 "manufacturer": "Setra",
 "manufacturer_slug": "setra",
 "model": "Setra FLEX Room Pressure Monitor",
 "model_slug": "flex-room-pressure-monitor",
 "short_model": "FLEX Room Pressure Monitor",
 "aliases": [
  "SetraFLEX",
  "Setra FLEX",
  "FLEX-RM",
  "FLEX-RC",
  "Setra FLEX Environmental Monitor"
 ],
 "equipment_type": "Room pressure monitor and controller",
 "applies_to": "Setra FLEX wall-mounted room pressure and environmental monitors (FLEX-RM monitor-only and FLEX-RC room control) covering up to three rooms.",
 "summary": "The Setra FLEX is a touch-screen room pressure and environmental monitor that watches up to three rooms with six parameters each (pressure, temperature, humidity, ACH and two user-defined). It talks BACnet IP or BACnet MS/TP and exposes the room readings, alarm states, limits and almost all setup as objects; each room parameter can come from an on-board input or be read from another BACnet device. The FLEX-RC version can also control equipment with PI loops or BACnet setpoint overrides.",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Access is taken from the list's Writable column. AI, BI and MI objects are marked writable only when out of service; they are shown here as read-only.",
  "The list gives no engineering units; room values follow the units of their configured source (BV 82-99 choose local or BACnet-source units).",
  "Analog input and alarm-limit values are bounded by each object's min-pres-value and max-pres-value.",
  "Room parameters, alarm limits and source settings repeat for Room 1, 2 and 3; profile settings repeat for profiles 1-4.",
  "MV 49 and MV 50 are both printed as \"Room Profile 3 Control Preset\"; names are kept as printed.",
  "The Loop rows print \"Loop 1\" to \"Loop 4\" in the type/instance column (without the hyphen the other rows use); they are read here as Loop instances 1-4."
 ],
 "source": {
  "title": "SetraFLEX Master BACnet Object List",
  "doc_number": "SS-FLEX-BAC-OBJ",
  "revision_date": "print D",
  "url": "https://www.setra.com/hubfs/SS-FLEX-BAC-OBJ_D.pdf"
 },
 "integration": {
  "summary": "Read the room pressure, temperature and humidity AIs and the per-room and system alarm state MIs; map the door inputs if used. Room standby (BV 72-74) and the active room profile (MV 19-21) can be written from the BMS to switch modes such as occupied and unoccupied. On FLEX-RC units the four setpoint controls have preset A/B setpoints and limits in AV 177-206.",
  "minimum_points": [
   {
    "ref": "BV 72",
    "name": "Room 1 Standby",
    "why": "Room 1 standby: 1 = Standby, 0 = Active"
   },
   {
    "ref": "MV 19",
    "name": "Room 1 Room Profile",
    "why": "Active room profile 1-4 (e.g. occupied/unoccupied)"
   },
   {
    "ref": "AV 177",
    "name": "Setpoint Control 1 - Preset A Setpoint",
    "why": "Control 1 setpoint, preset A (FLEX-RC)"
   },
   {
    "ref": "AI 13",
    "name": "Room 1 Pressure",
    "why": "Room 1 differential pressure"
   },
   {
    "ref": "AI 14",
    "name": "Room 1 Temperature",
    "why": "Room 1 temperature, from its configured source"
   },
   {
    "ref": "AI 15",
    "name": "Room 1 Humidity",
    "why": "Room 1 humidity, from its configured source"
   },
   {
    "ref": "BI 13",
    "name": "Room 1 Door Input",
    "why": "Room 1 door switch"
   },
   {
    "ref": "MI 19",
    "name": "Room 1 Alarm State",
    "why": "Room 1: 1 Normal, 2 Warning, 3 Alarm, 4 Standby"
   },
   {
    "ref": "MI 22",
    "name": "System Alarm State",
    "why": "Whole-unit alarm state, same states"
   }
  ],
  "enable": "Room 1-3 Standby (BV 72-74) put a room in standby, and Room 1-3 Room Profile (MV 19-21) pick which of the four profiles (alarm limits and control presets) is active.",
  "heartbeat": null,
  "remote_sensors": "Each room parameter has a source selector (MV 1-18, 6 = BACnet). With BACnet selected, the FLEX reads the value from another device set by the matching device instance, object instance and object type objects (AV 141-176, MV 55-72). The four setpoint controls point at external BACnet setpoint objects set by AV 183/184, 191/192, 199/200 and 207/208 (device and object instance).",
  "setup": [
   "BACnet IP uses IPv4 with static IP or DHCP; BACnet MS/TP runs at up to 76.8 kbps (Setra data sheet and specification guide).",
   "The device object is listed as Device-4194302 with an instance range of 0-4194303, where 4194303 means unconfigured.",
   "Setra states that anything set up on the touch screen can also be set over BACnet, except passwords, the device ID and read-only items."
  ],
  "gotchas": [
   "Most of the list is configuration (limits, delays, display, sources); avoid writing those objects cyclically from the BMS.",
   "MV 90-93 set the BACnet priority used for the setpoint overrides; check they do not clash with the BMS command priority.",
   "Execute BACnet Time Sync? (BV 7) must be 1 for the unit to accept BACnet time synchronization.",
   "Operator Password (CSV 18) is writable over BACnet; restrict write access on the BMS side."
  ]
 },
 "points": [
  {
   "type": "DEV",
   "instance": 4194302,
   "name": "Setra FLEX",
   "description": "Device object",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "On-Board Analog Input",
   "description": "On-board input value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "On-Board Universal Input 1",
   "description": "On-board input value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "On-Board Universal Input 2",
   "description": "On-board input value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "On-Board Universal Input 3",
   "description": "On-board input value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "Room 1 Pressure",
   "description": "Room 1 pressure value from its configured source",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "Room 1 Temperature",
   "description": "Room 1 temperature value from its configured source",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "Room 1 Humidity",
   "description": "Room 1 humidity value from its configured source",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "Room 1 ACH",
   "description": "Room 1 ACH value from its configured source",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "Room 1 User Defined 1",
   "description": "Room 1 user defined 1 value from its configured source",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "Room 1 User Defined 2",
   "description": "Room 1 user defined 2 value from its configured source",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "Room 2 Pressure",
   "description": "Room 2 pressure value from its configured source",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "Room 2 Temperature",
   "description": "Room 2 temperature value from its configured source",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "Room 2 Humidity",
   "description": "Room 2 humidity value from its configured source",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "Room 2 ACH",
   "description": "Room 2 ACH value from its configured source",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "Room 2 User Defined 1",
   "description": "Room 2 user defined 1 value from its configured source",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "Room 2 User Defined 2",
   "description": "Room 2 user defined 2 value from its configured source",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "Room 3 Pressure",
   "description": "Room 3 pressure value from its configured source",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "Room 3 Temperature",
   "description": "Room 3 temperature value from its configured source",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "Room 3 Humidity",
   "description": "Room 3 humidity value from its configured source",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "Room 3 ACH",
   "description": "Room 3 ACH value from its configured source",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "Room 3 User Defined 1",
   "description": "Room 3 user defined 1 value from its configured source",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "Room 3 User Defined 2",
   "description": "Room 3 user defined 2 value from its configured source",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 1,
   "name": "On-Board Analog Output",
   "description": "On-board analog output value",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Room 1 Pressure Low Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "Room 1 Pressure High Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Room 1 Pressure Low Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "Room 1 Pressure High Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "Room 1 Pressure Deadband",
   "description": "Alarm deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Room 1 Pressure To Off Normal Delay",
   "description": "Delay before the alarm is raised",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Room 1 Pressure Return To Normal Delay",
   "description": "Delay before the alarm clears",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Room 1 Temperature Low Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "Room 1 Temperature High Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "Room 1 Temperature Low Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "Room 1 Temperature High Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "Room 1 Temperature Deadband",
   "description": "Alarm deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "Room 1 Temperature To Off Normal Delay",
   "description": "Delay before the alarm is raised",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "Room 1 Temperature Return To Normal Delay",
   "description": "Delay before the alarm clears",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "Room 1 Humidity Low Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "Room 1 Humidity High Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "Room 1 Humidity Low Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "Room 1 Humidity High Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "Room 1 Humidity Deadband",
   "description": "Alarm deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "Room 1 Humidity To Off Normal Delay",
   "description": "Delay before the alarm is raised",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "Room 1 Humidity Return To Normal Delay",
   "description": "Delay before the alarm clears",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "Room 1 ACH Low Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "Room 1 ACH High Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "Room 1 ACH Low Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "Room 1 ACH High Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "Room 1 ACH Deadband",
   "description": "Alarm deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "Room 1 ACH To Off Normal Delay",
   "description": "Delay before the alarm is raised",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "Room 1 ACH Return To Normal Delay",
