",
   "description": "MMS Module Output Voltage Status (ModuleList 6)",
   "units": "",
   "access": "R",
   "states": "1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High"
  },
  {
   "type": "MV",
   "instance": 259,
   "name": "4860_6",
   "description": "MMS Module Output Source (ModuleList 6)",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=Normal, 3=Bypass, 4=Maintenance Bypass"
  },
  {
   "type": "MV",
   "instance": 270,
   "name": "4856_7",
   "description": "MMS Inter-Module Comm Status (ModuleList 7)",
   "units": "",
   "access": "R",
   "states": "1=Failed, 2=Normal"
  },
  {
   "type": "MV",
   "instance": 271,
   "name": "4857_7",
   "description": "MMS Event Summary (ModuleList 7)",
   "units": "",
   "access": "R",
   "states": "1=None, 2=Alarm, 3=Fault"
  },
  {
   "type": "MV",
   "instance": 272,
   "name": "4858_7",
   "description": "MMS Module Inverter Status (ModuleList 7)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 273,
   "name": "4859_7",
   "description": "MMS Module Output Voltage Status (ModuleList 7)",
   "units": "",
   "access": "R",
   "states": "1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High"
  },
  {
   "type": "MV",
   "instance": 274,
   "name": "4860_7",
   "description": "MMS Module Output Source (ModuleList 7)",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=Normal, 3=Bypass, 4=Maintenance Bypass"
  },
  {
   "type": "MV",
   "instance": 285,
   "name": "4856_8",
   "description": "MMS Inter-Module Comm Status (ModuleList 8)",
   "units": "",
   "access": "R",
   "states": "1=Failed, 2=Normal"
  },
  {
   "type": "MV",
   "instance": 286,
   "name": "4857_8",
   "description": "MMS Event Summary (ModuleList 8)",
   "units": "",
   "access": "R",
   "states": "1=None, 2=Alarm, 3=Fault"
  },
  {
   "type": "MV",
   "instance": 287,
   "name": "4858_8",
   "description": "MMS Module Inverter Status (ModuleList 8)",
   "units": "",
   "access": "R",
   "states": "1=off, 2=on"
  },
  {
   "type": "MV",
   "instance": 288,
   "name": "4859_8",
   "description": "MMS Module Output Voltage Status (ModuleList 8)",
   "units": "",
   "access": "R",
   "states": "1=Fail, 2=Marginal Low, 3=Normal, 4=Marginal High"
  },
  {
   "type": "MV",
   "instance": 289,
   "name": "4860_8",
   "description": "MMS Module Output Source (ModuleList 8)",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=Normal, 3=Bypass, 4=Maintenance Bypass"
  },
  {
   "type": "MV",
   "instance": 300,
   "name": "5448_1",
   "description": "Intelligent Parallel Operation State",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 301,
   "name": "5449_1",
   "description": "Intelligent Parallel Mode",
   "units": "",
   "access": "R",
   "states": "1=Idle (Fast Recovery), 2=Disconnect (More Efficient), 3=Off (Most Efficient)"
  },
  {
   "type": "MV",
   "instance": 312,
   "name": "5454_1",
   "description": "ECO Mode Operation State",
   "units": "",
   "access": "W",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 313,
   "name": "5455_1",
   "description": "Continuous Operation - ECO Mode",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 324,
   "name": "5461_1_1",
   "description": "Schedule Operation State - ECO Mode (EcoModeSchedule 1)",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 325,
   "name": "5462_1_1",
   "description": "Schedule Action - ECO Mode (EcoModeSchedule 1)",
   "units": "",
   "access": "R",
   "states": "1=stop, 2=start"
  },
  {
   "type": "MV",
   "instance": 326,
   "name": "5463_1_1",
   "description": "Schedule Day of Week - ECO Mode (EcoModeSchedule 1)",
   "units": "",
   "access": "R",
   "states": "1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday"
  },
  {
   "type": "MV",
   "instance": 337,
   "name": "5461_1_2",
   "description": "Schedule Operation State - ECO Mode (EcoModeSchedule 2)",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 338,
   "name": "5462_1_2",
   "description": "Schedule Action - ECO Mode (EcoModeSchedule 2)",
   "units": "",
   "access": "R",
   "states": "1=stop, 2=start"
  },
  {
   "type": "MV",
   "instance": 339,
   "name": "5463_1_2",
   "description": "Schedule Day of Week - ECO Mode (EcoModeSchedule 2)",
   "units": "",
   "access": "R",
   "states": "1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday"
  },
  {
