 "manufacturer": "Vertiv",
 "manufacturer_slug": "vertiv",
 "model": "Alber BDSU battery monitoring",
 "model_slug": "alber-bdsu",
 "aliases": [
  "Alber BDSU",
  "BDSU",
  "Vertiv Alber",
  "SL-28170"
 ],
 "equipment_type": "Battery monitoring system",
 "applies_to": "Alber BDSU battery monitoring systems (strings and cells).",
 "summary": "The Alber BDSU battery monitoring reports battery string and cell data through a Liebert IntelliSlot card: string voltage, current and temperatures, cell voltages, temperatures and resistance, and alarm thresholds. Object names for string and cell points are generated at runtime from the BDSU configuration.",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Tables 5.194, 5.195, 5.196, pdf pages 2287-2306 of the 2024 guide (printed page numbers are 4 lower).",
  "Object names are Vertiv data IDs (e.g. 5331_1); the description holds the guide's data label. Labels repeated for different sensors or circuits get the group name in brackets.",
  "Most temperature objects come in pairs: a °C object and a °F object (name ending _deg_F), usually at instance + 10000.",
  "String and cell object names contain a <SeeDnldMap> placeholder that the card fills at runtime; download BACnetDataMap.txt from the Unity card for the real names."
 ],
 "source": {
  "title": "Liebert IntelliSlot Modbus/BACnet Reference Guide (Modbus RTU and TCP, BACnet MSTP and IP)",
  "doc_number": "SL-28170",
  "revision_date": "2024-04 (Rev 29)",
  "url": "https://www.vertiv.com/49fb41/globalassets/shared/liebert-intellislot-modbus-rtu-reference-guide-SL-28170_0.pdf"
 },
 "integration": {
  "summary": "Fit a Liebert IntelliSlot BACnet card (IS-UNITY-DP for BACnet IP or MS/TP), give it a unique device instance and let it discover the equipment; the objects are then created automatically. Map the status, main measurements and event objects for monitoring.",
  "minimum_points": [
   {
    "ref": "MV 1",
    "name": "4123_<SeeDnldMap>",
    "why": "Normal, warning or alarm state"
   },
   {
    "ref": "AV 1",
    "name": "4150_1",
    "why": "Estimated battery runtime, s"
   },
   {
    "ref": "BV 1",
    "name": "4168_1",
    "why": "Load is on battery"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "The card needs a unique Device Instance Number; the device object represents the card, not the unit.",
   "The cards have no BBMD; IS-UNITY-DP and IS-IPBML support foreign device registration (BBMD address and time-to-live).",
   "IS-UNITY-DP adds BACnet MS/TP; IS-WEBADPT and IS-IPBML are BACnet IP only. Check the compatibility table (guide section 1.1.3) for the card your unit supports."
  ],
  "gotchas": [
   "Vertiv asks for no more than about two writes and two reads per second on average; do not rewrite setpoints continuously.",
   "No segmented responses: large ReadPropertyMultiple requests can fail, so split them.",
   "Only data the managed unit actually has is created on the card, so object counts vary by model and options."
  ]
 },
 "points": [
  {
   "type": "BV",
   "instance": 1,
   "name": "4168_1",
   "description": "Battery Discharging (Battery Entity 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "4168_2",
   "description": "Battery Discharging (Battery Entity 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 342,
   "name": "4168_32",
   "description": "Battery Discharging (Battery Entity 32)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 353,
   "name": "4906_<SeeDnldMap>",
   "description": "Low Ambient Temperature (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 354,
   "name": "4907_<SeeDnldMap>",
   "description": "High Ambient Temperature (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 355,
   "name": "5436_<SeeDnldMap>",
   "description": "Low Ambient Temperature Probe Two (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 356,
   "name": "5437_<SeeDnldMap>",
   "description": "High Ambient Temperature Probe Two (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 357,
   "name": "4908_<SeeDnldMap>",
   "description": "Low Overall Voltage (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 358,
   "name": "4909_<SeeDnldMap>",
   "description": "High Overall Voltage (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 359,
   "name": "4910_<SeeDnldMap>",
   "description": "High Battery String Current (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 360,
   "name": "4911_<SeeDnldMap>",
   "description": "Low Battery String Float Current (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 361,
   "name": "4912_<SeeDnldMap>",
   "description": "High Battery String Float Current (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 362,
   "name": "4913_<SeeDnldMap>",
   "description": "High Battery String Ripple Current (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 363,
   "name": "4914_<SeeDnldMap>",
   "description": "Battery String Discharge Detected (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 364,
   "name": "4915_<SeeDnldMap>",
   "description": "Maximum Discharge Time Exceeded (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 365,
   "name": "4916_<SeeDnldMap>",
   "description": "Discharge Low Overall Voltage (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 366,
   "name": "4918_<SeeDnldMap>",
   "description": "Discharge High Battery String Current (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 367,
   "name": "4920_<SeeDnldMap>",
   "description": "Excessive Cell to Ambient Temperature Deviation (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 368,
   "name": "4919_<SeeDnldMap>",
   "description": "Excessive Cell to Cell Temperature Deviation (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 369,
   "name": "5439_<SeeDnldMap>",
   "description": "Battery String Equalize (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 370,
   "name": "5440_<SeeDnldMap>",
   "description": "Battery String Offline (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 371,
   "name": "5438_<SeeDnldMap>",
   "description": "Thermal Runaway Detected (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 372,
   "name": "5609_<SeeDnldMap>",
   "description": "Thermal Runaway Cell to Ambient Temperature Event (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 373,
   "name": "5610_<SeeDnldMap>",
   "description": "Thermal Runaway Cell to Cell Temperature Event (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 374,
   "name": "5611_<SeeDnldMap>",
   "description": "Thermal Runaway Charger Current Level One Event (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 375,