   "description": "Delay before the alarm clears",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "Room 1 User Defined 1 Low Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "Room 1 User Defined 1 High Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "Room 1 User Defined 1 Low Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "Room 1 User Defined 1 High Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "Room 1 User Defined 1 Deadband",
   "description": "Alarm deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "Room 1 User Defined 1 To Off Normal Delay",
   "description": "Delay before the alarm is raised",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "Room 1 User Defined 1 Return To Normal Delay",
   "description": "Delay before the alarm clears",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "Room 1 User Defined 2 Low Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "Room 1 User Defined 2 High Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "Room 1 User Defined 2 Low Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "Room 1 User Defined 2 High Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "Room 1 User Defined 2 Deadband",
   "description": "Alarm deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "Room 1 User Defined 2 To Off Normal Delay",
   "description": "Delay before the alarm is raised",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "Room 1 User Defined 2 Return To Normal Delay",
   "description": "Delay before the alarm clears",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "Room 2 Pressure Low Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "Room 2 Pressure High Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "Room 2 Pressure Low Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "Room 2 Pressure High Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "Room 2 Pressure Deadband",
   "description": "Alarm deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "Room 2 Pressure To Off Normal Delay",
   "description": "Delay before the alarm is raised",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "Room 2 Pressure Return To Normal Delay",
   "description": "Delay before the alarm clears",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "Room 2 Temperature Low Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "Room 2 Temperature High Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "Room 2 Temperature Low Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "Room 2 Temperature High Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "Room 2 Temperature Deadband",
   "description": "Alarm deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "Room 2 Temperature To Off Normal Delay",
   "description": "Delay before the alarm is raised",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "Room 2 Temperature Return To Normal Delay",
   "description": "Delay before the alarm clears",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "Room 2 Humidity Low Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "Room 2 Humidity High Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "Room 2 Humidity Low Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "Room 2 Humidity High Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "Room 2 Humidity Deadband",
   "description": "Alarm deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "Room 2 Humidity To Off Normal Delay",
   "description": "Delay before the alarm is raised",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "Room 2 Humidity Return To Normal Delay",
   "description": "Delay before the alarm clears",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "Room 2 ACH Low Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "Room 2 ACH High Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "Room 2 ACH Low Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "Room 2 ACH High Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "Room 2 ACH Deadband",
   "description": "Alarm deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "Room 2 ACH To Off Normal Delay",
   "description": "Delay before the alarm is raised",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "Room 2 ACH Return To Normal Delay",
   "description": "Delay before the alarm clears",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "Room 2 User Defined 1 Low Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "Room 2 User Defined 1 High Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "Room 2 User Defined 1 Low Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "Room 2 User Defined 1 High Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "Room 2 User Defined 1 Deadband",
   "description": "Alarm deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 76,
   "name": "Room 2 User Defined 1 To Off Normal Delay",
   "description": "Delay before the alarm is raised",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 77,
   "name": "Room 2 User Defined 1 Return To Normal Delay",
   "description": "Delay before the alarm clears",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 78,
   "name": "Room 2 User Defined 2 Low Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 79,
   "name": "Room 2 User Defined 2 High Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 80,
   "name": "Room 2 User Defined 2 Low Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "Room 2 User Defined 2 High Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "Room 2 User Defined 2 Deadband",
   "description": "Alarm deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 83,
   "name": "Room 2 User Defined 2 To Off Normal Delay",
   "description": "Delay before the alarm is raised",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "Room 2 User Defined 2 Return To Normal Delay",
   "description": "Delay before the alarm clears",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "Room 3 Pressure Low Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 86,
   "name": "Room 3 Pressure High Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 87,
   "name": "Room 3 Pressure Low Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 88,
   "name": "Room 3 Pressure High Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 89,
   "name": "Room 3 Pressure Deadband",
   "description": "Alarm deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 90,
   "name": "Room 3 Pressure To Off Normal Delay",
   "description": "Delay before the alarm is raised",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 91,
   "name": "Room 3 Pressure Return To Normal Delay",
   "description": "Delay before the alarm clears",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 92,
   "name": "Room 3 Temperature Low Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 93,
   "name": "Room 3 Temperature High Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 94,
   "name": "Room 3 Temperature Low Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 95,
   "name": "Room 3 Temperature High Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 96,
   "name": "Room 3 Temperature Deadband",
   "description": "Alarm deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 97,
   "name": "Room 3 Temperature To Off Normal Delay",
   "description": "Delay before the alarm is raised",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 98,
   "name": "Room 3 Temperature Return To Normal Delay",
   "description": "Delay before the alarm clears",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 99,
   "name": "Room 3 Humidity Low Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 100,
   "name": "Room 3 Humidity High Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 101,
   "name": "Room 3 Humidity Low Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 102,
   "name": "Room 3 Humidity High Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "Room 3 Humidity Deadband",
   "description": "Alarm deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 104,
   "name": "Room 3 Humidity To Off Normal Delay",
   "description": "Delay before the alarm is raised",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 105,
   "name": "Room 3 Humidity Return To Normal Delay",
   "description": "Delay before the alarm clears",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 106,
   "name": "Room 3 ACH Low Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 107,
   "name": "Room 3 ACH High Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 108,
   "name": "Room 3 ACH Low Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 109,
   "name": "Room 3 ACH High Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 110,
   "name": "Room 3 ACH Deadband",
   "description": "Alarm deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 111,
   "name": "Room 3 ACH To Off Normal Delay",
   "description": "Delay before the alarm is raised",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 112,
   "name": "Room 3 ACH Return To Normal Delay",
   "description": "Delay before the alarm clears",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 113,
   "name": "Room 3 User Defined 1 Low Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 114,
   "name": "Room 3 User Defined 1 High Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 115,
   "name": "Room 3 User Defined 1 Low Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 116,
   "name": "Room 3 User Defined 1 High Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 117,
   "name": "Room 3 User Defined 1 Deadband",
   "description": "Alarm deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 118,
   "name": "Room 3 User Defined 1 To Off Normal Delay",
   "description": "Delay before the alarm is raised",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 119,
   "name": "Room 3 User Defined 1 Return To Normal Delay",
   "description": "Delay before the alarm clears",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 120,
   "name": "Room 3 User Defined 2 Low Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 121,
   "name": "Room 3 User Defined 2 High Limit - Monitor Preset A",
   "description": "Alarm limit for monitor preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 122,
   "name": "Room 3 User Defined 2 Low Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 123,
   "name": "Room 3 User Defined 2 High Limit - Monitor Preset B",
   "description": "Alarm limit for monitor preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 124,
   "name": "Room 3 User Defined 2 Deadband",
   "description": "Alarm deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 125,
   "name": "Room 3 User Defined 2 To Off Normal Delay",
   "description": "Delay before the alarm is raised",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 126,
   "name": "Room 3 User Defined 2 Return To Normal Delay",
   "description": "Delay before the alarm clears",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 127,
   "name": "Room 1 Length",
   "description": "Room dimension for ACH calculation",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 128,
   "name": "Room 1 Width",
   "description": "Room dimension for ACH calculation",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 129,
   "name": "Room 1 Height",
   "description": "Room dimension for ACH calculation",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 130,
   "name": "Room 2 Length",
   "description": "Room dimension for ACH calculation",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 131,
