 "manufacturer": "Taco",
 "manufacturer_slug": "taco",
 "model": "Booster Pump Sets (Danfoss drive controlled)",
 "model_slug": "booster-pump-sets",
 "aliases": [
  "Taco booster",
  "Taco booster pump set",
  "Taco duplex booster",
  "Taco triplex booster",
  "Danfoss VLT booster"
 ],
 "equipment_type": "Domestic water booster pump package",
 "applies_to": "Taco duplex and multiplex domestic water booster pump sets controlled by Danfoss drives (2019 IOM).",
 "summary": "Taco booster pump sets run each pump on a Danfoss drive that holds the discharge pressure setpoint. The IOM lists ten important BACnet points on the drive: run/stop and fault reset commands, setpoint 1, the analog input and PID feedback, run, fault and hand/auto status, a running flag and the active set-up. For the full object list it refers to the Danfoss BACnet instructions.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "This is the short 'Important BACnet Points for Boosters' list from the IOM, not the drive's full object list.",
  "The IOM writes the last object as MSO:1 'Multi_state_value: 1'; it is listed here as a Multi-state Value.",
  "The BAS wires to drive terminals 68/69 (the Danfoss RS-485 bus), on the lead drive (VFD #1) or daisy-chained through all drives; terminals are not chained at the factory.",
  "Units are not printed; the setpoint and feedback follow the drive's pressure scaling."
 ],
 "source": {
  "title": "Taco Booster Pump Sets - Installation, Operation, and Maintenance Manual",
  "doc_number": null,
  "revision_date": "2019-07",
  "url": "https://www.tacocomfort.com/documents/FileLibrary/Booster_IOM_RB_06_28_19.pdf"
 },
 "integration": {
  "summary": "Set up BACnet on the Danfoss drive per the Danfoss instructions, then use BV 1 to run or stop the booster and AV 30 to set the pressure setpoint. Monitor BV 33 running, BV 5 OK/fault and AV 4 feedback, and reset faults with BV 3.",
  "minimum_points": [
   {
    "ref": "BV 1",
    "name": "Run/Stop Command",
    "why": "Run/stop command"
   },
   {
    "ref": "AV 30",
    "name": "Setpoint 1",
    "why": "Discharge pressure setpoint"
   },
   {
    "ref": "BV 3",
    "name": "Fault Reset Command",
    "why": "Fault reset"
   },
   {
    "ref": "BV 33",
    "name": "Running",
    "why": "Running status"
   },
   {
    "ref": "AV 4",
    "name": "PID Feedback",
    "why": "Pressure feedback"
   },
   {
    "ref": "BV 6",
    "name": "Hand/Auto Reference",
    "why": "Hand or auto reference"
   },
   {
    "ref": "BV 5",
    "name": "OK/Fault Monitor",
    "why": "Drive OK or fault"
   }
  ],
  "enable": "BV 1 Run/Stop Command starts and stops the booster over BACnet.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "BACnet communication is set up in the Danfoss drive; the IOM points to the Danfoss BACnet instructions for details.",
   "Bus terminals are 68 and 69 on each drive; connect the BAS to the lead drive (VFD #1) or daisy-chain all drives as the project needs."
  ],
  "gotchas": [
   "Only these ten points are documented by Taco; other drive objects follow the Danfoss object list."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "Analog Input 54",
   "description": "Drive analog input 54 (pressure sensor)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "PID Feedback",
   "description": "Process feedback (system pressure)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "Setpoint 1",
   "description": "Pressure setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "Run/Stop Command",
   "description": "Run/stop command",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "Fault Reset Command",
   "description": "Fault reset command",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "Run/Stop Monitor",
   "description": "Run/stop status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "OK/Fault Monitor",
   "description": "Drive OK or in fault",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "Hand/Auto Reference",
   "description": "Hand or auto reference",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "Running",
   "description": "Pump running",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "Active Setup",
   "description": "Active drive parameter set-up",
   "units": "",
   "access": "W",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/taco/booster-pump-sets",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}