   "name": "5612_<SeeDnldMap>",
   "description": "Thermal Runaway Charger Current Level Two Event (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 376,
   "name": "5896_<SeeDnldMap>",
   "description": "Ground Fault Detected (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 387,
   "name": "4906_<SeeDnldMap>",
   "description": "Low Ambient Temperature (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 388,
   "name": "4907_<SeeDnldMap>",
   "description": "High Ambient Temperature (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 389,
   "name": "5436_<SeeDnldMap>",
   "description": "Low Ambient Temperature Probe Two (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 390,
   "name": "5437_<SeeDnldMap>",
   "description": "High Ambient Temperature Probe Two (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 391,
   "name": "4908_<SeeDnldMap>",
   "description": "Low Overall Voltage (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 392,
   "name": "4909_<SeeDnldMap>",
   "description": "High Overall Voltage (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 393,
   "name": "4910_<SeeDnldMap>",
   "description": "High Battery String Current (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 394,
   "name": "4911_<SeeDnldMap>",
   "description": "Low Battery String Float Current (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 395,
   "name": "4912_<SeeDnldMap>",
   "description": "High Battery String Float Current (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 396,
   "name": "4913_<SeeDnldMap>",
   "description": "High Battery String Ripple Current (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 397,
   "name": "4914_<SeeDnldMap>",
   "description": "Battery String Discharge Detected (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 398,
   "name": "4915_<SeeDnldMap>",
   "description": "Maximum Discharge Time Exceeded (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 399,
   "name": "4916_<SeeDnldMap>",
   "description": "Discharge Low Overall Voltage (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 400,
   "name": "4918_<SeeDnldMap>",
   "description": "Discharge High Battery String Current (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 401,
   "name": "4920_<SeeDnldMap>",
   "description": "Excessive Cell to Ambient Temperature Deviation (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 402,
   "name": "4919_<SeeDnldMap>",
   "description": "Excessive Cell to Cell Temperature Deviation (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 403,
   "name": "5439_<SeeDnldMap>",
   "description": "Battery String Equalize (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 404,
   "name": "5440_<SeeDnldMap>",
   "description": "Battery String Offline (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 405,
   "name": "5438_<SeeDnldMap>",
   "description": "Thermal Runaway Detected (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 406,
   "name": "5609_<SeeDnldMap>",
   "description": "Thermal Runaway Cell to Ambient Temperature Event (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 407,
   "name": "5610_<SeeDnldMap>",
   "description": "Thermal Runaway Cell to Cell Temperature Event (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 408,
   "name": "5611_<SeeDnldMap>",
   "description": "Thermal Runaway Charger Current Level One Event (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 409,
   "name": "5612_<SeeDnldMap>",
   "description": "Thermal Runaway Charger Current Level Two Event (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 410,
   "name": "5896_<SeeDnldMap>",
   "description": "Ground Fault Detected (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1407,
   "name": "4906_<SeeDnldMap>",
   "description": "Low Ambient Temperature (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1408,
   "name": "4907_<SeeDnldMap>",
   "description": "High Ambient Temperature (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1409,
   "name": "5436_<SeeDnldMap>",
   "description": "Low Ambient Temperature Probe Two (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1410,
   "name": "5437_<SeeDnldMap>",
   "description": "High Ambient Temperature Probe Two (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1411,
   "name": "4908_<SeeDnldMap>",
   "description": "Low Overall Voltage (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1412,
   "name": "4909_<SeeDnldMap>",
   "description": "High Overall Voltage (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1413,
   "name": "4910_<SeeDnldMap>",
   "description": "High Battery String Current (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1414,
   "name": "4911_<SeeDnldMap>",
   "description": "Low Battery String Float Current (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1415,
   "name": "4912_<SeeDnldMap>",
   "description": "High Battery String Float Current (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1416,
   "name": "4913_<SeeDnldMap>",
   "description": "High Battery String Ripple Current (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1417,
   "name": "4914_<SeeDnldMap>",
   "description": "Battery String Discharge Detected (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1418,
   "name": "4915_<SeeDnldMap>",
   "description": "Maximum Discharge Time Exceeded (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1419,
   "name": "4916_<SeeDnldMap>",
   "description": "Discharge Low Overall Voltage (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1420,
   "name": "4918_<SeeDnldMap>",
   "description": "Discharge High Battery String Current (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1421,
   "name": "4920_<SeeDnldMap>",
   "description": "Excessive Cell to Ambient Temperature Deviation (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1422,
   "name": "4919_<SeeDnldMap>",
   "description": "Excessive Cell to Cell Temperature Deviation (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1423,
   "name": "5439_<SeeDnldMap>",
   "description": "Battery String Equalize (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1424,
   "name": "5440_<SeeDnldMap>",
   "description": "Battery String Offline (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1425,
   "name": "5438_<SeeDnldMap>",
   "description": "Thermal Runaway Detected (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1426,
   "name": "5609_<SeeDnldMap>",
   "description": "Thermal Runaway Cell to Ambient Temperature Event (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1427,