   "name": "Room 2 Width",
   "description": "Room dimension for ACH calculation",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 132,
   "name": "Room 2 Height",
   "description": "Room dimension for ACH calculation",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 133,
   "name": "Room 3 Length",
   "description": "Room dimension for ACH calculation",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 134,
   "name": "Room 3 Width",
   "description": "Room dimension for ACH calculation",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 135,
   "name": "Room 3 Height",
   "description": "Room dimension for ACH calculation",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 209,
   "name": "Room 1 Duct Cross Sectional Area",
   "description": "Duct area for ACH from velocity",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 210,
   "name": "Room 2 Duct Cross Sectional Area",
   "description": "Duct area for ACH from velocity",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 211,
   "name": "Room 3 Duct Cross Sectional Area",
   "description": "Duct area for ACH from velocity",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 136,
   "name": "Mute Time Out",
   "description": "How long an alarm stays muted",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 138,
   "name": "Brightness Level",
   "description": "Display brightness level",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 139,
   "name": "Home Screen Timeout",
   "description": "Time before returning to the home screen",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 140,
   "name": "Room Carousel Interval",
   "description": "Time each room is shown in the carousel",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 212,
   "name": "Turn Off Display After Timeout",
   "description": "Time before the display turns off",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "Latch Alarm Enable",
   "description": "Alarms stay latched until acknowledged",
   "units": "",
   "access": "W",
   "states": "0 = Latch Disabled, 1 = Latch Enabled"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "Audible Alarm Status",
   "description": "Audible alarm on/off",
   "units": "",
   "access": "W",
   "states": "0 = Audible Alarm Disabled, 1 = Audible Alarm Enabled"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "Mute Alarm Enable",
   "description": "Allow alarm muting",
   "units": "",
   "access": "W",
   "states": "0 = Mute Disabled, 1 = Mute Enabled"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "Default To Full Screen",
   "description": "Home screen view",
   "units": "",
   "access": "W",
   "states": "0 = Show Single Room View, 1 = Show Full Screen View"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "Room Carousel",
   "description": "Cycle through rooms on the home screen",
   "units": "",
   "access": "W",
   "states": "0 = Room Carousel Disabled, 1 = Room Carousel Enabled"
  },
  {
   "type": "BV",
   "instance": 100,
   "name": "Display Turn Off Enable",
   "description": "Allow the display to turn off",
   "units": "",
   "access": "W",
   "states": "0 = Display turn off disabled, 1 = Display turn off enabled"
  },
  {
   "type": "AV",
   "instance": 141,
   "name": "Room 1 Pressure BACnet Device Instance",
   "description": "Device instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 142,
   "name": "Room 1 Pressure BACnet Object Instance",
   "description": "Object instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 143,
   "name": "Room 1 Temperature BACnet Device Instance",
   "description": "Device instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 144,
   "name": "Room 1 Temperature BACnet Object Instance",
   "description": "Object instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 145,
   "name": "Room 1 Humidity BACnet Device Instance",
   "description": "Device instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 146,
   "name": "Room 1 Humidity BACnet Object Instance",
   "description": "Object instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 147,
   "name": "Room 1 ACH BACnet Device Instance",
   "description": "Device instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 148,
   "name": "Room 1 ACH BACnet Object Instance",
   "description": "Object instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 149,
   "name": "Room 1 User Defined 1 BACnet Device Instance",
   "description": "Device instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 150,
   "name": "Room 1 User Defined 1 BACnet Object Instance",
   "description": "Object instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 151,
   "name": "Room 1 User Defined 2 BACnet Device Instance",
   "description": "Device instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 152,
   "name": "Room 1 User Defined 2 BACnet Object Instance",
   "description": "Object instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 153,
   "name": "Room 2 Pressure BACnet Device Instance",
   "description": "Device instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 154,
   "name": "Room 2 Pressure BACnet Object Instance",
   "description": "Object instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 155,
   "name": "Room 2 Temperature BACnet Device Instance",
   "description": "Device instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 156,
   "name": "Room 2 Temperature BACnet Object Instance",
   "description": "Object instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 157,
   "name": "Room 2 Humidity BACnet Device Instance",
   "description": "Device instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 158,
   "name": "Room 2 Humidity BACnet Object Instance",
   "description": "Object instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 159,
   "name": "Room 2 ACH BACnet Device Instance",
   "description": "Device instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 160,
   "name": "Room 2 ACH BACnet Object Instance",
   "description": "Object instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 161,
   "name": "Room 2 User Defined 1 BACnet Device Instance",
   "description": "Device instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 162,
   "name": "Room 2 User Defined 1 BACnet Object Instance",
   "description": "Object instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 163,
   "name": "Room 2 User Defined 2 BACnet Device Instance",
   "description": "Device instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 164,
   "name": "Room 2 User Defined 2 BACnet Object Instance",
   "description": "Object instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 165,
   "name": "Room 3 Pressure BACnet Device Instance",
   "description": "Device instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 166,
   "name": "Room 3 Pressure BACnet Object Instance",
   "description": "Object instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 167,
   "name": "Room 3 Temperature BACnet Device Instance",
   "description": "Device instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 168,
   "name": "Room 3 Temperature BACnet Object Instance",
   "description": "Object instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 169,
   "name": "Room 3 Humidity BACnet Device Instance",
   "description": "Device instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 170,
   "name": "Room 3 Humidity BACnet Object Instance",
   "description": "Object instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 171,
   "name": "Room 3 ACH BACnet Device Instance",
   "description": "Device instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 172,
   "name": "Room 3 ACH BACnet Object Instance",
   "description": "Object instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 173,
   "name": "Room 3 User Defined 1 BACnet Device Instance",
   "description": "Device instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 174,
   "name": "Room 3 User Defined 1 BACnet Object Instance",
   "description": "Object instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 175,
   "name": "Room 3 User Defined 2 BACnet Device Instance",
   "description": "Device instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 176,
   "name": "Room 3 User Defined 2 BACnet Object Instance",
   "description": "Object instance of the BACnet source",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 177,
   "name": "Setpoint Control 1 - Preset A Setpoint",
   "description": "Control setpoint for preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 178,
   "name": "Setpoint Control 1 - Preset A Max Setpoint",
   "description": "Highest setpoint allowed, preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 179,
   "name": "Setpoint Control 1 - Preset A Min Setpoint",
   "description": "Lowest setpoint allowed, preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 180,
   "name": "Setpoint Control 1 - Preset B Setpoint",
   "description": "Control setpoint for preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 181,
   "name": "Setpoint Control 1 - Preset B Max Setpoint",
   "description": "Highest setpoint allowed, preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 182,
   "name": "Setpoint Control 1 - Preset B Min Setpoint",
   "description": "Lowest setpoint allowed, preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 183,
   "name": "External Setpoint 1 BACnet Device Instance",
   "description": "Device instance of the external setpoint object",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 184,
   "name": "External Setpoint 1 BACnet Object Instance",
   "description": "Object instance of the external setpoint object",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 185,
   "name": "Setpoint Control 2 - Preset A Setpoint",
   "description": "Control setpoint for preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 186,
   "name": "Setpoint Control 2 - Preset A Max Setpoint",
   "description": "Highest setpoint allowed, preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 187,
   "name": "Setpoint Control 2 - Preset A Min Setpoint",
   "description": "Lowest setpoint allowed, preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 188,
   "name": "Setpoint Control 2 - Preset B Setpoint",
   "description": "Control setpoint for preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 189,
   "name": "Setpoint Control 2 - Preset B Max Setpoint",
   "description": "Highest setpoint allowed, preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 190,
   "name": "Setpoint Control 2 - Preset B Min Setpoint",
   "description": "Lowest setpoint allowed, preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 191,
   "name": "External Setpoint 2 BACnet Device Instance",
   "description": "Device instance of the external setpoint object",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 192,
   "name": "External Setpoint 2 BACnet Object Instance",
   "description": "Object instance of the external setpoint object",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 193,
   "name": "Setpoint Control 3 - Preset A Setpoint",
   "description": "Control setpoint for preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 194,
