 "manufacturer": "Vector Controls",
 "manufacturer_slug": "vector-controls",
 "model": "X2 controllers with BACnet IP (CS2-BAC-001)",
 "model_slug": "x2-bacnet-ip",
 "aliases": [
  "X2-BAC IP",
  "CS2-BAC-001",
  "X2 BACnet IP",
  "TCX2",
  "TCI2",
  "SxC2",
  "TRI2",
  "X2 Wi-Fi BACnet"
 ],
 "equipment_type": "Thermostat / room controller",
 "applies_to": "Vector Controls X2 family controllers fitted with the CS2-BAC-001 BACnet IP (Ethernet / Wi-Fi) communication module.",
 "summary": "The X2 BACnet IP module exposes the same core objects as the MS/TP module (controller state, inputs, loops, outputs, fans, alarms) plus the twelve time schedules as objects and fan lead-lag timers. Objects only appear for the I/O the specific X2 product has.",
 "bacnet_transport": [
  "BACnet IP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Objects are created only for the inputs, outputs, loops and alarms the X2 product actually has; the datasheet scope table says which exist.",
  "Digital output objects depend on how each output is configured (fan, 3-point floating, PWM or binary); the same instance can appear in several of these tables, listed here once.",
  "Alarm MVs (601-608) can only be written to Not Active when the alarm is waiting for confirmation.",
  "Other controller parameters are reached through ParAdd/ParValue (an address + value pair), not as separate objects.",
  "Each of the 12 time schedules has TYPE, NR (group ID) and DAYS MVs and TIME and SP AVs; in holiday mode the same schedule uses the HDAY/HMONTH start/end AVs.",
  "Object names in the controller-state block differ from the MS/TP module (e.g. MV 0 Occupation instead of OpStCoSt), and ParAdd/ParValue are AV 0/AV 1 here."
 ],
 "source": {
  "title": "X2 BACnet IP",
  "doc_number": "70-00-0899C V1.2",
  "revision_date": "2026-08-26",
  "url": "https://vectorcontrols.com/application/files/2417/8775/4816/70-00-0899C_X2_BACnetIP_V1_2.pdf"
 },
 "integration": {
  "summary": "Use BV 0 for on/off and MV 0 for occupancy, write loop set points (AV 211 for loop 1) and read inputs, loop outputs and alarms. Time schedules can be set over BACnet through the TS objects.",
  "minimum_points": [
   {
    "ref": "BV 0",
    "name": "OpStOo",
    "why": "Controller on/off"
   },
   {
    "ref": "MV 0",
    "name": "Occupation",
    "why": "Occupied / unoccupied"
   },
   {
    "ref": "MV 1",
    "name": "Ctrl-Mode",
    "why": "Cool / heat mode"
   },
   {
    "ref": "AV 211",
    "name": "LP-01-SSP",
    "why": "Loop 1 set point"
   },
   {
    "ref": "AI 101",
    "name": "UI-01",
    "why": "Universal input 1 (e.g. room temperature)"
   },
   {
    "ref": "MV 211",
    "name": "LP-01-ST",
    "why": "Loop 1 state"
   },
   {
    "ref": "AV 213",
    "name": "LP-01-PROP",
    "why": "Loop 1 output, %"
   },
   {
    "ref": "MV 601",
    "name": "AL-01",
    "why": "Alarm 1 state"
   }
  ],
  "enable": "BV 3-7 lock or unlock local access to modes, set points, manual control, heat/cool change and time programs.",
  "heartbeat": "Virtual inputs (AV 109-116) set to the communication module must be rewritten within the controller's timeout, or the input and its functions are disabled.",
  "remote_sensors": "Write sensor values to the virtual inputs VI-01..VI-04 (AV 109, 111, 113, 115) when they are set to the communication module.",
  "setup": [
   "IPv4 address and DHCP on/off are set in the controller's COM parameters."
  ],
  "gotchas": [
   "Temperature units follow MV 2 (Temp-Unit)."
