 "manufacturer": "Schneider Electric",
 "manufacturer_slug": "schneider-electric",
 "model": "PowerLogic EM4200 energy meter (BACnet MS/TP)",
 "model_slug": "powerlogic-em4200",
 "aliases": [
  "EM4200",
  "EM42xx",
  "PowerLogic EM4200",
  "EM4200 BACnet",
  "EM4200 BACnet object list",
  "Schneider energy meter BACnet MS/TP"
 ],
 "equipment_type": "Power and energy meter (BACnet MS/TP)",
 "applies_to": "Schneider Electric PowerLogic EM4200 series (EM42xx) power and energy meters with BACnet MS/TP.",
 "summary": "The EM4200 meter has a fixed BACnet MS/TP object list: 103 Analog Inputs for energy, power, demand, power factor, voltage, current and frequency (totals, per phase, and import/export), 26 Analog Values for commands and setup (system type, CT and PT settings, demand intervals, pulse output, MS/TP address and baud), and 22 Binary Inputs that flag voltage, current, frequency, phase-loss, power-factor and configuration errors.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "OS 1.00.20, RS 1.00.07 (device object values in the list)",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Energy totals, max demands and most setup values are kept in non-volatile memory.",
  "AV 1 Command takes one of four codes: 30078 clears energy accumulators, 21212 resets max demand, 21211 starts a new demand sub-interval, 16498 clears pulse counters. It always reads 0.",
  "BI 17-22 flag that control of a setting (CT size, pulse weight, address, meter mode, analog output, CT interface) is overridden; they are not measurement faults.",
  "The device object instance defaults to a pseudo-random value; Object_Name, Location and Max_Master are writable.",
  "Source is Schneider's Excel object list (EM4200_BACnet_ObjectList.xlsx); the file prints no revision or date."
 ],
 "source": {
  "title": "EM4200 BACnet object list (Excel version)",
  "doc_number": "EM4200_BACnet_ObjectList",
  "revision_date": null,
  "url": "https://download.schneider-electric.com/files?p_Doc_Ref=EM4200_BACnet_ObjectList"
 },
 "integration": {
  "summary": "Set the MS/TP MAC address and baud rate and a unique device instance, then read energy (AI 1), total power (AI 4), demand (AI 12), power factor (AI 7), average voltage and current. Use AV 1 Command only when you need to reset energy or demand. Watch the phase-loss and range-error BIs for wiring or supply problems.",
  "minimum_points": [
   {
    "ref": "AI 1",
    "name": "kWh",
    "why": "Active energy total, kWh"
   },
   {
    "ref": "AI 4",
    "name": "kW_Total",
    "why": "Total active power, kW"
   },
   {
    "ref": "AI 12",
    "name": "kW_Present_Demand",
    "why": "Present active power demand, kW"
   },
   {
    "ref": "AI 7",
    "name": "PF_Avg",
    "why": "Average power factor"
   },
   {
    "ref": "AI 8",
    "name": "Voltage_LL_Avg",
    "why": "Average line-to-line voltage"
   },
   {
    "ref": "AI 10",
    "name": "Current_Avg",
    "why": "Average phase current"
   },
   {
    "ref": "BI 9",
    "name": "Phase_Loss_L1",
    "why": "Phase loss on L1"
   },
   {
    "ref": "BI 10",
    "name": "Phase_Loss_L2",
    "why": "Phase loss on L2"
   },
   {
    "ref": "BI 11",
    "name": "Phase_Loss_L3",
    "why": "Phase loss on L3"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "MS/TP MAC address 1-127 (AV 19) and baud 9600, 19200, 38400, 76800 or 115200 (AV 20).",
   "The device instance is pseudo-random out of the box; set a unique one before adding the meter.",
   "Max_Master defaults to 127 and is writable (1-127); Max_Info_Frames is 1.",
   "System type (AV 2), CT size and type (AV 3-5) and PT ratio (AV 6) must match the installation or all readings are wrong.",
   "No segmentation; max APDU 480 bytes; APDU timeout 3000 ms with 3 retries."
