 "manufacturer": "PVI",
 "manufacturer_slug": "pvi",
 "model": "EOS (BTCII) boiler control - HeatStation",
 "model_slug": "eos-btcii-boiler-heatstation",
 "aliases": [
  "PVI EOS boiler",
  "BTCII",
  "EOS Controller",
  "HeatStation",
  "PVI HeatStation",
  "J1239D-570",
  "PV7214"
 ],
 "equipment_type": "Commercial boiler control",
 "applies_to": "PVI HeatStation boilers with the EOS BTCII touch-screen control, standalone or as the master of a cascade of up to 12 boilers, firmware J1239D-570 or newer.",
 "summary": "The boiler version of the PVI EOS BTCII control serves BACnet MS/TP (or Modbus RTU) from the master boiler's display. Besides boiler 1's probes, ignition state, modulation, relays, flame current, counters and error code, it gives the system (cascade) status, installed/talking/enabled boiler counts, the modulating and lead boiler, and writable system enable, BAS setpoint, setpoint and boiler enable. In a cascade the BAS connects only to the master.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "J1239D-570 and newer",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Object names and instances follow the discovery list printed in the manual. Only boiler 1 objects are printed; the manual says member boilers are numbered 2-12 but does not print their object instances.",
  "Probes 4-6 and EMS VOLTAGE are only valid on boiler 1 (the master); probe 5 is the building supply / system sensor and probe 6 the outdoor sensor.",
  "The point details list BOILER # DRIVE 2 at 1001 (pump 2, DHW/sanitary) and DRIVE 1 at 1002 (boiler pump), while the discovery list has DRIVE 1 at 1001 and DRIVE 2 at 1002. Check on site.",
  "Flame current is reported with BACnet units of milliamperes, but the value is in tenths of a microamp (10 = 1 µA).",
  "Error codes 1-31 (manual list): 1 EEPROM, 2 outdoor sensor, 3 supply sensor, 4 DHW sensor, 5 software, 6 FTBus comm, 7 LWCO, 8 remote proving, 9 air pressure, 10 low gas pressure, 11-14 outlet/inlet/vent/hi-limit sensor, 15 ignition failure, 16 flame loss, 17 vent hi-limit, 18 tank hi-limit, 19 false flame, 20 OEM card, 21 internal failure, 22 hi-delta, 23 low HSI, 24 low voltage, 25 blower speed, 26 high gas pressure, 27-31 linked-system communication."
 ],
 "source": {
  "title": "EOS Boiler Interface Guide and Points List - For EOS BTCII Firmware Version J1239D-570 and Newer",
  "doc_number": "PV7214 (PN 144593)",
  "revision_date": "2021-01",
  "url": "https://www.pvi.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/53662-source/eos-interface-boiler-interface-pv7214.pdf"
 },
 "integration": {
  "summary": "Set the master boiler's BTCII network mode to BACnet, give it a device instance and MAC, and wire its 3-pin RS-485 terminal. Enable with SYSTEM ENABLE / BOILER 1 ENABLE, drive the temperature with BAS TARGET (or SETPOINT), and read SYSTEM STATUS, SYSTEM TEMP, the cascade counts, ALERT and ERROR.",
  "minimum_points": [
   {
    "ref": "AV 0",
    "name": "SYSTEM ENABLE",
    "why": "System enable (1 = enabled)"
   },
   {
    "ref": "AV 1000",
    "name": "BOILER 1 ENABLE",
    "why": "Boiler 1 enable (1 = enable)"
   },
   {
    "ref": "AV 1",
    "name": "BAS TARGET",
    "why": "BAS setpoint; overrides SETPOINT when non-zero"
   },
   {
    "ref": "AV 2",
    "name": "SETPOINT",
    "why": "System or boiler setpoint"
   },
   {
    "ref": "AI 0",
    "name": "SYSTEM STATUS",
    "why": "0 disabled, 1 idle, 2 heating"
   },
   {
    "ref": "AI 4",
    "name": "SYSTEM TEMP",
    "why": "System (building supply) temperature"
   },
   {
    "ref": "AI 3",
    "name": "SYSTEM TARGET",
    "why": "Target temperature in use"
   },
   {
    "ref": "AI 2",
    "name": "SYSTEM ALERT",
    "why": "0 normal, 1 alert, 2 error (heating stopped)"
   },
   {
    "ref": "AI 1018",
    "name": "BOILER 1 ERROR",
    "why": "Latest error code (0 = none)"
   }
  ],
  "enable": "SYSTEM ENABLE (AV 0) and BOILER # ENABLE (AV 1000 for boiler 1) enable or disable with 1/0. The TH input (R1-R2, jumpered at the factory) must be closed; open on the master disables the whole system.",
  "heartbeat": null,
  "remote_sensors": "BAS TARGET (AV 1) takes over from SETPOINT whenever it is non-zero, until it is written back to 0 or the master loses power (it resets to 0 on power-up).",
  "setup": [
   "On the display: Toolbox menu, access level ADV, then NETWORK menu: set MODE (BAS) to BACN.",
   "Device instance is entered on the display (1-4194303); MAC 1-127 (default 3); baud 2400-115k (default 38k4); Max Master default 127; Max Info Frames default 1.",
   "RS-485 on a 3-pin terminal on the back of the BTCII display: A(-) to the BAS D+, B(+) to D-, plus ground. No bias or termination resistors are built in.",
   "The port is shared with Modbus RTU; only one protocol is active.",
   "With the cascade feature in use, connect the BAS (or any gateway) to the master boiler only."