   "name": "Setpoint Control 3 - Preset A Max Setpoint",
   "description": "Highest setpoint allowed, preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 195,
   "name": "Setpoint Control 3 - Preset A Min Setpoint",
   "description": "Lowest setpoint allowed, preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 196,
   "name": "Setpoint Control 3 - Preset B Setpoint",
   "description": "Control setpoint for preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 197,
   "name": "Setpoint Control 3 - Preset B Max Setpoint",
   "description": "Highest setpoint allowed, preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 198,
   "name": "Setpoint Control 3 - Preset B Min Setpoint",
   "description": "Lowest setpoint allowed, preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 199,
   "name": "External Setpoint 3 BACnet Device Instance",
   "description": "Device instance of the external setpoint object",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 200,
   "name": "External Setpoint 3 BACnet Object Instance",
   "description": "Object instance of the external setpoint object",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 201,
   "name": "Setpoint Control 4 - Preset A Setpoint",
   "description": "Control setpoint for preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 202,
   "name": "Setpoint Control 4 - Preset A Max Setpoint",
   "description": "Highest setpoint allowed, preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 203,
   "name": "Setpoint Control 4 - Preset A Min Setpoint",
   "description": "Lowest setpoint allowed, preset A",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 204,
   "name": "Setpoint Control 4 - Preset B Setpoint",
   "description": "Control setpoint for preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 205,
   "name": "Setpoint Control 4 - Preset B Max Setpoint",
   "description": "Highest setpoint allowed, preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 206,
   "name": "Setpoint Control 4 - Preset B Min Setpoint",
   "description": "Lowest setpoint allowed, preset B",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 207,
   "name": "External Setpoint 4 BACnet Device Instance",
   "description": "Device instance of the external setpoint object",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 208,
   "name": "External Setpoint 4 BACnet Object Instance",
   "description": "Object instance of the external setpoint object",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "On-Board Digital Input 2",
   "description": "On-board digital input",
   "units": "",
   "access": "R",
   "states": "Active, Inactive"
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "On-Board Digital Input 3",
   "description": "On-board digital input",
   "units": "",
   "access": "R",
   "states": "Active, Inactive"
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "On-Board Digital Input 4",
   "description": "On-board digital input",
   "units": "",
   "access": "R",
   "states": "Active, Inactive"
  },
  {
   "type": "BI",
   "instance": 13,
   "name": "Room 1 Door Input",
   "description": "Door switch input",
   "units": "",
   "access": "R",
   "states": "Active, Inactive"
  },
  {
   "type": "BI",
   "instance": 14,
   "name": "Room 2 Door Input",
   "description": "Door switch input",
   "units": "",
   "access": "R",
   "states": "Active, Inactive"
  },
  {
   "type": "BI",
   "instance": 15,
   "name": "Room 3 Door Input",
   "description": "Door switch input",
   "units": "",
   "access": "R",
   "states": "Active, Inactive"
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "On-Board Relay",
   "description": "On-board relay output",
   "units": "",
   "access": "W",
   "states": "0=COM NO Shorted, 1=COM NC Shorted"
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "Room 1 Pressure Parameter Enable",
   "description": "Show and monitor this room parameter",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "Room 1 Temperature Parameter Enable",
   "description": "Show and monitor this room parameter",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "Room 1 Humidity Parameter Enable",
   "description": "Show and monitor this room parameter",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "Room 1 ACH Parameter Enable",
   "description": "Show and monitor this room parameter",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "Room 1 User Defined 1 Parameter Enable",
   "description": "Show and monitor this room parameter",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "Room 1 User Defined 2 Parameter Enable",
   "description": "Show and monitor this room parameter",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "Room 2 Pressure Parameter Enable",
   "description": "Show and monitor this room parameter",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "Room 2 Temperature Parameter Enable",
   "description": "Show and monitor this room parameter",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "Room 2 Humidity Parameter Enable",
   "description": "Show and monitor this room parameter",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "Room 2 ACH Parameter Enable",
   "description": "Show and monitor this room parameter",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "Room 2 User Defined 1 Parameter Enable",
   "description": "Show and monitor this room parameter",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "Room 2 User Defined 2 Parameter Enable",
   "description": "Show and monitor this room parameter",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "Room 3 Pressure Parameter Enable",
   "description": "Show and monitor this room parameter",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "Room 3 Temperature Parameter Enable",
   "description": "Show and monitor this room parameter",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "Room 3 Humidity Parameter Enable",
   "description": "Show and monitor this room parameter",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 23,
   "name": "Room 3 ACH Parameter Enable",
   "description": "Show and monitor this room parameter",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "Room 3 User Defined 1 Parameter Enable",
   "description": "Show and monitor this room parameter",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 25,
   "name": "Room 3 User Defined 2 Parameter Enable",
   "description": "Show and monitor this room parameter",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 26,
   "name": "Room 1 Pressure Low Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "Room 1 Pressure High Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 28,
   "name": "Room 1 Temperature Low Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 29,
   "name": "Room 1 Temperature High Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "Room 1 Humidity Low Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "Room 1 Humidity High Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "Room 1 ACH Low Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "Room 1 ACH High Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 34,
   "name": "Room 1 User Defined 1 Low Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 35,
   "name": "Room 1 User Defined 1 High Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 36,
   "name": "Room 1 User Defined 2 Low Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 37,
   "name": "Room 1 User Defined 2 High Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 38,
   "name": "Room 2 Pressure Low Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 39,
   "name": "Room 2 Pressure High Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 40,
   "name": "Room 2 Temperature Low Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 41,
   "name": "Room 2 Temperature High Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 42,
   "name": "Room 2 Humidity Low Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 43,
   "name": "Room 2 Humidity High Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 44,
   "name": "Room 2 ACH Low Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 45,
   "name": "Room 2 ACH High Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 46,
   "name": "Room 2 User Defined 1 Low Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 47,
   "name": "Room 2 User Defined 1 High Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 48,
   "name": "Room 2 User Defined 2 Low Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 49,
   "name": "Room 2 User Defined 2 High Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 50,
   "name": "Room 3 Pressure Low Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 51,
   "name": "Room 3 Pressure High Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 52,
   "name": "Room 3 Temperature Low Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 53,
   "name": "Room 3 Temperature High Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 54,
   "name": "Room 3 Humidity Low Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 55,
   "name": "Room 3 Humidity High Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 56,
   "name": "Room 3 ACH Low Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 57,
   "name": "Room 3 ACH High Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 58,
   "name": "Room 3 User Defined 1 Low Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 59,
   "name": "Room 3 User Defined 1 High Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 60,
   "name": "Room 3 User Defined 2 Low Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 61,
   "name": "Room 3 User Defined 2 High Limit Enable",
   "description": "Enable this alarm limit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 62,
   "name": "Room 1 Door Enable",
   "description": "Enable door monitoring",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 63,
   "name": "Room 2 Door Enable",
   "description": "Enable door monitoring",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 64,
   "name": "Room 3 Door Enable",
   "description": "Enable door monitoring",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 65,
   "name": "Room 1 Enable",
   "description": "Enable this room",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 66,
   "name": "Room 2 Enable",
   "description": "Enable this room",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 67,
   "name": "Room 3 Enable",
   "description": "Enable this room",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 68,
   "name": "Room Profile 1 Alarm Enable",
   "description": "Enable alarms for this room profile",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 69,
   "name": "Room Profile 2 Alarm Enable",
   "description": "Enable alarms for this room profile",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 70,
   "name": "Room Profile 3 Alarm Enable",
   "description": "Enable alarms for this room profile",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 71,
   "name": "Room Profile 4 Alarm Enable",
   "description": "Enable alarms for this room profile",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 72,
   "name": "Room 1 Standby",
   "description": "Put the room in standby",
   "units": "",