  ]
 },
 "points": [
  {
   "type": "BV",
   "instance": 0,
   "name": "OpStOo",
   "description": "Operation state",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "MV",
   "instance": 0,
   "name": "Occupation",
   "description": "Operation state Occupied/Unoccupied",
   "units": "",
   "access": "W",
   "states": "1=Occupied, 2=Unoccupied"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "Ctrl-Mode",
   "description": "Operation state Cool/Heat",
   "units": "",
   "access": "W",
   "states": "1=Cool, 2=Heat"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "Temp-Unit",
   "description": "Operation state Celsius/Fahrenheit",
   "units": "",
   "access": "W",
   "states": "1=Celsius, 2=Fahrenheit"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "FanOnly",
   "description": "Operation state Fan Only",
   "units": "",
   "access": "W",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "Schedule",
   "description": "Operation state Time Schedules",
   "units": "",
   "access": "W",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "AccOpMod",
   "description": "Enable access to operation modes",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "AccSp",
   "description": "Enable access to set points",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "AccMan",
   "description": "Enable manual control in cascade and for fan speeds",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "AccHeCo",
   "description": "Enable change of heating/cooling mode for 2 pipe systems",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "AccSchd",
   "description": "Enable access to time programs",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "OPA-Mode",
   "description": "Operation State Master/Slave mode",
   "units": "",
   "access": "W",
   "states": "1=Master, 2=Slave"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "Wink",
   "description": "Operation State “Wink” function",
   "units": "",
   "access": "W",
   "states": "1=Wink OFF, 2=Wink ON"
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "Season",
   "description": "Operation State Summer/Winter mode",
   "units": "",
   "access": "W",
   "states": "1=Summer, 2=Winter"
  },
  {
   "type": "AI",
   "instance": 101,
   "name": "UI-01",
   "description": "Universal input 1 value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 101,
   "name": "UI-01-OS",
   "description": "Universal input 1 offset (calibration = 01u6)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 102,
   "name": "UI-02",
   "description": "Universal input 2 value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 102,
   "name": "UI-02-OS",
   "description": "Universal input 2 offset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 103,
   "name": "UI-03",
   "description": "Universal input 3 value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "UI-03-OS",
   "description": "Universal input 3 offset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 104,
   "name": "UI-04",
   "description": "Universal input 4 value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 104,
   "name": "UI-04-OS",
   "description": "Universal input 4 offset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 105,
   "name": "UI-05",
   "description": "Universal input 5 value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 105,
   "name": "UI-05-OS",
   "description": "Universal input 5 offset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 106,
   "name": "UI-06",
   "description": "Universal input 6 value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 106,
   "name": "UI-06-OS",
   "description": "Universal input 6 offset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 107,
   "name": "UI-07",
   "description": "Universal input 7 value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 107,
   "name": "UI-07-OS",
   "description": "Universal input 7 offset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 108,
   "name": "UI-08",
   "description": "Universal input 8 value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 108,
   "name": "UI-08-OS",
   "description": "Universal input 8 Offset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 109,
   "name": "VI-01",
   "description": "Virtual input 1 value",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 110,
   "name": "VI-01-OS",
   "description": "Virtual input 1 offset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 111,
   "name": "VI-02",
   "description": "Virtual input 2 value",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 112,
   "name": "VI-02-OS",
   "description": "Virtual input 2 offset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 113,
   "name": "VI-03",
   "description": "Virtual input 3 value",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 114,
   "name": "VI-03-OS",
   "description": "Virtual input 3 offset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 115,
   "name": "VI-04",
   "description": "Virtual input 4 value",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 116,
   "name": "VI-04-OS",
   "description": "Virtual input 4 offset",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 601,
   "name": "AL-01",
   "description": "Alarm 1",
   "units": "",
   "access": "W",
   "states": "1=Not Active, 2=Active, 3=Need confirmation"
  },
  {
   "type": "MV",
   "instance": 602,
   "name": "AL-02",
   "description": "Alarm 2",
   "units": "",
   "access": "W",
   "states": "1=Not Active, 2=Active, 3=Need confirmation"
  },
  {
   "type": "MV",
   "instance": 603,
   "name": "AL-03",
   "description": "Alarm 3",
   "units": "",
   "access": "W",