   "type": "MV",
   "instance": 350,
   "name": "5461_1_3",
   "description": "Schedule Operation State - ECO Mode (EcoModeSchedule 3)",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 351,
   "name": "5462_1_3",
   "description": "Schedule Action - ECO Mode (EcoModeSchedule 3)",
   "units": "",
   "access": "R",
   "states": "1=stop, 2=start"
  },
  {
   "type": "MV",
   "instance": 352,
   "name": "5463_1_3",
   "description": "Schedule Day of Week - ECO Mode (EcoModeSchedule 3)",
   "units": "",
   "access": "R",
   "states": "1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday"
  },
  {
   "type": "MV",
   "instance": 363,
   "name": "5461_1_4",
   "description": "Schedule Operation State - ECO Mode (EcoModeSchedule 4)",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 364,
   "name": "5462_1_4",
   "description": "Schedule Action - ECO Mode (EcoModeSchedule 4)",
   "units": "",
   "access": "R",
   "states": "1=stop, 2=start"
  },
  {
   "type": "MV",
   "instance": 365,
   "name": "5463_1_4",
   "description": "Schedule Day of Week - ECO Mode (EcoModeSchedule 4)",
   "units": "",
   "access": "R",
   "states": "1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday"
  },
  {
   "type": "MV",
   "instance": 376,
   "name": "5461_1_5",
   "description": "Schedule Operation State - ECO Mode (EcoModeSchedule 5)",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 377,
   "name": "5462_1_5",
   "description": "Schedule Action - ECO Mode (EcoModeSchedule 5)",
   "units": "",
   "access": "R",
   "states": "1=stop, 2=start"
  },
  {
   "type": "MV",
   "instance": 378,
   "name": "5463_1_5",
   "description": "Schedule Day of Week - ECO Mode (EcoModeSchedule 5)",
   "units": "",
   "access": "R",
   "states": "1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday"
  },
  {
   "type": "MV",
   "instance": 389,
   "name": "5461_1_6",
   "description": "Schedule Operation State - ECO Mode (EcoModeSchedule 6)",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 390,
   "name": "5462_1_6",
   "description": "Schedule Action - ECO Mode (EcoModeSchedule 6)",
   "units": "",
   "access": "R",
   "states": "1=stop, 2=start"
  },
  {
   "type": "MV",
   "instance": 391,
   "name": "5463_1_6",
   "description": "Schedule Day of Week - ECO Mode (EcoModeSchedule 6)",
   "units": "",
   "access": "R",
   "states": "1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday"
  },
  {
   "type": "MV",
   "instance": 402,
   "name": "5461_1_7",
   "description": "Schedule Operation State - ECO Mode (EcoModeSchedule 7)",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 403,
   "name": "5462_1_7",
   "description": "Schedule Action - ECO Mode (EcoModeSchedule 7)",
   "units": "",
   "access": "R",
   "states": "1=stop, 2=start"
  },
  {
   "type": "MV",
   "instance": 404,
   "name": "5463_1_7",
   "description": "Schedule Day of Week - ECO Mode (EcoModeSchedule 7)",
   "units": "",
   "access": "R",
   "states": "1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday"
  },
  {
   "type": "MV",
   "instance": 415,
   "name": "5461_1_8",
   "description": "Schedule Operation State - ECO Mode (EcoModeSchedule 8)",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 416,
   "name": "5462_1_8",
   "description": "Schedule Action - ECO Mode (EcoModeSchedule 8)",
   "units": "",
   "access": "R",
   "states": "1=stop, 2=start"
  },
  {
   "type": "MV",
   "instance": 417,
   "name": "5463_1_8",
   "description": "Schedule Day of Week - ECO Mode (EcoModeSchedule 8)",
   "units": "",
   "access": "R",
   "states": "1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday"
  },
  {
   "type": "MV",
   "instance": 428,
   "name": "5461_1_9",
   "description": "Schedule Operation State - ECO Mode (EcoModeSchedule 9)",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 429,
   "name": "5462_1_9",
   "description": "Schedule Action - ECO Mode (EcoModeSchedule 9)",
   "units": "",
   "access": "R",
   "states": "1=stop, 2=start"
  },
  {
   "type": "MV",
   "instance": 430,
   "name": "5463_1_9",
   "description": "Schedule Day of Week - ECO Mode (EcoModeSchedule 9)",
   "units": "",
   "access": "R",
   "states": "1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday"
  },
  {
   "type": "MV",
   "instance": 441,
   "name": "5461_1_10",
