 "manufacturer": "Schneider Electric",
 "manufacturer_slug": "schneider-electric",
 "model": "iEM3465 / iEM3565 energy meter (BACnet MS/TP)",
 "model_slug": "iem3465-iem3565",
 "aliases": [
  "iEM3465",
  "iEM3565",
  "iEM3400 BACnet",
  "iEM3500 BACnet",
  "iEM3X65",
  "7EN02-0438"
 ],
 "equipment_type": "Power and energy meter (BACnet MS/TP)",
 "applies_to": "Schneider Electric iEM3465 (LVCT inputs) and iEM3565 (Rogowski coil inputs) DIN-rail energy meters, the BACnet MS/TP models of the iEM3400 / iEM3500 series.",
 "summary": "The iEM3465 and iEM3565 are three-phase DIN-rail energy meters that take low-voltage CTs or Rogowski coils directly, with a BACnet MS/TP port. They serve Analog Inputs for current, voltage, power, power factor, frequency, total, partial, per-phase and per-tariff energy, demand and peak demand, plus meter and I/O configuration readbacks, one Analog Value for commands and seven Binary Inputs for I/O and the overload alarm. The object list matches the iEM3165/3265/3365 list plus twelve demand objects (AI 60-71).",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "BACnet V2.4 or later for the demand objects",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Demand objects AI 60-71 need meter firmware iEM3465 V1.2.003 / iEM3565 V1.1.001 and BACnet V2.4 or later; older meters can't be upgraded.",
  "Configuration readbacks (AI 0-6, AI 44-55) can't be changed over BACnet; set them at the front panel.",
  "Energy values are in Wh and survive power loss.",
  "AV00 Command accepts 20001 (acknowledge overload alarm), 2020 (reset partial energy) and 2023 (reset input metering).",
  "Up to 14 COV subscriptions on AI and BI objects."
 ],
 "integration": {
  "summary": "At the front panel set the MS/TP baud rate, MAC address and device ID, then read energy import (AI 27), total active power (AI 22), demand (AI 60), current, voltage and power factor. Read BI 05 if the overload alarm is used. Write AV00 only to reset partial counters or acknowledge alarms.",
  "minimum_points": [
   {
    "ref": "AI 27",
    "name": "AI27 - Total active energy import",
    "why": "Imported active energy, Wh"
   },
   {
    "ref": "AI 22",
    "name": "AI22 - Active Power Total",
    "why": "Total active power, kW"
   },
   {
    "ref": "AI 60",
    "name": "AI60 - Demand active power",
    "why": "Active power demand, kW"
   },
   {
    "ref": "AI 25",
    "name": "AI25 - Power Factor Total",
    "why": "Total power factor"
   },
   {
    "ref": "AI 10",
    "name": "AI10 - Current Average",
    "why": "Average phase current, A"
   },
   {
    "ref": "AI 18",
    "name": "AI18 - Voltage Average L-N",
    "why": "Average line-to-neutral voltage"
   },
   {
    "ref": "AI 26",
    "name": "AI26 - Frequency",
    "why": "Supply frequency"
   },
   {
    "ref": "BI 5",
    "name": "BI05 - Alarm Status",
    "why": "Overload alarm active"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "Set baud (9600, 19200, 38400, 57600 or 76800), MAC address (1-127) and device ID (0-4194303) at the front panel.",
   "The device ID can only be set at the front panel; Object_Name, Description and Location are writable over BACnet.",
   "No segmentation and no static device address binding."
  ],
  "gotchas": [
   "Energy is reported in Wh, not kWh.",
   "The comms LED flashes even when there is a communication error."