  ],
  "gotchas": [
   "Writing AV 1 with 30078 clears the energy accumulators; use it with care.",
   "Setup AVs are stored in non-volatile memory; don't write them cyclically.",
   "BI 17-22 report overridden control of CT size, pulse weight, address, meter mode, analog output and CT interface."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "kWh",
   "description": "Real (Active, P) Energy Consumption",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "kVARh",
   "description": "Reactive (Q) Energy Consumption",
   "units": "kVARh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "kVAh",
   "description": "Apparent (S) Energy Consumption",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "kW_Total",
   "description": "Total Real (Active, P) Power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "kVAR_Total",
   "description": "Total Reactive (Q) Power",
   "units": "kVAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "kVA_Total",
   "description": "Total Apparent (S) Power",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "PF_Avg",
   "description": "Average Power Factor (P/S) (0.00 - 1.00)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "Voltage_LL_Avg",
   "description": "Voltage Line to Line (U): Average of Active Phases",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "Voltage_LN_Avg",
   "description": "Voltage Line to Neutral (V): Average of Active Phases",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "Current_Avg",
   "description": "Current (I): Average of Active Phases",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "Frequency",
   "description": "Frequency Hz (45.0 - 65.0)",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "kW_Present_Demand",
   "description": "Total Real (Active, P) Power Present Demand",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "kVAR_Present_Demand",
   "description": "Total Reactive (Q) Power Present Demand",
   "units": "kVAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "kVA_Present_Demand",
   "description": "Total Apparent (S) Power Present Demand",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "kW_Max_Demand",
   "description": "Total Real (Active, P) Power Max Demand",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "kVAR_Max_Demand",
   "description": "Total Reactive (Q) Power Max Demand",
   "units": "kVAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "kVA_Max_Demand",
   "description": "Total Apparent (S) Power Max Demand",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "kWh_L1",
   "description": "Real (Active, P) Energy Consumption L1",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "kWh_L2",
   "description": "Real (Active, P) Energy Consumption L2",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "kWh_L3",
   "description": "Real (Active, P) Energy Consumption L3",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "kVARh_L1",
   "description": "Reactive (Q) Energy Consumption L1",
   "units": "kVARh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "kVARh_L2",
   "description": "Reactive (Q) Energy Consumption L2",
   "units": "kVARh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "kVARh_L3",
   "description": "Reactive (Q) Energy Consumption L3",
   "units": "kVARh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "kVAh_L1",
   "description": "Apparent (S) Energy Consumption L1",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "kVAh_L2",
   "description": "Apparent (S) Energy Consumption L2",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "kVAh_L3",
   "description": "Apparent (S) Energy Consumption L3",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "kW_L1",
   "description": "Real (Active, P) Power L1",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "kW_L2",
   "description": "Real (Active, P) Power L2",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "kW_L3",
   "description": "Real (Active, P) Power L3",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "kVAR_L1",
   "description": "Reactive (Q) Power L1",
   "units": "kVAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 31,
   "name": "kVAR_L2",
   "description": "Reactive (Q) Power L2",
   "units": "kVAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 32,
   "name": "kVAR_L3",
   "description": "Reactive (Q) Power L3",
   "units": "kVAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 33,
   "name": "kVA_L1",
   "description": "Apparent (S) Power L1",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 34,
   "name": "kVA_L2",
   "description": "Apparent (S) Power L2",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 35,
   "name": "kVA_L3",
   "description": "Apparent (S) Power L3",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 36,
   "name": "PF_L1",
   "description": "Power Factor L1 (0.00 - 1.00)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "PF_L2",
   "description": "Power Factor L2 (0.00 - 1.00)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "PF_L3",
   "description": "Power Factor L3 (0.00 - 1.00)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "Voltage_L12",
   "description": "Voltage L1-L2 (U12)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "Voltage_L23",
   "description": "Voltage L2-L3 (U23)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "Voltage_L31",
   "description": "Voltage L3-L1 (U31)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "Voltage_L1",
   "description": "Voltage L1-N (V1)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "Voltage_L2",