   "access": "W",
   "states": "0=Active, 1=Standby"
  },
  {
   "type": "BV",
   "instance": 73,
   "name": "Room 2 Standby",
   "description": "Put the room in standby",
   "units": "",
   "access": "W",
   "states": "0=Active, 1=Standby"
  },
  {
   "type": "BV",
   "instance": 74,
   "name": "Room 3 Standby",
   "description": "Put the room in standby",
   "units": "",
   "access": "W",
   "states": "0=Active, 1=Standby"
  },
  {
   "type": "BV",
   "instance": 75,
   "name": "Control Loop 1 Setpoint Type",
   "description": "Control by BACnet setpoint or PI loop",
   "units": "",
   "access": "W",
   "states": "0=BACnet, 1=PI Loop"
  },
  {
   "type": "BV",
   "instance": 76,
   "name": "Control Loop 2 Setpoint Type",
   "description": "Control by BACnet setpoint or PI loop",
   "units": "",
   "access": "W",
   "states": "0=BACnet, 1=PI Loop"
  },
  {
   "type": "BV",
   "instance": 77,
   "name": "Control Loop 3 Setpoint Type",
   "description": "Control by BACnet setpoint or PI loop",
   "units": "",
   "access": "W",
   "states": "0=BACnet, 1=PI Loop"
  },
  {
   "type": "BV",
   "instance": 78,
   "name": "Control Loop 4 Setpoint Type",
   "description": "Control by BACnet setpoint or PI loop",
   "units": "",
   "access": "W",
   "states": "0=BACnet, 1=PI Loop"
  },
  {
   "type": "BV",
   "instance": 79,
   "name": "Time Display Format",
   "description": "Decimal places shown",
   "units": "",
   "access": "W",
   "states": "0 = Use 12-hour format, 1 = Use 24-hour format"
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "Execute BACnet Time Sync?",
   "description": "Accept BACnet time synchronization",
   "units": "",
   "access": "W",
   "states": "0 = Ignore BACnet Time Sync, 1 = Execute BACnet Time Sync"
  },
  {
   "type": "BV",
   "instance": 80,
   "name": "Display date on home screen",
   "description": "Show the date on the home screen",
   "units": "",
   "access": "W",
   "states": "0=Date not displayed on home screen, 1=Date displayed on home screen"
  },
  {
   "type": "BV",
   "instance": 81,
   "name": "Display time on home screen",
   "description": "Show the time on the home screen",
   "units": "",
   "access": "W",
   "states": "0=Time not displayed on home screen, 1=Time displayed on home screen"
  },
  {
   "type": "BV",
   "instance": 82,
   "name": "Room 1 Pressure Display Unit",
   "description": "Units set locally or read from BACnet source",
   "units": "",
   "access": "W",
   "states": "0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source"
  },
  {
   "type": "BV",
   "instance": 83,
   "name": "Room 1 Temperature Display Unit",
   "description": "Units set locally or read from BACnet source",
   "units": "",
   "access": "W",
   "states": "0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source"
  },
  {
   "type": "BV",
   "instance": 84,
   "name": "Room 1 Humidity Display Unit",
   "description": "Units set locally or read from BACnet source",
   "units": "",
   "access": "W",
   "states": "0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source"
  },
  {
   "type": "BV",
   "instance": 85,
   "name": "Room 1 ACH Display Unit",
   "description": "Units set locally or read from BACnet source",
   "units": "",
   "access": "W",
   "states": "0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source"
  },
  {
   "type": "BV",
   "instance": 86,
   "name": "Room 1 User Defined 1 Display Unit",
   "description": "Units set locally or read from BACnet source",
   "units": "",
   "access": "W",
   "states": "0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source"
  },
  {
   "type": "BV",
   "instance": 87,
   "name": "Room 1 User Defined 2 Display Unit",
   "description": "Units set locally or read from BACnet source",
   "units": "",
   "access": "W",
   "states": "0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source"
  },
  {
   "type": "BV",
   "instance": 88,
   "name": "Room 2 Pressure Display Unit",
   "description": "Units set locally or read from BACnet source",
   "units": "",
   "access": "W",
   "states": "0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source"
  },
  {
   "type": "BV",
   "instance": 89,
   "name": "Room 2 Temperature Display Unit",
   "description": "Units set locally or read from BACnet source",
   "units": "",
   "access": "W",
   "states": "0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source"
  },
  {
   "type": "BV",
   "instance": 90,
   "name": "Room 2 Humidity Display Unit",
   "description": "Units set locally or read from BACnet source",
   "units": "",
   "access": "W",
   "states": "0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source"
  },
  {
   "type": "BV",
   "instance": 91,
   "name": "Room 2 ACH Display Unit",
   "description": "Units set locally or read from BACnet source",
   "units": "",
   "access": "W",
   "states": "0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source"
  },
  {
   "type": "BV",
   "instance": 92,
   "name": "Room 2 User Defined 1 Display Unit",
   "description": "Units set locally or read from BACnet source",
   "units": "",
   "access": "W",
   "states": "0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source"
  },
  {
   "type": "BV",
   "instance": 93,
   "name": "Room 2 User Defined 2 Display Unit",
   "description": "Units set locally or read from BACnet source",
   "units": "",
   "access": "W",
   "states": "0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source"
  },
  {
   "type": "BV",
   "instance": 94,
   "name": "Room 3 Pressure Display Unit",
   "description": "Units set locally or read from BACnet source",
   "units": "",
   "access": "W",
   "states": "0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source"
  },
  {
   "type": "BV",
   "instance": 95,
   "name": "Room 3 Temperature Display Unit",
   "description": "Units set locally or read from BACnet source",
   "units": "",
   "access": "W",
   "states": "0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source"
  },
  {
   "type": "BV",
   "instance": 96,
   "name": "Room 3 Humidity Display Unit",
   "description": "Units set locally or read from BACnet source",
   "units": "",
   "access": "W",
   "states": "0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source"
  },
  {
   "type": "BV",
   "instance": 97,
   "name": "Room 3 ACH Display Unit",
   "description": "Units set locally or read from BACnet source",
   "units": "",
   "access": "W",
   "states": "0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source"
  },
  {
   "type": "BV",
   "instance": 98,
   "name": "Room 3 User Defined 1 Display Unit",
   "description": "Units set locally or read from BACnet source",
   "units": "",
   "access": "W",
   "states": "0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source"
  },
  {
   "type": "BV",
   "instance": 99,
   "name": "Room 3 User Defined 2 Display Unit",
   "description": "Units set locally or read from BACnet source",
   "units": "",
   "access": "W",
   "states": "0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source"
  },
  {
   "type": "MI",
   "instance": 1,
   "name": "Room 1 Pressure Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 2,
   "name": "Room 1 Temperature Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 3,
   "name": "Room 1 Humidity Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 4,
   "name": "Room 1 ACH Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 5,
   "name": "Room 1 User Defined 1 Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 6,
   "name": "Room 1 user Defined 2 Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 7,
   "name": "Room 2 Pressure Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 8,
   "name": "Room 2 Temperature Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 9,
   "name": "Room 2 Humidity Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 10,
   "name": "Room 2 ACH Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 11,
   "name": "Room 2 User Defined 1 Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 12,
   "name": "Room 2 user Defined 2 Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 13,
   "name": "Room 3 Pressure Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 14,
   "name": "Room 3 Temperature Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 15,
   "name": "Room 3 Humidity Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 16,
   "name": "Room 3 ACH Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 17,
   "name": "Room 3 User Defined 1 Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 18,
   "name": "Room 3 user Defined 2 Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 19,
   "name": "Room 1 Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 20,
   "name": "Room 2 Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 21,
   "name": "Room 3 Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MI",
   "instance": 22,
   "name": "System Alarm State",
   "description": "Alarm state",
   "units": "",
   "access": "R",
   "states": "1=Normal, 2=Warning, 3=Alarm, 4=Standby"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "Room 1 Pressure Source",
   "description": "Where this room parameter comes from",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "Room 1 Temperature Source",
   "description": "Where this room parameter comes from",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "Room 1 Humidity Source",
   "description": "Where this room parameter comes from",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "Room 1 ACH Source",
   "description": "Where this room parameter comes from",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet"
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "Room 1 User Defined 1 Source",
   "description": "Where this room parameter comes from",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet"
  },
  {
   "type": "MV",
   "instance": 6,
   "name": "Room 1 User Defined 2 Source",
   "description": "Where this room parameter comes from",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet"
  },
  {
   "type": "MV",
   "instance": 7,
   "name": "Room 2 Pressure Source",
   "description": "Where this room parameter comes from",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet"
  },
  {
   "type": "MV",
   "instance": 8,
   "name": "Room 2 Temperature Source",
   "description": "Where this room parameter comes from",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet"
  },
  {
   "type": "MV",
   "instance": 9,
   "name": "Room 2 Humidity Source",
   "description": "Where this room parameter comes from",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet"
  },
  {
   "type": "MV",
   "instance": 10,
   "name": "Room 2 ACH Source",
   "description": "Where this room parameter comes from",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet"
  },
  {
   "type": "MV",
   "instance": 11,
   "name": "Room 2 User Defined 1 Source",
   "description": "Where this room parameter comes from",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet"
  },
  {
   "type": "MV",
   "instance": 12,
   "name": "Room 2 User Defined 2 Source",
   "description": "Where this room parameter comes from",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet"
  },
  {
   "type": "MV",
   "instance": 13,