  ]
 },
 "source": {
  "title": "iEM3400 / iEM3500 series energy meters user manual, 'Communications using BACnet'",
  "doc_number": "7EN02-0438-15",
  "revision_date": "05/2026",
  "url": "https://download.se.com/files?p_Doc_Ref=7EN02-0438"
 },
 "points": [
  {
   "type": "AI",
   "instance": 0,
   "name": "AI00 - BACnet MAC Address",
   "description": "MS/TP MAC address (set at the front panel)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "AI01 - BACnet Baud Rate",
   "description": "MS/TP baud rate (set at the front panel)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "AI02 - Pulse Duration",
   "description": "Energy pulse width of the digital output",
   "units": "ms",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "AI03 - Pulse Weight",
   "description": "Pulses per unit, digital input in input-metering mode",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "AI04 - Pulse Constant",
   "description": "Pulses per kWh of the digital output",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "AI05 - Digital Input Mode",
   "description": "Digital input function",
   "units": "",
   "access": "R",
   "states": "0=Normal (input status), 2=Multi Tariff control, 3=Input metering, 5=All partial energy logs reset"
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "AI06 - Digital Output Mode",
   "description": "Digital output function",
   "units": "",
   "access": "R",
   "states": "2=Alarm, 3=Energy, 65535=Disabled"
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "AI07 - Current Phase 1",
   "description": "",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "AI08 - Current Phase 2",
   "description": "",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "AI09 - Current Phase 3",
   "description": "",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "AI10 - Current Average",
   "description": "",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "AI11 - Voltage L1-L2",
   "description": "",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "AI12 - Voltage L2-L3",
   "description": "",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "AI13 - Voltage L3-L1",
   "description": "",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "AI14 - Voltage Average L-L",
   "description": "",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "AI15 - Voltage L1-N",
   "description": "",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "AI16 - Voltage L2-N",
   "description": "",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "AI17 - Voltage L3-N",
   "description": "",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "AI18 - Voltage Average L-N",
   "description": "",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "AI19 - Active Power Phase 1",
   "description": "",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "AI20 - Active Power Phase 2",
   "description": "",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "AI21 - Active Power Phase 3",
   "description": "",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "AI22 - Active Power Total",
   "description": "",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "AI23 - Reactive Power Total",
   "description": "",
   "units": "kVAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "AI24 - Apparent Power Total",
   "description": "",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "AI25 - Power Factor Total",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "AI26 - Frequency",
   "description": "",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "AI27 - Total active energy import",
   "description": "Kept through power failures",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "AI28 - Total active energy export",
   "description": "Kept through power failures",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "AI29 - Total reactive energy import",
   "description": "Kept through power failures",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "AI30 - Total reactive energy export",
   "description": "Kept through power failures",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 31,
   "name": "AI31 - Partial active energy import",
   "description": "Resettable partial counter",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 32,
   "name": "AI32 - Partial reactive energy import",
   "description": "Resettable partial counter",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 33,
   "name": "AI33 - Active energy import phase 1",
   "description": "",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 34,
   "name": "AI34 - Active energy import phase 2",
   "description": "",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 35,
   "name": "AI35 - Active energy import phase 3",
   "description": "",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 36,
   "name": "AI36 - Accumulation",
   "description": "Input metering accumulation (pulse input)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "AI37 - Tariff Energy Active Rate",
   "description": "Active tariff",
   "units": "",
   "access": "R",
   "states": "0=Multi tariff disabled, 1=Rate A, 2=Rate B, 3=Rate C, 4=Rate D"
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "AI38 - Rate A (Tariff 1) active energy import",
   "description": "",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "AI39 - Rate B (Tariff 2) active energy import",
   "description": "",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "AI40 - Rate C (Tariff 3) active energy import",
   "description": "",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "AI41 - Rate D (Tariff 4) active energy import",
   "description": "",
