 "manufacturer": "Melink",
 "manufacturer_slug": "melink",
 "model": "Intelli-Hood IH4 Exhaust Fan / Auxiliary Airflow",
 "model_slug": "intelli-hood-ih4-exhaust-fan",
 "aliases": [
  "Intelli-Hood",
  "IH4",
  "IH4-SC",
  "Melink IH4",
  "Intelli-Hood 4"
 ],
 "equipment_type": "Kitchen exhaust / make-up air fan VFD device (Intelli-Hood demand ventilation)",
 "applies_to": "Each exhaust fan and auxiliary airflow (make-up air fan) VFD run by a Melink Intelli-Hood 4 system.",
 "summary": "On a Melink Intelli-Hood 4 system every exhaust fan and auxiliary airflow (typically a make-up air unit) VFD appears as its own virtual BACnet IP device behind the System Controller. Each device has the same eight objects: run status, VFD fault, a fault reset, maximum frequency, commanded and actual speed, current and kWh. Fan speed is set by the Intelli-Hood from hood temperature and smoke, not by the BMS.",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet IPv6"
 ],
 "firmware": "Application 4.0, firmware 1.0.0",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "The same object list repeats on every exhaust fan and auxiliary airflow device; only the Device ID differs.",
  "Output Current is not updated for System VFDs; Output Energy is not updated for System and Allen-Bradley PowerFlex 4/40 VFDs.",
  "Actual speed lags commanded speed during VFD ramp up and ramp down; that difference is normal.",
  "To get speed in Hz, multiply the % speed by Maximum Output Frequency (AV 0).",
  "A fan can be hidden from BACnet with its 'Active on BACnet' setting (default Yes for fans)."
 ],
 "source": {
  "title": "Intelli-Hood BACnet Protocol Implementation Conformance Statement (PICS)",
  "doc_number": null,
  "revision_date": "Revision 250723 (PICS dated 07-18-2025)",
  "url": "https://melinkcorp.com/wp-content/uploads/2021/10/IH4_BACnet_PICS.pdf"
 },
 "integration": {
  "summary": "Read run status, actual speed and the VFD fault flag from each fan device; add the kWh counter for energy tracking. The BMS can only clear VFD faults (BV 2); speed and start/stop come from the Intelli-Hood.",
  "minimum_points": [
   {
    "ref": "BV 2",
    "name": "Reset VFD Fault",
    "why": "Write Active to clear a VFD fault"
   },
   {
    "ref": "BV 0",
    "name": "Operation Status",
    "why": "Fan running (Active) or stopped"
   },
   {
    "ref": "AV 2",
    "name": "% Actual Speed",
    "why": "Speed reported by the VFD, %"
   },
   {
    "ref": "AV 1",
    "name": "% Commanded Speed",
    "why": "Speed the Intelli-Hood is asking for, %"
   },
   {
    "ref": "AV 4",
    "name": "Output Energy",
    "why": "VFD kWh counter (rolls over)"
   },
   {
    "ref": "BV 1",
    "name": "Fault Active",
    "why": "VFD tripped or lost comms with the Intelli-Hood"
   }
  ],
  "enable": "No BACnet start/stop or speed command. Fans are started from the Touchpad, schedules or digital inputs; use the Virtual Input Module to do that over BACnet.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "The System Controller is the main BACnet IP device (default Device ID 654000) and a virtual router (default DNET 654) for the fan, hood controller and virtual module devices; UDP port 47808.",
   "With BACnet Auto Number on (default), the virtual devices are numbered from 654001: exhaust fans and auxiliary airflows (sorted by name), then hood controllers, virtual output modules, virtual input modules.",
   "IP defaults to DHCP. BACnet runs on IPv4 or IPv6, not both; for IPv6 set IP Type to 'IPv4 & IPv6' and BACnet IP Type to IPv6 (multicast scope default ff05).",
   "Settings are on the Touchpad (System Controller configuration) or the web configurator at http://<controller IP>/ih4-configurator.",
   "Check each fan's Device ID on the Touchpad: Status > VFDs, then press the progress bar above the device name."
  ],
  "gotchas": [
   "Front ends that send Who-Is without routing only find the System Controller; run a network/router discovery, select the router with the Intelli-Hood DNET, then discover devices again.",
   "The DNET must be unique; another router or BBMD using 654 breaks access to the virtual devices.",
   "Clearing a VFD fault before the cause is fixed can damage the VFD, motor or fan.",
   "Putting BV 2 Reset VFD Fault Out of Service disables it; writes then do nothing.",
   "Output Energy rolls over on every VFD; poll it often enough to catch the rollover."
  ]
 },
 "points": [
  {
   "type": "BV",
   "instance": 0,
   "name": "Operation Status",
   "description": "Fan running or stopped",
   "units": "",
   "access": "R",
   "states": "Inactive = Stopped, Active = Running"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "Fault Active",
   "description": "VFD tripped or lost communication with the Intelli-Hood",
   "units": "",
   "access": "R",
   "states": "Inactive = No, Active = Yes"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "Reset VFD Fault",
   "description": "Write Active to try clearing the VFD fault; reads back Inactive",
   "units": "",
   "access": "C",
   "states": "Inactive = No, Active = Yes"
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "Maximum Output Frequency",
   "description": "Fan maximum speed, 0-254 Hz",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "% Commanded Speed",
   "description": "Speed the Intelli-Hood is commanding, 0-100 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "% Actual Speed",
   "description": "Speed reported by the VFD, 0-100 %",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Output Current",
   "description": "VFD output current; not updated for System VFDs",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "Output Energy",
   "description": "VFD kWh counter; rolls over, not on all VFDs",
   "units": "kWh",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/melink/intelli-hood-ih4-exhaust-fan",
 "note": "Re-typed from the manufacturer's public documentation (see source). Point availability varies by firmware and options; verify against the live device."
}