   "name": "Room 3 Pressure Source",
   "description": "Where this room parameter comes from",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet"
  },
  {
   "type": "MV",
   "instance": 14,
   "name": "Room 3 Temperature Source",
   "description": "Where this room parameter comes from",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet"
  },
  {
   "type": "MV",
   "instance": 15,
   "name": "Room 3 Humidity Source",
   "description": "Where this room parameter comes from",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet"
  },
  {
   "type": "MV",
   "instance": 16,
   "name": "Room 3 ACH Source",
   "description": "Where this room parameter comes from",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet"
  },
  {
   "type": "MV",
   "instance": 17,
   "name": "Room 3 User Defined 1 Source",
   "description": "Where this room parameter comes from",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet"
  },
  {
   "type": "MV",
   "instance": 18,
   "name": "Room 3 User Defined 2 Source",
   "description": "Where this room parameter comes from",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet"
  },
  {
   "type": "MV",
   "instance": 83,
   "name": "Room 1 Door Source",
   "description": "Input used for the door switch",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board UI-1, 3=On-Board UI-2, 4=On-Board UI-3"
  },
  {
   "type": "MV",
   "instance": 84,
   "name": "Room 2 Door Source",
   "description": "Input used for the door switch",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board UI-1, 3=On-Board UI-2, 4=On-Board UI-3"
  },
  {
   "type": "MV",
   "instance": 85,
   "name": "Room 3 Door Source",
   "description": "Input used for the door switch",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=On-Board UI-1, 3=On-Board UI-2, 4=On-Board UI-3"
  },
  {
   "type": "MV",
   "instance": 19,
   "name": "Room 1 Room Profile",
   "description": "Active room profile",
   "units": "",
   "access": "W",
   "states": "1=Profile 1, 2=Profile 2, 3=Profile 3, 4=Profile 4"
  },
  {
   "type": "MV",
   "instance": 20,
   "name": "Room 2 Room Profile",
   "description": "Active room profile",
   "units": "",
   "access": "W",
   "states": "1=Profile 1, 2=Profile 2, 3=Profile 3, 4=Profile 4"
  },
  {
   "type": "MV",
   "instance": 21,
   "name": "Room 3 Room Profile",
   "description": "Active room profile",
   "units": "",
   "access": "W",
   "states": "1=Profile 1, 2=Profile 2, 3=Profile 3, 4=Profile 4"
  },
  {
   "type": "MV",
   "instance": 22,
   "name": "On-Board Analog Output Type",
   "description": "Output signal type",
   "units": "",
   "access": "W",
   "states": "1=4 to 20mA, 2=0 to 5VDC, 3=0 to 10VDC"
  },
  {
   "type": "MV",
   "instance": 27,
   "name": "On-Board Analog Input 1 Type",
   "description": "Signal type of input 1",
   "units": "",
   "access": "W",
   "states": "1=None, 2=mA, 3=VDC, 4=Digital (MSV 28, 29, & 30 only)"
  },
  {
   "type": "MV",
   "instance": 28,
   "name": "On-Board Analog Input 2 Type",
   "description": "Signal type of input 2",
   "units": "",
   "access": "W",
   "states": "1=None, 2=mA, 3=VDC, 4=Digital (MSV 28, 29, & 30 only)"
  },
  {
   "type": "MV",
   "instance": 29,
   "name": "On-Board Analog Input 3 Type",
   "description": "Signal type of input 3",
   "units": "",
   "access": "W",
   "states": "1=None, 2=mA, 3=VDC, 4=Digital (MSV 28, 29, & 30 only)"
  },
  {
   "type": "MV",
   "instance": 30,
   "name": "On-Board Analog Input 4 Type",
   "description": "Signal type of input 4",
   "units": "",
   "access": "W",
   "states": "1=None, 2=mA, 3=VDC, 4=Digital (MSV 28, 29, & 30 only)"
  },
  {
   "type": "MV",
   "instance": 39,
   "name": "Room Profile 1 Icon",
   "description": "Icon shown for this profile",
   "units": "",
   "access": "W",
   "states": "1=Icon 1, 2=Icon 2, 3=Icon 3, 4=Icon 4, 5=Icon 5, 6=Icon 6, 7=Icon 7, 8=Icon 8, 9=Icon 9, 10=Icon 10, 11=Icon 11, 12=Icon 12, 13=Icon 13, 14=Icon 14, 15=Icon 15, 16=Icon 16, 17=Icon 17, 18=Icon 18, 19=Icon 19, 20=Icon 20, 21=Icon 21, 22=Icon 22, 23=Icon 23, 24=Icon 24, 25=Icon 25, 26=Icon 26, 27=Icon 27, 28=Icon 28, 29=Icon 29, 30=Icon 30, 31=Icon 31, 32=Icon 32"
  },
  {
   "type": "MV",
   "instance": 40,
   "name": "Room Profile 2 Icon",
   "description": "Icon shown for this profile",
   "units": "",
   "access": "W",
   "states": "1=Icon 1, 2=Icon 2, 3=Icon 3, 4=Icon 4, 5=Icon 5, 6=Icon 6, 7=Icon 7, 8=Icon 8, 9=Icon 9, 10=Icon 10, 11=Icon 11, 12=Icon 12, 13=Icon 13, 14=Icon 14, 15=Icon 15, 16=Icon 16, 17=Icon 17, 18=Icon 18, 19=Icon 19, 20=Icon 20, 21=Icon 21, 22=Icon 22, 23=Icon 23, 24=Icon 24, 25=Icon 25, 26=Icon 26, 27=Icon 27, 28=Icon 28, 29=Icon 29, 30=Icon 30, 31=Icon 31, 32=Icon 32"
  },
  {
   "type": "MV",
   "instance": 41,
   "name": "Room Profile 3 Icon",
   "description": "Icon shown for this profile",
   "units": "",
   "access": "W",
   "states": "1=Icon 1, 2=Icon 2, 3=Icon 3, 4=Icon 4, 5=Icon 5, 6=Icon 6, 7=Icon 7, 8=Icon 8, 9=Icon 9, 10=Icon 10, 11=Icon 11, 12=Icon 12, 13=Icon 13, 14=Icon 14, 15=Icon 15, 16=Icon 16, 17=Icon 17, 18=Icon 18, 19=Icon 19, 20=Icon 20, 21=Icon 21, 22=Icon 22, 23=Icon 23, 24=Icon 24, 25=Icon 25, 26=Icon 26, 27=Icon 27, 28=Icon 28, 29=Icon 29, 30=Icon 30, 31=Icon 31, 32=Icon 32"
  },
  {
   "type": "MV",
   "instance": 42,
   "name": "Room Profile 4 Icon",
   "description": "Icon shown for this profile",
   "units": "",
   "access": "W",
   "states": "1=Icon 1, 2=Icon 2, 3=Icon 3, 4=Icon 4, 5=Icon 5, 6=Icon 6, 7=Icon 7, 8=Icon 8, 9=Icon 9, 10=Icon 10, 11=Icon 11, 12=Icon 12, 13=Icon 13, 14=Icon 14, 15=Icon 15, 16=Icon 16, 17=Icon 17, 18=Icon 18, 19=Icon 19, 20=Icon 20, 21=Icon 21, 22=Icon 22, 23=Icon 23, 24=Icon 24, 25=Icon 25, 26=Icon 26, 27=Icon 27, 28=Icon 28, 29=Icon 29, 30=Icon 30, 31=Icon 31, 32=Icon 32"
  },
  {
   "type": "MV",
   "instance": 43,
   "name": "Room Profile 1 Color",
   "description": "Color shown for this profile",
   "units": "",
   "access": "W",
   "states": "1=BLUE, 2=GREEN, 3=PURPLE"
  },
  {
   "type": "MV",
   "instance": 44,
   "name": "Room Profile 2 Color",
   "description": "Color shown for this profile",
   "units": "",
   "access": "W",
   "states": "1=BLUE, 2=GREEN, 3=PURPLE"
  },
  {
   "type": "MV",
   "instance": 45,
   "name": "Room Profile 3 Color",
   "description": "Color shown for this profile",
   "units": "",
   "access": "W",
   "states": "1=BLUE, 2=GREEN, 3=PURPLE"
  },
  {
   "type": "MV",
   "instance": 46,
   "name": "Room Profile 4 Color",
   "description": "Color shown for this profile",
   "units": "",
   "access": "W",
   "states": "1=BLUE, 2=GREEN, 3=PURPLE"
  },
  {
   "type": "MV",
   "instance": 47,
   "name": "Room Profile 1 Control Preset",
   "description": "Preset level used by this profile",
   "units": "",
   "access": "W",
   "states": "1=Level A, 2=Level B"
  },
  {
   "type": "MV",
   "instance": 48,
   "name": "Room Profile 2 Control Preset",
   "description": "Preset level used by this profile",
   "units": "",
   "access": "W",
   "states": "1=Level A, 2=Level B"
  },
  {
   "type": "MV",
   "instance": 49,
   "name": "Room Profile 3 Control Preset",
   "description": "Preset level used by this profile",
   "units": "",
   "access": "W",
   "states": "1=Level A, 2=Level B"
  },
  {
   "type": "MV",
   "instance": 50,
   "name": "Room Profile 3 Control Preset",
   "description": "Preset level used by this profile",
   "units": "",
   "access": "W",
   "states": "1=Level A, 2=Level B"
  },
  {
   "type": "MV",
   "instance": 51,
   "name": "Room Profile 1 Monitor Preset",
   "description": "Preset level used by this profile",
   "units": "",
   "access": "W",
   "states": "1=Level A, 2=Level B"
  },
  {
   "type": "MV",
   "instance": 52,
   "name": "Room Profile 2 Monitor Preset",
   "description": "Preset level used by this profile",
   "units": "",
   "access": "W",
   "states": "1=Level A, 2=Level B"
  },
  {
   "type": "MV",
   "instance": 53,
   "name": "Room Profile 3 Monitor Preset",
   "description": "Preset level used by this profile",
   "units": "",
   "access": "W",
   "states": "1=Level A, 2=Level B"
  },
  {
   "type": "MV",
   "instance": 54,
   "name": "Room Profile 4 Monitor Preset",
   "description": "Preset level used by this profile",
   "units": "",
   "access": "W",
   "states": "1=Level A, 2=Level B"
  },
  {
   "type": "MV",
   "instance": 55,
   "name": "Room 1 Pressure Source BACnet Object Type",
   "description": "Object type of the BACnet source",
   "units": "",
   "access": "W",
   "states": "1=Analog-Input, 2=Analog-Output, 3=Analog-Value"
  },
  {
   "type": "MV",
   "instance": 56,
   "name": "Room 1 Temperature Source BACnet Object Type",
   "description": "Object type of the BACnet source",
   "units": "",
   "access": "W",
   "states": "1=Analog-Input, 2=Analog-Output, 3=Analog-Value"
  },
  {
   "type": "MV",
   "instance": 57,
   "name": "Room 1 Humidity Source BACnet Object Type",
   "description": "Object type of the BACnet source",
   "units": "",
   "access": "W",
   "states": "1=Analog-Input, 2=Analog-Output, 3=Analog-Value"
  },
  {
   "type": "MV",
   "instance": 58,
   "name": "Room 1 ACH Source BACnet Object Type",
   "description": "Object type of the BACnet source",
   "units": "",
   "access": "W",
   "states": "1=Analog-Input, 2=Analog-Output, 3=Analog-Value"
  },
  {
   "type": "MV",
   "instance": 59,
   "name": "Room 1 User Defined 1 Source BACnet Object Type",
   "description": "Object type of the BACnet source",
   "units": "",
   "access": "W",
   "states": "1=Analog-Input, 2=Analog-Output, 3=Analog-Value"
  },
  {
   "type": "MV",
   "instance": 60,
   "name": "Room 1 User Defined 2 Source BACnet Object Type",
   "description": "Object type of the BACnet source",
   "units": "",
   "access": "W",
   "states": "1=Analog-Input, 2=Analog-Output, 3=Analog-Value"
  },
  {
   "type": "MV",
   "instance": 61,
   "name": "Room 2 Pressure Source BACnet Object Type",
   "description": "Object type of the BACnet source",
   "units": "",
   "access": "W",
   "states": "1=Analog-Input, 2=Analog-Output, 3=Analog-Value"
  },
  {
   "type": "MV",
   "instance": 62,
   "name": "Room 2 Temperature Source BACnet Object Type",
   "description": "Object type of the BACnet source",
   "units": "",
   "access": "W",
   "states": "1=Analog-Input, 2=Analog-Output, 3=Analog-Value"
  },
  {
   "type": "MV",
   "instance": 63,
   "name": "Room 2 Humidity Source BACnet Object Type",
   "description": "Object type of the BACnet source",
   "units": "",
   "access": "W",
   "states": "1=Analog-Input, 2=Analog-Output, 3=Analog-Value"
  },
  {
   "type": "MV",
   "instance": 64,
   "name": "Room 2 ACH Source BACnet Object Type",
   "description": "Object type of the BACnet source",
   "units": "",
   "access": "W",
   "states": "1=Analog-Input, 2=Analog-Output, 3=Analog-Value"
  },
  {
   "type": "MV",
   "instance": 65,
   "name": "Room 2 User Defined 1 Source BACnet Object Type",
   "description": "Object type of the BACnet source",
   "units": "",
   "access": "W",
   "states": "1=Analog-Input, 2=Analog-Output, 3=Analog-Value"
  },
  {
   "type": "MV",
   "instance": 66,
   "name": "Room 2 User Defined 2 Source BACnet Object Type",
   "description": "Object type of the BACnet source",