   "states": "1=Not Active, 2=Active, 3=Need confirmation"
  },
  {
   "type": "MV",
   "instance": 604,
   "name": "AL-04",
   "description": "Alarm 4",
   "units": "",
   "access": "W",
   "states": "1=Not Active, 2=Active, 3=Need confirmation"
  },
  {
   "type": "MV",
   "instance": 605,
   "name": "AL-05",
   "description": "Alarm 5",
   "units": "",
   "access": "W",
   "states": "1=Not Active, 2=Active, 3=Need confirmation"
  },
  {
   "type": "MV",
   "instance": 606,
   "name": "AL-06",
   "description": "Alarm 6",
   "units": "",
   "access": "W",
   "states": "1=Not Active, 2=Active, 3=Need confirmation"
  },
  {
   "type": "MV",
   "instance": 607,
   "name": "AL-07",
   "description": "Alarm 7",
   "units": "",
   "access": "W",
   "states": "1=Not Active, 2=Active, 3=Need confirmation"
  },
  {
   "type": "MV",
   "instance": 608,
   "name": "AL-08",
   "description": "Alarm 8",
   "units": "",
   "access": "W",
   "states": "1=Not Active, 2=Active, 3=Need confirmation"
  },
  {
   "type": "MV",
   "instance": 211,
   "name": "LP-01-ST",
   "description": "Loop 1 state",
   "units": "",
   "access": "R",
   "states": "1=Disabled, 2=Heating, 3=Cooling"
  },
  {
   "type": "AV",
   "instance": 211,
   "name": "LP-01-SSP",
   "description": "Loop 1 saved set point",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 212,
   "name": "LP-01-CSP",
   "description": "Loop 1 calculated set point",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 213,
   "name": "LP-01-PROP",
   "description": "Loop 1 proportional output 0-100%",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 212,
   "name": "LP-01-DO",
   "description": "Loop 1 binary output: Activated binary stage",
   "units": "",
   "access": "R",
   "states": "1=SOFF, 2=S01, 3=S02, 4=S03, …, 64=S63"
  },
  {
   "type": "MV",
   "instance": 221,
   "name": "LP-02-ST",
   "description": "Loop 2 state",
   "units": "",
   "access": "R",
   "states": "1=Disabled, 2=Heating, 3=Cooling"
  },
  {
   "type": "AV",
   "instance": 221,
   "name": "LP-02-SSP",
   "description": "Loop 2 saved set point",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 222,
   "name": "LP-02-CSP",
   "description": "Loop 2 calculated set point",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 223,
   "name": "LP-02-PROP",
   "description": "Loop 2 proportional output 0-100%",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 222,
   "name": "LP-02-DO",
   "description": "Loop 2 binary output: Activated binary stage",
   "units": "",
   "access": "R",
   "states": "1=SOFF, 2=S01, 3=S02, 4=S03, …, 64=S63"
  },
  {
   "type": "MV",
   "instance": 231,
   "name": "LP-03-ST",
   "description": "Loop 3 state",
   "units": "",
   "access": "R",
   "states": "1=Disabled, 2=Heating, 3=Cooling"
  },
  {
   "type": "AV",
   "instance": 231,
   "name": "LP-03-SSP",
   "description": "Loop 3 saved set point",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 232,
   "name": "LP-03-CSP",
   "description": "Loop 3 calculated set point",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 233,
   "name": "LP-03-PROP",
   "description": "Loop 3 proportional output 0-100%",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 232,
   "name": "LP-03-DO",
   "description": "Loop 3 binary output: Activated binary stage",
   "units": "",
   "access": "R",
   "states": "1=SOFF, 2=S01, 3=S02, 4=S03, …, 64=S63"
  },
  {
   "type": "MV",
   "instance": 241,
   "name": "LP-04-ST",
   "description": "Loop 4 state",
   "units": "",
   "access": "R",
   "states": "1=Disabled, 2=Heating, 3=Cooling"
  },
  {
   "type": "AV",
   "instance": 241,
   "name": "LP-04-SSP",
   "description": "Loop 4 saved set point",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 242,
   "name": "LP-04-CSP",
   "description": "Loop 4 calculated set point",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 243,
   "name": "LP-04-PROP",
   "description": "Loop 4 proportional output 0-100%",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 242,
   "name": "LP-04-DO",
   "description": "Loop 4 binary output: Activated binary stage",
   "units": "",
   "access": "R",
   "states": "1=SOFF, 2=S01, 3=S02, 4=S03, …, 64=S63"
  },
  {
   "type": "MV",
   "instance": 311,
   "name": "AO-01-ST",
   "description": "Analog output 1 state",
   "units": "",
   "access": "W",
   "states": "1=Disabled, 2=Normal, 3=Manual, 4=Override"
  },
  {
   "type": "AV",
   "instance": 311,
   "name": "AO-01-VAL",
   "description": "Analog output 1 value",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 312,
   "name": "AO-01-OV",
   "description": "Analog output 1 override value",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 321,
   "name": "AO-02-ST",
   "description": "Analog output 2 state",
   "units": "",
   "access": "W",
   "states": "1=Disabled, 2=Normal, 3=Manual, 4=Override"
  },
  {
   "type": "AV",
   "instance": 321,
   "name": "AO-02-VAL",
   "description": "Analog output 2 value",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 322,
   "name": "AO-02-OV",
   "description": "Analog output 2 override value",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 331,
   "name": "AO-03-ST",
   "description": "Analog output 3 state",
   "units": "",
   "access": "W",
   "states": "1=Disabled, 2=Normal, 3=Manual, 4=Override"
  },
  {
   "type": "AV",
   "instance": 331,
   "name": "AO-03-VAL",
   "description": "Analog output 3 value",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 332,
   "name": "AO-03-OV",
   "description": "Analog output 3 override value",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 411,
   "name": "DO-01-FLT",