   "description": "Voltage L2-N (V2)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 44,
   "name": "Voltage_L3",
   "description": "Voltage L3-N (V3)",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45,
   "name": "Current_L1",
   "description": "Current L1 (I1)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 46,
   "name": "Current_L2",
   "description": "Current L2 (I2)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 47,
   "name": "Current_L3",
   "description": "Current L3 (I3)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 48,
   "name": "Current_N",
   "description": "Current Neutral (IN)",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 49,
   "name": "kWh Net",
   "description": "Real (Active, P) Energy Consumption: Net (Import - Export)",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 50,
   "name": "kWh_Import",
   "description": "Real (Active, P) Energy Consumption: Import",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 51,
   "name": "kWh_Export",
   "description": "Real (Active, P) Energy Consumption: Export",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 52,
   "name": "kVARh_Q1",
   "description": "Reactive (Q) Energy Consumption: Quadrant 1",
   "units": "kVARh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 53,
   "name": "kVARh_Q2",
   "description": "Reactive (Q) Energy Consumption: Quadrant 2",
   "units": "kVARh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 54,
   "name": "kVARh_Q3",
   "description": "Reactive (Q) Energy Consumption: Quadrant 3",
   "units": "kVARh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 55,
   "name": "kVARh_Q4",
   "description": "Reactive (Q) Energy Consumption: Quadrant 4",
   "units": "kVARh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 56,
   "name": "kVAh_Net",
   "description": "Apparent (S) Energy Consumption: Net (Import - Export)",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 57,
   "name": "kVAh_Import",
   "description": "Apparent (S) Energy Consumption: Import",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 58,
   "name": "kVAh_Export",
   "description": "Apparent (S) Energy Consumption: Export",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 59,
   "name": "Bi-Dir_kW_Total",
   "description": "Bi-Directional Total Real (Active ,P) Power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 60,
   "name": "Bi-Dir_kVAR_Total",
   "description": "Bi-Directional Total Reactive (Q) Power",
   "units": "kVAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 61,
   "name": "Bi-Dir_PF_Avg",
   "description": "Bi-Directional Average Power Factor (-1.00 - 1.00)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 62,
   "name": "Bi-Dir_kW_Present_Demand",
   "description": "Bi-Directional Total Real (Active ,P) Power Present Demand",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 63,
   "name": "Bi-Dir_kVAR_Present_Demand",
   "description": "Bi-Directional Total Reactive (Q) Power Present Demand",
   "units": "kVAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 64,
   "name": "Bi-Dir_kVA_Present Demand",
   "description": "Bi-Directional Total Apparent (S) Power Present Demand",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65,
   "name": "kW_Max_Demand_Import",
   "description": "Total Real (Active ,P) Power Max Demand: Import",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 66,
   "name": "kVAR_Max_Demand_Import",
   "description": "Total Reactive (Q) Power Max Demand: Import",
   "units": "kVAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 67,
   "name": "kVA_Max_Demand_Import",
   "description": "Total Apparent (S) Power Max Demand: Import",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 68,
   "name": "kW_Max_Demand_Export",
   "description": "Total Real (Active ,P) Power Max Demand: Export",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 69,
   "name": "kVAR_Max_Demand_Export",
   "description": "Total Reactive (Q) Power Max Demand: Export",
   "units": "kVAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 70,
   "name": "kVA_Max_Demand_Export",
   "description": "Total Apparent (S) Power Max Demand: Export",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 71,
   "name": "kWh_Import_L1",
   "description": "Real (Active, P) Energy Consumption: Import L1",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 72,
   "name": "kWh_Import_L2",
   "description": "Real (Active, P) Energy Consumption: Import L2",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 73,
   "name": "kWh_Import_L3",
   "description": "Real (Active, P) Energy Consumption: Import L3",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 74,
   "name": "kWh_Export_L1",
   "description": "Real (Active, P) Energy Consumption: Export L1",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 75,
   "name": "kWh_Export_L2",
   "description": "Real (Active, P) Energy Consumption: Export L2",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 76,
   "name": "kWh_Export_L3",
   "description": "Real (Active, P) Energy Consumption: Export L3",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 77,
   "name": "kVARh_Q1_L1",
   "description": "Reactive (Q) Energy Consumption: Quadrant 1 L1",
   "units": "kVARh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 78,
   "name": "kVARh_Q1_L2",
   "description": "Reactive (Q) Energy Consumption: Quadrant 1 L2",
   "units": "kVARh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 79,
   "name": "kVARh_Q1_L3",
   "description": "Reactive (Q) Energy Consumption: Quadrant 1 L3",