   "units": "",
   "access": "W",
   "states": "1=Analog-Input, 2=Analog-Output, 3=Analog-Value"
  },
  {
   "type": "MV",
   "instance": 67,
   "name": "Room 3 Pressure Source BACnet Object Type",
   "description": "Object type of the BACnet source",
   "units": "",
   "access": "W",
   "states": "1=Analog-Input, 2=Analog-Output, 3=Analog-Value"
  },
  {
   "type": "MV",
   "instance": 68,
   "name": "Room 3 Temperature Source BACnet Object Type",
   "description": "Object type of the BACnet source",
   "units": "",
   "access": "W",
   "states": "1=Analog-Input, 2=Analog-Output, 3=Analog-Value"
  },
  {
   "type": "MV",
   "instance": 69,
   "name": "Room 3 Humidity Source BACnet Object Type",
   "description": "Object type of the BACnet source",
   "units": "",
   "access": "W",
   "states": "1=Analog-Input, 2=Analog-Output, 3=Analog-Value"
  },
  {
   "type": "MV",
   "instance": 70,
   "name": "Room 3 ACH Source BACnet Object Type",
   "description": "Object type of the BACnet source",
   "units": "",
   "access": "W",
   "states": "1=Analog-Input, 2=Analog-Output, 3=Analog-Value"
  },
  {
   "type": "MV",
   "instance": 71,
   "name": "Room 3 User Defined 1 Source BACnet Object Type",
   "description": "Object type of the BACnet source",
   "units": "",
   "access": "W",
   "states": "1=Analog-Input, 2=Analog-Output, 3=Analog-Value"
  },
  {
   "type": "MV",
   "instance": 72,
   "name": "Room 3 User Defined 2 Source BACnet Object Type",
   "description": "Object type of the BACnet source",
   "units": "",
   "access": "W",
   "states": "1=Analog-Input, 2=Analog-Output, 3=Analog-Value"
  },
  {
   "type": "MV",
   "instance": 73,
   "name": "On-Board Analog Output Source",
   "description": "Value sent to the analog output",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=Room 1 Pressure, 3=Room 1 Temperature, 4=Room 1 Humidity, 5=Room 1 ACH, 6=Room 1 User Defined 1, 7=Room 1 User Defined 2, 8=Room 2 Pressure, 9=Room 2 Temperature, 10=Room 2 Humidity, 11=Room 2 ACH, 12=Room 2 User Defined 1, 13=Room 2 User Defined 2, 14=Room 3 Pressure, 15=Room 3 Temperature, 16=Room 3 Humidity, 17=Room 3 ACH, 18=Room 3 User Defined 1, 19=Room 3 User Defined 2, 20=Control Loop 1, 21=Control Loop 2, 22=Control Loop 3, 23=Control Loop 4"
  },
  {
   "type": "MV",
   "instance": 78,
   "name": "On-Board Relay Source",
   "description": "Event that drives the relay",
   "units": "",
   "access": "W",
   "states": "1=NONE, 2=Room 1 Door, 3=Room 2 Door, 4=Room 3 Door, 5=Room 1 Alarm, 6=Room 2 Alarm, 7=Room 3 Alarm, 8=Master Alarm"
  },
  {
   "type": "MV",
   "instance": 86,
   "name": "Room 1 Pressure Mode",
   "description": "Room pressure mode (positive/negative/neutral)",
   "units": "",
   "access": "R",
   "states": "1=POS (Positive), 2=NEG (Negative), 3=NEU (Neutral)"
  },
  {
   "type": "MV",
   "instance": 87,
   "name": "Room 2 Pressure Mode",
   "description": "Room pressure mode (positive/negative/neutral)",
   "units": "",
   "access": "R",
   "states": "1=POS (Positive), 2=NEG (Negative), 3=NEU (Neutral)"
  },
  {
   "type": "MV",
   "instance": 88,
   "name": "Room 3 Pressure Mode",
   "description": "Room pressure mode (positive/negative/neutral)",
   "units": "",
   "access": "R",
   "states": "1=POS (Positive), 2=NEG (Negative), 3=NEU (Neutral)"
  },
  {
   "type": "MV",
   "instance": 89,
   "name": "Language Selection",
   "description": "Display language",
   "units": "",
   "access": "W",
   "states": "1=English, 2=French"
  },
  {
   "type": "MV",
   "instance": 90,
   "name": "BACnet Setpoint 1 Override Priority",
   "description": "Priority used to write the BACnet setpoint",
   "units": "",
   "access": "W",
   "states": "1=Priority Level  1 (Manual-Life Safety), 2=Priority Level 2 (Automatic Life-Safety), 3=Priority Level 3, 4=Priority Level 4, 5=Priority Level 5 (Critical Equipment Control), 6=Priority Level 6 (Minimum On/Off), 7=Priority Level 7, 8=Priority Level 8 (Manual Operator), 9=Priority Level 9, 10=Priority Level 10, 11=Priority Level  11, 12=Priority Level  12, 13=Priority Level  13, 14=Priority Level  14, 15=Priority Level 15, 16=Priority Level  16, 17=NONE"
  },
  {
   "type": "MV",
   "instance": 91,
   "name": "BACnet Setpoint 2 Override Priority",
   "description": "Priority used to write the BACnet setpoint",
   "units": "",
   "access": "W",
   "states": "1=Priority Level  1 (Manual-Life Safety), 2=Priority Level 2 (Automatic Life-Safety), 3=Priority Level 3, 4=Priority Level 4, 5=Priority Level 5 (Critical Equipment Control), 6=Priority Level 6 (Minimum On/Off), 7=Priority Level 7, 8=Priority Level 8 (Manual Operator), 9=Priority Level 9, 10=Priority Level 10, 11=Priority Level  11, 12=Priority Level  12, 13=Priority Level  13, 14=Priority Level  14, 15=Priority Level 15, 16=Priority Level  16, 17=NONE"
  },
  {
   "type": "MV",
   "instance": 92,
   "name": "BACnet Setpoint 3 Override Priority",
   "description": "Priority used to write the BACnet setpoint",
   "units": "",
   "access": "W",
   "states": "1=Priority Level  1 (Manual-Life Safety), 2=Priority Level 2 (Automatic Life-Safety), 3=Priority Level 3, 4=Priority Level 4, 5=Priority Level 5 (Critical Equipment Control), 6=Priority Level 6 (Minimum On/Off), 7=Priority Level 7, 8=Priority Level 8 (Manual Operator), 9=Priority Level 9, 10=Priority Level 10, 11=Priority Level  11, 12=Priority Level  12, 13=Priority Level  13, 14=Priority Level  14, 15=Priority Level 15, 16=Priority Level  16, 17=NONE"
  },
  {
   "type": "MV",
   "instance": 93,
   "name": "BACnet Setpoint 4 Override Priority",
   "description": "Priority used to write the BACnet setpoint",
   "units": "",
   "access": "W",
   "states": "1=Priority Level  1 (Manual-Life Safety), 2=Priority Level 2 (Automatic Life-Safety), 3=Priority Level 3, 4=Priority Level 4, 5=Priority Level 5 (Critical Equipment Control), 6=Priority Level 6 (Minimum On/Off), 7=Priority Level 7, 8=Priority Level 8 (Manual Operator), 9=Priority Level 9, 10=Priority Level 10, 11=Priority Level  11, 12=Priority Level  12, 13=Priority Level  13, 14=Priority Level  14, 15=Priority Level 15, 16=Priority Level  16, 17=NONE"
  },
  {
   "type": "MV",
   "instance": 94,
   "name": "Room 1 Pressure Display Format",
   "description": "Decimal places shown",
   "units": "",
   "access": "W",
   "states": "1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places)"
  },
  {
   "type": "MV",
   "instance": 95,
   "name": "Room 1 Temperature Display Format",
   "description": "Decimal places shown",
   "units": "",
   "access": "W",
   "states": "1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places)"
  },
  {
   "type": "MV",
   "instance": 96,
   "name": "Room 1 Humidity Display Format",
   "description": "Decimal places shown",
   "units": "",
   "access": "W",
   "states": "1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places)"
  },
  {
   "type": "MV",
   "instance": 97,
   "name": "Room 1 ACH Display Format",
   "description": "Decimal places shown",
   "units": "",
   "access": "W",
   "states": "1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places)"
  },
  {
   "type": "MV",
   "instance": 98,
   "name": "Room 1 User Defined 1 Display Format",
   "description": "Decimal places shown",
   "units": "",
   "access": "W",
   "states": "1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places)"
  },
  {
   "type": "MV",
   "instance": 99,
   "name": "Room 1 User Defined 2 Display Format",
   "description": "Decimal places shown",
   "units": "",
   "access": "W",
   "states": "1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places)"
  },
  {
   "type": "MV",
   "instance": 100,
   "name": "Room 2 Pressure Display Format",
   "description": "Decimal places shown",
   "units": "",
   "access": "W",
   "states": "1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places)"
  },
  {
   "type": "MV",
   "instance": 101,
   "name": "Room 2 Temperature Display Format",
   "description": "Decimal places shown",
   "units": "",
   "access": "W",
   "states": "1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places)"
  },
  {
   "type": "MV",
   "instance": 102,
   "name": "Room 2 Humidity Display Format",
   "description": "Decimal places shown",
   "units": "",
   "access": "W",
   "states": "1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places)"
  },
  {
   "type": "MV",
   "instance": 103,
   "name": "Room 2 ACH Display Format",
   "description": "Decimal places shown",
   "units": "",
   "access": "W",
   "states": "1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places)"
  },
  {
   "type": "MV",
   "instance": 104,
   "name": "Room 2 User Defined 1 Display Format",
   "description": "Decimal places shown",
   "units": "",
   "access": "W",
   "states": "1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places)"
  },
  {
   "type": "MV",
   "instance": 105,
   "name": "Room 2 User Defined 2 Display Format",
   "description": "Decimal places shown",
   "units": "",
   "access": "W",
   "states": "1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places)"
  },
  {
   "type": "MV",
   "instance": 106,
   "name": "Room 3 Pressure Display Format",
   "description": "Decimal places shown",
   "units": "",
   "access": "W",
   "states": "1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places)"
  },
  {
   "type": "MV",
   "instance": 107,
   "name": "Room 3 Temperature Display Format",
   "description": "Decimal places shown",
   "units": "",
   "access": "W",
   "states": "1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places)"
  },
  {
   "type": "MV",
   "instance": 108,
   "name": "Room 3 Humidity Display Format",
   "description": "Decimal places shown",
   "units": "",
   "access": "W",
   "states": "1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places)"
  },
  {
   "type": "MV",
   "instance": 109,
   "name": "Room 3 ACH Display Format",
   "description": "Decimal places shown",
   "units": "",
   "access": "W",
   "states": "1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places)"
  },
  {
   "type": "MV",
   "instance": 110,
   "name": "Room 3 User Defined 1 Display Format",
   "description": "Decimal places shown",
   "units": "",
   "access": "W",
   "states": "1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places)"
  },
  {
   "type": "MV",
   "instance": 111,
   "name": "Room 3 User Defined 2 Display Format",
   "description": "Decimal places shown",
   "units": "",
   "access": "W",
   "states": "1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places)"
  },
  {
   "type": "MV",
   "instance": 112,
   "name": "Room 1 BACnet ACH Source type",
   "description": "BACnet ACH source given as ACH, volume or velocity",
   "units": "",
   "access": "W",
   "states": "1=ACH, 2=Volumetric, 3=Velocity"
  },
  {
   "type": "MV",
   "instance": 113,
   "name": "Room 2 BACnet ACH Source type",
   "description": "BACnet ACH source given as ACH, volume or velocity",
   "units": "",
   "access": "W",
   "states": "1=ACH, 2=Volumetric, 3=Velocity"
  },
  {
   "type": "MV",
   "instance": 114,
   "name": "Room 3 BACnet ACH Source type",
   "description": "BACnet ACH source given as ACH, volume or velocity",
   "units": "",
   "access": "W",
   "states": "1=ACH, 2=Volumetric, 3=Velocity"