   "name": "5610_<SeeDnldMap>",
   "description": "Thermal Runaway Cell to Cell Temperature Event (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1428,
   "name": "5611_<SeeDnldMap>",
   "description": "Thermal Runaway Charger Current Level One Event (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1429,
   "name": "5612_<SeeDnldMap>",
   "description": "Thermal Runaway Charger Current Level Two Event (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1430,
   "name": "5896_<SeeDnldMap>",
   "description": "Ground Fault Detected (String Entity 3)",
   "units": "",
   "access": "W",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1441,
   "name": "4964_<SeeDnldMap>",
   "description": "Low Cell Voltage (Cell Entity 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1442,
   "name": "4965_<SeeDnldMap>",
   "description": "High Cell Voltage (Cell Entity 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1443,
   "name": "4966_<SeeDnldMap>",
   "description": "Low Cell Temperature (Cell Entity 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1444,
   "name": "4967_<SeeDnldMap>",
   "description": "High Cell Temperature (Cell Entity 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1445,
   "name": "4968_<SeeDnldMap>",
   "description": "Low Internal Resistance (Cell Entity 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1446,
   "name": "4969_<SeeDnldMap>",
   "description": "High Internal Resistance (Cell Entity 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1447,
   "name": "4970_<SeeDnldMap>",
   "description": "High Intercell Resistance (Cell Entity 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1448,
   "name": "5442_<SeeDnldMap>",
   "description": "Discharge Low Cell Voltage (Cell Entity 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1449,
   "name": "4978_<SeeDnldMap>",
   "description": "Intertier Resistance High (Cell Entity 1)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1460,
   "name": "4964_<SeeDnldMap>",
   "description": "Low Cell Voltage (Cell Entity 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1461,
   "name": "4965_<SeeDnldMap>",
   "description": "High Cell Voltage (Cell Entity 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1462,
   "name": "4966_<SeeDnldMap>",
   "description": "Low Cell Temperature (Cell Entity 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1463,
   "name": "4967_<SeeDnldMap>",
   "description": "High Cell Temperature (Cell Entity 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1464,
   "name": "4968_<SeeDnldMap>",
   "description": "Low Internal Resistance (Cell Entity 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1465,
   "name": "4969_<SeeDnldMap>",
   "description": "High Internal Resistance (Cell Entity 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1466,
   "name": "4970_<SeeDnldMap>",
   "description": "High Intercell Resistance (Cell Entity 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1467,
   "name": "5442_<SeeDnldMap>",
   "description": "Discharge Low Cell Voltage (Cell Entity 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 1468,
   "name": "4978_<SeeDnldMap>",
   "description": "Intertier Resistance High (Cell Entity 2)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 8262,
   "name": "4964_<SeeDnldMap>",
   "description": "Low Cell Voltage (Cell Entity 360)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 8263,
   "name": "4965_<SeeDnldMap>",
   "description": "High Cell Voltage (Cell Entity 360)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 8264,
   "name": "4966_<SeeDnldMap>",
   "description": "Low Cell Temperature (Cell Entity 360)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 8265,
   "name": "4967_<SeeDnldMap>",
   "description": "High Cell Temperature (Cell Entity 360)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 8266,
   "name": "4968_<SeeDnldMap>",
   "description": "Low Internal Resistance (Cell Entity 360)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 8267,
   "name": "4969_<SeeDnldMap>",
   "description": "High Internal Resistance (Cell Entity 360)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 8268,
   "name": "4970_<SeeDnldMap>",
   "description": "High Intercell Resistance (Cell Entity 360)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 8269,
   "name": "5442_<SeeDnldMap>",
   "description": "Discharge Low Cell Voltage (Cell Entity 360)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "BV",
   "instance": 8270,
   "name": "4978_<SeeDnldMap>",
   "description": "Intertier Resistance High (Cell Entity 360)",
   "units": "",
   "access": "R",
   "states": "Active = alarm"
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "4150_1",
   "description": "Battery Time Remaining (Battery Entity 1)",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "4151_1",
   "description": "Battery Discharge Time (Battery Entity 1)",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "4898_1_1",
   "description": "Battery Rating (Battery Entity 1 Battery Configuration 1)",
   "units": "AH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "4150_2",
   "description": "Battery Time Remaining (Battery Entity 2)",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "4151_2",
   "description": "Battery Discharge Time (Battery Entity 2)",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "4898_2_1",
   "description": "Battery Rating (Battery Entity 2 Battery Configuration 1)",
   "units": "AH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 714,
   "name": "4150_32",
   "description": "Battery Time Remaining (Battery Entity 32)",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 715,
   "name": "4151_32",
   "description": "Battery Discharge Time (Battery Entity 32)",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 726,
   "name": "4898_32_1",
   "description": "Battery Rating (Battery Entity 32 Battery Configuration 1)",
   "units": "AH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 737,
   "name": "4899_<SeeDnldMap>_1",
   "description": "String Ambient Temperature 1 (String Entity 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20737,
   "name": "4899_<SeeDnldMap>_1_deg_F",
   "description": "String Ambient Temperature 1 (String Entity 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 738,
   "name": "4899_<SeeDnldMap>_2",
   "description": "String Ambient Temperature 2 (String Entity 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20738,
   "name": "4899_<SeeDnldMap>_2_deg_F",
   "description": "String Ambient Temperature 2 (String Entity 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 739,