   "units": "kVARh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 80,
   "name": "kVARh_Q2_L1",
   "description": "Reactive (Q) Energy Consumption: Quadrant 2 L1",
   "units": "kVARh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 81,
   "name": "kVARh_Q2_L2",
   "description": "Reactive (Q) Energy Consumption: Quadrant 2 L2",
   "units": "kVARh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 82,
   "name": "kVARh_Q2_L3",
   "description": "Reactive (Q) Energy Consumption: Quadrant 2 L3",
   "units": "kVARh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 83,
   "name": "kVARh_Q3_L1",
   "description": "Reactive (Q) Energy Consumption: Quadrant 3 L1",
   "units": "kVARh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 84,
   "name": "kVARh_Q3_L2",
   "description": "Reactive (Q) Energy Consumption: Quadrant 3 L2",
   "units": "kVARh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 85,
   "name": "kVARh_Q3_L3",
   "description": "Reactive (Q) Energy Consumption: Quadrant 3 L3",
   "units": "kVARh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 86,
   "name": "kVARh_Q4_L1",
   "description": "Reactive (Q) Energy Consumption: Quadrant 4 L1",
   "units": "kVARh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 87,
   "name": "kVARh_Q4_L2",
   "description": "Reactive (Q) Energy Consumption: Quadrant 4 L2",
   "units": "kVARh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 88,
   "name": "kVARh_Q4_L3",
   "description": "Reactive (Q) Energy Consumption: Quadrant 4 L3",
   "units": "kVARh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 89,
   "name": "kVAh_Import_L1",
   "description": "Apparent (S) Energy Consumption: Import L1",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 90,
   "name": "kVAh_Import_L2",
   "description": "Apparent (S) Energy Consumption: Import L2",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 91,
   "name": "kVAh_Import_L3",
   "description": "Apparent (S) Energy Consumption: Import L3",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 92,
   "name": "kVAh_Export_L1",
   "description": "Apparent (S) Energy Consumption: Export L1",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 93,
   "name": "kVAh_Export_L2",
   "description": "Apparent (S) Energy Consumption: Export L2",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 94,
   "name": "kVAh_Export_L3",
   "description": "Apparent (S) Energy Consumption: Export L3",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 95,
   "name": "Bi-Dir_kW_L1",
   "description": "Bi-Directional Real (Active, P) Power L1",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 96,
   "name": "Bi-Dir_kW_L2",
   "description": "Bi-Directional Real (Active, P) Power L2",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 97,
   "name": "Bi-Dir_kW_L3",
   "description": "Bi-Directional Real (Active, P) Power L3",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 98,
   "name": "Bi-Dir_kVAR_L1",
   "description": "Bi-Directional Reactive (Q) Power L1",
   "units": "kVAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 99,
   "name": "Bi-Dir_kVAR_L2",
   "description": "Bi-Directional Reactive (Q) Power L2",
   "units": "kVAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 100,
   "name": "Bi-Dir_kVAR_L3",
   "description": "Bi-Directional Reactive (Q) Power L3",
   "units": "kVAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 101,
   "name": "Bi-Dir_PF_L1",
   "description": "Bi-Directional Power Factor L1 (-1.00 - 1.00)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 102,
   "name": "Bi-Dir_PF_L2",
   "description": "Bi-Directional Power Factor L2 (-1.00 - 1.00)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 103,
   "name": "Bi-Dir_PF_L3",
   "description": "Bi-Directional Power Factor L3 (-1.00 - 1.00)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Command",
   "description": "Command register; always reads 0",
   "units": "",
   "access": "W",
   "states": "30078 = Clear Energy Accumulators, 21212 = Reset Max Demand, 21211 = Begin New Sub-interval, 16498 = Clear Pulse Counters"
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "System_Type",
   "description": "System Type",
   "units": "",
   "access": "W",
   "states": "40 = A+B+C+N, 31 = A+B+C, 12 = A+B+N, 11 = A+B, 10 = A+N"
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "CT_Size",
   "description": "CT Primary (1 - 12800)",
   "units": "A",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "CT_Type",
   "description": "CT Type",
   "units": "",
   "access": "W",
   "states": "3 = 1/3V CT, 4 = Rogowski"
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "CT_Size_Neutral",
   "description": "CT Primary Neutral (1 - 12800)",
   "units": "A",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "PT_Ratio",
   "description": "PT Ratio",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "System_Voltage",
   "description": "System Voltage",
   "units": "V",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Max_System_Power",
   "description": "Max Sytem Power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "Phase_Loss_Voltage_Threshold",
   "description": "Phase Loss Voltage Threshold",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "Phase_Loss_Imbalance_Threshold",
   "description": "Phase Loss Imbalance Threshold",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "Energy_Pulse_Weight",
   "description": "Wh Per Pulse Output",
   "units": "Wh",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "Pulse_Contact_Closure_Duration",