   "description": "DO 1 value in 3-point floating (DO1 open / DO2 close)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 412,
   "name": "DO-01-FLT-OV",
   "description": "DO 1 override value in analog mode 3-point floating",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 411,
   "name": "DO-01-ST",
   "description": "Current State for DO 1",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=Normal, 3=Manual, 4=Override"
  },
  {
   "type": "AV",
   "instance": 431,
   "name": "DO-03-FLT",
   "description": "DO 3 value in 3-point floating (DO3 open / DO4 close)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 432,
   "name": "DO-03-FLT-OV",
   "description": "DO 3 override value in 3-point floating",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 431,
   "name": "DO-03-ST",
   "description": "Current State for DO 3",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=Normal, 3=Manual, 4=Override"
  },
  {
   "type": "AV",
   "instance": 451,
   "name": "DO-05-FLT",
   "description": "DO 5 value in 3-point floating (DO5 open / DO6 close)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 452,
   "name": "DO-05-FLT-OV",
   "description": "DO 5 override value in 3-point floating",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 451,
   "name": "DO-05-ST",
   "description": "Current State for DO 5",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=Normal, 3=Manual, 4=Override"
  },
  {
   "type": "AV",
   "instance": 413,
   "name": "DO-01-PWM",
   "description": "DO 1 in PWM from 0-100%",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 414,
   "name": "DO-01-PWM-OV",
   "description": "DO 1 override value in PWM from 0-100%",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 423,
   "name": "DO-02-PWM",
   "description": "DO 2 in PWM from 0-100%",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 424,
   "name": "DO-02-PWM-OV",
   "description": "DO 2 override value in PWM from 0-100%",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 421,
   "name": "DO-02-ST",
   "description": "Current State for DO 2",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=Normal, 3=Manual, 4=Override"
  },
  {
   "type": "AV",
   "instance": 433,
   "name": "DO-03-PWM",
   "description": "DO 3 in PWM from 0-100%",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 434,
   "name": "DO-03-PWM-OV",
   "description": "DO 3 override value in PWM from 0-100%",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 443,
   "name": "DO-04-PWM",
   "description": "DO 4 in PWM from 0-100%",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 444,
   "name": "DO-04-PWM-OV",
   "description": "DO 4 override value in PWM from 0-100%",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 441,
   "name": "DO-04-ST",
   "description": "Current State for DO 4",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=Normal, 3=Manual, 4=Override"
  },
  {
   "type": "AV",
   "instance": 453,
   "name": "DO-05-PWM",
   "description": "DO 5 in PWM from 0-100%",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 454,
   "name": "DO-05-PWM-OV",
   "description": "DO 5 override value in PWM from 0-100%",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 463,
   "name": "DO-06-PWM",
   "description": "DO 6 in PWM from 0-100%",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 464,
   "name": "DO-06-PWM-OV",
   "description": "DO 6 override value in PWM from 0-100%",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 461,
   "name": "DO-06-ST",
   "description": "Current State for DO 6",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=Normal, 3=Manual, 4=Override"
  },
  {
   "type": "AV",
   "instance": 473,
   "name": "DO-07-PWM",
   "description": "DO 7 in PWM from 0-100%",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 474,
   "name": "DO-07-PWM-OV",
   "description": "DO 7 override value in PWM from 0-100%",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 471,
   "name": "DO-07-ST",
   "description": "Current State for DO 7",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=Normal, 3=Manual, 4=Override"
  },
  {
   "type": "BV",
   "instance": 411,
   "name": "DO-01-BIN",
   "description": "DO 1 in binary",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 412,
   "name": "DO-01-BIN-OV",
   "description": "DO 1 override value in binary",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AV",
   "instance": 511,
   "name": "DO-01-RT",
   "description": "Run time totalizer in hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 511,
   "name": "DO-01-ALA",
   "description": "Run time limit exceeded",
   "units": "",
   "access": "R",
   "states": "0=No Error, 1=RT Limit Reached"
  },
  {
   "type": "BV",
   "instance": 421,
   "name": "DO-02-BIN",
   "description": "DO 2 in binary",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 422,
   "name": "DO-02-BIN-OV",
   "description": "DO 2 override value in binary",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AV",
   "instance": 521,
   "name": "DO-02-RT",
   "description": "Run time totalizer in hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 521,
   "name": "DO-02-ALA",
   "description": "Run time limit exceeded",
   "units": "",
   "access": "R",
   "states": "0=No Error, 1=RT Limit Reached"
  },
  {
   "type": "BV",
   "instance": 431,
   "name": "DO-03-BIN",
   "description": "DO 3 in binary",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 432,
   "name": "DO-03-BIN-OV",
   "description": "DO 3 override value in binary",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AV",
   "instance": 531,
   "name": "DO-03-RT",