   "units": "Wh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "AI42 - Pickup Setpoint",
   "description": "Active power alarm pickup setpoint",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "AI43 - Last Alarm Value",
   "description": "Value at the last alarm",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 44,
   "name": "AI44 - Meter operation time",
   "description": "Time since the meter last powered up",
   "units": "Seconds",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45,
   "name": "AI45 - Number of phases",
   "description": "1 or 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 46,
   "name": "AI46 - Number of wires",
   "description": "2, 3 or 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 47,
   "name": "AI47 - Power system type",
   "description": "Wiring configuration",
   "units": "",
   "access": "R",
   "states": "0=1PH2W L-N, 1=1PH2W L-L, 2=1PH3W L-L with N, 3=3PH3W, 11=3PH4W, 13=1PH4 wire multi L-N"
  },
  {
   "type": "AI",
   "instance": 48,
   "name": "AI48 - Nominal frequency",
   "description": "50 or 60",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 49,
   "name": "AI49 - Number of VTs",
   "description": "0-10",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 50,
   "name": "AI50 - VT Primary",
   "description": "",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 51,
   "name": "AI51 - VT Secondary",
   "description": "",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 52,
   "name": "AI52 - Number of CTs",
   "description": "1, 2 or 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 53,
   "name": "AI53 - CT Primary",
   "description": "",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 54,
   "name": "AI54 - CT Secondary",
   "description": "",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 55,
   "name": "AI55 - VT connection type",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Direct connection, no VTs, 1=3PH3W (2 VTs), 2=3PH4W (3 VTs)"
  },
  {
   "type": "AI",
   "instance": 60,
   "name": "AI60 - Demand active power",
   "description": "Active power demand",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 61,
   "name": "AI61 - Demand active power peak",
   "description": "Peak active power demand",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 62,
   "name": "AI62 - Demand reactive power",
   "description": "Reactive power demand",
   "units": "kVAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 63,
   "name": "AI63 - Demand reactive power peak",
   "description": "Peak reactive power demand",
   "units": "kVAR",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 64,
   "name": "AI64 - Demand apparent power",
   "description": "Apparent power demand",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65,
   "name": "AI65 - Demand apparent power peak",
   "description": "Peak apparent power demand",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 66,
   "name": "AI66 - Demand current phase 1",
   "description": "Current demand, phase 1",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 67,
   "name": "AI67 - Demand current phase 1 peak",
   "description": "Peak current demand, phase 1",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 68,
   "name": "AI68 - Demand current phase 2",
   "description": "Current demand, phase 2",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 69,
   "name": "AI69 - Demand current phase 2 peak",
   "description": "Peak current demand, phase 2",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 70,
   "name": "AI70 - Demand current phase 3",
   "description": "Current demand, phase 3",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 71,
   "name": "AI71 - Demand current phase 3 peak",
   "description": "Peak current demand, phase 3",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "AV00 - Command",
   "description": "Write a command code to the meter",
   "units": "",
   "access": "W",
   "states": "20001=Acknowledge overload alarm, 2020=Reset partial energy counters, 2023=Reset input metering counter"
  },
  {
   "type": "BI",
   "instance": 0,
   "name": "BI00 - Digital Output Enable",
   "description": "Digital output used as active energy pulse output",
   "units": "",
   "access": "R",
   "states": "0=Disabled, 1=Energy pulse output"
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "BI01 - Digital Input Association Enable",
   "description": "Digital input used for input metering",
   "units": "",
   "access": "R",
   "states": "0=Not associated, 1=Associated"
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "BI02 - Digital Input Status",
   "description": "Digital input contact state (input status mode)",
   "units": "",
   "access": "R",
   "states": "0=Relay open, 1=Relay closed"
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "BI03 - Alarm Enable",
   "description": "Overload alarm enabled",
   "units": "",
   "access": "R",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "BI04 - Digital Output Association Enable",
   "description": "Digital output used for the overload alarm",
   "units": "",
   "access": "R",
   "states": "0=Disabled, 1=Alarm"
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "BI05 - Alarm Status",
   "description": "Overload alarm active",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "BI06 - Unacknowledged status",
   "description": "Historic alarm not yet acknowledged",
   "units": "",
   "access": "R",
   "states": "0=Acknowledged, 1=Unacknowledged"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/schneider-electric/iem3465-iem3565",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}