   "name": "4900_<SeeDnldMap>",
   "description": "String Overall Voltage (String Entity 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 740,
   "name": "4901_<SeeDnldMap>",
   "description": "String Current (String Entity 1)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 741,
   "name": "4902_<SeeDnldMap>",
   "description": "Float Current (String Entity 1)",
   "units": "mA DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 742,
   "name": "4903_<SeeDnldMap>",
   "description": "Ripple Current (String Entity 1)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 743,
   "name": "4947_<SeeDnldMap>",
   "description": "Battery String Discharge Time (String Entity 1)",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 744,
   "name": "4904_<SeeDnldMap>",
   "description": "Total Active Alarms on a Battery String (String Entity 1)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 755,
   "name": "4945_<SeeDnldMap>",
   "description": "Battery String Time- To-Go (String Entity 1 State Of String 1)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 756,
   "name": "4946_<SeeDnldMap>",
   "description": "Amp-Hours Remaining in Battery String (String Entity 1 State Of String 1)",
   "units": "AH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 767,
   "name": "4921_<SeeDnldMap>",
   "description": "Low Ambient Temperature Global Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20767,
   "name": "4921_<SeeDnldMap>_deg_F",
   "description": "Low Ambient Temperature Global Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 768,
   "name": "4922_<SeeDnldMap>",
   "description": "High Ambient Temperature Global Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20768,
   "name": "4922_<SeeDnldMap>_deg_F",
   "description": "High Ambient Temperature Global Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 769,
   "name": "4923_<SeeDnldMap>",
   "description": "Battery String Overall Voltage Low Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 770,
   "name": "4924_<SeeDnldMap>",
   "description": "Battery String Overall Voltage High Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 771,
   "name": "4925_<SeeDnldMap>",
   "description": "Battery String Current High Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 772,
   "name": "4926_<SeeDnldMap>",
   "description": "Battery String Float Current Low Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "mA DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 773,
   "name": "4927_<SeeDnldMap>",
   "description": "Battery String Float Current High Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "mA DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 774,
   "name": "4928_<SeeDnldMap>",
   "description": "Battery String Ripple Current High Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 775,
   "name": "4929_<SeeDnldMap>",
   "description": "Cell Voltage Low Global Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 776,
   "name": "4930_<SeeDnldMap>",
   "description": "Cell Voltage High Global Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 777,
   "name": "4931_<SeeDnldMap>",
   "description": "Cell Temperature Low Global Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20777,
   "name": "4931_<SeeDnldMap>_deg_F",
   "description": "Cell Temperature Low Global Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 778,
   "name": "4932_<SeeDnldMap>",
   "description": "Cell Temperature High Global Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20778,
   "name": "4932_<SeeDnldMap>_deg_F",
   "description": "Cell Temperature High Global Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 779,
   "name": "4933_<SeeDnldMap>",
   "description": "Internal Resistance Low Global Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 780,
   "name": "4934_<SeeDnldMap>",
   "description": "Internal Resistance High Global Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 781,
   "name": "4935_<SeeDnldMap>",
   "description": "Intercell Resistance High Global Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 782,
   "name": "4936_<SeeDnldMap>",
   "description": "Intertier Resistance High Global Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 783,
   "name": "4937_<SeeDnldMap>",
   "description": "Cell to Cell Temperature Deviation Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20783,
   "name": "4937_<SeeDnldMap>_deg_F",
   "description": "Cell to Cell Temperature Deviation Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 784,
   "name": "4938_<SeeDnldMap>",
   "description": "Cell to Ambient Temperature Deviation Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20784,
   "name": "4938_<SeeDnldMap>_deg_F",
   "description": "Cell to Ambient Temperature Deviation Threshold (String Entity 1 String Alarm Thresholds 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 795,
   "name": "4940_<SeeDnldMap>",
   "description": "Installation Date (String Entity 1 String Configuration 1)",
   "units": "Secs since Epoch(UTC)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 796,
   "name": "4943_<SeeDnldMap>",
   "description": "Cell/Monobloc Rating (String Entity 1 String Configuration 1)",
   "units": "AH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 807,
   "name": "4948_<SeeDnldMap>",
   "description": "Discharge Low Cell Voltage Threshold (String Entity 1 Discharge Thresholds 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 808,
   "name": "4949_<SeeDnldMap>",
   "description": "Discharge Low Overall Voltage Threshold (String Entity 1 Discharge Thresholds 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 809,
   "name": "4950_<SeeDnldMap>",
   "description": "Discharge Battery String Current High Threshold (String Entity 1 Discharge Thresholds 1)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 810,
   "name": "4951_<SeeDnldMap>",
   "description": "Discharge Maximum Time (String Entity 1 Discharge Thresholds 1)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 821,
   "name": "4961_<SeeDnldMap>",
   "description": "Startup Date (String Entity 1 String Startup Information 1)",
   "units": "Secs since Epoch(UTC)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 832,
   "name": "4899_<SeeDnldMap>_1",
   "description": "String Ambient Temperature 1 (String Entity 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20832,
   "name": "4899_<SeeDnldMap>_1_deg_F",
   "description": "String Ambient Temperature 1 (String Entity 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 833,
   "name": "4899_<SeeDnldMap>_2",