   "description": "Run time totalizer in hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 531,
   "name": "DO-03-ALA",
   "description": "Run time limit exceeded",
   "units": "",
   "access": "R",
   "states": "0=No Error, 1=RT Limit Reached"
  },
  {
   "type": "BV",
   "instance": 441,
   "name": "DO-04-BIN",
   "description": "DO 4 in binary",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 442,
   "name": "DO-04-BIN-OV",
   "description": "DO 4 override value in binary",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AV",
   "instance": 541,
   "name": "DO-04-RT",
   "description": "Run time totalizer in hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 541,
   "name": "DO-04-ALA",
   "description": "Run time limit exceeded",
   "units": "",
   "access": "R",
   "states": "0=No Error, 1=RT Limit Reached"
  },
  {
   "type": "BV",
   "instance": 451,
   "name": "DO-05-BIN",
   "description": "DO 5 in binary",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 452,
   "name": "DO-05-BIN-OV",
   "description": "DO 5 override value in binary",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AV",
   "instance": 551,
   "name": "DO-05-RT",
   "description": "Run time totalizer in hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 551,
   "name": "DO-05-ALA",
   "description": "Run time limit exceeded",
   "units": "",
   "access": "R",
   "states": "0=No Error, 1=RT Limit Reached"
  },
  {
   "type": "BV",
   "instance": 461,
   "name": "DO-06-BIN",
   "description": "DO 6 in binary",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 462,
   "name": "DO-06-BIN-OV",
   "description": "DO 6 override value in binary",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AV",
   "instance": 561,
   "name": "DO-06-RT",
   "description": "Run time totalizer in hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 561,
   "name": "DO-06-ALA",
   "description": "Run time limit exceeded",
   "units": "",
   "access": "R",
   "states": "0=No Error, 1=RT Limit Reached"
  },
  {
   "type": "BV",
   "instance": 471,
   "name": "DO-07-BIN",
   "description": "DO 7 in binary",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 472,
   "name": "DO-07-BIN-OV",
   "description": "DO 7 override value in binary",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AV",
   "instance": 571,
   "name": "DO-07-RT",
   "description": "Run time totalizer in hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 571,
   "name": "DO-07-ALA",
   "description": "Run time limit exceeded",
   "units": "",
   "access": "R",
   "states": "0=No Error, 1=RT Limit Reached"
  },
  {
   "type": "MV",
   "instance": 412,
   "name": "FAN1",
   "description": "AO1 fan value (FAN1)",
   "units": "",
   "access": "R",
   "states": "1=OFF, 2=Stage 1, 3=Stage 2, 4=Stage 3"
  },
  {
   "type": "MV",
   "instance": 413,
   "name": "FAN1-OV",
   "description": "AO1 fan override value (FAN1)",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=Stage 1, 3=Stage 2, 4=Stage 3, 5=AUTO"
  },
  {
   "type": "MV",
   "instance": 414,
   "name": "FAN1-ST",
   "description": "FAN1 state description",
   "units": "",
   "access": "W",
   "states": "1=Disabled, 2=Normal, 3=Manual, 4=Override"
  },
  {
   "type": "MV",
   "instance": 442,
   "name": "FAN2",
   "description": "AO2 fan value (FAN2)",
   "units": "",
   "access": "R",
   "states": "1=OFF, 2=Stage 1, 3=Stage 2, 4=Stage 3"
  },
  {
   "type": "MV",
   "instance": 443,
   "name": "FAN2-OV",
   "description": "AO2 fan override value (FAN2)",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=Stage 1, 3=Stage 2, 4=Stage 3, 5=AUTO"
  },
  {
   "type": "MV",
   "instance": 444,
   "name": "FAN2-ST",
   "description": "FAN2 state description",
   "units": "",
   "access": "W",
   "states": "1=Disabled, 2=Normal, 3=Manual, 4=Override"
  },
  {
   "type": "AV",
   "instance": 415,
   "name": "FAN1-LL-TIME",
   "description": "FAN1 remaining time until next rotation in hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 445,
   "name": "FAN2-LL-TIME",
   "description": "FAN2 remaining time until next rotation in hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 711,
   "name": "TS1-TYPE",
   "description": "Type of time schedule object",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=OP (Operation mode), 3=LP (Control loop set point), 4=AO (Analog output set point), 5=FAN (Fan output), 6=DO (Digital output), 7=HDAY (Holiday)"
  },
  {
   "type": "MV",
   "instance": 712,
   "name": "TS1-NR",
   "description": "Type group ID - Valid only for the following types",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 713,
   "name": "TS1-DAYS",
   "description": "Active days",
   "units": "",
   "access": "W",
   "states": "1=No days, 2=Day 1 – Day 7, 3=Day 1 – Day 6, 4=Day 1 – Day 5, 5=Day 6 – Day 7, 6=Day 1, 7=Day 2, 8=Day 3, 9=Day 4, 10=Day 5, 11=Day 6, 12=Day 7, 13=other combination of active days (read-only)"
  },
  {
   "type": "AV",
   "instance": 711,
   "name": "TS1-TIME",
   "description": "Time (rounded to 0.25 hours, e.g. 5.25h)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 712,
   "name": "TS1-SP",
   "description": "Set point of time schedule",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 721,
   "name": "TS2-TYPE",
   "description": "Type of time schedule object",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=OP (Operation mode), 3=LP (Control loop set point), 4=AO (Analog output set point), 5=FAN (Fan output), 6=DO (Digital output), 7=HDAY (Holiday)"
  },
  {
   "type": "MV",
   "instance": 722,
   "name": "TS2-NR",
   "description": "Type group ID",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 723,