   "description": "Schedule Operation State - ECO Mode (EcoModeSchedule 10)",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 442,
   "name": "5462_1_10",
   "description": "Schedule Action - ECO Mode (EcoModeSchedule 10)",
   "units": "",
   "access": "R",
   "states": "1=stop, 2=start"
  },
  {
   "type": "MV",
   "instance": 443,
   "name": "5463_1_10",
   "description": "Schedule Day of Week - ECO Mode (EcoModeSchedule 10)",
   "units": "",
   "access": "R",
   "states": "1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday"
  },
  {
   "type": "MV",
   "instance": 454,
   "name": "5461_1_11",
   "description": "Schedule Operation State - ECO Mode (EcoModeSchedule 11)",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 455,
   "name": "5462_1_11",
   "description": "Schedule Action - ECO Mode (EcoModeSchedule 11)",
   "units": "",
   "access": "R",
   "states": "1=stop, 2=start"
  },
  {
   "type": "MV",
   "instance": 456,
   "name": "5463_1_11",
   "description": "Schedule Day of Week - ECO Mode (EcoModeSchedule 11)",
   "units": "",
   "access": "R",
   "states": "1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday"
  },
  {
   "type": "MV",
   "instance": 467,
   "name": "5461_1_12",
   "description": "Schedule Operation State - ECO Mode (EcoModeSchedule 12)",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 468,
   "name": "5462_1_12",
   "description": "Schedule Action - ECO Mode (EcoModeSchedule 12)",
   "units": "",
   "access": "R",
   "states": "1=stop, 2=start"
  },
  {
   "type": "MV",
   "instance": 469,
   "name": "5463_1_12",
   "description": "Schedule Day of Week - ECO Mode (EcoModeSchedule 12)",
   "units": "",
   "access": "R",
   "states": "1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday"
  },
  {
   "type": "MV",
   "instance": 480,
   "name": "5461_1_13",
   "description": "Schedule Operation State - ECO Mode (EcoModeSchedule 13)",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 481,
   "name": "5462_1_13",
   "description": "Schedule Action - ECO Mode (EcoModeSchedule 13)",
   "units": "",
   "access": "R",
   "states": "1=stop, 2=start"
  },
  {
   "type": "MV",
   "instance": 482,
   "name": "5463_1_13",
   "description": "Schedule Day of Week - ECO Mode (EcoModeSchedule 13)",
   "units": "",
   "access": "R",
   "states": "1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday"
  },
  {
   "type": "MV",
   "instance": 493,
   "name": "5461_1_14",
   "description": "Schedule Operation State - ECO Mode (EcoModeSchedule 14)",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 494,
   "name": "5462_1_14",
   "description": "Schedule Action - ECO Mode (EcoModeSchedule 14)",
   "units": "",
   "access": "R",
   "states": "1=stop, 2=start"
  },
  {
   "type": "MV",
   "instance": 495,
   "name": "5463_1_14",
   "description": "Schedule Day of Week - ECO Mode (EcoModeSchedule 14)",
   "units": "",
   "access": "R",
   "states": "1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday"
  },
  {
   "type": "MV",
   "instance": 506,
   "name": "5461_1_15",
   "description": "Schedule Operation State - ECO Mode (EcoModeSchedule 15)",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 507,
   "name": "5462_1_15",
   "description": "Schedule Action - ECO Mode (EcoModeSchedule 15)",
   "units": "",
   "access": "R",
   "states": "1=stop, 2=start"
  },
  {
   "type": "MV",
   "instance": 508,
   "name": "5463_1_15",
   "description": "Schedule Day of Week - ECO Mode (EcoModeSchedule 15)",
   "units": "",
   "access": "R",
   "states": "1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday"
  },
  {
   "type": "MV",
   "instance": 519,
   "name": "5461_1_16",
   "description": "Schedule Operation State - ECO Mode (EcoModeSchedule 16)",
   "units": "",
   "access": "R",
   "states": "1=disabled, 2=enabled"
  },
  {
   "type": "MV",
   "instance": 520,
   "name": "5462_1_16",
   "description": "Schedule Action - ECO Mode (EcoModeSchedule 16)",
   "units": "",
   "access": "R",
   "states": "1=stop, 2=start"
  },
  {
   "type": "MV",
   "instance": 521,
   "name": "5463_1_16",
   "description": "Schedule Day of Week - ECO Mode (EcoModeSchedule 16)",
   "units": "",
   "access": "R",
   "states": "1=Unknown, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/vertiv/exl",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}