   "description": "String Ambient Temperature 2 (String Entity 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20833,
   "name": "4899_<SeeDnldMap>_2_deg_F",
   "description": "String Ambient Temperature 2 (String Entity 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 834,
   "name": "4900_<SeeDnldMap>",
   "description": "String Overall Voltage (String Entity 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 835,
   "name": "4901_<SeeDnldMap>",
   "description": "String Current (String Entity 2)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 836,
   "name": "4902_<SeeDnldMap>",
   "description": "Float Current (String Entity 2)",
   "units": "mA DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 837,
   "name": "4903_<SeeDnldMap>",
   "description": "Ripple Current (String Entity 2)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 838,
   "name": "4947_<SeeDnldMap>",
   "description": "Battery String Discharge Time (String Entity 2)",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 839,
   "name": "4904_<SeeDnldMap>",
   "description": "Total Active Alarms on a Battery String (String Entity 2)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 850,
   "name": "4945_<SeeDnldMap>",
   "description": "Battery String Time- To-Go (String Entity 2 State of String 1)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 851,
   "name": "4946_<SeeDnldMap>",
   "description": "Amp-Hours Remaining in Battery String (String Entity 2 State of String 1)",
   "units": "AH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 862,
   "name": "4921_<SeeDnldMap>",
   "description": "Low Ambient Temperature Global Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20862,
   "name": "4921_<SeeDnldMap>_deg_F",
   "description": "Low Ambient Temperature Global Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 863,
   "name": "4922_<SeeDnldMap>",
   "description": "High Ambient Temperature Global Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20863,
   "name": "4922_<SeeDnldMap>_deg_F",
   "description": "High Ambient Temperature Global Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 864,
   "name": "4923_<SeeDnldMap>",
   "description": "Battery String Overall Voltage Low Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 865,
   "name": "4924_<SeeDnldMap>",
   "description": "Battery String Overall Voltage High Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 866,
   "name": "4925_<SeeDnldMap>",
   "description": "Battery String Current High Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 867,
   "name": "4926_<SeeDnldMap>",
   "description": "Battery String Float Current Low Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "mA DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 868,
   "name": "4927_<SeeDnldMap>",
   "description": "Battery String Float Current High Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "mA DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 869,
   "name": "4928_<SeeDnldMap>",
   "description": "Battery String Ripple Current High Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 870,
   "name": "4929_<SeeDnldMap>",
   "description": "Cell Voltage Low Global Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 871,
   "name": "4930_<SeeDnldMap>",
   "description": "Cell Voltage High Global Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 872,
   "name": "4931_<SeeDnldMap>",
   "description": "Cell Temperature Low Global Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20872,
   "name": "4931_<SeeDnldMap>_deg_F",
   "description": "Cell Temperature Low Global Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 873,
   "name": "4932_<SeeDnldMap>",
   "description": "Cell Temperature High Global Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20873,
   "name": "4932_<SeeDnldMap>_deg_F",
   "description": "Cell Temperature High Global Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 874,
   "name": "4933_<SeeDnldMap>",
   "description": "Internal Resistance Low Global Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 875,
   "name": "4934_<SeeDnldMap>",
   "description": "Internal Resistance High Global Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 876,
   "name": "4935_<SeeDnldMap>",
   "description": "Intercell Resistance High Global Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 877,
   "name": "4936_<SeeDnldMap>",
   "description": "Intertier Resistance High Global Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 878,
   "name": "4937_<SeeDnldMap>",
   "description": "Cell to Cell Temperature Deviation Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20878,
   "name": "4937_<SeeDnldMap>_deg_F",
   "description": "Cell to Cell Temperature Deviation Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 879,
   "name": "4938_<SeeDnldMap>",
   "description": "Cell to Ambient Temperature Deviation Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20879,
   "name": "4938_<SeeDnldMap>_deg_F",
   "description": "Cell to Ambient Temperature Deviation Threshold (String Entity 2 String Alarm Thresholds 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 890,
   "name": "4940_<SeeDnldMap>",
   "description": "Installation Date (String Entity 2 String Configuration 1)",
   "units": "Secs since Epoch(UTC)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 891,
   "name": "4943_<SeeDnldMap>",
   "description": "Cell/Monobloc Rating (String Entity 2 String Configuration 1)",
   "units": "AH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 902,
   "name": "4948_<SeeDnldMap>",
   "description": "Discharge Low Cell Voltage Threshold (String Entity 2 Discharge Thresholds 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 903,
   "name": "4949_<SeeDnldMap>",
   "description": "Discharge Low Overall Voltage Threshold (String Entity 2 Discharge Thresholds 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 904,
   "name": "4950_<SeeDnldMap>",
   "description": "Discharge Battery String Current High Threshold (String Entity 2 Discharge Thresholds 1)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 905,
   "name": "4951_<SeeDnldMap>",
   "description": "Discharge Maximum Time (String Entity 2 Discharge Thresholds 1)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 916,
   "name": "4961_<SeeDnldMap>",
   "description": "Startup Date (String Entity 2 String Startup Information 1)",
   "units": "Secs since Epoch(UTC)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3682,
   "name": "4899_<SeeDnldMap>_1",