   "description": "Pulse Contact Closure Duration",
   "units": "ms",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "Sub-Intervals",
   "description": "Number of Sub-Intervals per Demand Interval (1 - 6)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "Sub-Interval_Length",
   "description": "SubInterval Length (0 - 32767)",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "CT_Input_Polarity",
   "description": "CT Input Polarity",
   "units": "",
   "access": "W",
   "states": "xxx0b - xxx1b (bit 0) = Phase N; xx0xb - xx1xb (bit 1) = Phase A; x0xxb - x1xxb (bit 2) = Phase B; 0xxxb - 1xxxb (bit 3) = Phase C (0 = normal, 1 = reversed)"
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "Voltage_Input_L1_Association",
   "description": "Voltage Input L1 CT Association",
   "units": "",
   "access": "R",
   "states": "1 = Phase A, 2 = Phase B, 3 = Phase C"
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "Voltage_Input_L2_Association",
   "description": "Voltage Input L2 CT Association",
   "units": "",
   "access": "R",
   "states": "1 = Phase A, 2 = Phase B, 3 = Phase C"
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "Voltage_Input_L3_Association",
   "description": "Voltage Input L3 CT Association",
   "units": "",
   "access": "R",
   "states": "1 = Phase A, 2 = Phase B, 3 = Phase C"
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "MAC_Address",
   "description": "MSTP MAC Address (1 - 127)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "MSTP_Baud",
   "description": "MSTP Baudrate (9600, 19200, 38400, 76800, 115200)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "Energy_Resets",
   "description": "Energy Resets (0 - 32767)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "Power_Up_Counter",
   "description": "Power Up Counter (0 - 32767)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "Calibration_Event_Counter",
   "description": "Calibration Event Counter (0 - 32767)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "Configuration_Event_Counter",
   "description": "Configuration Event Counter (0 - 32767)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "Output_Configuration",
   "description": "Output Configuration (0 - 32767)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "Voltage_Input_To_CT_Association_General",
   "description": "Voltage input to CT association (123, 132, 231, 213, 321, 312)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "Voltage_Error_L1",
   "description": "Voltage Out of Range L1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "Voltage_Error_L2",
   "description": "Voltage Out of Range L2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "Voltage_Error_L3",
   "description": "Voltage Out of Range L3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "Current_Error_L1",
   "description": "Current Out of Range L1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "Current_Error_L2",
   "description": "Current Out of Range L2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "Current_Error_L3",
   "description": "Current Out of Range L3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "Neutral_Current_Error",
   "description": "Current Out of Range Neutral",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "Frequency_Error",
   "description": "Frequency Out of Range",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 9,
   "name": "Phase_Loss_L1",
   "description": "Voltage Phase Loss L1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "Phase_Loss_L2",
   "description": "Voltage Phase Loss L2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 11,
   "name": "Phase_Loss_L3",
   "description": "Voltage Phase Loss L3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 12,
   "name": "Low_Power_Factor_L1",
   "description": "Low Power Factor L1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 13,
   "name": "Low_Power_Factor_L2",
   "description": "Low Power Factor L2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 14,
   "name": "Low_Power_Factor_L3",
   "description": "Low Power Factor L3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 15,
   "name": "Pulse_Overrun_Error",
   "description": "Energy Pulse Output Overrun Error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 16,
   "name": "Pulse_Configuration_Error",
   "description": "Energy Pulse Output Configuration Error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 17,
   "name": "CT_Size_Override",
   "description": "CT Primary Size Control Overridden",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 18,
   "name": "Energy_Pulse_Weight_Override",
   "description": "Energy Pulse Weight Control Overridden",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 19,
   "name": "Device_Address_Override",
   "description": "Device Address Control Overridden",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 20,
   "name": "Meter_Mode_Override",
   "description": "Meter Mode Control Overridden",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 21,
   "name": "Analog_Output_Control_Override",
   "description": "Analog Output Control Overridden",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 22,
   "name": "CT_Interface_Override",
   "description": "CT Interface Overridden",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/schneider-electric/powerlogic-em4200",
 "note": "Re-typed from the manufacturer's public documentation (see source). Point availability varies by firmware and options; verify against the live device."
}