   "name": "TS2-DAYS",
   "description": "Active days",
   "units": "",
   "access": "W",
   "states": "1=No days, 2=Day 1 – Day 7, 3=Day 1 – Day 6, 4=Day 1 – Day 5, 5=Day 6 – Day 7, 6=Day 1, 7=Day 2, 8=Day 3, 9=Day 4, 10=Day 5, 11=Day 6, 12=Day 7, 13=other combination of active days (read-only)"
  },
  {
   "type": "AV",
   "instance": 721,
   "name": "TS2-TIME",
   "description": "Time (rounded to 0.25 hours, e.g. 5.25h)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 722,
   "name": "TS2-SP",
   "description": "Set point of time schedule",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 731,
   "name": "TS3-TYPE",
   "description": "Type of time schedule object",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=OP (Operation mode), 3=LP (Control loop set point), 4=AO (Analog output set point), 5=FAN (Fan output), 6=DO (Digital output), 7=HDAY (Holiday)"
  },
  {
   "type": "MV",
   "instance": 732,
   "name": "TS3-NR",
   "description": "Type group ID",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 733,
   "name": "TS3-DAYS",
   "description": "Active days",
   "units": "",
   "access": "W",
   "states": "1=No days, 2=Day 1 – Day 7, 3=Day 1 – Day 6, 4=Day 1 – Day 5, 5=Day 6 – Day 7, 6=Day 1, 7=Day 2, 8=Day 3, 9=Day 4, 10=Day 5, 11=Day 6, 12=Day 7, 13=other combination of active days (read-only)"
  },
  {
   "type": "AV",
   "instance": 731,
   "name": "TS3-TIME",
   "description": "Time (rounded to 0.25 hours, e.g. 5.25h)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 732,
   "name": "TS3-SP",
   "description": "Set point of time schedule",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 741,
   "name": "TS4-TYPE",
   "description": "Type of time schedule object",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=OP (Operation mode), 3=LP (Control loop set point), 4=AO (Analog output set point), 5=FAN (Fan output), 6=DO (Digital output), 7=HDAY (Holiday)"
  },
  {
   "type": "MV",
   "instance": 742,
   "name": "TS4-NR",
   "description": "Type group ID",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 743,
   "name": "TS4-DAYS",
   "description": "Active days",
   "units": "",
   "access": "W",
   "states": "1=No days, 2=Day 1 – Day 7, 3=Day 1 – Day 6, 4=Day 1 – Day 5, 5=Day 6 – Day 7, 6=Day 1, 7=Day 2, 8=Day 3, 9=Day 4, 10=Day 5, 11=Day 6, 12=Day 7, 13=other combination of active days (read-only)"
  },
  {
   "type": "AV",
   "instance": 741,
   "name": "TS4-TIME",
   "description": "Time (rounded to 0.25 hours, e.g. 5.25h)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 742,
   "name": "TS4-SP",
   "description": "Set point of time schedule",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 751,
   "name": "TS5-TYPE",
   "description": "Type of time schedule object",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=OP (Operation mode), 3=LP (Control loop set point), 4=AO (Analog output set point), 5=FAN (Fan output), 6=DO (Digital output), 7=HDAY (Holiday)"
  },
  {
   "type": "MV",
   "instance": 752,
   "name": "TS5-NR",
   "description": "Type group ID",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 753,
   "name": "TS5-DAYS",
   "description": "Active days",
   "units": "",
   "access": "W",
   "states": "1=No days, 2=Day 1 – Day 7, 3=Day 1 – Day 6, 4=Day 1 – Day 5, 5=Day 6 – Day 7, 6=Day 1, 7=Day 2, 8=Day 3, 9=Day 4, 10=Day 5, 11=Day 6, 12=Day 7, 13=other combination of active days (read-only)"
  },
  {
   "type": "AV",
   "instance": 751,
   "name": "TS5-TIME",
   "description": "Time (rounded to 0.25 hours, e.g. 5.25h)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 752,
   "name": "TS5-SP",
   "description": "Set point of time schedule",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 761,
   "name": "TS6-TYPE",
   "description": "Type of time schedule object",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=OP (Operation mode), 3=LP (Control loop set point), 4=AO (Analog output set point), 5=FAN (Fan output), 6=DO (Digital output), 7=HDAY (Holiday)"
  },
  {
   "type": "MV",
   "instance": 762,
   "name": "TS6-NR",
   "description": "Type group ID",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 763,
   "name": "TS6-DAYS",
   "description": "Active days",
   "units": "",
   "access": "W",
   "states": "1=No days, 2=Day 1 – Day 7, 3=Day 1 – Day 6, 4=Day 1 – Day 5, 5=Day 6 – Day 7, 6=Day 1, 7=Day 2, 8=Day 3, 9=Day 4, 10=Day 5, 11=Day 6, 12=Day 7, 13=other combination of active days (read-only)"
  },
  {
   "type": "AV",
   "instance": 761,
   "name": "TS6-TIME",
   "description": "Time (rounded to 0.25 hours, e.g. 5.25h)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 762,
   "name": "TS6-SP",
   "description": "Set point of time schedule",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 771,
   "name": "TS7-TYPE",
   "description": "Type of time schedule object",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=OP (Operation mode), 3=LP (Control loop set point), 4=AO (Analog output set point), 5=FAN (Fan output), 6=DO (Digital output), 7=HDAY (Holiday)"
  },
  {
   "type": "MV",
   "instance": 772,
   "name": "TS7-NR",
   "description": "Type group ID",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 773,
   "name": "TS7-DAYS",
   "description": "Active days",
   "units": "",
   "access": "W",
   "states": "1=No days, 2=Day 1 – Day 7, 3=Day 1 – Day 6, 4=Day 1 – Day 5, 5=Day 6 – Day 7, 6=Day 1, 7=Day 2, 8=Day 3, 9=Day 4, 10=Day 5, 11=Day 6, 12=Day 7, 13=other combination of active days (read-only)"
  },
  {
   "type": "AV",
   "instance": 771,
   "name": "TS7-TIME",
   "description": "Time (rounded to 0.25 hours, e.g. 5.25h)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 772,