   "description": "String Ambient Temperature 1 (String Entity 32)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23682,
   "name": "4899_<SeeDnldMap>_1_deg_F",
   "description": "String Ambient Temperature 1 (String Entity 32)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3683,
   "name": "4899_<SeeDnldMap>_2",
   "description": "String Ambient Temperature 2 (String Entity 32)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23683,
   "name": "4899_<SeeDnldMap>_2_deg_F",
   "description": "String Ambient Temperature 2 (String Entity 32)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3684,
   "name": "4900_<SeeDnldMap>",
   "description": "String Overall Voltage (String Entity 32)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3685,
   "name": "4901_<SeeDnldMap>",
   "description": "String Current (String Entity 32)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3686,
   "name": "4902_<SeeDnldMap>",
   "description": "Float Current (String Entity 32)",
   "units": "mA DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3687,
   "name": "4903_<SeeDnldMap>",
   "description": "Ripple Current (String Entity 32)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3688,
   "name": "4947_<SeeDnldMap>",
   "description": "Battery String Discharge Time (String Entity 32)",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3689,
   "name": "4904_<SeeDnldMap>",
   "description": "Total Active Alarms on a Battery String (String Entity 32)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3700,
   "name": "4945_<SeeDnldMap>",
   "description": "Battery String Time- To-Go (String Entity 32 State of String 1)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3701,
   "name": "4946_<SeeDnldMap>",
   "description": "Amp-Hours Remaining in Battery String (String Entity 32 State of String 1)",
   "units": "AH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3712,
   "name": "4921_<SeeDnldMap>",
   "description": "Low Ambient Temperature Global Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23712,
   "name": "4921_<SeeDnldMap>_deg_F",
   "description": "Low Ambient Temperature Global Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3713,
   "name": "4922_<SeeDnldMap>",
   "description": "High Ambient Temperature Global Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23713,
   "name": "4922_<SeeDnldMap>_deg_F",
   "description": "High Ambient Temperature Global Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3714,
   "name": "4923_<SeeDnldMap>",
   "description": "Battery String Overall Voltage Low Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3715,
   "name": "4924_<SeeDnldMap>",
   "description": "Battery String Overall Voltage High Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3716,
   "name": "4925_<SeeDnldMap>",
   "description": "Battery String Current High Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3717,
   "name": "4926_<SeeDnldMap>",
   "description": "Battery String Float Current Low Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "mA DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3718,
   "name": "4927_<SeeDnldMap>",
   "description": "Battery String Float Current High Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "mA DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3719,
   "name": "4928_<SeeDnldMap>",
   "description": "Battery String Ripple Current High Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3720,
   "name": "4929_<SeeDnldMap>",
   "description": "Cell Voltage Low Global Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3721,
   "name": "4930_<SeeDnldMap>",
   "description": "Cell Voltage High Global Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3722,
   "name": "4931_<SeeDnldMap>",
   "description": "Cell Temperature Low Global Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23722,
   "name": "4931_<SeeDnldMap>_deg_F",
   "description": "Cell Temperature Low Global Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3723,
   "name": "4932_<SeeDnldMap>",
   "description": "Cell Temperature High Global Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23723,
   "name": "4932_<SeeDnldMap>_deg_F",
   "description": "Cell Temperature High Global Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3724,
   "name": "4933_<SeeDnldMap>",
   "description": "Internal Resistance Low Global Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3725,
   "name": "4934_<SeeDnldMap>",
   "description": "Internal Resistance High Global Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3726,
   "name": "4935_<SeeDnldMap>",
   "description": "Intercell Resistance High Global Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3727,
   "name": "4936_<SeeDnldMap>",
   "description": "Intertier Resistance High Global Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3728,
   "name": "4937_<SeeDnldMap>",
   "description": "Cell to Cell Temperature Deviation Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23728,
   "name": "4937_<SeeDnldMap>_deg_F",
   "description": "Cell to Cell Temperature Deviation Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3729,
   "name": "4938_<SeeDnldMap>",
   "description": "Cell to Ambient Temperature Deviation Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23729,
   "name": "4938_<SeeDnldMap>_deg_F",
   "description": "Cell to Ambient Temperature Deviation Threshold (String Entity 32 String Alarm Thresholds 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3740,
   "name": "4940_<SeeDnldMap>",
   "description": "Installation Date (String Entity 32 String Configuration 1)",
   "units": "Secs since Epoch(UTC)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3741,
   "name": "4943_<SeeDnldMap>",
   "description": "Cell/Monobloc Rating (String Entity 32 String Configuration 1)",
   "units": "AH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3752,
   "name": "4948_<SeeDnldMap>",
   "description": "Discharge Low Cell Voltage Threshold (String Entity 32 Discharge Thresholds 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3753,
   "name": "4949_<SeeDnldMap>",
   "description": "Discharge Low Overall Voltage Threshold (String Entity 32 Discharge Thresholds 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3754,
   "name": "4950_<SeeDnldMap>",
   "description": "Discharge Battery String Current High Threshold (String Entity 32 Discharge Thresholds 1)",
   "units": "A DC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3755,
   "name": "4951_<SeeDnldMap>",
   "description": "Discharge Maximum Time (String Entity 32 Discharge Thresholds 1)",
   "units": "min",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3766,