  },
  {
   "type": "MV",
   "instance": 115,
   "name": "Room 1 Pressure Alarm Warning Mode",
   "description": "Warning on delay or on deadband",
   "units": "",
   "access": "W",
   "states": "1=On Delay, 2=On Deadband"
  },
  {
   "type": "MV",
   "instance": 116,
   "name": "Room 1 Temperature Alarm Warning Mode",
   "description": "Warning on delay or on deadband",
   "units": "",
   "access": "W",
   "states": "1=On Delay, 2=On Deadband"
  },
  {
   "type": "MV",
   "instance": 117,
   "name": "Room 1 Humidity Alarm Warning Mode",
   "description": "Warning on delay or on deadband",
   "units": "",
   "access": "W",
   "states": "1=On Delay, 2=On Deadband"
  },
  {
   "type": "MV",
   "instance": 118,
   "name": "Room 1 ACH Alarm Warning Mode",
   "description": "Warning on delay or on deadband",
   "units": "",
   "access": "W",
   "states": "1=On Delay, 2=On Deadband"
  },
  {
   "type": "MV",
   "instance": 119,
   "name": "Room 1 User Defined 1 Alarm Warning Mode",
   "description": "Warning on delay or on deadband",
   "units": "",
   "access": "W",
   "states": "1=On Delay, 2=On Deadband"
  },
  {
   "type": "MV",
   "instance": 120,
   "name": "Room 1 User Defined 2 Alarm Warning Mode",
   "description": "Warning on delay or on deadband",
   "units": "",
   "access": "W",
   "states": "1=On Delay, 2=On Deadband"
  },
  {
   "type": "MV",
   "instance": 121,
   "name": "Room 2 Pressure Alarm Warning Mode",
   "description": "Warning on delay or on deadband",
   "units": "",
   "access": "W",
   "states": "1=On Delay, 2=On Deadband"
  },
  {
   "type": "MV",
   "instance": 122,
   "name": "Room 2 Temperature Alarm Warning Mode",
   "description": "Warning on delay or on deadband",
   "units": "",
   "access": "W",
   "states": "1=On Delay, 2=On Deadband"
  },
  {
   "type": "MV",
   "instance": 123,
   "name": "Room 2 Humidity Alarm Warning Mode",
   "description": "Warning on delay or on deadband",
   "units": "",
   "access": "W",
   "states": "1=On Delay, 2=On Deadband"
  },
  {
   "type": "MV",
   "instance": 124,
   "name": "Room 2 ACH Alarm Warning Mode",
   "description": "Warning on delay or on deadband",
   "units": "",
   "access": "W",
   "states": "1=On Delay, 2=On Deadband"
  },
  {
   "type": "MV",
   "instance": 125,
   "name": "Room 2 User Defined 1 Alarm Warning Mode",
   "description": "Warning on delay or on deadband",
   "units": "",
   "access": "W",
   "states": "1=On Delay, 2=On Deadband"
  },
  {
   "type": "MV",
   "instance": 126,
   "name": "Room 2 User Defined 2 Alarm Warning Mode",
   "description": "Warning on delay or on deadband",
   "units": "",
   "access": "W",
   "states": "1=On Delay, 2=On Deadband"
  },
  {
   "type": "MV",
   "instance": 127,
   "name": "Room 3 Pressure Alarm Warning Mode",
   "description": "Warning on delay or on deadband",
   "units": "",
   "access": "W",
   "states": "1=On Delay, 2=On Deadband"
  },
  {
   "type": "MV",
   "instance": 128,
   "name": "Room 3 Temperature Alarm Warning Mode",
   "description": "Warning on delay or on deadband",
   "units": "",
   "access": "W",
   "states": "1=On Delay, 2=On Deadband"
  },
  {
   "type": "MV",
   "instance": 129,
   "name": "Room 3 Humidity Alarm Warning Mode",
   "description": "Warning on delay or on deadband",
   "units": "",
   "access": "W",
   "states": "1=On Delay, 2=On Deadband"
  },
  {
   "type": "MV",
   "instance": 130,
   "name": "Room 3 ACH Alarm Warning Mode",
   "description": "Warning on delay or on deadband",
   "units": "",
   "access": "W",
   "states": "1=On Delay, 2=On Deadband"
  },
  {
   "type": "MV",
   "instance": 131,
   "name": "Room 3 User Defined 1 Alarm Warning Mode",
   "description": "Warning on delay or on deadband",
   "units": "",
   "access": "W",
   "states": "1=On Delay, 2=On Deadband"
  },
  {
   "type": "MV",
   "instance": 132,
   "name": "Room 3 User Defined 2 Alarm Warning Mode",
   "description": "Warning on delay or on deadband",
   "units": "",
   "access": "W",
   "states": "1=On Delay, 2=On Deadband"
  },
  {
   "type": "MV",
   "instance": 133,
   "name": "Room 1 Door Alarm Action Type",
   "description": "What a door-open alarm does",
   "units": "",
   "access": "W",
   "states": "1=Door Open Indicator only, 2=Go into Standby"
  },
  {
   "type": "MV",
   "instance": 134,
   "name": "Room 2 Door Alarm Action Type",
   "description": "What a door-open alarm does",
   "units": "",
   "access": "W",
   "states": "1=Door Open Indicator only, 2=Go into Standby"
  },
  {
   "type": "MV",
   "instance": 135,
   "name": "Room 3 Door Alarm Action Type",
   "description": "What a door-open alarm does",
   "units": "",
   "access": "W",
   "states": "1=Door Open Indicator only, 2=Go into Standby"
  },
  {
   "type": "MV",
   "instance": 136,
   "name": "Air Flow/Air Velocity Unit for On-Board Analog Input 1",
   "description": "Airflow or velocity unit for this input",
   "units": "",
   "access": "W",
   "states": "1=ft/sec, 2=ft/min, 3=ft3/min, 4=m/sec, 5=liters/sec, 6=m3/sec, 7=m3/hr, 8=m3/min, 9=ft3/sec, 10=liters/min, 11=liters/hr, 12=m/min, 13=m/hr"
  },
  {
   "type": "MV",
   "instance": 137,
   "name": "Air Flow/Air Velocity Unit for On-Board Universal Input 1",
   "description": "Airflow or velocity unit for this input",
   "units": "",
   "access": "W",
   "states": "1=ft/sec, 2=ft/min, 3=ft3/min, 4=m/sec, 5=liters/sec, 6=m3/sec, 7=m3/hr, 8=m3/min, 9=ft3/sec, 10=liters/min, 11=liters/hr, 12=m/min, 13=m/hr"
  },
  {
   "type": "MV",
   "instance": 138,
   "name": "Air Flow/Air Velocity Unit for On-Board Universal Input 2",
   "description": "Airflow or velocity unit for this input",
   "units": "",
   "access": "W",
   "states": "1=ft/sec, 2=ft/min, 3=ft3/min, 4=m/sec, 5=liters/sec, 6=m3/sec, 7=m3/hr, 8=m3/min, 9=ft3/sec, 10=liters/min, 11=liters/hr, 12=m/min, 13=m/hr"
  },
  {
   "type": "MV",
   "instance": 139,
   "name": "Air Flow/Air Velocity Unit for On-Board Universal Input 3",
   "description": "Airflow or velocity unit for this input",
   "units": "",
   "access": "W",
   "states": "1=ft/sec, 2=ft/min, 3=ft3/min, 4=m/sec, 5=liters/sec, 6=m3/sec, 7=m3/hr, 8=m3/min, 9=ft3/sec, 10=liters/min, 11=liters/hr, 12=m/min, 13=m/hr"
  },
  {
   "type": "MV",
   "instance": 148,
   "name": "Air Flow/Air Velocity Unit for Room 1 Volumetric/Velocity BACnet Point",
   "description": "Airflow or velocity unit for this input",
   "units": "",
   "access": "W",
   "states": "1=ft/sec, 2=ft/min, 3=ft3/min, 4=m/sec, 5=liters/sec, 6=m3/sec, 7=m3/hr, 8=m3/min, 9=ft3/sec, 10=liters/min, 11=liters/hr, 12=m/min, 13=m/hr"
  },
  {
   "type": "MV",
   "instance": 149,
   "name": "Air Flow/Air Velocity Unit for Room 2 Volumetric/Velocity BACnet Point",
   "description": "Airflow or velocity unit for this input",
   "units": "",
   "access": "W",
   "states": "1=ft/sec, 2=ft/min, 3=ft3/min, 4=m/sec, 5=liters/sec, 6=m3/sec, 7=m3/hr, 8=m3/min, 9=ft3/sec, 10=liters/min, 11=liters/hr, 12=m/min, 13=m/hr"
  },
  {
   "type": "MV",
   "instance": 150,
   "name": "Air Flow/Air Velocity Unit for Room 3 Volumetric/Velocity BACnet Point",
   "description": "Airflow or velocity unit for this input",
   "units": "",
   "access": "W",
   "states": "1=ft/sec, 2=ft/min, 3=ft3/min, 4=m/sec, 5=liters/sec, 6=m3/sec, 7=m3/hr, 8=m3/min, 9=ft3/sec, 10=liters/min, 11=liters/hr, 12=m/min, 13=m/hr"
  },
  {
   "type": "LO",
   "instance": 1,
   "name": "Loop 1",
   "description": "PI control loop",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "LO",
   "instance": 2,
   "name": "Loop 2",
   "description": "PI control loop",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "LO",
   "instance": 3,
   "name": "Loop 3",
   "description": "PI control loop",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "LO",
   "instance": 4,
   "name": "Loop 4",
   "description": "PI control loop",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 1,
   "name": "Room 1 Label",
   "description": "Display text",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 2,
   "name": "Room 2 Label",
   "description": "Display text",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 3,
   "name": "Room 3 Label",
   "description": "Display text",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 4,
   "name": "Room Profile 1 Label",
   "description": "Display text",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 5,
   "name": "Room Profile 2 Label",
   "description": "Display text",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 6,
   "name": "Room Profile 3 Label",
   "description": "Display text",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 7,
   "name": "Room Profile 4 Label",
   "description": "Display text",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 8,
   "name": "Room Profile 1 Banner Label",
   "description": "Display text",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 9,
   "name": "Room Profile 2 Banner Label",
   "description": "Display text",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 10,
   "name": "Room Profile 3 Banner Label",
   "description": "Display text",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 11,
   "name": "Room Profile 4 Banner Label",
   "description": "Display text",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 12,
   "name": "Technical Support ID",
   "description": "Support contact text",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 13,
   "name": "Audit Trail String 1",
   "description": "Audit trail entry",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 14,
   "name": "Audit Trail String 2",
   "description": "Audit trail entry",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 15,
   "name": "Audit Trail String 3",
   "description": "Audit trail entry",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 16,
   "name": "Audit Trail String 4",
   "description": "Audit trail entry",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 17,
   "name": "Audit Trail String 5",
   "description": "Audit trail entry",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 18,
   "name": "Operator Password",
   "description": "Operator password",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 19,
   "name": "Room 1 User Defined 1 Badge Name",
   "description": "Name shown on the parameter badge",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 20,
   "name": "Room 1 User Defined 2 Badge Name",
   "description": "Name shown on the parameter badge",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 21,
   "name": "Room 2 User Defined 1 Badge Name",
   "description": "Name shown on the parameter badge",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 22,
   "name": "Room 2 User Defined 2 Badge Name",
   "description": "Name shown on the parameter badge",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 23,
   "name": "Room 3 User Defined 1 Badge Name",
   "description": "Name shown on the parameter badge",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "CSV",
   "instance": 24,
   "name": "Room 3 User Defined 2 Badge Name",
   "description": "Name shown on the parameter badge",
   "units": "",
   "access": "W",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/setra/flex-room-pressure-monitor",