 "manufacturer": "Telaire",
 "manufacturer_slug": "telaire",
 "model": "Ventostat T8000 series CO2 sensor, BACnet MS/TP",
 "model_slug": "ventostat-t8000-bacnet",
 "aliases": [
  "Ventostat 8000",
  "T8000",
  "T8100",
  "T8200",
  "T8300",
  "T8100-D",
  "T8300-D",
  "Telaire Ventostat BACnet",
  "Amphenol Telaire T8000"
 ],
 "equipment_type": "CO2 sensor (room / duct)",
 "applies_to": "Amphenol Telaire Ventostat T8000 BACnet series CO2 transmitters (T8100 wall, T8200 dual channel, T8300 duct/pitot), with optional humidity, temperature and relay.",
 "summary": "The Ventostat T8000 BACnet series are NDIR CO2 transmitters with BACnet MS/TP on RS485. Four Analog Inputs give CO2, humidity and two temperatures; Analog Values hold offsets, relay setpoint and hysteresis, elevation, single-point calibration, baud and MAC; Binary Values switch temperature units and ABC Logic self-calibration and start a calibration.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": "568000 + MAC address (568000-568127)",
 "access_inferred": true,
 "notes": [
  "The object table has no read/write column; Analog and Binary Values are listed as writable (settings and commands), inputs as read-only.",
  "Units are as printed in the table; AV 1, AV 5 and AV 7 point to footnotes (offset always °C, elevation always meters, baud in bits per second).",
  "Humidity, relay and thermistor objects only work if that option was ordered; the relay commands have no effect otherwise.",
  "Temperature units depend on factory options or BV 1; the temperature offset (AV 1) is always in °C and elevation (AV 5) always in meters."
 ],
 "source": {
  "title": "Telaire Ventostat 8000 BACnet Series CO2 Sensor - User Instructions",
  "doc_number": "T63348-002",
  "revision_date": "March 2014",
  "url": "https://core.instrumart.com/assets/Telaire-T8000BACnet-Manual.pdf",
  "unofficial": true,
  "host": "Instrumart"
 },
 "integration": {
  "summary": "Set the MAC on the DIP switches (and 9600 or 38400 baud on the last switch), then read AI 1 for CO2 and the humidity/temperature inputs if fitted.",
  "minimum_points": [
   {
    "ref": "AI 1",
    "name": "CO2",
    "why": "CO2 level, ppm"
   },
   {
    "ref": "AI 2",
    "name": "Relative Humidity",
    "why": "Relative humidity (if fitted)"
   },
   {
    "ref": "AI 3",
    "name": "Temperature, ChipCap",
    "why": "Temperature (if fitted)"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "MAC address from the left seven DIP switches (1-127; 0 is the router); the rightmost switch sets 38400 (on) or 9600 (off) baud.",
   "19200 and 76800 baud can be set through AV 7 over BACnet.",
   "Device instance is 568000 plus the MAC address."
  ],
  "gotchas": [
   "Turn ABC Logic off (BV 2) in spaces that are never unoccupied, such as greenhouses or 24-hour buildings.",
   "Set elevation (AV 5) for the site so CO2 readings are pressure-corrected."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "CO2",
   "description": "CO2 concentration",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Relative Humidity",
   "description": "Relative humidity (option)",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Temperature, ChipCap",
   "description": "Temperature from the RH/temp chip",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "Temperature, Thermistor",
   "description": "Temperature from the 10K thermistor",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Temperature Offset",
   "description": "Temperature offset, always °C, -50 to +50, default -0.40",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "RH Offset",
   "description": "RH offset, -100 to +100, default 0.30",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Relay Set Point",
   "description": "CO2 relay threshold, default 1000 (relay option)",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "Relay Hysteresis",
   "description": "CO2 relay hysteresis, default 80 (relay option)",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "Elevation",
   "description": "Site elevation for pressure correction, default 0",
   "units": "m",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Calibration, Single Point",
   "description": "Single-point CO2 calibration gas value, default 1000",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Baud Rate",
   "description": "MS/TP baud rate, 9600-76800",
   "units": "bps",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "MAC Address",
   "description": "MS/TP MAC address, 0-127 (default from DIP switches)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "Relay State",
   "description": "CO2 relay output state (relay option)",
   "units": "",
   "access": "R",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "Temperature Units",
   "description": "Temperature units",
   "units": "",
   "access": "W",
   "states": "0=°C, 1=°F"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "ABC Logic State",
   "description": "ABC Logic self-calibration on/off",
   "units": "",
   "access": "W",
   "states": "0=OFF, 1=ON"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "ABC Logic Reset",
   "description": "Reset ABC Logic",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Reset"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "CO2 Calibration",
   "description": "Start single-point CO2 calibration",
   "units": "",
   "access": "W",
   "states": "0=Normal, 1=Calibrate"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/telaire/ventostat-t8000-bacnet",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}