   "name": "4961_<SeeDnldMap>",
   "description": "Startup Date (String Entity 32 String Startup Information 1)",
   "units": "Secs since Epoch(UTC)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3777,
   "name": "4962_<SeeDnldMap>",
   "description": "Cell Voltage (Cell Entity 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3778,
   "name": "4963_<SeeDnldMap>",
   "description": "Cell Temperature (Cell Entity 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23778,
   "name": "4963_<SeeDnldMap>_deg_F",
   "description": "Cell Temperature (Cell Entity 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3779,
   "name": "5443_<SeeDnldMap>",
   "description": "Internal Resistance Value (Cell Entity 1)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3780,
   "name": "5444_<SeeDnldMap>",
   "description": "Intercell Resistance Value (Cell Entity 1)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3791,
   "name": "4971_<SeeDnldMap>",
   "description": "Cell Voltage Low Threshold (Cell Entity 1 Threshold settings for a Cell 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3792,
   "name": "4972_<SeeDnldMap>",
   "description": "Cell Voltage High Threshold (Cell Entity 1 Threshold settings for a Cell 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3793,
   "name": "4973_<SeeDnldMap>",
   "description": "Cell Temperature Low Threshold (Cell Entity 1 Threshold settings for a Cell 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23793,
   "name": "4973_<SeeDnldMap>_deg_F",
   "description": "Cell Temperature Low Threshold (Cell Entity 1 Threshold settings for a Cell 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3794,
   "name": "4974_<SeeDnldMap>",
   "description": "Cell Temperature High Threshold (Cell Entity 1 Threshold settings for a Cell 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23794,
   "name": "4974_<SeeDnldMap>_deg_F",
   "description": "Cell Temperature High Threshold (Cell Entity 1 Threshold settings for a Cell 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3795,
   "name": "4975_<SeeDnldMap>",
   "description": "Internal Resistance Low Threshold (Cell Entity 1 Threshold settings for a Cell 1)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3796,
   "name": "4976_<SeeDnldMap>",
   "description": "Internal Resistance High Threshold (Cell Entity 1 Threshold settings for a Cell 1)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3797,
   "name": "4977_<SeeDnldMap>",
   "description": "Intercell Resistance High Threshold (Cell Entity 1 Threshold settings for a Cell 1)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3808,
   "name": "4962_<SeeDnldMap>",
   "description": "Cell Voltage (Cell Entity 2)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3809,
   "name": "4963_<SeeDnldMap>",
   "description": "Cell Temperature (Cell Entity 2)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23809,
   "name": "4963_<SeeDnldMap>_deg_F",
   "description": "Cell Temperature (Cell Entity 2)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3810,
   "name": "5443_<SeeDnldMap>",
   "description": "Internal Resistance Value (Cell Entity 2)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3811,
   "name": "5444_<SeeDnldMap>",
   "description": "Intercell Resistance Value (Cell Entity 2)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3822,
   "name": "4971_<SeeDnldMap>",
   "description": "Cell Voltage Low Threshold (Cell Entity 2 Theshold Settings for a Cell 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3823,
   "name": "4972_<SeeDnldMap>",
   "description": "Cell Voltage High Threshold (Cell Entity 2 Theshold Settings for a Cell 1)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3824,
   "name": "4973_<SeeDnldMap>",
   "description": "Cell Temperature Low Threshold (Cell Entity 2 Theshold Settings for a Cell 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23824,
   "name": "4973_<SeeDnldMap>_deg_F",
   "description": "Cell Temperature Low Threshold (Cell Entity 2 Theshold Settings for a Cell 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3825,
   "name": "4974_<SeeDnldMap>",
   "description": "Cell Temperature High Threshold (Cell Entity 2 Theshold Settings for a Cell 1)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23825,
   "name": "4974_<SeeDnldMap>_deg_F",
   "description": "Cell Temperature High Threshold (Cell Entity 2 Theshold Settings for a Cell 1)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3826,
   "name": "4975_<SeeDnldMap>",
   "description": "Internal Resistance Low Threshold (Cell Entity 2 Theshold Settings for a Cell 1)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3827,
   "name": "4976_<SeeDnldMap>",
   "description": "Internal Resistance High Threshold (Cell Entity 2 Theshold Settings for a Cell 1)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3828,
   "name": "4977_<SeeDnldMap>",
   "description": "Intercell Resistance High Threshold (Cell Entity 2 Theshold Settings for a Cell 1)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14906,
   "name": "4962_<SeeDnldMap>",
   "description": "Cell Voltage (Cell Entity 360)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14907,
   "name": "4963_<SeeDnldMap>",
   "description": "Cell Temperature (Cell Entity 360)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34907,
   "name": "4963_<SeeDnldMap>_deg_F",
   "description": "Cell Temperature (Cell Entity 360)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14908,
   "name": "5443_<SeeDnldMap>",
   "description": "Internal Resistance Value (Cell Entity 360)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14909,
   "name": "5444_<SeeDnldMap>",
   "description": "Intercell Resistance Value (Cell Entity 360)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14920,
   "name": "4971_<SeeDnldMap>",
   "description": "Cell Voltage Low Threshold (Cell Entity 360 Threshold settings for a Cell)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14921,
   "name": "4972_<SeeDnldMap>",
   "description": "Cell Voltage High Threshold (Cell Entity 360 Threshold settings for a Cell)",
   "units": "VDC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14922,
   "name": "4973_<SeeDnldMap>",
   "description": "Cell Temperature Low Threshold (Cell Entity 360 Threshold settings for a Cell)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34922,
   "name": "4973_<SeeDnldMap>_deg_F",
   "description": "Cell Temperature Low Threshold (Cell Entity 360 Threshold settings for a Cell)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14923,