   "name": "TS7-SP",
   "description": "Set point of time schedule",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 781,
   "name": "TS8-TYPE",
   "description": "Type of time schedule object",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=OP (Operation mode), 3=LP (Control loop set point), 4=AO (Analog output set point), 5=FAN (Fan output), 6=DO (Digital output), 7=HDAY (Holiday)"
  },
  {
   "type": "MV",
   "instance": 782,
   "name": "TS8-NR",
   "description": "Type group ID",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 783,
   "name": "TS8-DAYS",
   "description": "Active days",
   "units": "",
   "access": "W",
   "states": "1=No days, 2=Day 1 – Day 7, 3=Day 1 – Day 6, 4=Day 1 – Day 5, 5=Day 6 – Day 7, 6=Day 1, 7=Day 2, 8=Day 3, 9=Day 4, 10=Day 5, 11=Day 6, 12=Day 7, 13=other combination of active days (read-only)"
  },
  {
   "type": "AV",
   "instance": 781,
   "name": "TS8-TIME",
   "description": "Time (rounded to 0.25 hours, e.g. 5.25h)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 782,
   "name": "TS8-SP",
   "description": "Set point of time schedule",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 791,
   "name": "TS9-TYPE",
   "description": "Type of time schedule object",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=OP (Operation mode), 3=LP (Control loop set point), 4=AO (Analog output set point), 5=FAN (Fan output), 6=DO (Digital output), 7=HDAY (Holiday)"
  },
  {
   "type": "MV",
   "instance": 792,
   "name": "TS9-NR",
   "description": "Type group ID",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 793,
   "name": "TS9-DAYS",
   "description": "Active days",
   "units": "",
   "access": "W",
   "states": "1=No days, 2=Day 1 – Day 7, 3=Day 1 – Day 6, 4=Day 1 – Day 5, 5=Day 6 – Day 7, 6=Day 1, 7=Day 2, 8=Day 3, 9=Day 4, 10=Day 5, 11=Day 6, 12=Day 7, 13=other combination of active days (read-only)"
  },
  {
   "type": "AV",
   "instance": 791,
   "name": "TS9-TIME",
   "description": "Time (rounded to 0.25 hours, e.g. 5.25h)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 792,
   "name": "TS9-SP",
   "description": "Set point of time schedule",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 801,
   "name": "TS10-TYPE",
   "description": "Type of time schedule object",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=OP (Operation mode), 3=LP (Control loop set point), 4=AO (Analog output set point), 5=FAN (Fan output), 6=DO (Digital output), 7=HDAY (Holiday)"
  },
  {
   "type": "MV",
   "instance": 802,
   "name": "TS10-NR",
   "description": "Type group ID",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 803,
   "name": "TS10-DAYS",
   "description": "Active days",
   "units": "",
   "access": "W",
   "states": "1=No days, 2=Day 1 – Day 7, 3=Day 1 – Day 6, 4=Day 1 – Day 5, 5=Day 6 – Day 7, 6=Day 1, 7=Day 2, 8=Day 3, 9=Day 4, 10=Day 5, 11=Day 6, 12=Day 7, 13=other combination of active days (read-only)"
  },
  {
   "type": "AV",
   "instance": 801,
   "name": "TS10-TIME",
   "description": "Time (rounded to 0.25 hours, e.g. 5.25h)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 802,
   "name": "TS10-SP",
   "description": "Set point of time schedule",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 811,
   "name": "TS11-TYPE",
   "description": "Type of time schedule object",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=OP (Operation mode), 3=LP (Control loop set point), 4=AO (Analog output set point), 5=FAN (Fan output), 6=DO (Digital output), 7=HDAY (Holiday)"
  },
  {
   "type": "MV",
   "instance": 812,
   "name": "TS11-NR",
   "description": "Type group ID",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 813,
   "name": "TS11-DAYS",
   "description": "Active days",
   "units": "",
   "access": "W",
   "states": "1=No days, 2=Day 1 – Day 7, 3=Day 1 – Day 6, 4=Day 1 – Day 5, 5=Day 6 – Day 7, 6=Day 1, 7=Day 2, 8=Day 3, 9=Day 4, 10=Day 5, 11=Day 6, 12=Day 7, 13=other combination of active days (read-only)"
  },
  {
   "type": "AV",
   "instance": 811,
   "name": "TS11-TIME",
   "description": "Time (rounded to 0.25 hours, e.g. 5.25h)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 812,
   "name": "TS11-SP",
   "description": "Set point of time schedule",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 821,
   "name": "TS12-TYPE",
   "description": "Type of time schedule object",
   "units": "",
   "access": "W",
   "states": "1=OFF, 2=OP (Operation mode), 3=LP (Control loop set point), 4=AO (Analog output set point), 5=FAN (Fan output), 6=DO (Digital output), 7=HDAY (Holiday)"
  },
  {
   "type": "MV",
   "instance": 822,
   "name": "TS12-NR",
   "description": "Type group ID",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 823,
   "name": "TS12-DAYS",
   "description": "Active days",
   "units": "",
   "access": "W",
   "states": "1=No days, 2=Day 1 – Day 7, 3=Day 1 – Day 6, 4=Day 1 – Day 5, 5=Day 6 – Day 7, 6=Day 1, 7=Day 2, 8=Day 3, 9=Day 4, 10=Day 5, 11=Day 6, 12=Day 7, 13=other combination of active days (read-only)"
  },
  {
   "type": "AV",
   "instance": 821,
   "name": "TS12-TIME",
   "description": "Time (rounded to 0.25 hours, e.g. 5.25h)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 822,
   "name": "TS12-SP",
   "description": "Set point of time schedule",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 713,
   "name": "TS1-HDAY-START",
   "description": "Start day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 714,
   "name": "TS1-HMONTH-START",
   "description": "Start month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 715,
   "name": "TS1-HDAY-END",