  ],
  "gotchas": [
   "BAS TARGET resets to 0 on a power cycle, so the boiler returns to SETPOINT; rewrite it after power-up.",
   "SYSTEM STATUS does not show errors; a lockout reads as Idle."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 0,
   "name": "SYSTEM STATUS",
   "description": "System status",
   "units": "",
   "access": "R",
   "states": "0=Disabled, 1=Idle, 2=Heating"
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "SYSTEM DEMAND",
   "description": "External enable input (1 = on)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "SYSTEM ALERT",
   "description": "System alert",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Alert, 2=Error"
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "SYSTEM TARGET",
   "description": "Target temperature in use",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "SYSTEM TEMP",
   "description": "Operating (system) sensor temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "CASCADE STATUS",
   "description": "Cascade communication status",
   "units": "",
   "access": "R",
   "states": "0=Standalone, 1=Working, 2=Not All Talking, 3=No Connection"
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "CASCADE INSTALLED",
   "description": "Boilers configured in the cascade",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "CASCADE TALKING",
   "description": "Boilers talking on the cascade",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "CASCADE ENABLED",
   "description": "Enabled boilers in the system",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "CASCADE OPERATING",
   "description": "Boiler currently modulating",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "CASCADE LEAD",
   "description": "Current lead boiler number",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1000,
   "name": "BOILER 1 STATUS",
   "description": "Cascade communication status of this unit",
   "units": "",
   "access": "R",
   "states": "0=No Communication, 1=Communicating, 2=Lost Communication"
  },
  {
   "type": "AI",
   "instance": 1001,
   "name": "BOILER 1 TH",
   "description": "TH enable input (R1-R2)",
   "units": "",
   "access": "R",
   "states": "0=Open (disabled), 1=Closed (enabled)"
  },
  {
   "type": "AI",
   "instance": 1002,
   "name": "BOILER 1 DHW",
   "description": "DHW call input",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 1003,
   "name": "BOILER 1 ALERT",
   "description": "Alert status",
   "units": "",
   "access": "R",
   "states": "0=None, 1=Alert, 2=Auto (soft lockout), 3=Manual (hard lockout)"
  },
  {
   "type": "AI",
   "instance": 1004,
   "name": "BOILER 1 IGNITION",
   "description": "Burner sequence",
   "units": "",
   "access": "R",
   "states": "0=Idle, 1=Prepurge, 2=Ignition, 3=Burner On, 4=Postpurge, 5=Fail"
  },
  {
   "type": "AI",
   "instance": 1005,
   "name": "BOILER 1 PROBE 1",
   "description": "Outlet probe (top of tank / boiler outlet)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1006,
   "name": "BOILER 1 PROBE 2",
   "description": "Inlet probe (mid tank / return)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1007,
   "name": "BOILER 1 PROBE 3",
   "description": "Vent (flue) probe",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1008,
   "name": "BOILER 1 PROBE 4",
   "description": "Probe 4 (DHW sensor input)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1009,
   "name": "BOILER 1 PROBE 5",
   "description": "Probe 5 (supply sensor input)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1010,
   "name": "BOILER 1 PROBE 6",
   "description": "Probe 6 (outdoor sensor input)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1011,
   "name": "BOILER 1 MOD",
   "description": "Modulation rate, 0-100 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1012,
   "name": "BOILER 1 RELAY 1",
   "description": "Relay J14-1 (pump 2, typically DHW/sanitary) status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 1013,
   "name": "BOILER 1 RELAY 2",
   "description": "Relay J14-2 (pump 1, boiler pump) status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 1014,
   "name": "BOILER 1 EMS VOLTAGE",
   "description": "EMS analog input (PIM J1-8/9)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1015,
   "name": "BOILER 1 CURRENT",
   "description": "Flame current (10 = 1 µA)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1016,
   "name": "BOILER 1 RUNTIME",
   "description": "Burner run hours, rolls over at 65535",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1017,
   "name": "BOILER 1 CYCLES",
   "description": "Burner start attempts, rolls over at 65535",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1018,
   "name": "BOILER 1 ERROR",
   "description": "Latest error code (0 = none)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "SYSTEM ENABLE",
   "description": "System enable",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "BAS TARGET",
   "description": "BAS setpoint; overrides SETPOINT when non-zero",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "SETPOINT",
   "description": "Boiler setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "ROTATION",
   "description": "Rotation (no details in the manual)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1000,
   "name": "BOILER 1 ENABLE",
   "description": "Boiler enable",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "AV",
   "instance": 1001,
   "name": "BOILER 1 DRIVE 1",
   "description": "Pump relay force-on (see note on drive numbering)",
   "units": "",
   "access": "W",
   "states": "0=Auto, 1=Force On"
  },
  {
   "type": "AV",
   "instance": 1002,
   "name": "BOILER 1 DRIVE 2",
   "description": "Pump relay force-on (see note on drive numbering)",
   "units": "",
   "access": "W",
   "states": "0=Auto, 1=Force On"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/pvi/eos-btcii-boiler-heatstation",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}