   "name": "4974_<SeeDnldMap>",
   "description": "Cell Temperature High Threshold (Cell Entity 360 Threshold settings for a Cell)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34923,
   "name": "4974_<SeeDnldMap>_deg_F",
   "description": "Cell Temperature High Threshold (Cell Entity 360 Threshold settings for a Cell)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14924,
   "name": "4975_<SeeDnldMap>",
   "description": "Internal Resistance Low Threshold (Cell Entity 360 Threshold settings for a Cell)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14925,
   "name": "4976_<SeeDnldMap>",
   "description": "Internal Resistance High Threshold (Cell Entity 360 Threshold settings for a Cell)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14926,
   "name": "4977_<SeeDnldMap>",
   "description": "Intercell Resistance High Threshold (Cell Entity 360 Threshold settings for a Cell)",
   "units": "microOhm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14937,
   "name": "4293_<SeeDnldMap>",
   "description": "System Date and Time",
   "units": "Secs since Epoch(UTC)",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "4123_<SeeDnldMap>",
   "description": "System Status",
   "units": "",
   "access": "R",
   "states": "1=Normal Operation, 2=StartUp, 3=Normal with Warning, 4=Normal with Alarm, 5=Abnormal Operation"
  },
  {
   "type": "MV",
   "instance": 12,
   "name": "5435_<SeeDnldMap>",
   "description": "Battery String Alarm Reset or Acknowledge (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "1=Reset, 2=Acknowledge"
  },
  {
   "type": "MV",
   "instance": 13,
   "name": "6548_<SeeDnldMap>",
   "description": "String Resistance Test Contact (String Entity 1)",
   "units": "",
   "access": "W",
   "states": "1=Stop, 2=Start"
  },
  {
   "type": "MV",
   "instance": 24,
   "name": "6549_<SeeDnldMap>",
   "description": "Maintenance Mode Status (String Entity 1 State of String 1)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 25,
   "name": "6550_<SeeDnldMap>",
   "description": "Discharge State (String Entity 1 State of String 1)",
   "units": "",
   "access": "R",
   "states": "1=Inactive, 2=Active, 3=Normalization"
  },
  {
   "type": "MV",
   "instance": 26,
   "name": "6551_<SeeDnldMap>",
   "description": "Resistance Test State (String Entity 1 State of String 1)",
   "units": "",
   "access": "R",
   "states": "1=Inactive, 2=Active, 3=Normalization"
  },
  {
   "type": "MV",
   "instance": 27,
   "name": "6552_<SeeDnldMap>",
   "description": "Battery String Status Summary (String Entity 1 State of String 1)",
   "units": "",
   "access": "R",
   "states": "1=Normal Operation, 2=Normal with Warning, 3=Normal with Alarm, 4=Abnormal Temperature Readings, 5=Abnormal Monitor Data Unavailable"
  },
  {
   "type": "MV",
   "instance": 23,
   "name": "5441_<SeeDnldMap>",
   "description": "Battery String Commissioned Status (String Entity 1 String Startup Information 1)",
   "units": "",
   "access": "R",
   "states": "1=Not Commissioned, 2=Commissioned"
  },
  {
   "type": "MV",
   "instance": 34,
   "name": "5435_<SeeDnldMap>",
   "description": "Battery String Alarm Reset or Acknowledge (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "1=Reset, 2=Acknowledge"
  },
  {
   "type": "MV",
   "instance": 35,
   "name": "6548_<SeeDnldMap>",
   "description": "String Resistance Test Contact (String Entity 2)",
   "units": "",
   "access": "W",
   "states": "1=Stop, 2=Start"
  },
  {
   "type": "MV",
   "instance": 46,
   "name": "6549_<SeeDnldMap>",
   "description": "Maintenance Mode Status (String Entity 2 State of String 1)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 47,
   "name": "6550_<SeeDnldMap>",
   "description": "Discharge State (String Entity 2 State of String 1)",
   "units": "",
   "access": "R",
   "states": "1=Inactive, 2=Active, 3=Normalization"
  },
  {
   "type": "MV",
   "instance": 48,
   "name": "6551_<SeeDnldMap>",
   "description": "Resistance Test State (String Entity 2 State of String 1)",
   "units": "",
   "access": "R",
   "states": "1=Inactive, 2=Active, 3=Normalization"
  },
  {
   "type": "MV",
   "instance": 49,
   "name": "6552_<SeeDnldMap>",
   "description": "Battery String Status Summary (String Entity 2 State of String 1)",
   "units": "",
   "access": "R",
   "states": "1=Normal Operation, 2=Normal with Warning, 3=Normal with Alarm, 4=Abnormal Temperature Readings, 5=Abnormal Monitor Data Unavailable"
  },
  {
   "type": "MV",
   "instance": 45,
   "name": "5441_<SeeDnldMap>",
   "description": "Battery String Commissioned Status (String Entity 2 String Startup Information 1)",
   "units": "",
   "access": "R",
   "states": "1=Not Commissioned, 2=Commissioned"
  },
  {
   "type": "MV",
   "instance": 694,
   "name": "5435_<SeeDnldMap>",
   "description": "Battery String Alarm Reset or Acknowledge (String Entity 32)",
   "units": "",
   "access": "W",
   "states": "1=Reset, 2=Acknowledge"
  },
  {
   "type": "MV",
   "instance": 695,
   "name": "6548_<SeeDnldMap>",
   "description": "String Resistance Test Contact (String Entity 32)",
   "units": "",
   "access": "W",
   "states": "1=Stop, 2=Start"
  },
  {
   "type": "MV",
   "instance": 706,
   "name": "6549_<SeeDnldMap>",
   "description": "Maintenance Mode Status (String Entity 32 State of String 1)",
   "units": "",
   "access": "R",
   "states": "1=false, 2=true"
  },
  {
   "type": "MV",
   "instance": 707,
   "name": "6550_<SeeDnldMap>",
   "description": "Discharge State (String Entity 32 State of String 1)",
   "units": "",
   "access": "R",
   "states": "1=Inactive, 2=Active, 3=Normalization"
  },
  {
   "type": "MV",
   "instance": 708,
   "name": "6551_<SeeDnldMap>",
   "description": "Resistance Test State (String Entity 32 State of String 1)",
   "units": "",
   "access": "R",
   "states": "1=Inactive, 2=Active, 3=Normalization"
  },
  {
   "type": "MV",
   "instance": 709,
   "name": "6552_<SeeDnldMap>",
   "description": "Battery String Status Summary (String Entity 32 State of String 1)",
   "units": "",
   "access": "R",
   "states": "1=Normal Operation, 2=Normal with Warning, 3=Normal with Alarm, 4=Abnormal Temperature Readings, 5=Abnormal Monitor Data Unavailable"
  },
  {
   "type": "MV",
   "instance": 705,
   "name": "5441_<SeeDnldMap>",
   "description": "Battery String Commissioned Status (String Entity 32 String Startup Information 1)",
   "units": "",
   "access": "R",
   "states": "1=Not Commissioned, 2=Commissioned"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/vertiv/alber-bdsu",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}