   "description": "End day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 716,
   "name": "TS1-HMONTH-END",
   "description": "End month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 723,
   "name": "TS2-HDAY-START",
   "description": "Start day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 724,
   "name": "TS2-HMONTH-START",
   "description": "Start month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 725,
   "name": "TS2-HDAY-END",
   "description": "End day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 726,
   "name": "TS2-HMONTH-END",
   "description": "End month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 733,
   "name": "TS3-HDAY-START",
   "description": "Start day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 734,
   "name": "TS3-HMONTH-START",
   "description": "Start month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 735,
   "name": "TS3-HDAY-END",
   "description": "End day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 736,
   "name": "TS3-HMONTH-END",
   "description": "End month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 743,
   "name": "TS4-HDAY-START",
   "description": "Start day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 744,
   "name": "TS4-HMONTH-START",
   "description": "Start month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 745,
   "name": "TS4-HDAY-END",
   "description": "End day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 746,
   "name": "TS4-HMONTH-END",
   "description": "End month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 753,
   "name": "TS5-HDAY-START",
   "description": "Start day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 754,
   "name": "TS5-HMONTH-START",
   "description": "Start month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 755,
   "name": "TS5-HDAY-END",
   "description": "End day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 756,
   "name": "TS5-HMONTH-END",
   "description": "End month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 763,
   "name": "TS6-HDAY-START",
   "description": "Start day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 764,
   "name": "TS6-HMONTH-START",
   "description": "Start month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 765,
   "name": "TS6-HDAY-END",
   "description": "End day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 766,
   "name": "TS6-HMONTH-END",
   "description": "End month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 773,
   "name": "TS7-HDAY-START",
   "description": "Start day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 774,
   "name": "TS7-HMONTH-START",
   "description": "Start month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 775,
   "name": "TS7-HDAY-END",
   "description": "End day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 776,
   "name": "TS7-HMONTH-END",
   "description": "End month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 783,
   "name": "TS8-HDAY-START",
   "description": "Start day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 784,
   "name": "TS8-HMONTH-START",
   "description": "Start month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 785,
   "name": "TS8-HDAY-END",
   "description": "End day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 786,
   "name": "TS8-HMONTH-END",
   "description": "End month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 793,
   "name": "TS9-HDAY-START",
   "description": "Start day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 794,
   "name": "TS9-HMONTH-START",
   "description": "Start month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 795,
   "name": "TS9-HDAY-END",
   "description": "End day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 796,
   "name": "TS9-HMONTH-END",
   "description": "End month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 803,
   "name": "TS10-HDAY-START",
   "description": "Start day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 804,
   "name": "TS10-HMONTH-START",
   "description": "Start month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 805,
   "name": "TS10-HDAY-END",
   "description": "End day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 806,
   "name": "TS10-HMONTH-END",
   "description": "End month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 813,
   "name": "TS11-HDAY-START",
   "description": "Start day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 814,
   "name": "TS11-HMONTH-START",
   "description": "Start month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 815,
   "name": "TS11-HDAY-END",
   "description": "End day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 816,
   "name": "TS11-HMONTH-END",
   "description": "End month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 823,
   "name": "TS12-HDAY-START",
   "description": "Start day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 824,
   "name": "TS12-HMONTH-START",
   "description": "Start month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 825,
   "name": "TS12-HDAY-END",
   "description": "End day of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 826,
   "name": "TS12-HMONTH-END",
   "description": "End month of holiday",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "ParAdd",
   "description": "Address of parameter, address per the doc's table",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "ParValue",
   "description": "Parameter value",
   "units": "",
   "access": "W",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/vector-controls/x2-bacnet-ip",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}